DRIVES
DRIVE PRODUCTS INTELLIGENT PUMP CONTROL
IMPROVED PROCESS CONTROL AND SYSTEM RELIABILITY By matching pump output flow or pressure directly to the process requirements, applications can be fine tuned more rapidly by iQpump drives than by other control forms. Any reduction in speed achieved by using iQpump drives has major benefits in reducing pump wear, particularly in bearings and seals.
INTELLIGENT PUMP DESIGN
REDUCE TOTAL SYSTEM COST iQpump drives lower system cost by eliminating sensors, jockey pumps, and restriction valves, as well as reducing pressure tank sizing.
Yaskawa’s family of iQpump® drives offers a wide variety of package options and the most advanced comprehensive pump and motor protection in the industry, while still maintaining ease of setup and diagnostics designed for pump operators and service technicians. Our integrated pump specific software allows for a wide range of pumping applications from constant pressure, flow, geothermal, multiple pump booster systems to wet well lift stations and many others. Designed with the user in mind, iQpump drives use intuitive pump related terminology, with simple process control selection of engineering units such as PSI, GPM, feet, meters, degrees, inches of mercury, and many other units.
ENERGY SAVINGS Depending on the application, iQpump drives reduce the demand for energy 20% to 50% by adjusting pump speed to match a lower flow/pressure. EASE OF INSTALLATION AND SET UP iQpump drives use pump terminology on all setup parameters and monitors. Application presets apply most of the parameters for you. Also included is a “Pump Quick Setup” and “Modified Constants” menu. iQpump1000 is your total pumping solution for whatever your system demands, while maintaining the simple pump terminology programming customers have come to expect. Yaskawa understands that many light commercial, industrial, agricultural and groundwater
iQpump drives are designed with the user in mind. Our goal is to ensure that the pump is operating at the best efficiency point (BEP), saving energy and decreasing life-cycle costs.
well systems are looking for a more cost effective simplex and multiplex constant pressure pump control solution without sacrificing what they have come to enjoy from Yaskawa.
Cotización: https://podio.com/webforms/19719714/1335065
xbombas@gmail.com
COOLER RUNNING PUMP MOTOR Soft starts eliminate high inrush current, dramatically increasing winding insulation life. PC Support Tools: DRIVE WIZARD IQPUMP Provides users a startup wizard, parameter management tools, drive status monitoring and trending. UTILITY HARMONICS ESTIMATOR Estimation of harmonics contribution back to main power source.
iQpump Micro offers many of the same comprehensive software features and control along with the same programming interface as iQpump1000, but in a package that saves cost.
2
ELIMINATE COMPLEX CONTROL PANELS iQpump drive installation eliminates many electro-mechanical controls. This reduces maintenance requirements.
ENERGY SAVINGS PREDICTOR Analysis of energy savings with carbon footprint calculation.
IQPUMP1000
IQPUMP MICRO
3/4-175 HP 200-240V 3-Phase Input 1-1000 HP 380-480V 3-Phase Input 2-250 HP 500-600V 3-Phase Input
1-5HP 200-230V 1-Phase Input 1-25HP 200-240V 3-Phase Input 1-25HP 380-480V 3-Phase Input
APPLICATION SIMULATOR SOFTWARE Allows for the user to program multiple pump applications and then simulate operation without the need for a drive.
3
IQPUMP 1000 & MICRO
YASKAWA ADVANTAGE
Environmental Considerations: Yaskawa maintains a corporate commitment to sustainability goals with an emphasis on the following environmental guidelines:
The difference that matters
RoHS Restriction of Hazardous Substances
Yaskawa continually trains its people, partners and end-users. It designs products to specifically prevent defects. It qualifies product through arduous and varied testing processes. This is all part of the way we differentiate ourselves from the competition.
Leadership in Energy and Environmental Design
EPA Program to Promote Superior Energy Efficiency
TECHNICAL TRAINING Both standard and customized courses are available with hands-on activities and demonstrations. Instruction is offered at Yaskawa locations, as well as during traveling road shows. This is supplemented by live web classes and e-Learning modules / videos to provide the right level of training to fit your needs. Trainers are degreed engineers with extensive industry experience.
4
DEFECT PREVENTION Yaskawa manufacturing processes are designed to prevent defects. Production associates have paperless on-line resources at their workstations, providing highly detailed and up-to-date work instructions for every process step. Practice mechanisms are available in the Kaizen center for them to improve their assembly skills. Complex assemblies are made simple with the use of animations and video. These processes enable us to approach our ultimate goal of zero-defect manufacturing.
Cotización: https://podio.com/webforms/19719714/1335065
PRODUCT QUALIFICATION/TESTING No other manufacturer puts its products through as many tests, or as arduous a testing process, as Yaskawa. All printed circuit boards are functionally tested while under power. All Yaskawa products are 100% tested under full current. Yaskawa conducts its own product qualification testing in its ISO certified test lab. Products are tested not only under normal spec conditions, but also for the following: • Extreme Temperature/Humidity • Vibration • Package Drop • Input Voltage Tolerance • Noise Immunity • Electrical Insulation Stress • Under/Over Voltage Protection
xbombas@gmail.com
• Momentary Power Loss • Output Short Circuit Protection • Overload Protection • Ground Fault Protection • Washdown Test • Input/Output Phase Loss Test • Power ON/OFF and Start-Up Iterations
Energy Efficiency with Reduction of Carbon Footprint
5
IQPUMP 1000 & MICRO
PACKAGES FOR ANY ENVIRONMENT
Yaskawa offers quick lead time on cost-effective iQpump drive standard packages. You can also get standard packages configured to meet your custom requirements.
