D100523338
2024
Systems Components Services Facility Services
SAUTER – your local partner. www.sauter-controls.com
Right of amendments reserved © 2024 Fr. Sauter AG
Catalogue Product and Systems Information
Complete solutions from a single source New building, refurbishment or building operation – SAUTER is your reliable partner for sustainability, operational safety and comfort of real estate. With our intelligent solutions for building control, room automation and technical facility management, we safeguard your investment and support you in achieving your ESG goals. We create sustainable environments. Since 1910.
The SAUTER Group •
Global company headquartered in Basel, Switzerland
•
Technology leader in the field of building automation, system integration and building services
•
Focus: maximum energy efficiency and sustainability
•
Goal: investment and operational safety throughout the entire building life cycle
•
Member of the BACnet Interest Group (BIG-EU), BACnet International, EnOcean Alliance as well as the eu.bac, KNX and DALI Alliance (DiiA)
Right of amendment reserved © 2024 Fr. Sauter AG
1
2
Right of amendment reserved © 2024 Fr. Sauter AG
Contents Field devices 2-point controllers
9
Data capture
47
Single-room, heating and air-conditioning controllers
91
Valves, control valves, dampers, actuators
127
HVAC automation
355
Room automation
397
Management level
449
Engineering tools
459
Abbreviations used
461
Alphabetical list of contents
462
Right of amendment reserved © 2024 Fr. Sauter AG
3
Y X C V
Building management
Appendix
¨ N > _
Product highlights
Smart Sensor viaSens Smart buildings need comprehensive sensor technology. The Smart Sensor viaSens measures temperature, air humidity and air quality as well as brightness, presence and sound pressure level. It also has an animated LED light ring. Multiple sensors communicate wirelessly via a Bluetooth mesh network. Effective IoT integration is possible with the secure MQTT interface of the sensor gateway.
SAUTER Vision Center The web-based building management and integration platform for operating and visualising building operations is constantly being expanded. Highlights in 2024 include new alarm features, improved user administration, audit trail updates and intrinsic security mechanisms.
modulo 6 IP coupler for I/O modules The new modu612-LC unit enables I/O and communication modules of a modulo 6 automation station to be remotely connected via the IP network. Communication is encrypted via MQTT. The integrated web server provides a secure user interface for configuration during commissioning.
4
Right of amendment reserved © 2024 Fr. Sauter AG
AXT3/AXS3 actuators for unit valves The AXT3 actuators for unit valves and AXS3 continuous actuators for unit valves with stroke indicator ensure efficient room temperature control. The range includes two basic types for different operating voltages as well as NC (normally closed) and NO (normally open) versions. There are also versions with plug-in cables for flexible use. Numerous valve adapters allow fitting on all common unit valves. OEM solutions are possible.
Redesigned room transducers with app The comprehensive range of room transducers for optional detection of temperature, humidity, VOC or CO2 now have upgraded CO2 sensors and a new, timeless design. A smartphone app is now available for individually configuring the measuring ranges and output signals of the room transducers with active signals.
modulo 6 with BACnet/SC Firmware update 2.0 for modulo 6 provides multi-layered protection for installations of any size. It supports BACnet/SC and the RADIUS protocol and has even more secure network separation. moduWebUnity, the web application for visualisation, now supports operation via touch panels and the export of measurement data for further processing with ERP systems.
Right of amendment reserved © 2024 Fr. Sauter AG
5
6
Right of amendment reserved © 2024 Fr. Sauter AG
Mobile Apps From installation to service. Mobile apps supplement the SAUTER product portfolio. They help users execute tasks or provide services remotely. Here is a handy overview of the apps that are currently available.
Overview of mobile apps (alphabetical order)
Name
Main functions
ecoUnit
•
Controlling the ecoUnit Touch room operating unit (EY-RU365)
eValveco Assistant
•
Commissioning, configuration, service and operation Creating and managing projects
•
Mobile Room Control, the Mobile Building Services app
•
modulo 6
•
Commissioning, service and operation
Smart Actuator
• • •
Commissioning, service and operation Application selection and configuration Creating and managing projects
ValveDim
•
Access to the SAUTER valve and actuator portfolio Configuring valve and actuator combinations
•
iOS
Android
Operating room functions, information and notifications for tenants, owners and operators Booking meeting rooms, assets, parking spaces and workspaces
modulo 6
•
viaSens
•
Commissioning the sensor in the SAUTER meshNet • Sensor network configuration • Basic configuration of the sensor • Calibration of the sensor • Beacon transmission capacity display
Right of amendment reserved © 2024 Fr. Sauter AG
7
On/off controllers
Proven technology developed further. Two-point controllers from SAUTER are used to limit, regulate and monitor temperature, pressure and humidity, with no auxiliary energy required. They provide reliability, even in difficult conditions.
8
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers Thermostats Overview of fan-coil room-temperature controllers
10
TSHK 681, 682: Fan-coil room temperature controller
17
TSO, TSH: Room thermostat
11
Overview of universal thermostats
19
TSHK 621...643: Fan-coil room temperature controller
13
TUC: Universal thermostat
20
TSHK 670...672: Fan-coil room temperature controller
15
Thermowells
22
Frost monitors Overview of frost monitors
24
TFL 201: Frost protection monitor/limiter with capillary-tube sensor
25
TFL 611: Continuous frost monitor
27
Pressure switches Overview of pressure switches
29
DSL, DSH: Pressure limiters
34
DSA: Pressure switches
30
DFC 17B, 27B: Pressure switch
36
DSB, DSF: Pressure monitors and pressure switches
32
DSD: Differential pressure switch
38
Humidistats HSC 120: Room humidistat
41
HSC 101: Panel-mounted humidistat
42
HBC: Duct-mounted humidistat
43
Right of amendment reserved © 2024 Fr. Sauter AG
9
Y
Fan-coil room-temperature controllers SAUTER fan-coil controllers are used for demand-led activation of fan-coil units and ensure that they are operated with optimum use of energy. There are controllers for fan-coil units with a three-speed fan and for the continuous activation of EC motors. The controllers are suitable for 2- and 4-pipe installations and also for fan-coil units with an electric reheater.
Overview of fan-coil room-temperature controllers
Type designation Indicating and operating elements Mode switch for heating Mode switch for cooling Mode switch for fan Setpoint adjuster LCD Method of operation Load (A) External sensor 2-pipe installation 4-pipe installation C/O (changeover) Further information
10
TSO, TSH
TSHK 621…643
TSHK 670…672
TSHK 681…682
• • • • −
• • • • −
• • • • −
− − • • •
≤ 10 − − − − Page 11
≤6 − • • − Page 13
≤ 10 − − • − Page 15
≤6 • • • • Page 17
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Thermostats
TSO, TSH: Room thermostat Features • Variable room temperature as setpoint based on printed temperature scale
Y
• Variants of the standard devices are available, such as thermal feedback, night set-back mode, fan switches
and switches for heating/cooling • Setpoint adjuster with mechanical min. and max. limitation of the setting range
Technical data TSO67*F001
Power supply
Load1)
230 V~ 10(2,5) A, 24 V= max. 1 A, 24 V~ min. 0.2 A
Setting range Night-time reduction (N/R) Time constant in still air Time constant in moving air (0.2 m/s) Proportional band Shortest switching interval
5...30 °C Approx. 5 K 17 minutes 13 minutes Approx. 3 K Approx. 19 minutes (E = 0.5)
TSO67*F001
Parameters
Thermal feedback
TSH67*F002 E 1
Ambient conditions
Ambient temperature
0...50 °C 0,5
Weight Dimensions Housing Housing material Fitting Cable inlet Baseplate Screw terminals
0.11 kg 76 × 76 mm Pure white (RAL 9010) Fire-retardant thermoplastic Wall/recessed At rear Black thermoplastic with membrane sensor and contact system For electrical cables of up to 1.5 mm²
Standards, directives
Type of protection Protection class Energy class
CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP20 (EN 60529) II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC EN 60730-1, EN 60730-2-9 EN 60730-1
Xs xi
0 Xp
Xt/2 E=0,25
E=0,50
E=0,75
B01806_de
Construction
E= control factor
Overview of types
/
Supply voltage: 10% more voltage means proportional band approx. 4 K, switching period 15 minutes and actualvalue reduction approx. 0.5 K
/
H/C = heating or cooling, depending on connection; H//C = heating or cooling, selectable
Type
Operating mode switch
Output for
Power supply
TSO670F001
-
H/C
-
TSH670F002
-
H/C
230 VAC, ± 10%, 50...60 Hz
TSH676F002
-
H/C
230 VAC, ± 10%, 50...60 Hz
1)
For TSO672F001 for cooling 5(1.5) A
Right of amendment reserved © 2024 Fr. Sauter AG
11
2-point controllers | Thermostats
A A A
Y
TSO670F001, TSO672F001: Switching difference 1.3 K without thermal feedback2) TSH670F002, TSH676F002: Dynamic switching difference 0.5 K with thermal feedback3) TSH676F002: Additional feature N/R (normal/reduced) for external clock
Accessories Type
Description
0362225001
Intermediate plate, pure white, for wall mounting on recessed junction box
2)
3)
12
Devices without thermal feedback are pure 2-point controllers. The static switching difference is given, i.e. for very slow changes in temperature. For faster changes in temperature, the time constant must be taken into account. Devices with thermal feedback are pulsed by a built-in heating resistor. The control factor falls as the temperature increases, i.e. the controller has proportional behaviour. A small temperature variation of ±0.1...0.5 K occurs as a result of switching, depending on the time constant of the room.
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Thermostats
TSHK 621...643: Fan-coil room temperature controller, electromechanical Features
Y
• Variable room temperature as setpoint based on printed temperature scale • Changeover from heating to cooling via switch or type of connection • ON/OFF toggle switch for mains voltage, plus other slide switches for operating mode and fan, depending
on the type • More constant room temperature due to thermal feedback
TSHK6**F00*
• Suitable for wall mounting or fitting on recessed junction boxes • Setpoint adjuster with mechanical min. and max. limitation of the setting range • 2-point pulsed activation • Individual unitary temperature control in residential and business rooms for activating, for example, electric
heating systems, thermal actuators, or fans or cooling units in air-conditioning systems. Technical data Power supply
Power supply1)
230 V~, approx. ±10%, 50...60 Hz
Setting range Proportional band Hysteresis2) Shortest switching interval Time constant in still air Dead time in still air Time constant in moving air (0.2 m/s) Dead time in moving air (0.2 m/s)
5...30 °C 3K Approx. ±0.1...0.5 K Approx. 19 minutes (E = 0.5) 20 minutes 2 minutes 15 minutes 1 minute
Ambient temperature
0...55 °C
Load Fan load
6(3) A, 230 V~ 6(3) A, 230 V~
Weight Housing Housing material
0.18 kg Pure white (RAL 9010) Fire-retardant thermoplastic (fire classification UL94 HB) Black thermoplastic with bimetallic sensor and contact snap mechanism with permanent magnet At rear For electrical cables of up to 2.5 mm²
Parameters
Ambient conditions
Outputs
Construction
Baseplate
Cable inlet Screw terminals Standards and directives
Type of protection Protection class Energy class
1)
2)
IP30 (EN 60529) II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC
10% more voltage results in: Proportional band approx. 4 K, switching period 15 min, actual-value reduction approx. 0.5 K Devices with thermal feedback are pulsed by a built-in heating resistor. The control factor reduces as the temperature increases (i.e. the controller has proportional behaviour). A small temperature variation of ±0.1...0.5 K occurs as a result of pulsing, depending on the time constant of the room
Right of amendment reserved © 2024 Fr. Sauter AG
13
2-point controllers | Thermostats Overview of types
Y
Type
Operating mode
TSHK621F001
Heating/cooling; 2-pipe
TSHK642F001
Heating only / cooling only; 2-pipe
TSHK643F001
Heating/cooling; 4-pipe
Mains switch on/off Operating mode switch Fan speeds
TSHK621 • ir opü
TSHK642 • − opü
TSHK643 • ir opü
Accessories
14
Type
Description
0362239001
Pure white intermediate cover plate, suitable for various recessed junction boxes
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Thermostats
TSHK 670...672: Fan-coil room temperature controller, heating/cooling sequence Features
Y
• Variable room temperature as setpoint based on printed temperature scale • Gradual transition from heating to cooling through sequence characteristic • Variants with master switch plus slide switch for the fan • Suitable for wall mounting or fitting on recessed junction boxes
TSHK67*F001
• Electronics unit and switching relay • Setpoint adjuster with mechanical min. and max. limitation of the setting range • Quasi-continuous temperature control • 2-point pulsed activation • Individual unitary temperature control in residential and business rooms for activating, for example, electric
heating systems, thermal actuators, or fans or cooling units in air-conditioning systems. Technical data Power supply
Power supply
230 V~, approx. ±10%, 50...60 Hz
Setting range Proportional band Sequence dead zone Hysteresis1) Shortest switching interval Time constant in still air Dead time in still air Time constant in moving air (0.2 m/s) Dead time in moving air (0.2 m/s)
5...30 °C 2×3K 2 K ±0,7 Approx. ±0.1...0.5 K Approx. 19 minutes (E = 0.5) 20 minutes 2 minutes 15 minutes 1 minute
Ambient temperature
0...55 °C
Load Fan load
10(4) A, 230 V~ 6(3) A, 230 V~
Operating mode
Heating/cooling sequence; 4-pipe
Weight Housing Housing material Baseplate Cable inlet Screw terminals
0.18 kg Pure white (RAL 9010) Fire-retardant thermoplastic (fire classification UL94 HB) Black thermoplastic with NTC sensor At rear For cables of up to 2.5 mm²
Type of protection
IP30 (EN 60529)
Parameters
Ambient conditions
Outputs
Function
Construction
Standards and directives
1)
The device is pulsed electronically. When the temperature increases, the control factor is reduced to 0 on the “Heating” output and increased to E = 1 on the “Cooling” output. A small temperature variation of ±0.1...0.5 K occurs as a result of pulsing, depending on the time constant of the room
Right of amendment reserved © 2024 Fr. Sauter AG
15
2-point controllers | Thermostats Protection class Energy class
Y
II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC
Overview of types Type
Number of switches
TSHK670F001
0
TSHK672F001
2 TSHK670
TSHK672
Mains switch ON/OFF Fan speeds
— —
Indicators/display
—
• opü 1 LED
Accessories
16
Type
Description
0362239001
Pure white intermediate cover plate, suitable for various recessed junction boxes
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Thermostats
TSHK 681, 682: Fan-coil room temperature controller, with digital display Features
Y
• LCD of the room temperature or setpoint, with two buttons (±) for adjusting the setpoint • Output for heating or cooling depending on connection type, or change in direction of operation with
external switch • With main switch for mains power supply and slide switch for three fan speeds • Suitable for wall mounting or fitting on recessed junction boxes
TSHK68*F001
• Electronics unit and switching relay • Quasi-continuous temperature control • 2-point pulsed activation • Individual unitary temperature control in residential and business rooms for activating e.g. electric heating
systems, thermal actuators, or fans or cooling units in air-conditioning systems. Technical data Power supply
Power supply1)
230 V~, approx. ±10 V, 50...60 Hz
Setting range Proportional band Display of actual value Hysteresis2) Shortest switching interval Time constant in still air Dead time in still air Time constant in moving air (0.2 m/s) Dead time in moving air (0.2 m/s)
5...30 °C; resolution 0.5 °C 3K 0...40 °C; resolution 0.1 °C Approx. ±0.1...0.5 K Approx. 18 minutes (E = 0.5) 20 minutes 2 minutes 15 minutes 1 minutes
Ambient temperature
0...55 °C
Load Fan load
3(2) A, 230 V~ 6(3) A, 230 V~
Weight Housing Housing material
0.18 kg Pure white (RAL 9010) Fire-retardant thermoplastic (fire classification UL94 HB) Black thermoplastic with NTC sensor At rear For cables of up to 2.5 mm²
Parameters
Ambient conditions
Outputs
Construction
Baseplate Cable inlet Screw terminals Standards and directives
Type of protection Protection class Energy class
1)
2)
IP30 (EN 60529) II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC
10% more voltage results in: Proportional band approx. 4 K, switching period 15 min, actual-value reduction approx. 0.5 K The device is pulsed electronically. When the temperature increases, the control factor falls to zero at the “Heating” output and rises to E = 1 at the “Cooling” output. A small temperature variation of ±0.1...0.5 K occurs as a result of pulsing, depending on the time constant of the room
Right of amendment reserved © 2024 Fr. Sauter AG
17
2-point controllers | Thermostats Overview of types
Y
Type
Operating mode
TSHK681F001
Heating or cooling or heating/cooling; 2-pipe
TSHK682F001
Heating/cooling; 4-pipe TSHK681
Mains switch ON/OFF Operating mode switch Fan speeds Indicators/display
TSHK682 • —
i OFF r o
(•)
opü °C digital
opü °C digital
Accessories
18
Type
Description
0362238001
Cable temperature sensor, 4 m long, made of PVC, for external temperature measurement (max. 50 m)
0362239001
Pure white intermediate cover plate, suitable for various recessed junction boxes
Right of amendment reserved © 2024 Fr. Sauter AG
Universal thermostats Temperature control, temperature monitoring and temperature limitation: SAUTER universal thermostats are used for these three applications. They provide control, monitoring and limitation according to needs without auxiliary energy.
Overview of universal thermostats
Type designation
TUC
Application Clamp-on temperature Duct Pipe
• • •
Operating mode Temperature controller, monitor (TR, TW) Safety temperature limiter (STB) Temperature limiter (TB) Further information
Right of amendment reserved © 2024 Fr. Sauter AG
• • • Page 20
19
2-point controllers | Thermostats
TUC: Universal thermostat Features • Regulates and monitors the temperature of liquids in baths, containers, pipes, ducts and HVAC installations
Y
• Variants as temperature monitor (TW) and temperature limiter (TB) • Double thermostat as TW and TB • Thermostat with remote sensor • Clamp-on thermostat • Capillary tube thermostat with or without thermowell • The shift in the change-over point is minimised due to the temperature compensation
TUC*0*F00*
• Thermowell supplied (max. 12 bar)
The following features and certifications do not apply to the United Kingdom of Great Britain and Northern Ireland (UK): • Variants as safety temperature monitor (STW), or safety temperature limiter (STB) • Double thermostat as STW or STB
TW, STW
• As per PED 2014/68/EU classified as cat. IV (TUC207F003, TUC407F001, TUC407F002)
Use in safety applications is not permitted in the United Kingdom. Technical data Power supply
Max. load
Terminal 1-2
Min. load
Terminal 1-4 Terminal 1-2, 1-4
Parameters
Adjustment point At ta 22 °C Effect of temperature at instrument Approx. –0.1...–0.2 K/K head Time constant with thermowell (LW 7) < 45 s (water) < 60 s (oil) Time constant without thermowell < 120 s (air)
Xsd
Xs
T
TB, STB
230 VAC, 10(2.5) A (on the normallyclosed contact) 230 VAC 2(0.4) A 24 VAC/DC, 100 mA
1
B01571
4 2
Ambient conditions
Ambient temperature Storage and transport temperature Max. pipe temperature during fitting
0...70 °C −25...80 °C 120 °C
Connection terminals Cable cross-section
Plug-in connectors
Construction
TUC207F003
Housing material Weight
0.75...2.5 mm2 Ø 6.5 mm Two sections, lower section black, upper section yellow, including inspection window PA, ABS, PMMA 0.2 kg
Type of protection Protection class
IP54 (EN 60529) I (EN 60730)
Sensor cartridge Housing
TUC407F001 TUC407F002
Standards, directives
20
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Thermostats Overview of types Type
Setting range Type
Switching difference
Capillary Sensor cartube length tridge length (± 12 mm)
Thermowell
Max. sen- Approval sor temp.
