Skip to main content

Refrigerants: Real GWP and PFAS

Page 1

Impact of Refrigerants Fact Sheet #2 (V.1.)

Refrigerants: Real GWP and PFAS IPCC AR4 (2007)

IPCC AR6 (2021)

PFAS

Refrigerants / Brand Name

Type

Composition

GWP 100 years

Real GWP 20 years

GWP 100 years

Real GWP 20 years

Yes/No

R143a

HFC

100% R143a

4470

5890

5810

7840

Yes

R125

HFC

100% R125

3500

6350

3740

6740

Yes

R134a

HFC

100% R134a

1430

3830

1530

4140

Yes

R32

HFC

100% R32

650

2330

771

2690

No

R404A Freon 404A

HFC

44% R125 / 4% R134a / 52% R143a

3922

6010

4728

7208

Yes

R407A Freon 407A

HFC

20% R32, 40% R125, 40% R134a

2102

4538

2262

4890

Yes

R410A Freon 410A

HFC

50% R125 / 50% R32

2075

4340

2255

4715

Yes

R407C Freon 407C

HFC

23% R32 / 25% R125 / 52% R134a

1768

4115

1908

4457

Yes

R452A Opteon XP44

HFC/ HFO

11% R32 / 59% R125 / 30% R1234yf

2137

4003

2292

4273

Yes

R449A Opteon XP40

HFC/ HFO

24.3% R32 / 24.7% R125 / 25.7% R134a / 25.3% R1234yf

1390

3119

1504

3383

Yes

R448A Solstice N40

HFC/ HFO

26% R32 / 26% R125 / 21% R134a / 7% R1234ze / 20% R1234yf

1379

3062

1494

3321

Yes

R449C Opteon XP20

HFC/ HFO

20% R32 / 20% R125 / 29% R134a / 31% R1234yf

1245

2847

1346

3087

Yes

R452B Opteon XL55

HFC/ HFO

67% R32 / 7% R125 / 26% R1234yf

681

2006

779

2275

Yes

R454B Opteon XL41

HFC/ HFO

68.9% R32 / 31.1% R1234yf

448

1606

531

1854

Yes

R513A Opteon XP10

HFC/ HFO

44% R134a / 56% R1234yf

629

1686

673

1823

Yes

R450A Solstice N13

HFC/ HFO

42% R134a / 58% R1234ze

601

1611

643

1742

Yes

R454C Opteon XL20

HFC/ HFO

78.5% R1234yf / 21.5% R32

140

502

166

580

Yes

R455A Solstice L40X

HFC/ HFO

75.5% R1234yf / 21.5% R32 / 3% R744

140

502

166

580

Yes

R744

Natural

CO2

1

1

1

1

No

R600a

Natural

Isobutane

<1

<1

<1

<1

No

R290

Natural

Propane

<1

<1

<1

<1

No

R1270

Natural

Propylene

<1

<1

<1

<1

No

R717

Natural

NH3

0

0

0

0

No

R718

Natural

H2O

0

0

0

0

No

R729

Natural

Air

0

0

0

0

No


Turn static files into dynamic content formats.