NEMA 3R PACKAGES FOR IQPUMP1000 AND IQPUMP MICRO iQpump1000 and iQpump Micro configured packages are also offered with a NEMA 3R (UL Type 3R) enclosure option. This enclosure can be installed in direct sunlight without the need for additional cooling or sunshade protection. Standard construction features include:
NEMA 1 PACKAGES FOR IQPUMP1000 Yaskawa offers a standard NEMA 1 (UL Type 1) package for iQpump1000 drives and configured units. All units are UL rated, with the configured packages built to UL 508A (Industrial Control Panel) standards. Installation, setup, service and quick delivery have all been considered in these package designs.
FULLY-ENGINEERED PACKAGES FOR IQPUMP1000 Both end users and OEM customers have come to rely on our custom product engineering capabilities. These products are based off of our standard configurations, but can evolve into a totally customized package.
Standard construction features include:
Engineered packages include:
• 12-Gauge Steel • Padlock Hasp • Whole Door Gasket • Integral ¼ Turn Door Latches • Lifting Eyes • Removable Air Filter from Outside of Cabinet
• Redundant Drive Packages • 12- or 18-Pulse Configurations • Soft Start Bypass Packages • Integrated Trap Filter Packages • Multiple Motor Configurations
NEMA 12 PACKAGES FOR IQPUMP1000 iQpump1000 configured packages are available with a NEMA 12 (UL Type 12) enclosure option. Fans, when required, are provided with Type 12 rated filters to maintain a Type 12 rating on the enclosure.
6
• 12-Gauge Steel • Padlock Hasp • Whole Door Gasket • Integral ¼ Turn Door Latches • Brass Hinges • UV/Type 3R Keypad Membrane • Lifting Eyes • Sun Reflective White Powder Coat Paint • Stainless Steel Hardware
Cotización: https://podio.com/webforms/19719714/1335065
Engineered packages can be provided as NEMA 1, 12 or 3R. Theyare supported with custom engineered drawings and documentation.
xbombas@gmail.com
7
IQPUMP 1000 & MICRO
DESIGN CONTROLS PUMP SPECIFIC HAND-OFF-AUTO (H-O-A) OPERATOR What makes iQpump drives the industry standard is the simplicity of the operator keypad messages that are formatted in pump terminology. This informs the user about the status of the system operation along with alarms or specific pump algorithm functions that are being initiated.
Designed with the user in mind
Application macros: • Constant Pressure • Pump Down Level Control • General Purpose Mode
Keypad Screen
• Submersible Motor, General Purpose, Operator Control • Geothermal Control*
iQpump drives use intuitive pump-related terminology with simple process control selection of engineering units such as PSI, GPM, feet, meters, degrees, inches of mercury and many other units.
SYSTEM PRESSURE SETPOINT
1 1 3
2
CONTROL OPERATION STATUS
2
4
3
5
PUMP MOTOR OUTPUT FREQUENCY
4 5
REAL-TIME CLOCK iQpump drives are supported with a real-time clock that will log the last 10 fault events with a date and time stamp to provide the pump service technicians with real data for troubleshooting. This feature also enables the user to set calendar run and stop configurations, allowing the system to avoid high utility kW rates during peak operation hours.
DATE & TIME STAMP
TRANSDUCER FEEDBACK DRIVE STATUS MONITORS
• Vertical Turbine Pump Pressure Control (VTC)* • Pivot Panel VTC* • Advanced Constant Pressure* *Not Supported with iQpump Micro
PRE-PROGRAMMED APPLICATION MACROS Pre-programmed application presets reduce start-up time significantly. Users enter simple motor and application information within the pump quick setup menu for each of the application macros. CONSTANT PRESSURE
GEOTHERMAL CONTROL
GENERAL PURPOSE
ADVANCED PRESSURE CONTROL
VERTICAL TURBINE PRESSURE CONTROL
SUBMERSIBLE MOTOR GENERAL PURPOSE
PUMP DOWN LEVEL CONTROL PIVOT PANEL VERTICAL TURBINEPRESSURECONTROL
8
Cotización: https://podio.com/webforms/19719714/1335065
xbombas@gmail.com
9
IQPUMP 1000 & MICRO
SIMPLEX PUMP FEATURES
Investing made easy The most common applications are simplex (single pump) constant pressure and pump down level control. iQpump drives are an easy investment choice with preset application macros, dedicated pump control features and pump system protection.
SLEEP MODE MINIMUM FLOW PROTECTION Protects and shuts down the pump at low speeds or in low flow conditions. NO FLOW / DEADHEAD PROTECTION Detects changes in pressure and flow when the system has been closed off via mechanical valves or restrictions. If a system is not protected from this condition, the water within the pump can vaporize, building up excessive heat that can damage the pump and the discharge piping.
WELL PUMP
SUBMERSIBLE MOTOR THRUST BEARING CONTROL Protects the bearings of submersible pump motors by ensuring proper start-up speeds and times.