TUC101F003
−10…50 °C TW
Approx. 4.2 K
1.6 m
80 mm
100 mm, brass
140 °C CE, UKCA
TUC102F001
5...30 °C
TW
Approx. 5.6 K
0.7 m
65 mm
100 mm, brass
200 °C CE, UKCA
TUC105F001
15...95 °C
TW
Approx. 5.6 K
0.7 m
65 mm
100 mm, brass
200 °C CE, UKCA
TUC106F001
40...120 °C TW
Approx. 5.6 K
0.7 m
65 mm
100 mm, brass
200 °C CE, UKCA
TUC107F001
50...130 °C TW
Approx. 5.6 K
0.7 m
65 mm
100 mm, brass
200 °C CE, UKCA
TUC108F001
80...160 °C TW
Approx. 5.6 K
0.7 m
65 mm
100 mm, 200 °C CE, stainless steel UKCA
TUC207F003
70...130 °C STW
Approx. 10 K
1.6 m
60 mm
100 mm, brass
160 °C CE
TUC303F001
15...60 °C
TB
≤ 20 K
0.7 m
70 mm
100 mm, brass
200 °C CE, UKCA
TUC307F001
50...130 °C TB
≤ 20 K
0.7 m
65 mm
100 mm, brass
200 °C CE, UKCA
TUC407F001
95...130 °C STB
≤ 20 K
0.7 m
76 mm
100 mm, brass
160 °C CE
TUC407F002
95...130 °C STB
≤ 20 K
0.7 m
76 mm
150 mm, brass
160 °C CE
A A
Y
Universal thermostats approved in the UK must not be used as STW or STB in safety applications. The TUC207F003, TUC407F001 and TUC407F002 devices comply with modules B (type test) and D (QA system, CE 0035) of Pressure Equipment Directive 2014/68/EU.
A
Only use the supplied thermowells or stainless steel thermowells (part nos.: 0393022*** or 0392022***) with the TÜV-certified devices.
A
TUC108F001 with adapter for temperature reduction, only mount with supplied thermowell.
Accessories Type
Description
0300360008
Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)
0300360009
Holder for sensor cartridge
0300360010
Retaining strap for fitting onto pipes with a diameter of 15…100 mm
0300360011
Mounting plate for double thermostats
0300360012
Sensor support spiral for fitting in ventilation duct
0300360013
Duct/wall mounting bracket
Right of amendment reserved © 2024 Fr. Sauter AG
21
2-point controllers | Thermostats
Thermowells Features • Fitted in pipes and containers for holding sensor cartridges, immersion stems, temperature sensors,
Y
temperature controllers or thermostats Made of brass (Ms) or stainless steel (V4A) • • Versions with cylindrical pipe thread (G½" male ISO 228/1, flat-sealing)
1)
or cone-shaped
(R½" ISO 7/1 sealing in thread) • With pressure spring (LW 15) • With retaining holder
Overview of types Type
LW
Length
Material
Thread
Nominal pressure
Test pressure Tmax
0391022050
7
50 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022100
7
100 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022200
7
200 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022300
7
300 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022450
7
450 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022600
7
600 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391011050
7
50 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011100
7
100 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011150
7
150 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011200
7
200 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011300
7
300 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011450
7
450 mm
Brass
R½"
10 bar
16 bar
160 °C
0393022100
15
100 mm
Stainless steel
G½"
40 bar
60 bar
450 °C
0393022200
15
200 mm
Stainless steel
G½"
40 bar
60 bar
450 °C
0393022450
15
450 mm
Stainless steel
G½"
40 bar
60 bar
450 °C
0393012100
15
100 mm
Brass
G½"
16 bar
25 bar
160 °C
0393012200
15
200 mm
Brass
G½"
16 bar
25 bar
160 °C
0392022100
7
100 mm
Stainless steel
G½"
25 bar
40 bar
450 °C
0392022200
7
100 mm
Stainless steel
G½"
25 bar
40 bar
450 °C
0392022300
7
300 mm
Stainless steel
G½"
25 bar
40 bar
450 °C
1)
22
G½" male ISO 228/1, flat-sealing: for welding bushings with flat seal (accessories)
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Thermostats
A A A
0392022100 and 0392022300 for TUC thermostats only With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). 0391... with pressure screw (retaining holder) up to max. 200 °C
Y
Accessories Type
Description
0300360008
Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)
0364263000
Welding sleeve of steel, with female thread G½", flat seal of copper
0300360017
Pressure spring for LW 15 (10 pieces)
•
LW 7, 50 mm LW 7, 100 mm LW 7, 150 mm LW 7, 200 mm
• • • •
LW 7, 300 mm LW 7, 450 mm LW 7, 600 mm LW 15, 100 mm LW 15, 200 mm LW 15, 450 mm 0392022100 0392022200 0392022300
A A A A
• • • • • − − −
• L > 50 mm • • • • L > 300 mm • − − − − − − −
− − − − − − − • • • • • •
0392022100 and 0392022300 for TUC thermostats only. With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). Only use the thermowells (LW 15) with at least 2 sensors or thermostats with a diameter of at least 6 mm 0391... with pressure screw (retaining holder) up to max. 200 °C.
Right of amendment reserved © 2024 Fr. Sauter AG
23
Frost monitors SAUTER frost monitors protect ventilation systems against icing. With their special construction and design, they are particularly suitable for compact installations and/or installations that are subject to vibrations.
Overview of frost monitors
Type designation Function Monitor Limiter Output signal Switched Continuous Auxiliary energy Further information
24
TFL 201
TFL 611
• •
• −
• − • Page 25
• • − Page 27
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Frost monitors
TFL 201: Frost protection monitor/limiter with capillary-tube sensor Features
Y
• Temperature monitoring in heating coils and air ducts • Variants as monitors or limiters • Copper capillary tube • Switching point can be set internally • Small switching difference • With capillary-tube holders made of plastic
TFL201F**2
Technical data Power supply
230 VAC, 10(2.5) A (on the normallyclosed contact) 230 VAC 2(0.4) A
Parameters
Setting range −10...15 °C Factory setting 5 °C Switching difference 1.5 K Tolerance of switching difference Max. ±1 K Max. sensor temperature 120 °C Time constant in moving air (0.3 m/s)1) Capillary tube length 1.5 m: 25 s Capillary tube length 3 m: 31 s Capillary tube length 6 m: 51 s
Time characteristic
TFL201F*02 T
Terminal 1-4
Xs
Terminal 1-2
Xsd
Max. load
2 4
Ambient conditions
Ambient temperature2) Max. capillary temperature Storage and transport temperature
−5...70 °C 120 °C −30...80 °C
Connection terminals Cable cross-section
Plug-in connectors
1
Construction
Housing material Weight
Ø 0.75...2.5 mm2 Two sections, lower section black, upper section yellow, including inspection window ABS, PMMA 0.2 kg
Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP65 (EN 60529) I (IEC 60730) EN 60730-1, EN 60730-2-9 EN 60730-1, EN 60730-2-9
Housing
TFL201F*22
Standards, directives
Overview of types Type
Function
Switching difference
Capillary tube
Capillary tube holder
TFL201F002
Monitor
1.5 K (±1 K)
3000 mm
3
TFL201F022
Limiter
1.5 K (±1 K)
3000 mm
3
TFL201F102
Monitor
1.5 K (±1 K)
1500 mm
3
TFL201F602
Monitor
1.5 K (±1 K)
6000 mm
6
TFL201F622
Limiter
1.5 K (±1 K)
6000 mm
6
1) 2)
The frost monitor always reacts to the coldest point (minimum length 7.5 cm (1.5 m), 15 cm (3 m) and 30 cm (6 m)) The head of the instrument must be fitted in a warmer location than the sensor; see fitting instructions
Right of amendment reserved © 2024 Fr. Sauter AG
25
2-point controllers | Frost monitors Accessories Type
Description
0300360014
Six holders for fitting the capillary tube
Y
26
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Frost monitors
TFL 611: Continuous frost monitor with capillary sensor Features • Records the lowest temperature that occurs for a length of at least 250 mm at any position along the
Y
capillary tube • Used on air side in ventilation and air conditioning units where protective measures must be taken against freezing Active capillary sensor for measuring the lowest temperatures in the range 0...15 °C • • Vapour-filled capillary tube and diaphragm system with inductive system of measurement • Setting range 1...10 °C
TFL611F*01
• Start-up function • LED and 7-segment display • Self-monitoring of sensor line
Technical data Power supply
Y10
Power supply Power consumption Frequency 1)
24 V~, 10/-20% < 6.6 VA 50...60 Hz
6K Q11
10 V
Q12 Q14
Q11
Parameters
Measuring range Setting range Adjustment point Accuracy for adjustment point Switching difference Temperature for capillary tube Time constant in still air Time constant in moving air Response length for capillary tube
0...15 °C 1...10 °C 5 °C ±1K Approx. 2 K < 110 °C Approx. 90 s < 40 s Min. 250 mm
Admissible cable length Valve control for terminal Y Current Sensor temperature for terminal B Valve control for terminal Y10 Current Min. switching capacity
300 m with 1.5 mm² 0...10 V < 0.1 mA 0...10 V ≙ 0...15 °C 0...10 V ±1 mA 12 V~/=, 100 mA
Max. switching capacity
250 V~, 6(2) A; 24 V=, 6 A
Humidity (non-condensing) Temperature Humidity (non-condensing) Temperature
< 85% rh -15...55 °C < 95% rh -25...65 °C
Terminals with spring technology
Max. 2 × 1.5 mm² Or 1 × 2.5 mm² Min. 0.25 mm² Cable gland M16 for cable diameter 5...10 mm I PA, silver grey (RAL 7001)
Q12 Q14 0V 2K
T [°C]
P (1...10 °C)
Inputs/outputs
Analogue input Analogue outputs
Potential-free relay outputs (Q terminals)
Ambient conditions
Operation Storage and transport
Construction
Cable inlet Protection class2) Housing 1) 2)
SELV/PELV: Safety Extra Low Voltage/Protected Extra Low Voltage No earth conductor necessary
Right of amendment reserved © 2024 Fr. Sauter AG
27
2-point controllers | Frost monitors Housing cover Cap Capillary tube
PC, transparent ABS, light grey (RAL 7035) Copper
Vibration resistance Type of protection Operation as per IEC 721-3-3 Storage and transport as per IEC 721-3-2 RoHS Directive 2011/65/EU EMC Directive 2014/30/EU
EN 60721-3-3 (class 3M2) IP42 (EN 60529) Class 3K5 Class 2K3
Standards and directives
Y
Low-Voltage Directive 2014/35/EU
EN IEC 63000 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN60730-2-9
Overview of types Type
Description
Weight
TFL611F201
Continuous frost monitor; 0...15 °C; capillary tube length= 2 m
340 g
TFL611F601
Continuous frost monitor; 0...15 °C; capillary tube length= 6 m
410 g
Accessories
28
Type
Description
0292146001
Set for duct fitting consisting of: 5 capillary-tube holders, 1 depth-adjustable flange
0300360014
Six holders for fitting the capillary tube
0374534001
Depth-adjustable flange
Right of amendment reserved © 2024 Fr. Sauter AG
Pressure switches SAUTER pressure switches can be used in any application for controlling and monitoring the pressure in liquids, gases and vapours. They detect changes in pressure in gaseous and/or liquid media and are used to switch pumps, valves or compressors.
Overview of pressure switches
Type designation
DSA •
DSB •
DSF •
DSL −
DSH −
DFC 17B •
DFC 27B •
DSD −
−
−
−
−
•
•*)
•*)
−
For falling pressure
−
−
−
•
−
•*)
•*)
−
Differential pressure switch Pressure sensors Of brass Of stainless steel
−
−
−
−
−
−
−
•
• −
• −
− •
• −
− •
• −
− •
− •
Switching difference Fixed Variable
• −
− •
− •
• −
• −
− •
− •
• −
− − − − − Page 30
• • • • −
• • • • •
• • • • −
• • • • •
• • • − −
• • • − •
− − − − − Page 38
Pressure monitors Pressure limiters For rising pressure
Certification VdTÜV 100 EN 12952-11, EN 12953-9 Germanischer Lloyd (GL) Lloyds Register Can be used for aggressive media Further information
A
Page 32
Page 34
Page 36
*) Depending on approval
Right of amendment reserved © 2024 Fr. Sauter AG
29
2-point controllers | Pressure switches
DSA: Pressure switch Features • For regulating and monitoring pressure in liquids, gases and vapours
Y
• Especially suitable for applications in compact installations • Upper switching point can be adjusted • Fixed switching difference, no hysteresis setting is necessary • Sealable
DSA14*F002
• Pressure sensor made of brass for non-aggressive media
Technical data Power supply
Xsd
Xs
P
Maximum load with gold-plated contacts1) Minimum load with gold-plated contacts Maximum load with silver-plated contacts Minimum load with silver-plated contacts
400 mA, 24 V, 10 VA 4 mA, 5 V 10(4) A, 250 VAC, 50 W, 250 VDC 100 mA, 24 V
Parameters
1
B01574
3 2
Pressure connection
G½" A
Admissible sensor temperature Ambient temperature
70 °C −20...70 °C
Fitting Housing Housing material Device plug
Pipe and wall mounting Transparent cover Impact-proof thermoplastic Standard female connector for Ø 6...10 mm cable
Type of protection2) Protection class LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE)
IP65 (EN 60529) I (IEC 60730) EN 60730-1, EN 60730-2-6 EN 60730-1, EN 60730-2-6 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN ISO12100: Annex II B of the Reg. EN ISO12100: Annex II B of the Reg. (Partly Completed Machinery) EN IEC 63000
Ambient conditions
Construction
Standards, directives
CE/UKCA conformity3)
EMC-2016 (UKCA) Machinery-D 2006/42/EC (CE) SMSR-2008 (UKCA)
RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) PED 2014/68/EU (CE) PESR-2016 (UKCA)
1)
2) 3)
30
EN IEC 63000 Article 4.3 and Annex A of the Reg. Article 8.3 and Essential Safety Requirements of the Reg.
If the contacts are subjected to a load greater than specified, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts. Depending on the fitting position, see the fitting instructions. The devices are not suitable for outdoor applications. Use as a pressure limiter is not permitted. The use of an electrical interlock is not permitted.
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Pressure switches Overview of types Type
Setting range
Switching difference
Maximum pressure Admissible vacuum Weight loading
DSA140F002
0.5...2.5 bar
0.25 bar
12 bar
-0.7 bar
0.5 kg
DSA143F002
0.5...6 bar
0.3 bar
16 bar
-0.7 bar
0.5 kg
DSA146F002
1...10 bar
0.4 bar
20 bar
-1.0 bar
0.4 kg
A
Y
DSA: Pressure sensor made of brass for non-aggressive media; Xs = upper switching point
Accessories Type
Description
0035465000
Throttle screw for absorbing pressure surges, brass
0214120000
Throttle screw for absorbing pressure surges, stainless steel
0259239000
Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass
0292001000
Setpoint adjuster according to customer's wishes (setting accuracy: ±3% of the setting range, but a minimum of ±0.2 bar)
0292004000
Setpoint adjuster sealed (with accessory 0292001000 only)
0292018001
Damping screw for absorbing pressure surges in low viscosity media
0292150001
Fixing bracket for wall mounting
0296936000
Fixing brackets for rail: top-hat rail EN 60715, 35 × 7.5 mm and 35 × 15 mm
0300360007
Capillary throttle, stainless steel, length 1 m, G½"-G½"
0311572000
Screw fitting for copper tubes of Ø 6 mm, brass
0381141001
Profile sealing ring, copper, for G½"
A
0296936000: With accessory 0292150001 only
Right of amendment reserved © 2024 Fr. Sauter AG
31
2-point controllers | Pressure switches
DSB, DSF: Pressure monitors and pressure switches Features • For regulating and monitoring pressure in liquids, gases and vapours
Y
• Adjustable lower switching point • Adjustable switching difference • Sealable • Pressure sensor made of brass for non-aggressive media (DSB)
DSB1**F001
• Pressure sensor made of stainless steel for aggressive media (DSF) • SIL 2-certified as per IEC 61508
1)
• Approved for marine applications (GL- and LR-certified)
Technical data
Xs
Xsd
P
Power supply
1
B03377
3 2
Maximum load with gold-plated contacts2) Minimum load with gold-plated contacts Maximum load with silver-plated contacts Minimum load with silver-plated contacts
400 mA, 24 V, 10 VA
Pressure connection
G ½" A
Ambient temperature
−20…70 °C
Housing Housing material Device plug
Transparent cover Impact-proof thermoplastic Standard female connector for cable Ø 6…10 mm
Type of protection3) Protection class Test mark4)
IP65 (EN 60529) I (IEC 60730) TÜV DWFS (SDBFS) ID: 06024 Germanischer Lloyd (GL) Lloyds Register (LR) EN 60730-1, EN 60730-2-6 EN 60730-1, EN 60730-2-6 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN ISO12100:2018
4 mA, 5 V 10(4) A, 250 VAC, 50 W, 250 VDC 100 mA, 24 V
Parameters
Ambient conditions
Construction
Standards, directives
Ship-approved CE/UKCA conformity5)
LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) Machinery-D 2006/42/EC (CE)
1) 2)
3) 4)
5)
32
SIL 2 approval is not valid in the United Kingdom (UK). If the contacts are subjected to a load greater than specified, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts Depending on the fitting position, see the fitting instructions. The devices are not suitable for outdoor applications. For the EU: DWFS (SDBFS): As a safety pressure limiter when an external electrical locking facility is fitted downstream in the circuit. Certificates can be downloaded from www.certipedia.com. For the United Kingdom (UK): Use as a safety pressure limiter is not permitted. The use of an electrical interlock is not permitted. Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Pressure switches SMSR-2008 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) PED 2014/68/EU (CE)
EN ISO12100:2018 EN IEC 63000:2018 EN IEC 63000:2018 VdTÜV pressure information sheet 100, sheet 1, cat. IV EN 12952-11, EN 12953-9 Article 8.3 of the Reg. AD 2000 Rulebook IEC 61508 parts 1-2 and 4-7
PESR-2016 (UKCA)6) SIL conformity as per SIL 2
Standards7)
Y
Overview of types Type
Setting range
Switching differ- Maximum pres- Max. sensor ence sure temp.
Admissible vac- Weight uum loading
DSB138F001
0...1.6 bar
0.25...0.65 ba 12 bar r
70 °C
-0.7 bar
0.5 kg
DSB140F001
0...2.5 bar
0.25...0.75 ba 12 bar r
70 °C
-0.7 bar
0.5 kg
DSB143F001
0...6 bar
0.3...1.6 bar
16 bar
70 °C
-0.7 bar
0.5 kg
DSB146F001
0...10 bar
0.8...3.7 bar
30 bar
70 °C
-1 bar
0.4 kg
DSB152F001
6...16 bar
1...4 bar
30 bar
70 °C
-1 bar
0.4 kg
DSB158F001
0...25 bar
1...7.5 bar
60 bar
70 °C
-1 bar
0.4 kg
DSB170F001
5...40 bar
1.4...7.5 bar
60 bar
70 °C
-1 bar
0.4 kg
DSF125F001
–1...1.5 bar
0.25...0.75 ba 12 bar r
110 °C
-1 bar
0.5 kg
DSF127F001
–1...5 bar
0.3...1.5 bar
16 bar
110 °C
-1 bar
0.5 kg
DSF135F001
0...0.6 bar
0.12...0.60 ba 12 bar r
110 °C
-1 bar
0.5 kg
DSF138F001
0...1.6 bar
0.25...0.7 bar 12 bar
110 °C
-1 bar
0.5 kg
DSF140F001
0...2.5 bar
0.25...0.75 ba 12 bar r
110 °C
-1 bar
0.5 kg
DSF143F001
0...6 bar
0.3...1.5 bar
16 bar
110 °C
-1 bar
0.5 kg
DSF146F001
0...10 bar
0.8...3.0 bar
18 bar
110 °C
-1 bar
0.5 kg
DSF152F001
0...16 bar
1.2...3.8 bar
60 bar
110 °C
-1 bar
0.3 kg
DSF158F001
0...25 bar
1.5...8.0 bar
60 bar
110 °C
-1 bar
0.3 kg
DSF170F001
15...40 bar
1.7...8.2 bar
60 bar
110 °C
-1 bar
0.3 kg
A A A
DSB: Pressure sensor made of brass for non-aggressive media; XS = lower switching point. DSF: Pressure sensor made of stainless steel for aggressive media; XS = lower switching point. The switching difference must be within the setting range of the switching point. The minimum values of the switching difference are only possible in the lower setting range.