3-Phase Power Input Pressure Feedback Pressure Tank
Pressure Gauge Pressure Transducer Discharge (Constant Pressure to System)
3-Phase Output to Submersible Motor
AUTOMATIC SYSTEM RESTART Programmable timers allow iQpump drives to automatically restart the system in Auto Mode for faults relating to brown outs, loss of power and pump specific faults. LOSS OF PRIME (LOP) / PUMP DRY-RUN PROTECTION Loss of prime protection is a feature protecting the pump and motor from damage caused by running the pump without water. If a pump were to lose prime and continue to operate without water moving through the pump, the pump would develop heat which would eventually damage the pump seal, motor, pipe manifold and related components.
Pump
LOW- AND HIGH-PRESSURE FEEDBACK DETECTION iQpump drives continuously monitor the system feedback device to provide a warning alarm or fault based on the programmed level.
BOOSTER PUMP 3-Phase Power Input
Pressure Feedback
Pump Motor Pressure Tank
Pressure Gauge
Discharge (Constant Pressure to System)
Product Features: • Sleep Mode Minimum Flow Protection • No Flow / Deadhead Protection • Submersible Motor Thrust Bearing Control • Automatic System Restart • Sleep Boost • Low and High Pressure Feedback Detection • Impeller Anti-jam Protection • Power Loss Utility Start Delay Timer • Loss of Prime (LOP) / Pump Dry-Run Protection • Pre-Charge Control (Controlled Pipe Fill)
IMPELLER ANTI-JAM AUTOMATIC CONTROL Provides a method for the iQpump drive to detect high current and attempt to expel corrosion or solids which are impeding the pump impeller. The system will perform a quick reversal attempt to dislodge a jam.
• Constant Pressure with Well Drawn Down Control
POWER LOSS UTILITY START DELAY TIMER Used in conjunction with “Automatic Restart”, a programmable timer will delay starting to allow for multiple pumps to sequence start on loss of power. This function ensures that the power system is not stressed when utility power has returned and the pump system is automatically restarted.
• Impeller De-scaling / De-ragging Control
• Optional Dual Transducer Feedback for Redundancy
SLEEP BOOST Intended for use with a pressure tank, the iQpump drive boosts the set pressure prior to shutdown, extending the pump’s sleep time, reducing cycling and saving energy. PRE-CHARGE CONTROL (CONTROLLED PIPE FILL) This programmable feature eliminates water hammer and extends system life by gradually filling a pipeline before normal full pressure and flow operation. Pump motor speed can be controlled with a system timer, level or pressure control device to indicate when normal operation may begin.
TANK LEVEL
3-Phase Power Input
High Water Level (Float Switch or Liquid Level Sensor)
CONSTANT PRESSURE WITH WELL DRAW DOWN CONTROL* This function allows the iQpump drive to control constant pressure when there is adequate water in the well, while monitoring a second down hole transducer for water level. If the water level drops below user settings, the iQpump drive reduces pump speed to maximize well output. The system will return automatically to normal operation when well water is recharged to an adequate level.
Tank Level Feedback Either by Ultrasonic or Submersible Transducer
Ultrasonic or Submersible Transducer
Setpoint Level Pump Motor
Low Water Level Outlet
SECONDARY TRANSDUCER BACKUP* This option used for Simplex control allows for a secondary backup transducer to be automatically used if the main transducer has failed. The keypad text message will alert what feedback transducer is being used.* * Not Supported with iQpump Micro
10
Cotización: https://podio.com/webforms/19719714/1335065
xbombas@gmail.com
11
IQPUMP 1000 & MICRO
DRIVE-TO-DRIVE MULTIPLEXING FEATURES
PUMP ALTERNATION From duplex to quadplex systems, the pumps will be exercised evenly to ensure that they receive equal run times, thereby increasing the life cycle of the pumps and motors.
When ultimate pump control flexibility matters iQpump drives have enhanced software not available in standard variable frequency drives, allowing for multiple drives to operate as a coordinated system. This allows pump system engineers the ability to add more modular pump systems together (Duplex, Triplex, etc.) to meet customer specifications and minimize cost by eliminating external control via PLCs and HMIs. 3-Phase Power Input
Pressure Feedback Minimum of a One Transducer Required For System Operation
RS485 Onboard Communication
• Pump Alternation by means of run time hours or actual date and time
PUMP AND DRIVE REDUNDANCY If a drive or pump fails during operation, or is taken out of service for maintenance, the remaining pumps continue to operate. The other drives on the network will automatically recognize when the drive and pump are restored to active healthy status and put them back into the pump rotation.
• Ability to change parameters system wide by means of programming one drive
TRANSDUCER FEEDBACK REDUNDANCY Systems can be configured using multiple transducers on the discharge allowing for redundancy. A minimum of one transducer is required for system operation.
• Transducer Feedback Redundancy
JOCKEY PUMP CONTROL Pressure booster systems that use a jockey pump to maintain minimum water flow with larger secondary booster pumps for peak demand require the jockey pump to always be defined as the lead pump. The larger booster pumps will alternate based on time or run cycle for even pump wear.
• Pump and Drive Redundancy
• Pump Run Priority Selection • Jockey Pump Control • Pump Stage and De-Stage • Lag Pump Lead Speed Follower Mode
LAG PUMP LEAD SPEED FOLLOWER MODE When enabled, all lag iQpump drives will follow the main output speed (Hz or RPM) of the lead iQpump drives, thereby allowing all lead and lag pumps to run at the same speed for better system efficiency. PUMP STAGE AND DE-STAGE System dynamics and pump curves will determine the best method of pump staging and de-staging. The user can select a variety of methods such as: pump output speed, pressure differential to setpoint, combination of output speed and differential pressure and flow rate using an in-line flow meter.