Accessories Type
Description
0259239000
Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass
0292001000
Setpoint adjuster according to customer's wishes (setting accuracy: ±3% of the setting range, but a minimum of ±0.2 bar)
0292002000
Switching difference according to customers' wishes (setting accuracy: ±5% of the setting range, but a minimum of ±0.05 bar, with accessory 0292001000 only)
0292004000
Setpoint adjuster sealed (with accessory 0292001000 only)
0292150001
Fixing bracket for wall mounting
0296936000
Fixing brackets for rail: top-hat rail EN 60715, 35 × 7.5 mm and 35 × 15 mm
0311572000
Screw fitting for copper tubes of Ø 6 mm, brass
0381141001
Profile sealing ring, copper, for G½"
A 6) 7)
0296936000: With accessory 0292150001 only
SIL 2 approval is not valid in the United Kingdom (UK). SIL 2 approval is not valid in the United Kingdom (UK).
Right of amendment reserved © 2024 Fr. Sauter AG
33
2-point controllers | Pressure switches
DSL, DSH: Specially designed pressure limiter Features • Switching point can be adjusted
Y
• Sealable • Pressure sensor made of brass for non-aggressive media (DSL) • Pressure sensor made of stainless steel for aggressive media (DSH) • Locking type: With falling pressure (DSL) or with rising pressure (DSH) • SIL 2 certified as per IEC 61508 • Approved for marine applications (GL and LR certified)
P
Technical data
Xs
Xsd
Power supply
B03377
3 2
1
DSL1**F001
Maximum load with gold-plated contacts1) Minimum load with gold-plated contacts Maximum load with silver-plated contacts Minimum load with silver-plated contacts
400 mA, 24 V, 10 VA
Pressure connection
G ½" A
Ambient temperature
−20…70 °C
Housing Housing material Device plug
Transparent cover Impact-proof thermoplastic Standard female connector for cable of Ø 6…10 mm
Type of protection2) Protection class Test mark3)
IP65 (EN 60529) I (IEC 60730) TÜV DSL: SDBF ID: 06022 DSH: SDB ID: 06023 PED: 2014/68/EU, cat. IV Germanischer Lloyd (GL) Lloyds Register (LR) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-6 VdTÜV pressure information sheet 100, cat. IV EN 12952-11, EN 12953-9 EN ISO 12100:2018
4 mA, 5 V 10(4) A, 250 VAC, 50 W, 250 VDC 100 mA, 24 V
Xsd
Xs
P
Parameters
Ambient conditions
1
B01574
3 2
Construction
DSH1**F001
Standards and directives
Ship-approved CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU PED 2014/68/EU
SIL conformity as per SIL 2
1)
2) 3)
34
Machinery Directive 2006/42/EC (according to Appendix II, 1B) Standards
IEC 61508 parts 1-2 and 4-7
If the contacts are subjected to a load greater than specified, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts Depending on the fitting position, see the fitting instructions. The devices are not suitable for outdoor applications. Certificates can be downloaded from www.certipedia.com. The certificates are not valid in the United Kingdom of Great Britain and Northern Ireland.
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Pressure switches Overview of types
/
Min. change for reset: Average values
Type
Setting range
Min. change for Maximum pres- Admissible sen- Admissible vac- Weight reset sure sor temperature uum loading
DSL140F001
0...2.5 bar
0.4 bar
12 bar
70 °C
-0.7 bar
DSL143F001
0...6 bar
0.5 bar
16 bar
70 °C
-0.7 bar
0.5 kg
DSL152F001
6...16 bar
1.2 bar
30 bar
70 °C
-1.0 bar
0.4 kg
DSH127F001
-1...5 bar
-0.4 bar
16 bar
110 °C
-1.0 bar
0.5 kg
DSH143F001
0.5...6 bar
-0.45 bar
16 bar
110 °C
-0.7 bar
0.5 kg
DSH146F001
1...10 bar
-0.8 bar
18 bar
110 °C
-1.0 bar
0.5 kg
DSH152F001
2...16 bar
-1.5 bar
60 bar
110 °C
-1.0 bar
0.3 kg
DSH158F001
5...25 bar
-1.8 bar
60 bar
110 °C
-1.0 bar
0.3 kg
DSH170F001
15...40 bar
-2.0 bar
60 bar
110 °C
-1.0 bar
0.3 kg
A A
Y
0.5 kg
DSL: Locks when the pressure falls (SDBF); pressure sensor made of brass for non-aggressive media. DSH: Locks when the pressure rises (SDB); pressure sensor made of stainless steel.
Accessories Type
Description
0259239000
Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass
0292001000
Setpoint adjuster according to customer's wishes (setting accuracy: ±3% of the setting range, but a minimum of ±0.2 bar)
0292004000
Setpoint adjuster sealed (with accessory 0292001000 only)
0292150001
Fixing bracket for wall mounting
0296936000
Fixing brackets for rail: top-hat rail EN 60715, 35 × 7.5 mm and 35 × 15 mm
0311572000
Screw fitting for copper tubes of Ø 6 mm, brass
0381141001
Profile sealing ring, copper, for G½"
A
0296936000: With accessory 0292150001 only
Right of amendment reserved © 2024 Fr. Sauter AG
35
2-point controllers | Pressure switches
DFC 17B, 27B: Heavy-duty pressure switch Features • For regulating and monitoring pressure in liquids, gases and vapours
Y
• Especially suitable for installations subject to vibrations • Contact rating 1 mA/6 V to 10 A/400 V • Gold-plated silver contacts, vibration-proof snap-action switch with single-pole change-over switch • Upper and lower switching points can be set independently of each other
DFC17B76F001
• Sealable • Splashproof • DFC17B**F001: Pressure sensor made of brass for non-aggressive media • DFC27B**F002: Pressure sensor made of stainless steel for aggressive media
Technical data
Xs2
Xsd
Xs1
P
Power supply
1
B03311
3 2
Maximum load with gold-plated contacts1) Minimum load with gold-plated contacts Maximum load with silver-plated contacts2) Minimum load with silver-plated contacts
200 mA, 50 V
Media temperature Ambient temperature
≤ 110 °C −40...70 °C
Housing Housing material Cable inlet Screw terminals Pressure connection
Transparent cover Light alloy PG 13.5 For electrical cables up to 2.5 mm² G½" A
Type of protection Protection class Test mark3)
IP44 (EN 60529) I (IEC 60730) TÜV DWFS (SDBF) ID: 06018 DWFS (SDB) ID: 06019 DB (SDBF) ID: 06017 Type 2 B (EN 60730) EN 60730-1, EN 60730-2-6 EN 60730-1, EN 60730-2-6 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN ISO12100:2018
1 mA, 6 V 10(2) A, 400 VAC (25 W), 250 VDC 100 mA, 24 V
Ambient conditions
Construction
Standards, directives
CE/UKCA conformity4)
Mode of operation LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) Machinery-D 2006/42/EC (CE)
1)
2)
3) 4)
36
If the contacts are subjected to a load greater than 200 mA, 50 V, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts Take the RC circuitry into account for inductive loads 230/400 V networks From 70 °C media temperature, the current must be reduced to 6 A Certificates can be downloaded from www.certipedia.com. The certificates are not valid in the United Kingdom (UK). Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Pressure switches SMSR-2008 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) PED 2014/68/EU (CE)
EN ISO12100:2018 EN IEC 63000:2018 EN IEC 63000:2018 VdTÜV pressure information sheet 100, sheet 1, cat. IV EN 12952-11, EN 12953-9 Article 8.3 of the Reg. AD 2000 Rulebook
PESR-2016 (UKCA)5)
Y
Overview of types Type
Setting range (bar)
Min. switching Maximum pres- Max. temp., difference (bar) sure (bar) sensor (°C)
Admissible vac- Weight (kg) uum loading (bar)
DFC17B54F001
0...2.5
0.14
16
70
-0.7
1.2
DFC17B58F001
0...6.0
0.18
16
70
-1.0
1.2
DFC17B59F001
–1...5.0
0.20
16
70
-1.0
1.2
DFC17B76F001
0...10
0.50
40
70
-1.0
1.1
DFC17B78F001
0...16
0.50
40
70
-1.0
1.1
DFC17B79F001
16...32
0.80
42
70
-1.0
1.1
DFC17B96F001
0...25
1.70
100
70
-1.0
1
DFC17B97F001
25...50
2.00
100
70
-1.0
1
DFC17B98F001
0...40
1.80
100
70
-1.0
1
DFC27B26F002
–1...2.5
0.30
21
110
-1.0
0.9
DFC27B43F002
0.5...6.0
0.30
21
110
-1.0
0.9
DFC27B46F002
1...10
0.30
21
110
-1.0
0.9
DFC27B52F002
2...16
0.30
21
110
-1.0
0.9
A
The switching difference must be within the setting range of the switching point. The minimum values of the switching difference are only possible in the lower setting range.
Accessories Type
Description
0259239000
Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass
0311572000
Screw fitting for copper tubes of Ø 6 mm, brass
0035465000
Throttle screw for absorbing pressure surges, brass
0214120000
Throttle screw for absorbing pressure surges, stainless steel
0300360007
Capillary throttle, stainless steel, length 1 m, G½"-G½"
0292018001
Damping screw for absorbing pressure surges in low viscosity media
0259189000
Holder for raised wall mounting
0292019001
Setpoint adjustment for each switching point according to customer's wishes (setting accuracy: ±3% of the setting range)
0292019002
Sealing of the adjustment screw for each switching point (only with accessory 0292019001)
0381141001
Profile sealing ring, copper, for G½"
5)
For the United Kingdom (UK): Use as a safety pressure limiter is not permitted. The use of an electrical interlock is not permitted.
Right of amendment reserved © 2024 Fr. Sauter AG
37
2-point controllers | Pressure switches
DSD: Differential pressure switch Features • For monitoring the differential pressure in liquids, gases and vapours
Y
• For use in, for example, filter technology and in process plants • Differential pressure setting ranges from 0.06 to 6 bar • Up to 80 °C media temperature • High repeatability • High overload protection • Can be used in all neutral media, such as heating water, neutral gases, oils etc.
DSD1**F002
• Long serviceable life • With fitting bracket
Technical data Parameters
Min. load
AC min: 0.1 A, 250 VAC, 25 VA DC min: 0.1 A, 30 VDC AC max: 3(1) A, 250 VAC, 250 VA DC max: 0.4 A, 30 VDC, 10 W 1.5%/10 K 3% of the setting range 12% of the setting range
Max. load Temperature dependence Accuracy Hysteresis Mechanical serviceable life
2 3
106 switchings 16 bar
Max. static operating pressure (positive and negative pressure) Ambient conditions
Ambient temperature Media temperature Ambient humidity
−10…70 °C 0...80 °C (non-freezing media) 45…75% rh
Power cable1) Diaphragms Connection thread Weight
3...0.5 mm2 Chromium-nickel steel 1.4310 G ⅛" (female thread) 0.2 kg
Type of protection Protection class Low-Voltage Directive 2014/35/EU
IP65 (EN 60529) II (EN 60730) EN 60730-1, EN 60730-2-6 Altitude up to 2000 m EN 55014-1 Click rate N < 0.2 Art. 4.4 Art. 4.3 and Art. 13, fluid group 2
Construction
Standards, directives
CE conformity according to
EMC Directive 2014/30/EU PED 2014/68/EU
Overview of types Type
Setting range (bar)
DSD134F102
0.06...0.6
DSD137F002
0.10...1.0
DSD140F002
0.25...2.5
DSD143F002
0.6...6.0
1)
38
1 m long, fixed wiring
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Pressure switches Accessories Type
Description
0300360005
Cutting ring fitting G⅛" to 6 mm pipe (2 pcs)
0300360006
Pneumatic fitting G⅛" to 6 mm hose (2 pcs)
0300360016
Throttle screws G⅛", G⅛" (2 pcs)
Right of amendment reserved © 2024 Fr. Sauter AG
Y
39
Humidistats Room-, panel- and duct-mounted humidistats are employed for monitoring and controlling devices that are used for humidity regulation (fans, driers and humidifiers).
Overview of humidistats
Type designation Application Room Panel Duct Further information
40
HSC 120
HSC 101
HBC
• − − Page 41
− • − Page 42
− − • Page 43
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Humidistats
HSC 120: Room humidistat Features • Monitoring and regulation of relative air humidity in rooms by controlling fans, drying units and air
Y
humidifiers • Variable relative humidity as setpoint based on printed scale in % rh • Measurement taken via a measuring element of stabilised synthetic textile tape. • Controller with fixed switching difference of Xsd
Technical data HSC120F001
Power supply
Max. load Min. load
5(3) A, 250 VAC 100 mA, 24 VAC/DC
Setting range Setting accuracy1) Humidity calibration at Switching difference Xsd Long-term stability Time constant in moving air (0.2 m/s) Temperature effect
30...90% rh ±5% rh 55% rh, 23 °C Typ. 8% rh Approx. -1.5% rh/a Approx. 5 minutes 0.5% rh/K
Ambient humidity Temperature Ambient humidity Temperature
30...90% rh non-condensing 0...50 °C 10...95% rh non-condensing -25...70 °C without condensation
Dimensions W × H × D Weight Housing Housing material Screw terminals
76 × 76 × 34 mm 0.09 kg Pure white (RAL 9010) Fire-retardant thermoplastic, UL94V-0 For electrical wires of up to 1.5 mm²
Parameters
Ambient conditions
Operation Storage and transport
HSC120F010
XSd
Xs
H%
Construction
3 2
CE conformity according to
Type of protection2) Protection class Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP 30 (EN 60730-1), operating status II (IEC 60730) 3K3 (IEC 60721-3-3) EN 60730 EN 60730-1, EN 60730-2-13
Overview of types Type
Features
HSC120F001
Setting via external setpoint adjuster
HSC120F010
Internal setpoint adjuster
1
B01572
Standards, directives
relative humidity at 23 °C
Accessories Type
Description
0362225001
Intermediate plate, pure white, for wall mounting on recessed junction box
1)
2)
The setting accuracy of the humidistat is valid for the calibration point ±5% rh at 55% rh and 23 °C following initial calibration at the factory. See diagram “Setting accuracy”. In general, humidity sensors (humidistats) are subject to increased ageing if they are used and/or stored in very contaminated air or aggressive gases. The humidistat may start to drift and its linearity may change under these conditions. If the humidistats are used in very contaminated air, the warranty does not cover a premature re-calibration or the replacement of the complete humidistat Operating status: device mounted and closed
Right of amendment reserved © 2024 Fr. Sauter AG
41
2-point controllers | Humidistats
HSC 101: Panel-mounted humidistat (packing unit: 50 pieces) Features
Y
• Monitoring and regulation of relative humidity by controlling fans, drying units and air humidifiers • Adjustment of change-over point via setpoint adjustment axis
HSC101F001
• Suitable for fitted applications with protection class II • Measurement via a measuring element of stabilised synthetic textile tape • Secured with bolting hole and fixing hole (blind hole) • Micro-switch with single-pole change-over contacts and fixed switching difference
Xs
H%
• Suitable for panel-mounted units only
XSd
Technical data Power supply
1
B01572
3 2
Max. load Min. load
5(3) A, 250 VAC 100 mA, 24 V
Setting range Setting accuracy1) Humidity calibration at Switching difference Xsd2) Long-term stability Time constant in moving air (0.2 m/s) Temperature effect
25...95% rh ±5% rh 55% rh, 23 °C Typ. 8% rh
Humidity (non-condensing) Temperature Humidity (non-condensing) Temperature
25...95% rh 0...70 °C 10...95% rh -20...70 °C
Weight Baseplate Electrical connection
0.03 kg Thermoplastic AMP terminals 2.8 mm
Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP00 (EN 60529) 0 (IEC 60730) EN 55014 Art. 4.2 EN 60730-1, EN 60730-2-13
Parameters
relative humidity at 23 °C
–1.5% rh/a Approx. 3 minutes 0.5% rh/K
Ambient conditions
Operation Storage and transport
Construction
Standards, directives3)
CE conformity according to
Overview of types Type
Features
HSC101F001
Panel-mounted humidistat
1)
2) 3)
42
The setting accuracy of the humidistat is valid for the calibration point ±5% rh at 55% rh and 23 °C following initial calibration at the factory. See diagram “Setting accuracy”. In general, humidity sensors (humidistats) are subject to increased ageing if they are used and/or stored in very contaminated air or aggressive gases. The humidistat may start to drift and its linearity may change under these conditions. If the humidistats are used in very contaminated air, the warranty does not cover a premature re-calibration or the replacement of the complete humidistat Can be substantially improved by recalibration during usage The fitting method must adhere to the relevant safety standards
Right of amendment reserved © 2024 Fr. Sauter AG
2-point controllers | Humidistats
HBC: Duct-mounted humidistat Features • Monitoring and regulation of relative humidity by controlling fans, drying units and air humidifiers
Y
• Temperature-compensated humidity sensor • Variable relative humidity as setpoint based on printed scale in % rh • Includes fixing bracket with seal for duct or wall mounting • For fitting in a ventilation duct or on a wall • With single-pole change-over contacts and fixed switching difference Xsd
HBC11*F001
• Immersion depth 130...156 mm; includes fixing bracket
Technical data Power supply
5(3) A, 250 VAC 100 mA, 24 V
Setting range Setting accuracy Humidity calibration at Temperature influence Long-term stability Time constant in moving air (0.2 m/s) Switching difference Xsd Max. air speed
15...95% rh ±5% rh 55% rh, 23 °C Compensated –1.5% rh/a Approx. 3 minutes Typically 8% rh (after humidity calibration) 10 m/s
Humidity (non-condensing) Temperature Humidity (non-condensing) Temperature
30...90% rh 0...70 °C 10...95% rh -20...70 °C
Housing material Housing cover Sensor tube
Glass-fibre-reinforced thermoplastic Thermoplastic, sealable Glass-fibre-reinforced thermoplastic, Ø 30 mm PG 11 For electrical cables of up to 1.5 mm²
HBC111F001
Storage and transport
Xs XSd 3 2
1
HBC111F001
Ambient conditions
Operation
H%
Parameters
B01572
Max. load Min. load
Construction
H% Xs XSh
XSd
Cable inlet Screw terminals
HBC112F001
Low-Voltage Directive 2014/35/EU
IP30 (EN 60529) II (IEC 60730) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-13
Overview of types
1
Type
Switching range Xsh
Number of switches
Weight
HBC111F001
–
1
0.33 kg
HBC112F001
6...25% rh
2
0.35 kg
A
6 5 3 2 B04333
Type of protection Protection class EMC Directive 2014/30/EU
XSd
Standards and directives
HBC112F001
HBC 112: For 3-point control or min./max. monitoring and internally adjustable switching range X sd
Right of amendment reserved © 2024 Fr. Sauter AG
43
2-point controllers | Humidistats Accessories
Y
44
Type
Description
0303538001
Set for increasing protection rating to IP55 (housing lid with transparent cap for setpoint knob, seal, 1 cable gland - PG 11, 1 plug - PG 11)
0370560011
Cable screw fitting PG 11, plastic, for cable of Ø 9...11 mm
Right of amendment reserved © 2024 Fr. Sauter AG
Right of amendment reserved © 2024 Fr. Sauter AG
45
Data capture
Accurate measured values are the basis for efficient control. The results from the data capture form the basis for control and monitoring. SAUTER provides quality sensors for all physical variables, such as temperature, humidity, pressure, flow and air quality, that are specifically geared towards building automation systems and the HVAC industry.