Flow Feedback (Optional) Suction Pressure Feedback (Optional)
Product Features:
Up to 8 pumps for iQpump1000
Pump Motor n
Pump Motor 4
Pump Motor 3
Pump Motor 2
Pump Motor 1
*Pressure Transducer
Up to 4 pumps for iQpump Micro
Pressure Gauge
Typical Multiplex Keypad Messages
Pressure Transducer
Discharge Suction
Optional Individual Transducers For Feedback Redundancy
APPLICATION NOTES: • Automatically alternates all pumps with a system programmable timer to provide even mechanical pump wear.
The iQpump LCD keypad (recommended option on iQpump Micro) will provide the user with all the necessary system status operation and pump fault messages to ensure that service operators can efficiently monitor and diagnose any condition.
• Configurable transducer feedback settings to provide redundant backup, if failure occurs.
• With the use of an optional suction transducer, all iQpump drives will monitor inlet pressure with programmable PSI settings for faults, alarms and station controlled shutdown.
• Digital switch inputs for Low Suction / Low City Pressure / Low Water in Break Tank can be configured with a selectable keypad message to match application. With the use of an optional flow input, all iQpump drives can be configured to control staging and de-staging of lag pumps on GPM.
12
Cotización: https://podio.com/webforms/19719714/1335065
IQPUMP DRIVE IS IN OFF MODE (STOPPED)ANDHASNOTBEEN GIVEN AN AUTO RUN COMMAND. DRIVE IS TAKEN OUT OF THE RUNNING QUEUE.
xbombas@gmail.com
IQPUMP DRIVE IS IN AUTO MODE AND WAITING FOR A RUN COMMAND FROM THE NETWORK.
IQPUMP DRIVE IS IN AUTO MODE AND IS THE LEAD PUMP.
IQPUMP DRIVE IS IN AUTO MODE AND WHEN A NEW LEAD PUMP IS STAGED, THE LAG PUMP WILL BE LOCKED AT A FIXED SPEED.
13
IQPUMP 1000
CONSTANT SPEED LAG PUMP MULTIPLEXING
INLET SUCTION CONTROL When installed with an inlet suction transducer, the iQpump drive monitors suction pressure drop to a programmed pressure setpoint. It seamlessly switches over to control suction pressure, so the system runs efficiently. If the inlet pressure returns to the suction pressure setpoint, the iQpump drive will switch back to controlling outlet pressure. A suction pressure alarm/fault detection is available, if the suction pressure drops below the Low Suction Pressure Detection Level for more than the Low Suction Pressure Detection Time.
Enabling multiple large vertical turbine pumps
SPEED REDUCTION “GO TO SPEED” AFTER LAG PUMP STAGING Forces the lead iQpump drive, when in VTC mode, to operate at a lower fixed speed for a specified amount of time whenever a lag pump is staged on. This dampens the shock loading of a lag pump starting across the line to the system.
Many agricultural farms use multiple large vertical turbine pumps to provide pressurized water to large pivot irrigation systems. Applying a VFD to each of the booster pumps on these systems may not be practical. However, an iQpump drive, using its on-board digital outputs, can control up to 5 lag pump starters from a single VFD to maintain pressure by staging and de-staging the lag pumps. 3-Phase Power Input
Option Card
2 Additional Lag Pumps With Digital Option Card DO-A3
• Setpoint Boost After De-staging • Low Flow and High Flow (GPM) Protection • Flow Meter Data Logging • Lube Pump Control • Hard Current Limit • Back Spin Timer • High Discharge Pressure Lag Pump Quick de-Staging
BACK SPIN TIMER After “Stop” or “Hand” command, the iQpump drive will not restart until the timer expires, allowing the water column to flow back down the well.
Motor Starter
Motor Starter
Motor Starter
Lag Pump 4
Lag Pump 5
Pressure Gauge
Lag Pump 3
Lag Pump 2
Lag Pump 1
Lead Pump 1
*Pressure Transducer
Motor Starter
• Speed Reduction “Go To Speed” After Lag Pump Staging
HARD CURRENT LIMIT As the pump impeller wears over time, it changes the efficiency of the pump. In order to maintain a constant pressure or flow the pump speed will increase, resulting in greater motor current. This can cause the drive to trip on nuisance motor overload (OL).
Pressure Feedback Suction Pressure Feedback (Optional)
Motor Starter
LOW FLOW AND HIGH FLOW (GPM) PROTECTION iQpump drives continuously monitor the system flow signal feedback to provide a warning alarm or fault based on the programmed level.
• Inlet Suction Control
FLOW METER DATA LOGGING Through a secondary analog or pulse train input, a flow sensor can be connected inline with the pump system back to the iQpump drive to read and accumulate total system flow to report to authorities. The system can be configured to detect “No Flow” and switch to “Sleep” on low demand.
Flow Feedback (Optional)
Standard Control 3 Lag Pumps
SETPOINT BOOST AFTER DE-STAGING Automatically boosts the auto setpoint pressure to a new specified incremental amount for a programmable time whenever a pump is de-staged. This allows the lead iQpump drive, when in VTC mode, to accelerate more quickly to lessen the pressure drop on the system of a lag pump that is being de-staged.
Product Features:
Flow Meter
Multi-Plex River Booster System. Discharge
Pressure Transducer Suction
APPLICATION NOTES:
• Automatically starts and stops up to 5 Lag pumps based on the system demand, and will automatically stage and de-stage the booster pumps. • Alternation of lag pumps to provide even wear. • Allows a single lag pump to be selected during Pre-Charge (Pipe Fill) to reduce fill rate time. • For large water consumers, acre-feet can be selected for water accumulation units.
• When the discharge pressure exceeds a high level setting, all running lag pumps will be quickly de-staged to prevent unsafe high pressure conditions.
• When using Pre-Charge, Lag Pump Staging and De-Staging functions, the drive’s keypad will provide a message of time remaining before pre-charge is finished and/or time remaining before lag pumps are to stage and de-stage.
14
Cotización: https://podio.com/webforms/19719714/1335065
xbombas@gmail.com
15
IQPUMP 1000 & MICRO
SINGLE-PHASE
SYSTEM PROTECTION
Making the most of single-phase Single-phase motor control is limited and challenging, Yaskawa makes the complicated simple combining the latest in power conversion technology with the straightforward iQpump drives.
PUMP FAULT AND ALARMS iQpump drives provide a comprehensive set of pump related alarms and faults. Faults are displayed on the keypad in clear text to eliminate confusion (the following is just a sample): • Over Cycling • Set Point Not Met • Transducer Feedback Lost (Broken Pipe Detection) • No Flow • Over Torque • Low and High Feedback Detection • Pumping Over Cycle Protection • Loss of Prime/Dry Run • Pump Cavitation Protection
Yaskawa’s industry leading Single Phase Converter (SPC) cleanly converts single-phase AC power to DC power for Yaskawa variable frequency drives. The SPC marries Yaskawa reliability and drive technology with motor control solutions for businesses in remote areas. The SPC eliminates the need to oversize variable frequency drives for singlephase applications while reducing distortion to less than 10% iTHD. With lower input harmonics and near unity power factor, the SPC also eliminates the need to significantly oversize transformers in single-phase applications, reducing overall installation costs.
Converting Single-Phase to Three-Phase Power SYSTEM ADVANTAGES 1. Less than 10% iTHD reduces installation costs 2. Eliminates the need for drive oversizing 230 to 240V and 460 to 480V Single-Phase Power Supply
Single Phase Converter
iQpump1000
Three Phase Motor
3. Three-phase motors are more efficient and less expensive than single-phase motors 4. No rotating parts needed for phase conversion 5. UL listed.
Choke
16
Cotización: https://podio.com/webforms/19719714/1335065
MOTOR PROTECTION • Output Phase Loss • Motor Over Temperature • Hard Current Limit • Ground Fault • Broken Shaft • Motor Overload • Minimum Speed
xbombas@gmail.com
IQPUMP DRIVE PROTECTION • Over / Under Voltage • Short Circuit • Input Phase Loss • Over Temperature • Phase Imbalance • Heatsink Fan Failure
17
IQPUMP 1000 VS IQPUMP MICRO
HARDWARE COMPARISON
SOFTWARE COMPARISON
FEATURES FEATURES
IQPUMP1000
IQPUMP MICRO
1 - 175HP 200 - 240V 3-Phase
1 - 5HP 200 - 240V 1-Phase
1 - 500HP 380 - 480V 3-Phase
1 - 25HP 200 - 240V 3-Phase
2 - 250HP 500 - 600V 3-Phase
1 - 25HP 380 - 480V 3-Phase
Real Time Clock
Standard (Mounted on Drive)
With Optional Remote H-O-A Operator Installed
H-O-A Operator
Standard (Mounted on Drive)
Option (Externally Mounted)
24V @ 150mA
24V @ 30mA
Analog Inputs
Qty 3 - Programmable 0-10VDC or 4-20mA
Qty 1 - Non-Programmable 0-10VDC Qty 1 - Programmable 0-10VDC or 4-20mA
Analog Outputs
Qty 2 - Programmable 0-10VDC or 4-20mA
Qty 1 - Programmable 0-10VDC
8 Programmable
7 Programmable
Qty 1 - Form C Fault Relay (Non-Programmable) Qty 1 - Form C Programmable Relay Qty 2 - Form A Programmable Relay
Qty 1 - Form C Fault Relay Programmable Qty 2 - Programmable Photo-Couplers
Standard
Not Used
2 Additional Programmable Analog Outputs 2 Additional Programmable Digital Outputs
Not Available
RS-485/422
RS-485/422
Voltage / HP Range
Transducer Power Supply
Digital Inputs Digital Outputs Pulse Input Expansion I/O Adapters Standard Communications
EtherNet/IP Communications Network Options