46
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture Temperature EGT 130, 330, 332, 335, 430: Room temperature sensor, surface-mounted
49
EGT 386, 388, 486, 686, 688: Room temperature sensors, recessed
51
EGT 301, 401, 601: Outdoor-temperature sensor
52
EGT 353...356, 456, 554, 654: Cable temperature sensors
54
EGT 346...348, 392, 446, 447, 646, 647: Duct temperature sensors
56
Thermowells
58
EGT 311, 411, 611: Clamp-on temperature sensors
60
EGS 100: Radiation temperature sensor
62
Air quality EGQ 220, 222: Room transducer, CO2, surface-mounted
64
EGQ 212: Duct transducer, CO2, temperature
68
EGQ 120: Room transducer, air quality, surface-mounted
66
EGQ 110: Duct transducer, air quality (VOC), temperature
70
EGQ 281: Room transducer, CO2, recessed
67
72
EGE 112: Duct transducer, enthalpy
76
EGH 120, 130: Room transducer
73
EGH 102: Dew point monitor and transducer
77
EGH 681: Room transducer, relative humidity and temperature, recessed
74
EGH 103: Dew point monitor
78
EGH 110...112: Duct transducer, relative humidity and temperature
75
Humidity Overview of humidity sensors
Flow and pressure Overview of flow and pressure sensors
79
EGP 100: Differential pressure transmitter
80
XAFP 100: Flow probe
82
SVU 100: Air-flow transducer
83
DSU, DSI: Pressure transmitters
84
DSDU, DSDI: Differential pressure transmitter
86
SGU 100: Sash sensor
88
Right of amendment reserved © 2024 Fr. Sauter AG
47
X
Temperature sensors SAUTER temperature sensors are used for heating and air-conditioning systems in residential, office and business spaces. They are used to measure room, duct, outside and pipe temperatures.
Overview of temperature sensors
Type designation Application Pipe/duct Cable Room (passive) Room (active) Clamp-on temperature Outdoor temperature Further information
Type designation Application Pipe/duct Cable Room (passive) Room (active) Clamp-on temperature Outdoor temperature Radiation temperature Further information
48
EGT 130
EGT 330...335, 430
EGT 386, 388, 486, 686, 688
EGT 301, 401
− − − • − − Page 49
− − • − − − Page 49
− − • − − − Page 51
− − − − − • Page 52
EGT 353...356, 456, 554
EGT 346...348, 392, 446, 447
EGT 311, 411
EGS 100
− • − − − − − Page 54
• − − − − − − Page 56
− − − − • − − Page 60
− − − − − − • Page 62
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Temperature
EGT 130, 330, 332, 335, 430: Room temperature sensor, surface-mounted Features • Passive or active measuring element for room temperature • Variants with setpoint adjuster, presence button and multicolour status LED • Suitable for direct wall mounting and recessed junction boxes
X
Technical data Ambient conditions
Ambient temperature Ambient humidity
−35…70 °C Max. 85% rh, non-condensing
Colour Housing material Cable inlet Connection terminals Weight
Traffic white (RAL9016) Polycarbonate (PC) UL94-V0 Through the back Spring-type terminals, max. 1.5 mm² 50 g
Type of protection EMC-D 2014/30/EU (CE)
IP20 (EN 60529) after fitting EGT130F032: EN 60730-1 (mode of operation 1, residential premises) See EMC Directive EN IEC 63000
EGT*30F***
Construction
Standards, directives
CE/UKCA conformity1)
EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
EN IEC 63000
EGT332F103
Resistance values Measuring element Ni500 Ni1000 Pt100 Pt1000
A
Standard DIN 43760 DIN 43760 DIN EN 60751 DIN EN 60751
Nominal value at 0 °C 500 Ω 1000 Ω 100 Ω 1000 Ω
Tolerance at 0 °C ±0.4 K ±0.4 K ±0.3 K ±0.3 K
The tolerances only apply to the measuring elements. The accuracy of the sensor depends on the measuring element used and the cable length
Active type EGT130F032
Measuring range Measuring accura- Output signal cy at 21 °C Typically ±1% of 0...10 V, min. load 0…50 °C impedance 5 kΩ Other ranges can measuring be parametrised range2)3)
Power supply
Power consumption
15…24 VDC Max. 0.3 W (±10%) / (24 VDC) 24 VAC (±10%) 0.5 VA (24 VAC)
EGT335F103
Overview of types Type
Description
Output signal
Measuring range
EGT330F053
Room temperature sensor
Passive, Ni500
−35…70 °C
−
EGT330F103
Room temperature sensor
Passive, Ni1000
−35…70 °C
−
EGT332F103
Room temperature sensor, setpoint ad- Passive, Ni1000 juster
−35…70 °C
Pot. 2.5 kΩ
1)
2) 3)
Setpoint adjuster
Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be prevented by the customer.
Right of amendment reserved © 2024 Fr. Sauter AG
49
Data capture | Temperature
X
Type
Description
Measuring range
Setpoint adjuster
EGT335F103
Room temperature sensor, setpoint ad- Passive, Ni1000 juster, presence button, status LED (RGB)
Output signal
−35…70 °C
Pot. 2.5 kΩ
EGT430F013
Room temperature sensor
Passive, Pt100
−35…70 °C
−
EGT430F103
Room temperature sensor
Passive, Pt1000
−35…70 °C
−
EGT130F032
Room temperature transducer
Active, 0…10 V
0…50 °C
−
Accessories
50
Type
Description
0300230010
USB Bluetooth® dongle
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Temperature
EGT 386, 388, 486, 686, 688: Room temperature sensor, recessed Features • Passive room temperature measurement • For temperature measurement in dry rooms (e.g. in residential properties, offices and business premises) • Including frame
X
Technical data Parameters
Measuring range Time constant in still air
Time characteristic
-35...70 °C 30 minutes
EGT386F101 EGT486F101
Ambient conditions
Storage and transport temperature Ambient temperature
–35...70 °C -35...70 °C
Housing Housing material Frame design
Pure white Thermoplastic Gira E2
Type of protection RoHS Directive 2011/65/EU
IP20 (EN 60529) EN IEC 63000
EGT686F101
Construction
Standards, directives
CE conformity according to
Resistance values / characteristics
/
The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.
Measuring element Ni1000 Pt1000 NTC 10k
Standard DIN 43760 DIN EN 60751 -
Nominal value at 0 °C 1000 Ω 1000 Ω 10 kΩ at 25 °C
Tolerance at 0 °C ±0.4 K ±0.3 K ±0.3 K
EGT388F101 EGT388F102 EGT688F101
Overview of types Type
Measuring element
Adjuster
Weight
EGT386F101
Ni1000
–
53 g
EGT388F101
Ni1000
10 kΩ
83 g
EGT388F102
Ni1000
100 Ω
83 g
EGT486F101
Pt1000
–
83 g
EGT686F101
NTC 10k
–
53 g
EGT688F101
NTC 10k
10 kΩ
83 g
Right of amendment reserved © 2024 Fr. Sauter AG
51
Data capture | Temperature
EGT 301, 401, 601: Outdoor-temperature sensor Features • Passive or active measuring element • Extra protection against dust and humidity (IP65) • Cable inlet on back or via cable gland
X
EGT*01F102
• For weather-dependent heating and ventilation systems
Technical data Parameters
Time characteristic
Recommended measurement current Time constant in still air
< 1 mA EGT*01F102: 12 minutes EGT301F031: 7 minutes
Ambient temperature
EGT*01F102: −35…90 °C EGT301F031: −35…70 °C −35…70 °C 85% rh
Ambient conditions
Storage and transport
Storage and transport temperature Humidity (non-condensing)
EGT301F031 Construction
Sensor sleeve
EGT301F031: stainless steel 1.4571 Ø 6 × 25 mm White Polyamide Screw terminals 0.35...1.5 mm2, for number of poles, see connection diagram EGT*01F102: M16 for cable min. Ø 5 mm, max. Ø 8 mm EGT301F031: M20 for cable min. Ø 5 mm, max. Ø 8 mm
Housing Housing material Connection terminals
Cable inlet
Standards, directives
Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU
CE conformity according to
IP65 (EN 60529) EN IEC 63000 EGT301F031: EN 60730-1 (mode of operation 1, residential premises)
Resistance values / characteristics
/
The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.
Measuring element Ni1000 Ni1000 TK5000 Pt1000
52
Standards DIN 43760 – DIN EN 60751
Nominal value at 0 °C 1000 Ω 1000 Ω 1000 Ω
Tolerance at 0 °C ±0.4 K ±0.4 K ±0.3 K
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Temperature Active type EGT301F031
Measuring range
Measuring accura- Output signal cy at 21 °C 5 temperature ranges Typically ±1% of 0...10 V, min. (−50...160 °C), adjustable on measuring range1)2) load impedevice (see connection diadance 1 kΩ gram)
Power supply 15…24 VDC (±10%) / 24 VAC (±10%)
Power consumption Max. 0.42 W / 0.84 VA
Overview of types Type
Description
Output signal
Measuring range
Weight
EGT301F102
Outdoor temperature sensor
Passive, Ni1000
−35…90 °C
80 g
EGT401F102
Outdoor temperature sensor
Passive, Pt1000
−35…90 °C
80 g
EGT601F102
Outdoor temperature sensor
Passive, Ni1000 TK5000
−35…90 °C
80 g
EGT301F031
Outdoor temperature transmit- Active, 0…10 V ter
1) 2)
X
−50...160 °C 120 g (5 ranges)
With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be avoided by the customer.
Right of amendment reserved © 2024 Fr. Sauter AG
53
Data capture | Temperature
EGT 353...356, 456, 554, 654: Cable temperature sensor Features • Passive measuring element • Particularly suitable for direct connection in installations with short distances between the controllers and the
sensors • Sensor with a wide range of applications and high type of protection (IP67) and fast time characteristic
X
• Used in air, used in liquid media with thermowells, or as a clamp-on temperature sensor with an accessory • Large temperature measuring range
EGT*5*F***
Technical data Parameters
Recommended measurement current Time constant with thermowell (LW 7) in still water Time constant in still air Time constant in moving air (3 m/s)
Time characteristic in water Time characteristic in air
Typ. < 1 mA 9 seconds (t63) 155 seconds (t63) 35 seconds (t63)
Construction
Sensor sleeve Material
Ø 6 × L (mm) - see table, up to 16 bar Sensor sleeve: Stainless steel 1.4571 Cable: see table Ø 5 mm with wire ferrules
Power cable Cable cross-section Active length
2 x 0.25 mm2 10 mm
Type of protection RoHS Directive 2011/65/EU
IP67 (EN 60529) EN IEC 63000
Standards and directives
CE conformity according to Resistance values / characteristics
/
The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.
Measuring element Ni1000 Ni1000 TK5000 Pt100 Pt1000 NTC 10k NTC 22k
Standards DIN 43760
Nominal value 1000 Ω at 0 °C 1000 Ω at 0 °C 100 Ω at 0 °C 1000 Ω at 0 °C 10 kΩ at 25 °C 22 kΩ at 25 °C
DIN EN 60751 DIN EN 60751 -
Tolerance at 0 °C ±0.4 K ±0.4 K ±0.3 K ±0.3 K ±0.3 K ±0.3 K
Overview of types Type
54
Measuring element
Sleeve length LH
Total length Lg
Material
Measuring range
Weight
EGT353F101
NTC 10k
50 mm
1.5 m
PVC
-35...100 °C
40 g
EGT353F103
NTC 10k
50 mm
3m
PVC
-35...100 °C
85 g
EGT353F110
NTC 10k
50 mm
10 m
PVC
-35...100 °C
280 g
EGT353F120
NTC 10k
50 mm
20 m
PVC
-35...100 °C
550 g
EGT554F103
NTC 22k
50 mm
3m
PVC
-35...100 °C
85 g
EGT354F102
Ni1000
50 mm
1m
PVC
-35...100 °C
30 g
EGT354F104
Ni1000
50 mm
3m
PVC
-35...100 °C
85 g
EGT354F111
Ni1000
50 mm
10 m
PVC
-35...100 °C
280 g
EGT354F121
Ni1000
50 mm
20 m
PVC
-35...100 °C
550 g
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Temperature Type
Measuring element
Sleeve length LH
Total length Lg
Material
Measuring range
Weight
EGT654F102
Ni1000 TK5000
50 mm
1m
PVC
-35…100 °C
30 g
EGT355F902
Ni1000
100 mm
2m
Silicone
-50...180 °C
60 g
EGT355F903
Ni1000
150 mm
2m
Silicone
-50...180 °C
60 g
EGT356F102
Ni1000
50 mm
1m
Silicone
-50...180 °C
30 g
EGT356F104
Ni1000
50 mm
3m
Silicone
-50...180 °C
90 g
EGT356F111
Ni1000
50 mm
10 m
Silicone
-50...180 °C
300 g
EGT356F304
Ni200
50 mm
3m
Silicone
-50...180 °C
90 g
EGT456F012
Pt100
50 mm
1m
Silicone
-50...180 °C
30 g
EGT456F102
Pt1000
50 mm
1m
Silicone
-50...180 °C
30 g
X
Accessories Type
Description
0300360000
Compression fitting G¼"; stainless steel, up to 16 bar
0300360003
Mounting flange; plastic
0300360004
Heat-conducting paste incl. gun with 2 g content
0300360008
Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)
0300360012
Sensor support spiral for fitting in ventilation duct
0313214001
Fixing kit for cable temperature sensor (holder, heat-conducting paste, retaining strap)
A
039*******: Thermowells (LW 7 and LW 15) made of brass or stainless steel (see product data sheet)
Right of amendment reserved © 2024 Fr. Sauter AG
55
Data capture | Temperature
EGT 346...348, 392, 446, 447, 646, 647: Duct temperature sensor Features • Passive or active measuring element • For use in pipes and vessels by means of optional thermowells (LW 7). For use in standard HVAC
applications up to 160 °C and aggressive ambient conditions up to 260 °C (EGT392F102)
X
Technical data Parameters
Time characteristic
EGT*4*
Recommended measurement current Typ. < 1 mA Time constant in moving air (3 m/s) 35 s (t63) Time constant in still air 155 s (t63) Time constant in still water 9 s (t63) Time constant in still water, with thermo- 17 s (t63) well made of brass Time constant in still water, with thermo- 20 s (t63) well made of stainless steel
Ambient conditions
Ambient temperature
Storage and transport
Storage and transport temperature Humidity (non-condensing)
EGT*4* passive: −35...90 °C EGT*4* active: −35...70 °C EGT392F102: −25...90 °C −35...70 °C 85% rh
Construction
Housing Housing material
EGT*4*: Black/yellow EGT*4*: Polyamide EGT392F102: Form J made of die-cast aluminium EGT*4*: 45° screw terminals 0.35...1.5 mm2 For number of poles, see connection diagram M16 for cable min. Ø 5 mm, max. Ø 8 mm Ø 6×L (mm) made of stainless steel 1.4571, up to 16 bar, see table 10 mm
Connection terminals EGT392F102
Cable inlet Immersion stem
Active length Standards, directives
CE conformity according to
Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU
IP65 (EN 60529) EN IEC 63000 EGT34*F031: EN 60730-1 (mode of operation 1, residential premises)
Resistance values / characteristics
/
The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.
Measuring element Ni1000 Ni1000 TK5000 Ni200 Pt1000 Pt100
56
Standard DIN 43760 – DIN 43760 DIN EN 60751 DIN EN 60751
Nominal value at 0 °C 1000 Ω 1000 Ω 200 Ω 1000 Ω 100 Ω
Tolerance at 0 °C ±0.4 K ±0.4 K ±0.4 K ±0.3 K ±0.3 K
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Temperature Measuring accura- Output signal cy at 21 °C1)2)
Active types
Measuring range
EGT346F031 EGT347F031 EGT348F031
5 temperature ranges Typically ±1% of (−50...160 °C), adjustable on measuring range device (see connection diagram)
0...10 V, min. load 5 kΩ
Power supply
Power consumption
15…24 V= Typical (±10%) / 0.35 W / 24 V~ (±10%) 0.82 VA
Overview of types Type
Description
Output signal Measuring range
Immersion length (L)
Weight
EGT346F022
Duct temperature sensor
Passive, Ni200
−50… 160 °C
100 mm
85 g
EGT346F102
Duct temperature sensor
Passive, Ni1000
−50… 160 °C
100 mm
85 g
EGT347F022
Duct temperature sensor
Passive, Ni200
−50… 160 °C
200 mm
95 g
EGT347F102
Duct temperature sensor
Passive, Ni1000
−50… 160 °C
200 mm
95 g
EGT348F102
Duct temperature sensor
Passive, Ni1000
−50… 160 °C
450 mm
120 g
EGT392F102
Duct temperature sensor
Passive, Ni1000
−50… 260 °C
100 mm
105 g
EGT446F012
Duct temperature sensor
Passive, Pt100
−50… 160 °C
100 mm
85 g
EGT446F102
Duct temperature sensor
Passive, Pt1000
−50… 160 °C
100 mm
85 g
EGT447F012
Duct temperature sensor
Passive, Pt100
−50… 160 °C
200 mm
95 g
EGT447F102
Duct temperature sensor
Passive, Pt1000
−50… 160 °C
200 mm
95 g
EGT646F102
Duct temperature sensor
Passive, Ni1000 TK5000
−35… 160 °C
100 mm
85 g
EGT647F102
Duct temperature sensor
Passive, Ni1000 TK5000
−35… 160 °C
200 mm
85 g
EGT346F031
Duct temperature transmit- Active, ter 0…10 V
−50...160 ° 100 mm C (5 ranges)
90 g
EGT347F031
Duct temperature transmit- Active, ter 0…10 V
−50...160 ° 200 mm C (5 ranges)
100 g
EGT348F031
Duct temperature transmit- Active, ter 0…10 V
−50...160 ° 450 mm C (5 ranges)
120 g
X
Accessories Type
Description
0300360000
Compression fitting G¼"; stainless steel, up to 16 bar
0300360003
Mounting flange; plastic
0300360004
Heat-conducting paste incl. gun with 2 g content
A
1) 2)
039*******: Thermowells (LW 7 and LW 15) made of brass or stainless steel (see product data sheet)
With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be avoided by the customer.