Modbus TCP/IP PROFIBUS-DP PROFINET
18
DeviceNet MetaSys Apogee BACnet LonWorks
Cotización: https://podio.com/webforms/19719714/1335065
Not Available
Pump Control Configurations (P1-01 Group): Simplex Drive to Drive Multiplexing Simplex with Constant Speed Lag Multiplexing (VTC Mode) Pre-Programmed Application Macros (A1-03 Group): Constant Pressure Pump Down Constant Level General Purpose Mode - External Run and Speed Reference Submersible Motor General Purpose Mode Using Digital Operator Geothermal Mode VTC (Vertical Turbine) Pressure Control with Lag Pump Multiplexing Advanced Pressure Control Pivot Panel Run VTC (Vertical Turbine) Pressure Control Pump Specific Software Features: Selectable Engineering System Units Sleep Mode / Minimum Flow Start Level / Drawdown Hand Mode Control Operations Minimum Pump Speed Transducer feedback Scaling No Flow / Deadhead Protection Submersible Thrust Bearing Control Automatic Fault Restarts for Drive and Pump Protection Sleep Boost Low and High Feedback Detection Low and High Water Float Inputs Pump Over Cycle Protection Impeller Anti-jam Protection Loss of Prime (LOP) / Well Dry Run Automatic Power Loss Utility Start Delay Broken Pipe Protection Transducer Feedback Loss Transducer Feedback Loss with Programmable GOTO speeds Pre-Charge / Controlled Pipe Fill Hard Current Limit Over Torque Detection Pump Back Spin Timer Single Phase Loss Speed Foldback Protection Multiplex Drive to Drive Pump Setup and Adjustments Pulse Input for Flow Meter Control and Water Usage Data Logging Pump De-Scale / De-Ragging Measuring Water Well Drawdown via transducer with Constant Discharge Pressure Inlet Suction Pressure Control via Transducer Feedback Real Time Clock Sequence Drive On/Off Run Timers Secondary Transducer Input for Redundancy in Simplex and Multiplex Mode
xbombas@gmail.com
IQPUMP1000
IQPUMP MICRO
Up to 8 Pumps
Up to 4 Pumps
= Not Supported
= Supported
19
IQPUMP MICRO
IQPUMP 1000
MODELS & SPECIFICATIONS Model Number
MODELS & SPECIFICATIONS Model Number
CIMR-PW 2 V 0006 F A A Design Revision
AC Drive iQpump Series No.
Voltage Class
BV
1-phase, 240V iQpump Micro
2V
3-phase, 240V iQpump Micro
4V
3-phase, 480V iQpump Micro
No.
Environmental Specification
A
Standard
CIMR - PW 2 A
Output Current Code (A)
Enclosure Type
F
IP20/NEMA 1 Type
G
NEMA Type 4X (IP66)
Note: Current codes are equivalent to the current rating.
Dimensions (in.)
Dedicated Single-Phase, 240V
NEMA 1 (CIMR-PWBV-XXXX-FAA)
Max Capacity (HP)
Rated Current (A)
Height
Width
Depth
Height
Width
1
6.0
5.89
4.25
6.47
10.04
7.36
9.25
CIMR-PWBV0010
3
9.6
5.89
4.25
7.12
10.04
7.36
9.25
CIMR-PWBV0012
3
12.0
6.02
5.51
7.48
10.04
7.36
9.25
CIMR-PWBV0018
5
17.5
6.02
6.69
8.15
Without Additional Input Reactor
Model Number Max Capacity (HP)
CIMR-PW2V0006
1.5
Rated Current (A)
Max Capacity (HP)
6.0
1
Rated Current (A)
With Additional Input Reactor Max Capacity (HP)
4.9
1
Rated Current (A)
4.9
NEMA 1 (CIMR-PWBV-XXXX-FAA)
Height
Width
Depth
Height
Width
Depth
5.89
2.68
6.10
8.74
6.38
7.28
9.6
1.5
6.8
1.5
6.8
5.89
4.25
6.14
10.04
7.36
9.25
2
7.5
2
7.5
5.89
4.25
6.47
10.04
7.36
9.25
CIMR-PW2V0020
5
19.6
2
9.7
3
12.3
6.02
5.51
6.69
10.04
7.36
9.25
CIMR-PW2V0030
7.5 / 10
30
2
7.5
3
15.2
10.0
5.51
6.57
16.54
11.42
12.01
CIMR-PW2V0040
10
40
5
16.7
5
21.0
10.0
5.51
6.57
16.54
11.42
12.01
CIMR-PW2V0056
15 / 20
56
5
23.4
7.5
27.7
11.42
7.09
7.48
16.54
11.42
12.01
10
30.8
14.09
8.66
8.42
18.31
11.42
12.01
480V- Three-Phase Models Single-Phase, 480V De-Rate (NEMA 1, 4X) - (Continuous Full Power)
Dimensions (in.)
3-Phase, 480V Ratings Without Additional Input Reactor
Model Number
CIMR-PW4V0002
5A
3-phase, 600V
With Additional Input Reactor
NEMA-4X
NEMA 1
No.
Enclosure Type
A
IP00 (Protected Chassis)
F
NEMA Type1
U
Flange (Type 12 backside)
Output Current Code (A) See Following Charts
NEMA-4X (CIMR-PWBV-XXXX-GAA)
12.0
25.8
6-phase, 12-pulse, 480V
3-Phase Input, 240V
3
7.5
3-phase, 480V
4T
Model Number
2/3
69
3-phase, 240V
4A
Standard
No.
Dimensions (in.)
CIMR-PW2V0010
25
2A
Environmental Specification
A
240V - Three-Phase Models
Not Available
CIMR-PW2V0012
CIMR-PW2V0069
Voltage Class
No.
Depth
240V - Three-Phase Models Single-Phase, 240V De-Rate (NEMA 1, 4X) - (Continuous Full Power)
No.