Right of amendment reserved © 2024 Fr. Sauter AG
57
Data capture | Temperature
Thermowells Features • Fitted in pipes and containers for holding sensor cartridges, immersion stems, temperature sensors,
temperature controllers or thermostats Made of brass (Ms) or stainless steel (V4A) • • Versions with cylindrical pipe thread (G½" male ISO 228/1, flat-sealing)
X
1)
or cone-shaped
(R½" ISO 7/1 sealing in thread) • With pressure spring (LW 15) • With retaining holder
Overview of types Type
LW
Length
Material
Thread
Nominal pressure
Test pressure Tmax
0391022050
7
50 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022100
7
100 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022200
7
200 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022300
7
300 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022450
7
450 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391022600
7
600 mm
Stainless steel
G½"
40 bar
60 bar
325 °C
0391011050
7
50 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011100
7
100 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011150
7
150 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011200
7
200 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011300
7
300 mm
Brass
R½"
10 bar
16 bar
160 °C
0391011450
7
450 mm
Brass
R½"
10 bar
16 bar
160 °C
0393022100
15
100 mm
Stainless steel
G½"
40 bar
60 bar
450 °C
0393022200
15
200 mm
Stainless steel
G½"
40 bar
60 bar
450 °C
0393022450
15
450 mm
Stainless steel
G½"
40 bar
60 bar
450 °C
0393012100
15
100 mm
Brass
G½"
16 bar
25 bar
160 °C
0393012200
15
200 mm
Brass
G½"
16 bar
25 bar
160 °C
0392022100
7
100 mm
Stainless steel
G½"
25 bar
40 bar
450 °C
0392022200
7
100 mm
Stainless steel
G½"
25 bar
40 bar
450 °C
0392022300
7
300 mm
Stainless steel
G½"
25 bar
40 bar
450 °C
1)
58
G½" male ISO 228/1, flat-sealing: for welding bushings with flat seal (accessories)
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Temperature
A A A
0392022100 and 0392022300 for TUC thermostats only With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). 0391... with pressure screw (retaining holder) up to max. 200 °C
Accessories Type
Description
0300360008
Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)
0364263000
Welding sleeve of steel, with female thread G½", flat seal of copper
0300360017
Pressure spring for LW 15 (10 pieces)
•
LW 7, 50 mm LW 7, 100 mm LW 7, 150 mm LW 7, 200 mm
• • • •
LW 7, 300 mm LW 7, 450 mm LW 7, 600 mm LW 15, 100 mm LW 15, 200 mm LW 15, 450 mm 0392022100 0392022200 0392022300
A A A A
• • • • • − − −
• L > 50 mm • • • • L > 300 mm • − − − − − − −
X
− − − − − − − • • • • • •
0392022100 and 0392022300 for TUC thermostats only. With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). Only use the thermowells (LW 15) with at least 2 sensors or thermostats with a diameter of at least 6 mm 0391... with pressure screw (retaining holder) up to max. 200 °C.
Right of amendment reserved © 2024 Fr. Sauter AG
59
Data capture | Temperature
EGT 311, 411, 611: Clamp-on temperature sensor Features • Passive or active measuring element • Extra protection against dust and humidity (IP65) • Temperature measurement on pipes • Including retaining strap for pipes of Ø 10...50 mm
X
• Heat-conducting paste (silicone-free) is included in the scope of delivery
EGT*11F***
Technical data Parameters
Time characteristic with heatconducting paste
Recommended measurement current Time constant
Typ. < 1 mA 16 s
Storage and transport temperature Humidity (non-condensing)
−35…70 °C 85% rh
Housing Housing material Connection terminals
Yellow/black Polyamide
Ambient conditions
Construction
Screw terminals 0.35...1.5 mm2, for number of poles, see connection diagram M16 for cable min. Ø 5 mm, max. Ø 8 mm
Cable inlet
Standards, directives
Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU
CE conformity according to
IP65 (EN 60529) EN IEC 63000 EGT311F031: EN 60730-1 (mode of operation 1, residential premises)
Resistance values / characteristics
/
The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.
Measuring element Ni1000 Ni1000 TK5000 Ni200 Pt1000 Active type EGT311F031
1) 2)
60
Standards DIN 43760 – DIN 43760 DIN EN 60751 Measuring range
Nominal value at 0 °C 1000 Ω 1000 Ω 200 Ω 1000 Ω
Measuring accura- Output signal cy at 21 °C 5 temperature ranges Typically ±1% of 0...10 V, min. (−50...160 °C), adjustable on measuring range1)2) load impedevice (see connection diadance 5 kΩ gram)
Tolerance at 0 °C ±0.4 K ±0.4 K ±0.4 K ±0.3 K Power supply
Power consumption 15…24 V= Max. (±10%) / 0.42 W / 24 V~ (±10%) 0.84 VA
With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be avoided by the customer.
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Temperature Overview of types Type
Description
Output signal
Measuring range
Weight
EGT311F022
Clamp-on temperature sensor
Passive, Ni200
−35…90 °C
80 g
EGT311F102
Clamp-on temperature sensor
Passive, Ni1000 −35…90 °C
80 g
EGT411F102
Clamp-on temperature sensor
Passive, Pt1000
−35…90 °C
80 g
EGT611F102
Clamp-on temperature sensor
Passive, Ni1000 −35…90 °C TK5000
80 g
EGT311F031
Clamp-on temperature trans- Active, 0…10 V mitter
−50...160 °C (5 ranges)
X
120 g
Accessories Type
Description
0300360002
Retaining strap 900 mm and heat-conducting paste
0300360004
Heat-conducting paste incl. gun with 2 g content
Right of amendment reserved © 2024 Fr. Sauter AG
61
Data capture | Temperature
EGS 100: Radiation temperature sensor Features • Mean value measuring of radiation temperature and room temperature • Ni or NTC characteristic • Passive measuring element • Measuring range: -35…70 °C
X
• Measuring element: Thin-film sensor
EGS100F70*
Technical data Parameters
Time characteristic
Measuring range Time constant in still air
-35...70 °C 15 min
Weight Dimensions Housing Housing material Connection terminals
0.1 kg 84.5 × 84.5 mm Pure white, similar to RAL 9010 Thermoplastic with black hemisphere 2 × 1.5 mm²
Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU
IP30 (EN 60529) EN IEC 63000 EN 60730-1 (mode of operation 1, residential premises)
Construction
Standards and directives
CE conformity
Overview of types
62
Type
Resistance values
Tolerance
Measuring elements
EGS100F705
1 kΩ (at 0 °C)
±0.4 K (at 0 °C)
2 × Ni500 as per DIN 43760 in series
EGS100F706
10 kΩ (at 25 °C)
±1% (at 25 °C)
2 × NTC 5 kΩ in series
EGS100F707
22 kΩ (at 25 °C)
±1% (at 25 °C)
2 × NTC 11 kΩ in series
Right of amendment reserved © 2024 Fr. Sauter AG
Air quality sensors Air quality is of the utmost importance for the performance and well-being of people in closed rooms. With CO2 and VOC sensors from SAUTER, it is possible to measure air quality exactly, so that ventilation systems can be controlled in accordance with demand. As a result, not only is the indoor air quality improved, but energy consumption is also reduced by improving the operational efficiency of ventilation systems.
Overview of air quality sensors
EGQ 220, 222
EGQ 120
EGQ 281
Application Room, surface-mounted Room, recessed Duct
Type designation
• − −
• − −
− • −
Variables CO2
•
−
•
− • − − Page 64
• − − − Page 66
− − − − Page 67
VOC Temperature Humidity Pressure Further information
EGQ 212
EGQ 110
Application Room, surface-mounted Room, recessed Duct
Type designation
− − •
− − •
Variables CO2
•
−
− • − − − Page 68
• − − − − Page 70
VOC Temperature Humidity Pressure Volume flow Further information
Right of amendment reserved © 2024 Fr. Sauter AG
63
Data capture | Air quality
EGQ 220, 222: Room transducer, CO2, surface-mounted Features • Measurement of CO2 concentration for demand-controlled ventilation of rooms such as meeting and
conference rooms, offices and classrooms • Available with and without temperature sensor • CO2 measurement with NDIR
Dual-beam technology, therefore stable in the long term and largely resistant to external influences • Very fast response to changes in the CO2 concentration in rooms
X EGQ220F032
1)
• Developed according to EN 13779, EN 15251, VDI 6038 and VDI 6040 directives
Technical data Power supply
Power supply Power consumption EGQ222F032
Start-up current
15…35 VDC / 19…29 VAC SELV Typ. 0.4 W at 24 VDC Typ. 0.8 VA at 24 VAC Max. 1.6 A
Parameters
Time characteristic
Readiness for operation
Temperature dependence Gradual drift2) Measuring range Average measuring accuracy
< 2 minutes operational, < 15 minutes response time 2 minutes 0…2000 ppm (ex works) ±75 ppm >750 ppm: ±10% (typ. at 21 °C) Typ. 0.135% of the measured value per mm Hg Typ. 2 ppm per °C (0…50 °C) < 5% FS or < 10% per year −35…70 °C ±0.5 K (typ. at 21 °C)
CO2
In room (0.1 m/s) Measuring range Average measuring accuracy
Ambient temperature Ambient humidity
−35…70 °C Max. 85% rh, non-condensing
Output signal
0…10 V CO2/temperature
Colour Housing material Cable inlet Connection terminals
Traffic white (RAL9016) Polycarbonate (PC) UL94-V0 Through the rear wall
Pressure dependence
Temperature (EGQ 222)
Ambient conditions
Inputs/outputs
Construction
Weight
Spring-type terminal, max. 1.5 mm2 90 g
Standards, directives
CE/UKCA conformity3)
Type of protection EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
1) 2) 3)
64
IP20 (EN 60529) after fitting EN 60730-1 (mode of operation 1, residential premises) See EMC-D EN IEC 63000 EN IEC 63000
NDIR: Non-dispersive infrared sensor Air flow velocity: 0.15 m/s. Air flow direction: Laminar upwards Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Air quality Overview of types Type
Description
EGQ220F032
Room transducer, CO2
Output signal
Active, 1 × 0…10 V, load ≥ 10 kΩ
EGQ222F032
Room transducer, CO2, temp.
Active, 2 × 0…10 V, load ≥ 10 kΩ
Accessories Type
Description
0300230010
USB Bluetooth® dongle
Right of amendment reserved © 2024 Fr. Sauter AG
X
65
Data capture | Air quality
EGQ 120: Room transducer, air quality, surface-mounted Features • Measures the relative VOC mixed gas concentration (organic components in the room air), such as
tobacco smoke, kitchen vapours • Demand-based ventilation control in buildings such as restaurants and offices • Active VOC semi-conductor sensor for measuring mixed gas concentration
X
• Suitable for direct wall mounting and recessed junction boxes
EGQ120F032
Technical data Power supply
Power supply Power consumption Start-up current
15…35 VDC / 19…29 VAC SELV Typ. 0.4 W at 24 VDC Typ. 0.8 VA at 24 VAC Max. 1.6 A
Parameters
Type of sensor
VOC (heated metal oxide semiconductor)
Ambient temperature Ambient humidity
−35…70 °C Max. 85% rh, no condensation
Output signal
Active, 0…10 V, min. load 10 kΩ
Colour Housing material Cable inlet Connection terminals
Traffic white (RAL9016) Polycarbonate (PC UL94-V0) Through the rear wall
Ambient conditions
Inputs/outputs
Construction
Weight
Spring-type terminal, max. 1.5 mm2 65 g
Standards, directives
CE/UKCA conformity1)
Type of protection EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
IP20 (EN 60529) after fitting EN 60730-1 (mode of operation 1, residential premises) See EMC-D EN IEC 63000 EN IEC 63000
Overview of types Type
Description
EGQ120F032
Room transducer, active, air quality
Accessories Type
Description
0300230010
USB Bluetooth® dongle
1)
66
Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Air quality
EGQ 281: Room transducer, CO2, recessed Features • CO2 sensor for continuous measurement of the CO2 concentration for the demand-controlled ventilation of
rooms (e.g. meeting rooms, conference rooms, offices, classrooms, etc.) • CO2 measurement with NDIR dual-beam technology , therefore stable in the long term and resistant to 1)
external influences
X
• Any ageing or contaminating effects are continuously compensated in real time • Very fast response to changes in the CO2 concentration in rooms • Temperature-compensated calibration for the standard air pressure of 1013 mbar
EGQ281F031
• Calibrated ex works and ready to use immediately • Low energy requirement of the ventilation system during the warming up time of the sensor • Including frame
Technical data Power supply
Power supply (SELV) Power consumption
15...24 V= (±10%) / 24 V~ (±10%) < 1.6 W (typ. 0.3 W) < 3.9 VA (typ. 0.7 VA)
Analogue output Load current
0...10 V Max. 10 mA
Measuring range Measuring accuracy Time constant Measuring cycle Long-term stability
0...2000 ppm < ±50 ppm 2% of the measured value (25 °C and 1013 mbar) < 195 s (t90) 15 s Typ. 20 ppm/year
Ambient temperature
−20...70 °C
Housing Housing material
Pure white Lower section: PA6 Front plate: PC Gira E2 90 g
Output signal
Parameters
Ambient conditions
Construction
Frame design Weight Standards, directives
CE conformity according to
Type of protection EMC Directive 2014/30/EU RoHS Directive 2011/65/EU
IP30 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000
Overview of types Type
Description
EGQ281F031
Room transducer, CO2; 0...10 V, recessed
1)
NDIR: Non-dispersive infrared sensor
Right of amendment reserved © 2024 Fr. Sauter AG
67
Data capture | Air quality
EGQ 212: Duct transducer, CO2 and temperature Features • Duct sensor for measuring carbon dioxide (CO2) content for demand-based ventilation of indoor spaces • CO2 measurement with NDIR
1)
Dual-beam technology, therefore stable in the long term and largely
resistant to external influences • Measurement of temperature in ventilation ducts
X
• Two analogue 0...10 V outputs are available: one for CO2 measurement and one for temperature
measurement. This allows direct connection to an automation station • Automatic drift compensation • Mounting accessories and flange included
Technical data EGQ212F032
Power supply
Power supply (SELV) Power consumption Peak inrush current
15…35 V= / 19…29 V~ Max. 2.3 W (24 V=) / 4.3 VA (24 V~) 1.2 A < 3 ms
Output signal
2 × 0…10 V, load min.: 10 kΩ
Flow speed In moving air (3 m/s) Measuring range Measuring accuracy
Measuring range Measuring accuracy
Min. 0.3 m/s, max. 12 m/s 5 minutes 0…2000 ppm ±50 ppm drift over the serviceable life +3% of the measured value (typical at 21 C, 50% rh) 0…50 °C ±0.5 K (typical at 21 °C)
Ambient temperature Ambient humidity
0...50 °C Max. 85% rh non-condensing
Connection terminals Cable cross-section Cable inlet
Plug-in female connectors, removable Max. 2.5 mm² Removable insert, M20 for cable, min. Ø 4.5 mm, max. Ø 9 mm Yellow/black Housing: PC, sensor tube: PA6 Stainless steel, wire mesh 19.5 mm 180 mm 150 g
Outputs
Parameters
Time characteristic CO2
Temperature
Ambient conditions
Construction
Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards, directives
CE conformity according to
Type of protection EMC Directive 2014/30/EU RoHS Directive 2011/65/EU
1)
68
Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000
NDIR: Non-dispersive infrared sensor
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Air quality Overview of types Type
Features
EGQ212F032
Duct transducer, CO2 and temperature; 2 × 0...10 V
Accessories Type
Description
0300360003
Mounting flange; plastic
X
Right of amendment reserved © 2024 Fr. Sauter AG
69
Data capture | Air quality
EGQ 110: Duct transducer, air quality (VOC), temperature Features • Duct air quality sensor for detection of volatile organic compounds (VOC) for demand-controlled ventilation
of indoor spaces. VOC sources include flue gases, solvents as well as various cleaning agents and building materials • Measurement of temperature in ventilation ducts
X
• Two analogue 0...10 V outputs are available: one for VOC measurement and one for temperature
measurement. This allows direct connection to an automation station • Automatic calibration via an integrated algorithm • Mounting accessories and flange included
Technical data EGQ110F032
Power supply
Power supply (SELV) Power consumption Peak inrush current
15…35 V= / 19…29 V~ Max. 2.3 W (24 V=) / 4.3 VA (24 V~) 1.2 A < 3 ms
Output signal
2 × 0…10 V, load min.: 10 kΩ
Flow speed In moving air (3 m/s) Measuring range Serviceable life Sensor Measuring range Measuring accuracy
Min. 0.3 m/s, max. 12 m/s 5 minutes 0...100% Typically 10 years Heated tin dioxide semiconductor 0…50 °C ±0.5 K (typical at 21 °C)
Ambient temperature Ambient humidity
0...50 °C Max. 85% rh non-condensing
Connection terminals Cable cross-section Cable inlet
Plug-in female connectors, removable Max. 2.5 mm² Removable insert, M20 for cable, min. Ø 4.5 mm, max. Ø 9 mm Yellow/black Housing: PC, sensor tube: PA6 Stainless steel, wire mesh 19.5 mm 180 mm 150 g
Outputs
Parameters
Time characteristic VOC
Temperature
Ambient conditions
Construction
Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards, directives
CE conformity according to
Type of protection EMC Directive 2014/30/EU
Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000
RoHS Directive 2011/65/EU
Overview of types
70
Type
Features
EGQ110F032
Duct transducer; VOC and temperature; 2 × 0...10 V
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Air quality Accessories Type
Description
0300360003
Mounting flange; plastic
X
Right of amendment reserved © 2024 Fr. Sauter AG
71
Humidity sensors SAUTER humidity sensors are used for the energy-efficient control and monitoring of ventilation systems. Sensors are available for measuring the relative humidity and enthalpy of the air. They can be used in residential or business premises and can also be fitted in air ducts.
Overview of humidity sensors
Type designation Application Room, surface-mounted Room, recessed Duct Clamp-on sensor Measurement Temperature Relative humidity Enthalpy Dew point Further information
72
EGH 120, 130
EGH 681
EGH 110…112
EGE 112
EGH 102
• − − −
− • − −
− − • −
− − • −
− − − •
• • − − Page 73
• • − − Page 74
• • − − Page 75
• − • − Page 76
− − − • Page 77
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Humidity
EGH 120, 130: Room transducer, relative humidity and temperature, surface-mounted Features • Measurement of humidity via a fast, capacitive sensor • Active measuring element • Suitable for direct wall mounting and recessed junction boxes
X
• Converts the measured values into a continuous analogue signal (0...10 V / 4...20 mA)
Technical data EGH120F042
Parameters
Relative humidity
Measuring range Measuring accuracy
Temperature
Measuring range Measuring accuracy
0...100% rh, no condensation ±2 % between 10…90 % rh (typ. at 21 °C) 0…50 °C ±0.5 °C (typ. at 25 °C)
Ambient temperature Ambient humidity
−35…70 °C Max. 85% rh, non-condensing
Colour Housing material Cable inlet Connection terminals
Traffic white (RAL9016) Polycarbonate (PC) UL94-V0 Through the rear wall
EGH130F032
Ambient conditions
Construction
Weight
Spring-type terminals, max. 1.5 mm2 80 g
Standards, directives
CE/UKCA conformity1)
Type of protection EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
IP20 (EN 60529) after fitting EN 60730-1 (mode of operation 1, residential premises) See EMC Directive EN IEC 63000 EN IEC 63000
Overview of types Type
Description
Output signal
Power supply
Power consumption
EGH120F042
Room transducer, rh, temp.
Active, 2 × 4…20 mA Max. load 500 Ω
15…24 VDC, ±10%
Max. 1 W
EGH130F032
Room transducer, rh, temp.
Active, 2 × 0…10 V Min. load 20 kΩ
15…24 VDC, ±10% 24 VAC, ±10%
Max. 0.3 W (24 VDC) 0.5 VA (24 VAC)
Accessories Type
Description
0300230010
USB Bluetooth® dongle
1)
Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
73
Data capture | Humidity
EGH 681: Room transducer, relative humidity and temperature, recessed Features • Measures the relative humidity and temperature in rooms • Regulation of the room climate in combination with room automation systems • Fast response time and high precision
X
• Including frame
EGH681F031
Technical data Power supply
Power supply Power consumption
15...24 V= (±10%) or 24 V~ (±10%) Typ. 0.3 W / 0.5 VA
Output signal
0...10 V, load resistance at least 10 kΩ
Measuring range, temperature Measuring range, humidity
0...50 °C 0...100% rh
Ambient temperature
−20...70 °C
Housing Housing material
Pure white Lower section: ABS Front plate: PC Gira E2 80 g
Output signal
Parameters
Ambient conditions
Construction
Frame design Weight Standards, directives
CE conformity according to
Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU
IP30 (EN 60529) EN IEC 63000 EN 60730-1 (mode of operation 1, residential premises)
Overview of types
74
Type
Description
EGH681F031
Room transducer, relative humidity and temperature, recessed
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Humidity
EGH 110...112: Duct transducer, relative humidity and temperature Features • Measures the relative humidity and temperature in air ducts • Measurement by means of fast capacitive measuring element • Active and passive measuring element
X
• Immersion depth 140 mm • Mounting flange supplied
Technical data Power supply
EGH11*F0*1
Power supply Peak inrush current
15...24 V= (±10%) or 24 V~ (±10%) 1.5 A, 4 ms
Measuring range, humidity Measuring accuracy, humidity Repeat accuracy Gradual drift Measuring range, temperature Measuring accuracy, temperature Repeat accuracy Gradual drift In moving air (3 m/s) Readiness for operation
Hysteresis
0...100% rh, no condensation Typ. ±2% (10...90% rh) Typ. ±0.1% rh Typ. < 0.5% rh/year -20...80 °C ±0.5 °C (typ. at 25 °C) Typ. ±0.1 °C Typ. < 0.04 °C/year 2 minutes (t63) 10 seconds (operational), 5 minutes (max. precision) Min: 0 m/s Max: 10 m/s ±1%
Ambient temperature
-20...70 C
Connection terminals
Screw terminals, max. 1.5 mm2 M20 for cable with min. Ø 5 mm, max. Ø 10 mm Yellow/black PA6 Stainless steel, wire mesh 19.5 mm 140 mm 120 g
Parameters
Humidity
Temperature
Time characteristic
Flow speed
Ambient conditions
Construction
Cable inlet Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards and directives
CE conformity according to
Type of protection EMC Directive 2014/30/EU RoHS Directive 2011/65/EU
Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000
Overview of types Type
Power consumption
Output signal
EGH110F041
Max. 1 W (24 V=)
2 × 4...20 mA (max. load 500 Ω)
EGH111F031
Max. 0.4 W (24 V=) | 0.8 VA (24 V~)
2 × 0...10 V (min. load 10 kΩ) + Ni1000
EGH112F031
Max. 0.4 W (24 V=) | 0.8 VA (24 V~)
2 × 0...10 V (min. load 10 kΩ)
Right of amendment reserved © 2024 Fr. Sauter AG
75
Data capture | Humidity
EGE 112: Duct transducer, enthalpy Features • Measures the enthalpy and temperature in air ducts • Measurement by means of fast capacitive measuring element • Active measuring element • Unaffected by flow speeds and normal contamination
X
• Mounting flange supplied
Technical data Power supply
EGE112F031
Power supply Power consumption
15...24 V= (±10%) or 24 V~ (±10%) Max. 0.4 W (24 V=) | 0.8 VA (24 V~)
Output signal
2 x 0...10 V (min. load 10 kΩ)
Flow speed Time constant in moving air (3 m/s) Measuring range Measuring accuracy Measuring range Measuring accuracy
Min. 3 m/s Max. 10 m/s 3 minutes 0...100 kJ/kg 3.5 kJ/kg (typ. at 21 °C) −20...80 °C ±0.5 °C (typ. at 25 °C)
Ambient temperature
−20...70 °C
Connection terminals
Screw terminal, max. 1.5 mm2 M20 for cable Ø min. 5.8 mm, max. 10 mm Yellow/black PA6 Stainless steel, wire mesh 19.5 mm 140 mm 120 g
h
Outputs
Parameters
Time characteristic Enthalpy Temperature
Ambient conditions
Construction
Cable inlet Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards, directives
CE conformity according to
Type of protection EMC Directive 2014/30/EU
Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000
RoHS Directive 2011/65/EU
Overview of types
76
Type
Description
EGE112F031
Duct transducer, enthalpy and temperature, 2 x 0...10 V
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Humidity
EGH 102: Dew point monitor and transducer Features • Protects against dew formation on chilled ceilings • Controls a regulating unit via a holding relay that interrupts the cooling water flow or increases the cooling
water temperature • Best solution for monitoring chilled-ceiling systems
X
• Measurement taken by a spring-mounted dew point sensor • Active measuring element • Variant with external sensor (EGH102F101)
EGH102F*01
• Holding relay with changeover contacts • Includes retaining strap for pipes of Ø 10...100 mm and heat-conducting paste
Technical data
24 V~/=, ±20% Max. 1 VA
Measuring range Changeover contact1) Response time in still air Exposure to dew Switching difference Switching point
70...85% rh 1 A, 24 V~/= 80 to 99% rh, 99 to 80% rh, max. 3 minutes Max. 30 min Fixed, approx. 5% rh 95 ±4% rh
Ambient temperature
5...60 °C
Output signal
Approx. 70...85% rh, 0...10 V, load > 10 kΩ
Screw terminals Housing Housing material Weight Cable inlet
For electrical cables of up to 1.5 mm² Pure white (RAL 9010) Fire-retardant thermoplastic 0.1 kg For Pg 11
Type of protection Mode of operation
IP40 (EN 60529) Type 1 C (EN 60730)
XSd
Power supply Power consumption
95 %rh
Power supply
Parameters
6
5
4
Ambient conditions
Inputs/outputs
Construction
Standards and directives
Overview of types Type
Clamp-on sensor
EGH102F001
Integrated in housing
EGH102F101
Cable 1 m long, sensor integrated in the cable end
1)
When activating relays, gates etc. with cos φ < 0.3, it is recommended to use RC circuitry in parallel to the coil. This reduces contact pitting and prevents high-frequency interference
Right of amendment reserved © 2024 Fr. Sauter AG
77
Data capture | Humidity
EGH 103: Dew point monitor Features • Protects against dew formation on chilled ceilings, etc. • Controls a regulating unit via a holding relay that interrupts the cooling water flow or increases the cooling
water temperature. • Measurement is performed by a dew point sensor
X
• Potential-free output contact for 24 V and 230 V • Holding relay with changeover contacts • LED indicator for power supply and dew formation
EGH103F001
• Plug-in connectors for electrical cables up to 1.5 mm2 • Cable inlet M20 • Fitted onto pipes using the provided cable tie for pipes Ø 10...40 mm
Technical data Power supply
Power supply Power consumption
230 V~ ±10% Max. 3.5 VA
Changeover contact1) Switching point Switching difference
5 A, 230 V~ 95 ±4% rh Fixed, approx. 5% rh
Ambient temperature
−20…60 °C (non-condensing)
Housing Weight
Pure white, PA6 0.19 kg
Type of protection EMC Directive 2014/30/EU
IP 65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN 61000-6-1, EN 61000-6-3
Parameters
Ambient conditions
Construction
Standards and directives
CE conformity according to
Low-Voltage Directive 2014/35/EU
Overview of types Type
Description
EGH103F001
Dew point monitor 230 V~
Accessories Type
Description
0300360004
Heat-conducting paste incl. gun with 2 g content
1)
78
When activating relays, gates, etc. with cos φ < 0.3, it is recommended to use RC circuitry in parallel to the coil. This reduces contact pitting and prevents high-frequency interference
Right of amendment reserved © 2024 Fr. Sauter AG
Flow and pressure sensors SAUTER flow and pressure sensors enable the accurate measurement of air pressures and flow speeds in rooms and ventilation ducts. This includes the measurement of duct pressures for precise control and monitoring of ventilation systems. Additionally, SAUTER flow and pressure sensors can also be used to measure room pressures in laboratories and clean rooms and for flow monitoring in fume cupboards.
Overview of flow and pressure sensors
Type designation Variable Application Duct Laboratories & clean rooms Fume cupboards Pressure monitoring in liquids, gases and vapours Travel measurement Further information
EGP 100 ∆p
XAFP 100 ∆p
SVU 100 m/s
DSU, DSI ∆p
DSDU, DSDI ∆p
SGU 100 mm
• • • −
• • • −
− − • −
− − − •
− − − •
− − • −
− Page 80
− Page 82
− Page 83
− Page 84
− Page 86
• Page 88
Right of amendment reserved © 2024 Fr. Sauter AG
79
Data capture | Flow and pressure
EGP 100: Differential pressure transducer Features • Exact measurement of positive, negative and differential pressures in gases • Optimised for applications such as filter monitoring, room or duct pressure monitoring, level monitoring in
fluids, actuating frequency converters for fan control and recording volume flow, especially for room air balancing in laboratories • Can be ideally combined with XAFP 100 flow probe for precise measurement of volume flow
X
• Static pressure sensor • Can be fitted in any position • Can be used for dusty air or air polluted with chemicals (not ATEX approved)
EGP100F*12
• Manufacturer’s test certificate ex works • The measuring range can be adapted optimally to the needs of the application • Variable zero point and filter time constant to suppress pressure surges in the system • Display shows the actual value and the signal progression (depending on type) • Status LED for immediate indication of operating status (depending on type) • Measuring range can be reduced to one third (depending on type) • Fitted to either wall or DIN rail (EN 60715) • Cover that does not require special tools to open
Technical data Power supply
Power consumption F**2 Power consumption F**1
Power supply 24 V~ 24 V= 24 V~ 24 V=
24 V~/=, ±20% 3.0 VA 1.3 W 1.4 VA 0.4 W
Admissible positive pressure Influence of position1) Non-linearity Zero point stability Reproducibility Pneumatic connection2) Parts in contact with media
±20 kPa < 0.1% FS (full span) 1% FS pressure-linear < 0.3% FS 0.2% FS 6.2 mm PC/ABS blend
Media temperature Admissible operating pressure pstat3) Ambient temperature Ambient humidity
0…70 °C ±7 kPa
Output signal4)
F*01: 0...10 V, load > 10 kΩ F*02/F*12: 0(2)...10 V, load < 500 Ω F*01: 0.05...2 s F*02, F*12: 0.15...5.2 s
Parameters
Output signal (sqr) 10 V-
Ambient conditions
0(2) 0
Differential pressure Dp Measuring range
Gain Dp = 1
Inputs/outputs
Gain Dp = 3
Filter time constant
1)
2)
3) 4)
80
0…60 °C 5...95% rh, no condensation
The sensor is calibrated at the factory for vertical fitting. The influence of position must be taken into account if the unit is not fitted in the vertical position Max. length of measuring wire (di = 6.2 mm): Lmax = 15 m for time constant < 0.5 s, Lmax = 60 m for time constant > 0.5 s The zero point should be recalibrated if the admissible operating pressure is exceeded With a load of < 500 Ω, a change-over to 0...20 mA or 4...20 mA occurs automatically. Output protected against short circuits and excess voltage up to 24 V~
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Flow and pressure
Construction
Pressure connection Housing Cable gland Screw terminals
Internal Ø 6 mm PC/ABS M16 For electrical cables of up to 1.5 mm²
Type of protection Protection class EMC Directive 2014/30/EU
IP65 (EN 60529) III (EN 60730-1) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4
Standards, directives
X
Overview of types
/
Output signal: Analogue output limited to 10.6 V. Measured values with an overrun of 6% of the measuring range can therefore be transferred
/
Variable characteristic/LED: Manual adjustment of measuring range with gain potentiometer. Signal curve: linear/rootextracted. Output signal: 0...10 V / 2...10 V via DIP switches or with CASE Sensors software
Type
Measuring range
Display
Variable characteristic/LED
Weight (kg)
EGP100F101
±75 Pa, ±0.75 mbar
−
−
0.17
EGP100F102
±75 Pa, ±0.75 mbar
−
•
0.18
EGP100F112
±75 Pa, ±0.75 mbar
•
•
0.19
EGP100F201
±150, 1.5 mbar
−
−
0.17 0.18
EGP100F202
±150, 1.5 mbar
−
•
EGP100F212
±150, 1.5 mbar
•
•
0.19
EGP100F301
0...150 Pa, 0...1.5 mbar
−
−
0.17
EGP100F302
0...150 Pa, 0...1.5 mbar
−
•
0.18
EGP100F312
0...150 Pa, 0...1.5 mbar
•
•
0.19
EGP100F401
0...300 Pa, 0...3.0 mbar
−
−
0.17
EGP100F402
0...300 Pa, 0...3.0 mbar
−
•
0.18
EGP100F412
0...300 Pa, 0...3.0 mbar
•
•
0.19
EGP100F601
0...1000 Pa, 0...10.0 mbar
−
−
0.17
EGP100F602
0...1000 Pa, 0...10.0 mbar
−
•
0.18
EGP100F612
0...1000 Pa, 0...10.0 mbar
•
•
0.19
Accessories Type
Description
0010240300
Connection set, 6 mm, complete
XAFP100F001
Flow probe to measure the air volume in ventilation ducts
CERTIFICAT001
Manufacturer’s test certificate type M
CERTIFICAT999
Test for further device (from 2 pcs.)
0300360001
USB-RS-485 converter
Right of amendment reserved © 2024 Fr. Sauter AG
81
Data capture | Flow and pressure
XAFP 100: Flow probe for ventilation ducts Features • Flow probe for precise and inexpensive recording of differential pressure signals in ventilation and air
X XAFP100F001
conditioning systems • Efficient regulation of applications for demand-controlled ventilation in offices, laboratories, fume cupboards and clean rooms, by combining an air damper and an electronic/pneumatic volume flow controller In combination with a square root differential pressure sensor, air volume flows can be reliably recorded • and monitored • Optimised flow profile for accurate measurement of differential pressure signals • Can be used in atmospheres containing aggressive substances • Length (396 mm) can be shortened on site if necessary
Technical data Parameters
Measurement tolerance Range (mm)
< 3% DN 80…400
Operating temperature Ambient humidity
0...50 °C < 85% rh, no condensation
Function
Flow probe
Dimensions Bore Flow probe Seal Connecting tube
65 × 40 × 396 mm (W × H × L) Ø 30...32 mm PA 6 PE, physiologically safe PU
Electrical Flammability
UL 7468 UL 94, IEC 60695-2-12, IEC 60695-2-13
Admissible ambient conditions
Function
Construction
Material
Standards and directives
Flow probe
Overview of types
82
Type
Features
XAFP100F001
Flow probe for ventilation ducts
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Flow and pressure
SVU 100: Air-flow transducer Features • Precise and long-term stable recording of air inflow speeds in fume cupboards with a time constant of <100
ms Particularly suitable for fume cupboards with horizontal and vertical front sashes • • Air volume control according to needs for fume cupboards with horizontal and vertical front sashes
X
• Precise and long-term stable recording of air inflow speeds in fume cupboards • Reliable detection of reversal of flow direction • Integrated filter unit that protects against contamination of the sensor
SVU100F005
• Dynamic pressure sensor based on thin-film technology • Fitted to the fume cupboard simply and quickly
Technical data Power supply
Power supply Power consumption
24 V~, -15%/+20%, 50...60 Hz 1 VA
Measuring range Measuring span1) Differential pressure Time constant Air throughput rate
0...1 Pa 0...1.3 m/s Approx. 0...1 Pa < 0.1 s
Ambient temperature Ambient humidity
5...55 °C < 90% rh
Output signal2) Linearity
0...10 V 2% (based on the output signal)
Type of protection EMC Directive 2014/30/EU
IP40 (EN 60529) with terminal cover EN 61000-6-1, EN 61000-6-3
Parameters
3 cm3/min (at 1 m/s)
Ambient conditions
Inputs/outputs
Standards and directives
CE conformity according to
Overview of types Type
Feature
SVU100F005
Linear to v [m/s]
A
1) 2)
Specified flow speed is based on ρ = 1.2 kg/m3
Recommended measuring span 0.2...1.3 m/s (output 2...10 V) Output signal: Output protected against short circuits and excess voltage up to 24 V~
Right of amendment reserved © 2024 Fr. Sauter AG
83
Data capture | Flow and pressure
DSU, DSI: Pressure transmitter Features • For measuring pressure in liquids, gases and vapours • Sturdy device with ceramic diaphragm • High precision • High positive pressure protection
X
• High vibration resistance • Low hysteresis • Standard signal 2...10 V or 4...20 mA
DS*2**F002
• Pressure sensor made of stainless steel for aggressive media • With standard plug as per DIN EN 175301-803-A
Technical data Power supply
Power supply Electrical connection
See type list DSI: Two-wire DSU: Three-wire
Temperature dependence
Zero point 0.07% FS/K Measuring range 0.05% FS/K DSU: Ub ≥ 15 V ≥ 5 kΩ Ub ≥ 20 V ≥ 2 kΩ DSI: (Ub-6 V)/0.02 A
Parameters
Admissible load
Ambient conditions
Ambient temperature Media temperature
0...60 °C 0...85 °C
Hysteresis Linearity
< 0.5% FS < 1% FS
Housing material Device plug
Chromium-nickel steel 1.4305 Plug connection 4-pin, standard plug DIN EN 175 01-803-A, cable gland M16
Cable cross-section
Max. 1.5 mm2 G ½" 0.2 kg
Inputs/outputs
Construction
Pressure connection Weight Standards and directives
CE conformity according to
Type of protection Protection class EMC Directive 2014/30/EU
PED 2014/68/EU
84
IP65 (EN 60529) III (EN 61140) EN 61000-6-1 / EN 61000-6-2 EN 61000-6-3 / EN 61000-6-4 EN 60730 Subject to Art. 3.3 of PED without safety function
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Flow and pressure Overview of types Type
Measuring range (bar)
Output signal
Power supply
Maximum pressure Power consumption
DSU203F002
0...2.5 bar
0...10 V
24 V=/~
8 bar
24 V=/~, 0.5 W (VA)
DSU206F002
0...6 bar
0...10 V
24 V=/~
20 bar
24 V=/~, 0.5 W (VA)
DSU210F002
0...10 bar
0...10 V
24 V=/~
32 bar
24 V=/~, 0.5 W (VA)
DSU216F002
0...16 bar
0...10 V
24 V=/~
50 bar
24 V=/~, 0.5 W (VA)
DSU225F002
0...25 bar
0...10 V
24 V=/~
80 bar
24 V=/~, 0.5 W (VA)
DSI203F002
0...2.5 bar
4...20 mA
24 V=
8 bar
24 V=, 0.7 W
DSI206F002
0...6 bar
4...20 mA
24 V=
30 bar
24 V=, 0.7 W
DSI210F002
0...10 bar
4...20 mA
24 V=
32 bar
24 V=, 0.7 W
DSI216F002
0...16 bar
4...20 mA
24 V=
50 bar
24 V=, 0.7 W
DSI225F002
0...25 bar
4...20 mA
24 V=
80 bar
24 V=, 0.7 W
X
Accessories Type
Description
0300360007
Capillary throttle, stainless steel, length 1 m, G½"-G½"
0300360015
Wall holder for DSU/DSI
Right of amendment reserved © 2024 Fr. Sauter AG
85
Data capture | Flow and pressure
DSDU, DSDI: Differential pressure transmitter Features • For measuring pressure differences in liquids, gases and vapours • Pressure measuring in non-aggressive fluids or gaseous media • Sturdy device with ceramic diaphragm • For use in filter technology, heating systems etc.