NEMA-4X (CIMR-PWBV-XXXX-GAA)
CIMR-PWBV0006
3-Phase, 240V Ratings
Design Revision
iQpump1000 Series No.
See charts below
Model Number
F A A
AC Drive
No.
240V - Dedicated Single-Phase Models
0004
Single-Phase Input, 240V; 3-Phase Output, 208-230V Maximum 1.15 Service Factor Without Additional Input Reactor
With Additional Reactor
iQpump1000 Dimensions
Weight (lb)
Rated Current (A)
Max Capacity (HP)
Max Capacity (HP)
Max Capacity (HP)
Height
Width
CIMR-PW2A0004
3.5
3/4
1/3
1/2
12.06
5.51
5.79
7.3
--
CIMR-PW2A0006
6
1
3/4
3/4
12.06
5.51
5.79
7.3
--
CIMR-PW2A0008
8
2
1
1
12.06
5.51
5.79
7.5
--
CIMR-PW2A0010
9.6
3
1
1
12.06
5.51
5.79
7.5
--
Depth
NEMA 1
Protected Chassis
CIMR-PW2A0012
12
3
1.5
2
12.06
5.51
5.79
7.5
--
CIMR-PW2A0018
17.5
5
2
3
12.06
5.51
6.46
8.2
--
CIMR-PW2A0021
21
7.5
2
3
12.06
5.51
6.46
8.2
--
CIMR-PW2A0030
30
10
3
3
12.06
5.51
6.57
9.3
--
CIMR-PW2A0040
40
15
3
5
12.06
5.51
6.57
9.3
--
CIMR-PW2A0056
56
20
7.5
7.5
13.38
7.09
7.36
13.0
--
CIMR-PW2A0069
69
25
7.5
10
15.47
8.66
7.76
20.1
--
CIMR-PW2A0081
81
30
10
15
15.47
8.66
7.76
22.0
--
CIMR-PW2A0110
110
40
10
10
21.37
10.00
10.16
50.7
46.2
CIMR-PW2A0138
138
50
15
15
24.52
10.98
10.16
61.7
55.0
CIMR-PW2A0169
169
60
20
20
30.08
12.95
11.14
90.2
81.4
Max Capacity (HP)
Rated Current (A)
Max Capacity (HP)
Rated Current (A)
Max Capacity (HP)
Rated Current (A)
Height
Width
Depth
Height
Width
Depth
CIMR-PW2A0211
211
75
25
25
30.08
12.95
11.14
92.4
83.6
1
2.1
0.5
1.3
0.5
1.7
5.89
4.25
4.96
8.74
6.38
7.28
CIMR-PW2A0250
250
100
30
30
37.80
17.95
12.99
191.8
167.6
CIMR-PW2A0312
312
125
40
40
37.80
17.95
12.99
191.8
176.4
CIMR-PW2A0360
360
150
50
50
45.98
19.84
13.78
233.7
216.1
CIMR-PW2A0415
415
175
60
60
45.98
19.84
13.78
233.7
218.3
CIMR-PW4V0004
2
4.1
1
2.4
1
2.8
5.89
4.25
6.47
8.74
6.38
7.28
CIMR-PW4V0005
3
5.4
1.5
3.5
2
3.9
5.89
4.25
7.12
10.04
7.36
9.25
CIMR-PW4V0007
3
6.9
1.5
3.5
2
5.4
5.89
4.25
7.12
10.04
7.36
9.25
CIMR-PW4V0009
5
8.8
2
5.1
3
5.5
5.89
4.25
7.12
10.04
7.36
9.25
CIMR-PW4V0011
7.5
11.1
3
5.5
3
7.5
6.02
5.51
6.69
10.04
7.36
9.25
CIMR-PW4V0018
10
17.5
2
4.5
5
8.7
10.0
5.51
6.57
16.54
11.42
12.01
CIMR-PW4V0023
15
23
3
5.5
5
10.5
10.0
5.51
6.57
16.54
11.42
12.01
CIMR-PW4V0031
20
31
3
7.9
7.5
13.5
11.42
7.09
6.69
16.54
11.42
12.01
CIMR-PW4V0038
25
38
5
11.3
10
16.1
11.42
7.09
7.48
16.54
11.42
12.01
NOTES: Reference User Manual for proper drive sizing when using service factors larger than 1.15 When two or more drives in the same voltage class have the same power rating any drive with that rating can be selected
NOTES: Reference User Manual for proper drive sizing when using service factors larger than 1.15 When two or more drives in the same voltage class have the same power rating any drive with that rating can be selected
20
Cotización: https://podio.com/webforms/19719714/1335065
xbombas@gmail.com
21
IQPUMP 1000
IQPUMP 1000
MODELS & SPECIFICATIONS
MODELS & SPECIFICATIONS
480V - Three-Phase Models
600V - Three-Phase Models
3-Phase Input, 480V
Model Number
Single-Phase Input, 480V; 3-Phase Output, 460V Maximum 1.15 Service Factor
3-Phase Input, 600V Weight (lb)
iQpump1000 Dimensions
Model Number
Without Additional Input Reactor
With Additional Input Reactor
Max Capacity (HP)
Max Capacity (HP)
Height
Width
Depth
NEMA 1
Protected Chassis