X
• Differential pressure measuring range from 0...6 bar • Analogue signal 0...10 V or 4...20 mA • 24 V~/= supply voltage
DSD*10*F021
• With fitting bracket • Standard plug as per DIN EN 175301-803-A
Technical data Power supply
Power supply Electrical connection Power consumption
24 V=/~, ±20%, (50...60 Hz) Three-wire < 1.5 W (VA)
Output signal
0...10 V Load: > 2 kΩ 4...20 mA Load: ≤ 700 Ω (V=), ≤ 400 Ω (V~) ≤ 1%
Parameters
Accuracy1) Ambient conditions
Ambient temperature Media temperature
-20...80°C 0...80°C (non-freezing media) 45...75% rh 64 bar (both sides)
Ambient humidity Burst pressure Construction
Housing material Diaphragms Connection thread Device plug
Weight
Brass Ceramic G ⅛" (female thread) Plug connection 4-pin, standard plug DIN EN 175 01-803-A, cable gland M16 0.62 kg
Type of protection EMC Directive 2014/30/EU PED 2014/68/EU
IP65 (EN 60529) EN 61326-1, EN 61326-2-3 Fluid group II, article 4.3
Standards and directives
CE conformity according to
Overview of types Type
Measuring range ∆p
Output signal
Max. pressure (connection +)
Max. pressure (connection -)
DSDI101F021
0...1 bar
4...20 mA
10 bar
5 bar
DSDI103F021
0...2.5 bar
4...20 mA
21 bar
15 bar
DSDI106F021
0...6 bar
4...20 mA
21 bar
15 bar
DSDU101F021
0...1 bar
0...10 V
10 bar
5 bar
DSDU103F021
0...2.5 bar
0...10 V
21 bar
15 bar
DSDU106F021
0...6 bar
0...10 V
21 bar
15 bar
1)
86
Including non-linearity and hysteresis in compensated temperature range 10...70°C
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Flow and pressure Accessories Type
Description
0300360005
Cutting ring fitting G⅛" to 6 mm pipe (2 pcs)
0300360006
Pneumatic fitting G⅛" to 6 mm hose (2 pcs)
0300360016
Throttle screws G⅛", G⅛" (2 pcs)
X
Right of amendment reserved © 2024 Fr. Sauter AG
87
Data capture | Flow and pressure
SGU 100: Sash sensor Features • Infinitely-variable measurement of the position of the vertical front sash on laboratory fume cupboards • Accurate detection of sash position, with no wear and tear • Fast control of the air volume; no oscillation • Easy fitting, preferably on the counterweight of the front sash
X
• Teach-in function for adjusting the travel of the front sash
SGU100F01
• Easy to program using the SAUTER CASE Sensors software • Integrated excess-travel alarm • Power cable 2.5 m long, 7 × 0.32 mm2, fixed to housing • Fitted with halogen-free cable as standard • Remote access and remote maintenance: Commissioning and service via bus or external push-button • 3-colour LED status indicator • Acoustic status and alarm elements (can be deactivated)
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power consumption 24 V~1)
±20%, 50...60 Hz ±20% Typically: 2 VA, 0.75 W, inactive buzzer, max.: 4 VA, 1.5 W, active buzzer Typically: 0.6 W, inactive buzzer, max.: 1.1 W, active buzzer
Power consumption 24 V=2)
Parameters
Linearity error
Max. 1.5% based on working range, e.g.: 2...10 V = 8 V < 100 ms 0...5, 22 s, variable using SAUTER CASE Sensors
Hardware response time3) Filter time constant
Ambient conditions
Operating temperature Storage and transport temperature Humidity
0...55 °C –20...70 °C 85% rh, no condensation
Digital input
Iout_source max.: 1 mA, Vout max.: 18 V at Rload = ∞ Isink max.: 2 mA, open collector output, 100 mV at Isink 2 mA, Vin max.: 24 V=, 20% at Isink = 0 mA 0/2...10 V, 1 mA max., Vout max.: 11.5 V, can be parametrised, Default 2...10 V 2.5% (unlinearity, hysteresis, offset, amplified; based on working range) < 0.04 %/K
Inputs/outputs
Alarm output
Voltage output4)
Typical overall error Temperature effect
1) 2) 3) 4)
88
Default is buzzer active Inactive/active buzzer: Default is buzzer active The set filter time constant must be added Protected against short circuits and excess voltage to 24~
Right of amendment reserved © 2024 Fr. Sauter AG
Data capture | Flow and pressure Construction
Weight Length of cable without bus termination5)
0.68 kg Up to 200 m, Ø 0.5 mm
Type of protection Protection class Software EMC Directive 2014/30/EU
IP10 (EN 60529, IP20 (EN 60529) III (EN 60730) A (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4
Standards and directives
X
Overview of types Type
Working range
Resolution of working stroke
SGU100F010
200…800 mm for bench-mounted fume cupboards (max. spring travel 1000 mm)
< 1 mm
SGU100F011
400…1600 mm for walk-in fume cupboards (max. spring travel 2000 mm)
< 2 mm
Accessories Type
Description
0300360001
USB-RS-485 converter
5)
Cable length of bus termination on both sides 120 Ω: 200...500 m, Ø 0.5 mm
Right of amendment reserved © 2024 Fr. Sauter AG
89
Single-room, heating and airconditioning controllers
For all building situations: stand-alone or networked. SAUTER stand-alone controllers are tailored to applications such as heating, air-conditioning, ventilation or room control. They can be installed quickly. The intuitive operating concept ensures maximum comfort and guarantees, at the same time, the greatest possible energy efficiency in day-to-day operations. This allows all requirements for smooth functionality and economical operation to be combined. 90
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers Single-room control Overview of room temperature controllers
92
NRFC 413, 422…424: Modbus fan coil thermostat
93
TRA 410, 421: Room thermostat for heating and heating/cooling with display
97
TRT 317, 327: Electronic room thermostat for heating and heating/cooling
99
FXV 3***: Electrical distributor
101
FXV 33** EasySwitch: Electric distributor for control signals
103
equitherm heating control Overview of heating controllers
105
EQJW 146: Heating and district heating controller, equitherm
108
EQJW 126: Heating controller, equitherm
106
EQJW 246: Heating and district heating controller, equitherm
111
flexotron controllers for ventilation and air-conditioning Overview of controllers for ventilation and air-conditioning
114
RDT 405, 410: Electronic controller for heating, cooling and ventilation, flexotron400
115
VAV compact controllers ASV205BF132*, ASV215BF132*: VAV compact controller
118
ASV2*5BF152*: VAV controller for laboratory and pharmaceutical applications
121
FCCP: Fume cupboard indicator and monitor
124
Right of amendment reserved © 2024 Fr. Sauter AG
91
C
Room temperature controllers The SAUTER single-room controller combines the highest standards of operability with a modern design. The device can be used in various applications in hotel, business or residential premises. These include individual temperature control for single rooms, apartments and zones in 2- and 4-pipe systems. The electronic room controller is powerful, economical and easy to operate.
Overview of room temperature controllers
Type designation
NRFC 4
Application Air-conditioning controller Fan-coil controller For 2-pipe installation For 4-pipe installation For 2/3-way zone valve For 6-way ball valve
• • • • − −
Outputs Continuous Quasi-continuous, 2-point 3-point Relay
• • − •
Control PI
•
Operation and indicator Display Presence button
• −
Communication Protocols Further information
92
Modbus RTU Page 93
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | Single-room control
NRFC 413, 422…424: Modbus fan coil thermostat Features • Single-room controller for heating and cooling by means of air conditioning units in commercial and
residential buildings For 2- or 4-pipe fan coil units, two-stage heating systems or water-bearing heat pumps • • Can be integrated into building management systems via Modbus/RTU • Large configurable display with backlight • Integrated ON/OFF timer • Deactivatable button operation for public installations • Valve control via 2-point or 0...10 V output
C
NRFC413MF111
• Supports 3-speed fans or fans with EC motor • Summertime/wintertime change-over in 2-pipe applications • Automatic deactivation of internal temperature sensor when using a cable temperature sensor • Installation via mounting plate without opening the controller • Universal design and low installation height of 14 mm for inconspicuous fitting
Technical data Power supply
Power supply Power consumption
100…240 V~, 50/60 Hz 5 VA
Ambient temperature Ambient humidity Storage and transport temperature
0…40 °C 10…90% rh, no condensation -10…60 °C
Temperature sensor Digital input
NTC 10k closed < 0.3 V= open > 0.7 V= 0…10 V 0…10 V (100 kΩ) 2.2 A (IR); 3.6 A (IX) cos φ 0.98 each at 240 V~
Ambient conditions
Inputs/outputs
Inputs
Analogue input Analogue output U Relay output
Outputs
Interfaces, communication
RS-485
Communication protocol Connection
Indicator/display Buttons
Modbus/RTU Screw terminal, 3-pole 0.14...1.5 mm² rigid A (D+) / B (D-) 4800, 9600 bit/s (adjustable) 164 01, 03, 04, 06, 16 CRC-16 u16 10 bit, 1 start, 8 data, 1 stop, no parity LCD display with backlight (adjustable) 6
Weight Dimensions W × H × D Housing Housing material Fitting
0.3 kg 88 × 88 × 46.2 mm Upper and lower part white Polycarbonate On round or square recessed box
Bus speed Address range Function codes CRC check Data type Data format
Construction
Right of amendment reserved © 2024 Fr. Sauter AG
93
Single-room, heating and air-conditioning controllers | Single-room control
Standards, directives
CE conformity according to
Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RoHS Directive 2011/65/EU
IP20 (EN 60529) II as per IEC 60730 EN 60730-1, EN 60730-2-9 residential premises Type1.C EN 60730-1, EN 60730-2-9 EN IEC 63000
Inputs/outputs Type NRFC413MF111 NRFC422MF111 NRFC423MF111 NRFC424MF112
C
AI 1 × NTC, 1 × 0...10 V 1 × NTC 1 × NTC 1 × NTC
DI 1 1 1 1
AO 1 0 2 2
DO 3 × relay (single-pole normally-open contact) 5 × relay (single-pole normally-open contact) 3 × relay (single-pole normally-open contact) 3 × relay (single-pole normally-open contact)
Overview of types
94
Type
Description
Fan
NRFC413MF111
2-pipe, continuous, with positional feedback signal
3 speeds 3 speeds
NRFC422MF111
2-pipe or 4-pipe, 2-point
NRFC423MF111
2-pipe or 4-pipe, continuous
3 speeds
NRFC424MF112
2-pipe or 4-pipe, 2-point or 2-pipe, continuous
EC motor with cut-off function
Right of amendment reserved © 2024 Fr. Sauter AG
Surface temperature regulation The systems and solutions from SAUTER set standards for convenient control of surface heating and cooling systems. The products stand for technologically advanced, precise and easy to operate installations. The systems provide modern solutions for single- and multi-family buildings, hotels and public buildings, where the focus is on optimal comfort, easy operation and energy efficiency.
Overview of surface temperature regulation
Type designation
TRA 410, 421
TRT 317, 327
Application Controller Electrical distributor Operating device
• − •
• − •
Circuits/zones Channels Time programme/set-back mode
− •
− •
Power supply 24 V / 230 V Battery mode
• −
• −
Operation and indicator Display Sensor buttons Rotary knob Status LED
• − • −
− − • −
− • − • − Page 97
− • − • − Page 99
Communication and functions Communication via wireless connection Communication via wire connection Network connection/LAN Heating/cooling Access via app Further information
Right of amendment reserved © 2024 Fr. Sauter AG
95
Type designation
FXV 3***
FXV 33**
Application Controller Electrical distributor Operating device
− • −
− • −
Circuits/zones Channels Time programme/set-back mode
6/10 •
8 •
Power supply 24 V / 230 V Battery mode
•/• −
−/• −
− − − •
− − − •
− • − • − Page 101
− • − • − Page 103
Operation and indicator Display Sensor buttons Rotary knob Status LED Communication and functions Communication via wireless connection Communication via wire connection Network connection/LAN Heating/cooling Access via app Further information
96
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | Single-room control
TRA 410, 421: Electronic room thermostat for heating and heating/cooling with display Features • Electronic room thermostat for 24 V or 230 V for heating or heating/cooling with display • Easy to read LCD with backlight on TRA 421 • Silent-switching Triac output (24 V types) • Easy to wire up • NTC sensor
C
• Time programme and pilot clock output integrated in TRA 421 • Optimised time programme for comfort control and energy saving • Input for lowering the room temperature (TRA 410)
TRA4**F21*
• Input for heating/cooling changeover (TRA 421) • Input for external temperature sensor • Cooling lock function on versions for heating/cooling • Integrated “NC” and “NO” changeover • Modern design with ergonomic setpoint adjuster • Restriction of temperature setting range • Automatic frost protection facility at 5 °C and valve protection facility
Technical data Power supply
Power supply Power consumption Fuse
See type list < 0.3 W in idle state In housing: 230 V= T1AH 24 V= T1A
Number of actuators
Setting range Switching difference Set-back Measuring element
AXT: 230 V, max. 5 pcs. parallel 24 V, max. 4 pcs. parallel 5...30 °C ±0.2 K 2 K or adjustable NTC 22k
Ambient temperature Ambient humidity
0...50 °C 5...80% rh, no condensation
Housing
Cover: White (RAL 9016) Lower section: Signal white (RAL 9003) Thermoplastic PC + ABS Wall, recessed junction box
Parameters
Ambient conditions
Construction
Housing material Fitting Inputs/outputs
Switching element Switch rating ECO input
Right of amendment reserved © 2024 Fr. Sauter AG
230 V, relay 24 V, Triac 230 V, 1 A 24 V, 1 A 230 V, voltage detection 230 V 24 V, voltage detection 24 V
97
Single-room, heating and air-conditioning controllers | Single-room control Heating/cooling
Input: 230 V, voltage detection 230 V 24 V, voltage detection 24 V Output: 230 V, 100 mA 24 V, 100 mA
Pilot timer
Connection terminals / cable
Connection terminals
C
Power cable
Screw terminals 0.22 mm2 to 1.5 mm2 Solid: NYM-J/NYM-O (max. 5 × 1.5 mm²) Flexible: H03V2V2H2-F / H05V2V2H2-F
Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP20 (EN 60529) III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-3 EN 60730-1, EN 60730-2-9
Standards, directives
CE conformity according to
Overview of types Type
Description
Power supply
Weight
TRA410F210
Heating, lowering, frost protection function
230 V~, ±10%, 50 Hz
130 g
TRA410F212
Heating, lowering, frost protection function
24 V~, ±20%, 50 Hz
130 g
TRA421F210
Heating/cooling, lowering, frost protection and valve protection function, cooling lock
230 V~, ±10%, 50 Hz
140 g
TRA421F212
Heating/cooling, lowering, frost protection and valve protection function, cooling lock
24 V~, ±10%, 50 Hz
140 g
Accessories Type
98
Description
AXT3**
Thermal actuators for unit valves (see product data sheet)
EGT554F103
Cable temperature sensor, NTC 22k, −35...100 °C, IP67, length 3 m
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | Single-room control
TRT 317, 327: Electronic room thermostat for heating and heating/cooling Features • Electronic room thermostat for 24 V or 230 V for heating or heating/cooling • Silent-switching Triac output on 24 V types • Easy to wire up • NTC sensor • With input for lowering the room temperature
C
• With input for heating/cooling changeover (TRT 327) • With cooling lock function on versions for heating/cooling • Modern design with ergonomic setpoint adjuster
TRT3**F21*
• With restriction of temperature setting range • Electrical connection in baseplate with screw terminals • With automatic frost protection facility at 8 °C and valve protection function
Technical data Power supply
Power supply Power consumption Fuse
24 V~ / 230 V~ < 0.3 W in idle state In housing: 230 V= T2AH 24 V= T1A
Number of actuators
Setting range Switching difference Set-back Measuring element
AXT: 230 V, max. 6 pcs. parallel 24 V, max. 4 pcs. parallel 10...28 °C ±0.5 K 2K NTC
Ambient temperature Ambient humidity
0...50 °C 5...80% rh, no condensation
Housing
Cover: White (RAL 9016) Lower section: Signal white (RAL 9003) Thermoplastic PC + ABS Wall, recessed junction box
Parameters
Ambient conditions
Construction
Housing material Fitting Inputs/outputs
Switching element Switch rating ECO input Heating/cooling
230 V, relay 24 V, Triac 230 V, 1.8 A 230 V, voltage detection 230 V 24 V, voltage detection 24 V 230 V, voltage detection 230 V 24 V, voltage detection 24 V
Connection terminals / cable
Connection terminals Switching difference Cord grip
Right of amendment reserved © 2024 Fr. Sauter AG
Screw terminals 0.22mm2 to 1.5mm2 ±0.5 K External
99
Single-room, heating and air-conditioning controllers | Single-room control
Standards, directives
CE conformity according to
Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP20 (EN 60529) III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-3 EN 60730-1, EN 60730-2-9
Overview of types
C
Type
Description
Voltage
TRT317F210
Heating, lowering, frost protection function
230 V~, ± 10 %, 50 Hz 90 g
Weight
TRT317F212
Heating, lowering, frost protection function
24 V~, ± 20 %, 50 Hz
TRT327F210
Heating/cooling, lowering, frost protection and valve protection function, cooling lock
230 V~, ± 10 %, 50 Hz 135 g
TRT327F212
Heating/cooling, lowering, frost protection and valve protection function, cooling lock
24 V~, ± 10 %, 50 Hz
90 g
135 g
Accessories
100
Type
Description
AXT3**
Thermal actuators for unit valves (see product data sheet)
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | Single-room control
FXV 3***: Electric distributor for positioning signals Features • For easy wiring of up to 6 or 10 zones in a surface heating system • For transferring switching signals from the unitary controllers for heating or heating/cooling • Individual forwarding of time commands or night set-back to the appropriate actuators; max. 2 timer
FXV3210F002
channels • With pump and boiler control • Pump logic with adjustable follow-on time for actuating the circulation pump • Integrated valve protection function
C
• Input for temperature limiter or dew point monitor • LED status indicator • Pump control direction switching for NC/NO actuators • For connecting up to 18 actuators • Cable guidance, standard-compliant cord grip and screwless terminal connections • Easy, intuitive wiring and installation
Technical data Power supply
Power supply 230 VAC Power supply 24 VAC Distributor fuse 24 V Distributor fuse 230 V
±10%, 50...60 Hz ±20%, 50...60 Hz T2A T4AH
Circuits/zones Timer channels/set-back
6 or 10 2
Ambient temperature Storage temperature Ambient humidity
0...50 °C –20…70 °C < 80% rh
Outputs
Number of actuators
Inputs
Pump connection Boiler connection Set-back Heating/cooling TB or dew point
6 channels: Max. 15 pcs. 10 channels: Max. 18 pcs. Max. 6 (2) A Max. 6 (2) A Potential-free contact input Potential-free contact input Potential-free NC contact
Parameters
Ambient conditions
Inputs/outputs
Construction
Housing material Cover Fitting
Flame-retardant ABS plastic, black RAL9005 Transparent grey plastic Mounted unit, DIN rail
Connection terminals / cable
Connection terminals
Power cable
Cable clamping device
Right of amendment reserved © 2024 Fr. Sauter AG
Terminals with spring technology for 0.2 to 1.5 mm² vertical cable entry Solid: NYM-J/NYM-O (max. 5 × 1.5 mm²) Flexible: H03V2V2H2-F / H05V2V2H2-F Integrated in housing
101
Single-room, heating and air-conditioning controllers | Single-room control Standards, directives
Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
CE conformity
IP20 (EN 60529) II (EN 60730) EN 60730-1 Type 1C EN 60730-1 & -2-9 Type 1C
Overview of types
C
Type
Nominal voltage
Channels
Weight
FXV3006F001
24 V~ / 230 V~ Heating, with decrease
Features
6
482 g
FXV3110F001
230 V~
Heating/cooling, with decrease and pump control
10
515 g
FXV3110F002
24 V~
Heating/cooling, with decrease and pump control
10
515 g
FXV3210F001
230 V~
Heating/cooling, with decrease, pump logic, boiler control and LED indicator
10
550 g
FXV3210F002
24 V~
Heating/cooling, with decrease, pump logic, boiler control and LED indicator
10
534 g
Accessories
102
Type
Description
0450573001
Transformer 230 / 24 V, 42 VA
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | Single-room control
FXV 33** EasySwitch: Electric distributor for control signals Features • For the control of a maximum of twelve thermal actuators for unit valves and the connection of up to eight
room thermostats • Flexible assignment of the actuators to the room thermostats via rotary switch
FXV3308F011
• Distribution of the power supply, the positioning signals and a shared time programme for room operating
units • Easy-to-change channel assignment without rewiring • Pump logic module for activating a circulation pump
C
• Input for timer for individual forwarding of time commands to the heating zones • LED status indicators for power supply, pump logic module and active heating channels • Integrated cable guides and terminal connection without tools • Fitting on DIN rail or wall mounting
Technical data Power supply
Power supply Distributor fuse 230 V
230 V~, ±10%, 50...60 Hz T4AH (5 × 20 mm)
Control loops/heating zones1) Timer channel/set-back
Max. 8 inputs Yes
Ambient temperature Storage temperature Ambient humidity
0...50 °C −20...70 °C 10...85% rh
Outputs
Number of actuators
Inputs
Pump connection Set-back
Max. 12 thermal actuators for unit valves (for heating circuits) Max. 2 (1) A Contact input
Parameters
Ambient conditions
Inputs/outputs
Construction
Housing material
Cover material Fitting Dimensions W × H × D
PC-ABS plastic, black (similar to RAL9005) Fire-retardant as per UL94V-0 PC plastic, grey transparent Fire-retardant as per UL94V-0 Mounted unit, DIN rail, 35 mm or optionally screw-on mounting 350 × 100 × 52 mm
Connection terminals / cable
Connection terminals Cable cross-section Power cable
Cable clamping device
1)
Spring-loaded plug-in connectors 0.5...1.5 mm² Solid: NYM-J/NYM-O (max. 5 × 1.5 mm²) Flexible: H05V2V2H2-F Cable fastening points integrated without tools into housing
TRA or TRT room thermostats: TRA: max. five AXT per heating zone TRT: max. six AXT per heating zone
Right of amendment reserved © 2024 Fr. Sauter AG
103
Single-room, heating and air-conditioning controllers | Single-room control Standards, directives
Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
CE conformity
IP20 (EN 60730) II (EN 60730) EN 60730-1, residential premises EN 60730-1 & -2-9 Type 1C
Overview of types Type
Nominal voltage
Features
Channels
Weight
FXV3308F011
230 V~
Heating/cooling, with decrease, pump logic and LED indicator
8
580 g
C
104
Right of amendment reserved © 2024 Fr. Sauter AG
Heating controller SAUTER heating controllers of the equitherm series are easy to operate, while ensuring that your installation meets the highest standards of energy-optimised operation. Using communication accessories, the devices can be networked together in larger plants or integrated into a building automation system. The applications for these heating controllers include weather-dependent boiler and/or supply temperature control and domestic hot water preparation, as well as heating control in local or district heating networks.