Single-Phase Input, 600V; 3-Phase Output, 575V Maximum 1.15 Service Factor
iQpump Dimensions
Weight (lb)
Without Additional Input Reactor
With Additional Input Reactor
Max Capacity (HP)
Max Capacity (HP)
Height
Width
Depth
NEMA 1
1&2
1
1.5
12.06
5.51
5.79
7.3
--
3
1.5
2
12.06
5.51
5.79
7.3
--
6.1
5
2
3
12.06
5.51
6.46
8.2
--
9
7.5
3
5
12.06
5.51
6.46
8.2
--
CIMR-PW5A0011_AA
11
10
2
3
12.06
5.51
6.57
9.3
--
--
CIMR-PW5A0017_AA
17.5
15
5
5
13.38
7.09
7.36
13.0
--
--
CIMR-PW5A0022_AA
---
Rated Current (A)
Max Capacity (HP)
CIMR-PW4A0002_AA
2.1
1
1/3
1/2
12.06
5.51
5.79
7.3
--
CIMR-PW4A0004_AA
4.1
2
3/4
1
12.06
5.51
5.79
7.3
--
CIMR-PW4A0005_AA
5.4
3
1
1.5
12.06
5.51
5.79
7.3
CIMR-PW4A0007_AA
6.9
4
1.5
2
12.06
5.51
6.46
8.2
CIMR-PW4A0009_AA
8.8
5
2
3
12.06
5.51
6.46
CIMR-PW4A0011_AA
11.1
7.5
2
3
12.06
5.51
Rated Current (A)
Max Capacity (HP)
CIMR-PW5A0003_AA
2.7
CIMR-PW5A0004_AA
3.9
--
CIMR-PW5A0006_AA
--
CIMR-PW5A0009_AA
8.2
--
6.46
8.2
Protected Chassis
CIMR-PW4A0018_AA
17.5
10
3
3
12.06
5.51
6.57
9.3
22
20
5
7.5
13.38
7.09
7.36
13.0
CIMR-PW4A0023_AA
23
15
3
5
12.06
5.51
6.57
9.3
--
CIMR-PW5A0027_AA
27
25
7.5
10
15.47
8.66
7.76
20.1
CIMR-PW4A0031_AA
31
20
7.5
7.5
13.38
7.09
6.88
12.5
--
CIMR-PW5A0032_AA
32
30
7.5
10
15.47
8.66
7.76
20.1
--
CIMR-PW4A0038_AA
38
25
7.5
10
13.38
7.09
7.36
13.0
--
CIMR-PW5A0041_AA
41
40
15
15
20.62
11.35
10.16
59.4
59.4
CIMR-PW4A0044_AA
44
30
10
10
15.47
8.66
7.76
20.1
--
CIMR-PW5A0052_AA
52
50
15
15
20.62
11.35
10.16
59.4
59.4
CIMR-PW4A0058_AA
58
40
15
15
18.65
10.37
10.16
50.6
50.6
CIMR-PW5A0062_AA
62
60
25
25
30.08
12.95
11.14
99.0
90.2
CIMR-PW4A0072_AA
72
50
20
20
20.62
11.35
10.16
59.4
59.4
CIMR-PW5A0077_AA
77
75
30
30
30.08
12.95
11.14
99.0
90.2
CIMR-PW4A0088_AA
88
60
20
20
25.16
13.32
10.27
85.8
79.2
CIMR-PW5A0099_AA
99
100
30
30
30.08
12.95
11.14
99.0
90.2
CIMR-PW4A0103_AA
103
75
20
20
25.16
13.32
10.27
85.8
79.2
CIMR-PW5A0125_AA
125
125
50
50
37.80
17.95
12.99
191
174
CIMR-PW4A0139_AA
139
100
40
40
30.08
12.95
11.14
99.0
90.2
CIMR-PW5A0145_AA
145
150
50
50
37.80
17.95
12.99
191
174
CIMR-PW4A0165_AA
165
125
40
40
30.08
12.95
11.14
101
92.4
CIMR-PW5A0192_AA
192
200
75
75
45.98
19.84
13.78
233
235
CIMR-PW4A0208_AA
208
150
50
50
37.80
17.95
12.99
191
174
CIMR-PW5A0242_AA
242
250
75
75
45.98
19.84
13.78
257
235
CIMR-PW4A0250_AA
250
200
60
60
45.98
19.84
13.78
233
211
CIMR-PW4A0296_AA
296
250
60
75
45.98
19.84
13.78
246
224
CIMR-PW4A0362_AA
362
300
75
100
45.98
19.84
13.78
257
235
CIMR-PW4A0414_AA UUX000861(C)
414
350
125
125
48.3
20.29
14.68
292
275
CIMR-PW4A0515_AA UUX000862(C)
515
400
125
125
61.3
26.86
14.72
504
475
CIMR-PW4A0675_AA UUX000863(C)
675
500 - 550
150
150
61.3
26.86
14.72
515
486
CIMR-PW4A0930_AA
930
600 - 800
Consult Yaskawa Factory
80.4
50.2
14.73
1394
1195
CIMR-PW4A1200_AA
1200
900 - 1000
Consult Yaskawa Factory
80.4
50.2
14.73
1420
1221
NOTES: Reference User Manual for proper drive sizing when using service factors larger than 1.15 When two or more drives in the same voltage class have the same power rating any drive with that rating can be selected
NOTES: Reference User Manual for proper drive sizing when using service factors larger than 1.15 When two or more drives in the same voltage class have the same power rating any drive with that rating can be selected.