Overview of heating controllers
EQJW 126
EQJW146F001
EQJW146F002
EQJW246F002
Application Solar Boiler control Supply temperature control Heating of drinking water Local/district heating
Type designation
− − • − •
• • • • •
• • • • •
• • • • •
Operation Symbol display Graphics display
• −
• −
− •
− •
Function Control loops Switching programmes
1 •
•
•
3 •
Inputs/outputs Inputs/outputs (0...10 V) Digital inputs Analogue inputs (Ni1000/ Pt1000) Relay (pump/actuator)
− − 3 3
Communication Interfaces Protocols
Logbook Further information
2
1 2 8 7
1/1 17 17 11
RJ45 Modbus RTU, device bus (TAP)
− Page 106
Right of amendment reserved © 2024 Fr. Sauter AG
− Page 108
• Page 108
Modbus RTU, Device bus (TAP), M-Bus • Page 111
105
Single-room, heating and air-conditioning controllers | equitherm heating control
EQJW 126: Heating controller with digital user interface, equitherm Features • PI supply temperature control by heating curve or 4-point characteristic • Convenient to use with modern operating concept (turn and press) and large LCD • Convenient weekly and annual switching programmes with optimisation of switching times
EQJW126F001
C
• Automatic summertime/wintertime changeover • Min./max. limitation of supply temperature and max. limitation of return temperature • Frost-protection facility and pump and valve anti-jamming function • Function heating (floor-drying function) • Room temperature switching using room temperature sensor • Ni/Pt1000 inputs for the outside, supply, return flow and room temperature • Relay outputs with varistor suppression for activating control units and pump • Manual mode • Electrical connection in baseplate • Interface for various accessories such as modem, gateway, data logging module etc.
Technical data Power supply
Power supply Power consumption
230 V~, ±15%, 50...60 Hz Approx. 1.5 VA
Amplification KP Integral action time Frost-protection temperature Normal temperature Reduced temperature Supply temperature Outdoor temperature Cycle time Running time of valve
0.1...50 1...999 seconds 3 °C 0...40 °C 0...40 °C −5...150 °C −50...50 °C Running time of the valve ÷ 15 30...300 seconds
Ambient temperature Ambient humidity Storage and transport temperature
0...40 °C 5...95% rh, no condensation −10...60 °C
Number of inputs Number of outputs Pump relay1) Actuator relay (3-point or 2-point)2)
3 analogue, Ni1000/Pt1000 3 relays 1 × 2 A, 250 V~, cos φ > 0,5 2 × 2 A, 250 V~, cos φ > 0,5
Backup power supply
Min. 24 hours, typically 48 hours
Accuracy Number of switching commands Min. switching interval Number of switching commands Min. switching interval
< 10 minutes/year 42/week 15 minutes 20 1 day
Parameters
Control parameters
Temperature ranges
Ambient conditions
Inputs/outputs
Function
Digital timer for weekly/annual switching programme Weekly switching programme Annual switching programme
1) 2)
106
Start-up current max. 16 A (1 second) Extra low voltage not admissible
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | equitherm heating control
Interfaces and communication
Interface Protocol
RJ45 Modbus, device bus (TAP)
Weight Dimensions Housing Housing material Fitting Screw terminals
0.5 kg 144 × 98 × 54 mm Light-grey Fire-retardant thermoplastic Wall, switch panel, DIN rail For electrical cables of up to 2.5 mm²
Type of protection (when fitted in panels) Protection class Software class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP40 (EN 60529)
Construction
C
Standards and directives
CE conformity according to
II (IEC 60730-1) A (IEC 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-3 EN 60730-1
Overview of types Type
Features
EQJW126F001
Heating controller with digital user interface
Accessories Type
Description
AVF***
Motorised valve actuator (see product data sheet)
AVM***
Motorised valve actuator (see product data sheet)
AXM***
Motorised valve actuator (see product data sheet)
EGT***
External temperature sensor Ni1000 (see product data sheet)
0440210001
Communication module for connecting EQJW 126/146 controllers to RS-232 (PC)
0440210002
Communication module for connecting EQJW 126/146 controllers to modem
0440210003
Communication module for connecting EQJW 126/146 controllers to RS-485 bus
0440210004
Communication module for connecting EQJW 126/146 controllers to RS-485 bus (master)
0440210005
ModBus-TCP gateway
0440210011
ModBus-GPRS gateway
0440210006
ModBus-MBus gateway
0440210007
Converter/repeater for RS-232 or RS-485 interfaces
0440210008
RS-485 overvoltage protection
0440210010
Parameter storage module for transferring controller parameters
0440210012
Cable converter, 2 conductors, RS-485
Right of amendment reserved © 2024 Fr. Sauter AG
107
Single-room, heating and air-conditioning controllers | equitherm heating control
EQJW 146: Heating and district heating controller, equitherm Features • Weather-dependent supply temperature control by heating curve or 4-point characteristic and drinking
water heating • 29 system models, for example for district heating, single-stage boilers, drinking water heating with solar
energy or buffer tank EQJW146F002
C
• Convenient to use with modern operating concept (turn and press) and large LCD • Convenient weekly and annual switching programmes with optimisation of switching times • Automatic summertime/wintertime changeover • Min./max. limitation of supply temperature and max. limitation of return temperature • Frost-protection facility and anti-jamming function for valve and pump • Floor-drying function • Function for protecting against legionellae • Room temperature switching using room-temperature sensors • Ni/PT1000 inputs for the outside, supply, drinking water, return flow and room temperature • Relay outputs with varistor suppression for activating control units and pumps • Manual mode • Logbook • Configurable input/output 0...10 V • External demand processing, binary or analogue (0..10 V) • Interface for various accessories such as modem, gateway, data logging module etc.
Technical data Power supply
Power supply Power consumption
230 V~, ±15%, 50...60 Hz Approx. 1.5 VA
Parameters
Control characteristic Control parameters
Temperature ranges
Supply temperature PI control Drinking water temperature 2-point Amplification KP 0.1...50 Integral action time 1...999 seconds Switching difference for drinking water 1...30 K Normal temperature 0...40 °C Reduced temperature 0...40 °C Supply temperature 0...140 °C Return temperature 0...140 °C Outdoor temperature −50...50 °C Drinking water temperature 20...90 °C Frost-protection temperature −15...3°C Running time of valve 30...300 seconds Cycle time Running time of the valve ÷ 15
Ambient conditions
Ambient temperature Ambient humidity Storage and transport temperature
0...40 °C 5...95% rh, no condensation −10...60 °C
Number of outputs Pump relay1)
7 relays 3 × 2 A, 250 V~, cos φ > 0,5
Inputs/outputs
1)
108
Start-up current max. 16 A (1 second)
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | equitherm heating control Actuator relay2) Continuous input/output3) Number of inputs Analogue inputs
4 × 2 A, 250 V~, cos φ > 0,5 1 × 0...10 V 2 digital, 8 analogue 8 Ni1000/Pt1000
Backup power supply Accuracy Number of programmes Number of switching commands Min. switching interval Number of programmes Number of switching commands Min. switching interval
Min. 24 hours, typically 48 hours < 10 minutes/year 3 42 each 15 minutes 1 (for heating circuits) 20 each 1 day
Interface Protocol
RJ45 Modbus, device bus (TAP)
Weight Dimensions Housing Housing material Fitting Screw terminals
0.5 kg 144 × 98 x 54 mm Light-grey Fire-retardant thermoplastic Wall, switch panel, DIN rail For electrical cables of up to 2.5 mm²
Type of protection
IP40 (EN 60529) (when fitted in panels) II (IEC 60730-1) A (IEC 60730-1, Appendix H) EN 61000-6‑1, EN 61000‑6‑3 EN 60730-1
Function
Timer Weekly switching programme
Annual switching programme
C
Interfaces, communication
Communication
Construction
Standards, directives
CE conformity according to
Protection class Software class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
Overview of types Type
Features
EQJW146F001
Heating and district heating controller with symbol display
EQJW146F002
Heating and district heating controller with graphic display
Accessories Type
Description
AVF***
Motorised valve actuator (see product data sheet)
AVM***
Motorised valve actuator (see product data sheet)
AXM***
Motorised valve actuator (see product data sheet)
EGT***
External temperature sensor Ni1000 (see product data sheet)
0440210001
Communication module for connecting EQJW 126/146 controllers to RS-232 (PC)
0440210002
Communication module for connecting EQJW 126/146 controllers to modem
0440210003
Communication module for connecting EQJW 126/146 controllers to RS-485 bus
0440210004
Communication module for connecting EQJW 126/146 controllers to RS-485 bus (master)
0440210005
ModBus-TCP gateway
0440210011
ModBus-GPRS gateway
0440210006
ModBus-MBus gateway
0440210007
Converter/repeater for RS-232 or RS-485 interfaces
0440210008
RS-485 overvoltage protection
2) 3)
Extra low voltage not admissible As input for requirement or outside temperature signal. As output for continuous control or requirement request, load > 5 kΩ
Right of amendment reserved © 2024 Fr. Sauter AG
109
Single-room, heating and air-conditioning controllers | equitherm heating control Type
Description
0440210010
Parameter storage module for transferring controller parameters
0440210012
Cable converter for 2-conductor RS-485 interface
C
110
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | equitherm heating control
EQJW 246: Heating and district heating controller, equitherm Features • Max. three control loops in the following combinations: • Control of a primary heat exchanger or boiler, two regulated and one unregulated heating circuit, and
control of the drinking water heating in the secondary circuit • Weather-dependent buffer tank control with solid fuel boiler and solar circuit control, as well as max. two
mixed-heating circuits • Control of two weather-dependent heating circuits and one drinking water heating with three valves in
the primary circuit
EQJW246F002
C
EQJW246F003
• Control of three weather-dependent heating circuits • EQJW246F003: Applications with up to six control loops via expansion modules • Different system models, e.g. for district heating, single-stage boilers, buffer tanks, drinking water heating
with solar energy • Weather-dependent supply temperature control based on heating characteristic or 4-point characteristic • To regulate more circuits, multiple controllers can be connected to each other via a device bus • Convenient operation with state-of-the-art operating concept (turn and press) and large graphical display • Convenient weekly and annual switching programmes with optimisation of switching times • Automatic summertime/wintertime change-over • Min./max. limitation of supply temperature and max. limitation of return temperature • Frost-protection facility and anti-jamming function for valve and pump • Floor-drying function • Function for protecting against legionellae • Room temperature switching using room-temperature sensors • Ni/Pt1000 inputs for the outside, supply, drinking water, return flow and room temperature • Relay outputs with varistor suppression for activating control units and pumps • Manual mode • Logbook • 0...10 V inputs for external requirement or outdoor temperature signal • 0...10 V outputs for external requirement, analogue/PWM outputs, speed-controlled pump etc. • Binary interfaces for fault signals or external requirement processing • Interfaces for various accessories such as modem, gateway, data storage module etc.
Technical data Power supply
Power supply Power consumption
230 VAC, ±15%, 50...60 Hz Max. 10 VA
Parameters
Control characteristic Control parameters
Temperature ranges
Supply temperature PI control Drinking water temperature 2-point Amplification KP 0.1…50 Integral action time 1...999 sec. Switching difference for drinking water 1…30 K Normal temperature 0…40 °C Reduced temperature 0…40 °C Supply temperature 0…140 °C Return temperature 0…140 °C Outdoor temperature −50…50 °C Drinking water temperature 20…90 °C Frost-protection temperature −15…3°C
Right of amendment reserved © 2024 Fr. Sauter AG
111
Single-room, heating and air-conditioning controllers | equitherm heating control Running time of valve Cycle time
15...240 sec. Running time of the valve ÷ 15
Ambient temperature Ambient humidity Storage and transport temperature
0…40 °C 5…95% rh, no condensation −10…60 °C
Pump relay2) Actuator relay3)
Inputs
5 × 2 A, 250 VAC F002: 6 × 2 A, 250 VAC F003: 4 × 2 A, 250 VAC, 2 × 0,12 A, 250 VAC (Triac) F002: 2 × 0…10 V F003: 4 × 0…10 V F002: 17 configurable Ni/Pt1000, binary, 1 × 0…10 V F003: 14 configurable Ni/Pt1000, binary, 3 × 0…10 V F002 and F003: 1 × pulse 3…800 lmp/h of h from heat meter for power limitation in HK1
Backup power supply Accuracy Number of programmes Number of switching commands Min. switching interval Number of programmes Number of switching commands Min. switching interval
Min. 24 h; typically 48 h < 10 minutes/year 3 42 each 15 minutes 1 (for heating circuits) 20 each 1 day
M-Bus
Ethernet
For max. 3 M-Bus units, protocol as per EN 1434-3 F002: 1 × RS-485 for device bus or Modbus/RTU F003: 2 × RS-485 for device bus and Modbus/RTU Modbus TCP/IP
Weight Dimensions Housing Housing material Fitting Screw terminals
0.5 kg 144 × 98 × 54 mm Light-grey Fire-retardant thermoplastic Wall, switch panel, DIN rail For electrical cables up to 2.5 mm²
Type of protection Protection class Software class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
IP40 (EN 60529) (panel mounting) II (IEC 60730-1) A (IEC 60730-1, Appendix H) EN 61000-6‑1, EN 61000‑6‑3 EN 60730-1
Ambient conditions
Inputs/outputs1)
C
Continuous output4)
Function
Timer Weekly switching programme
Annual switching programme
Interfaces, communication
RS-4855)
Construction
Standards, directives
CE conformity according to
1) 2) 3) 4)
5)
112
See also “Type overview” Start-up current max. 16 A (1 second) Extra low voltage not admissible 0...10 V output, e.g. for continuous control, outside temperature, external requirement or for speed control of pumps, load > 5 kΩ. 0/10 V: PWM signal for pump speed control Device bus: 2-wire bus, inverse, with reverse polarity protection, max. 32 users. Modbus/RTU: Modbus protocol data format 8N1, RJ45
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | equitherm heating control Overview of types Type
Features
Outputs
Inputs
EQJW246F002
Heating and district heating controller with graphic display, 1 × RS-485
11 relays, 2 × 0…10 V.
17 × Ni1000/Pt1000 and binary 1 × 0…10 V 1 × pulse
EQJW246F003
Heating and district heating controller with graphic display, 2 × RS-485, expandable for up to 6 control loops with accessories
12 relays, 4 × 0…10 V.
14 × Ni1000/Pt1000 and binary 3 × 0…10 V 1 × pulse
Accessories Type
Description
AVF***
Motorised valve actuator (see product data sheet)
AVM***
Motorised valve actuator (see product data sheet)
AXM***
Motorised valve actuator (see product data sheet)
EGT***
External temperature sensor Ni1000 (see product data sheet)
0440210001
Communication module for connecting EQJW 126/146 controllers to RS-232 (PC)
0440210002
Communication module for connecting EQJW 126/146 controllers to modem
0440210003
Communication module for connecting EQJW 126/146 controllers to RS-485 bus
0440210004
Communication module for connecting EQJW 126/146 controllers to RS-485 bus (master)
0440210005
ModBus-TCP gateway
0440210006
ModBus-MBus gateway
0440210011
ModBus-GPRS gateway
0440210007
Converter/repeater for RS-232 or RS-485 interfaces
0440210008
RS-485 overvoltage protection
0440210010
Parameter storage module for transferring controller parameters
0440210012
Cable converter for 2-conductor RS-485 interface
0440210014
I/O extension module for EQJW246F003
Right of amendment reserved © 2024 Fr. Sauter AG
C
113
Controllers for ventilation and air-conditioning SAUTER controllers for ventilation and air-conditioning cover all the possible applications for demand-based control of ventilation and air-conditioning systems. The large number of integrated standard applications meets the requirements for the modularity and the energy-efficient operation of your installations. A wide range of additional functions enable the establishment of complex control systems and the integration into a building automation system.
Overview of controllers for ventilation and air-conditioning
flexotron400 Type designation
RDT405F201
RDT410F*01
Control loops Cascade P-controller PI-controller PID-controller
− • • −
• • • •
Function Time programme
−
•
3 2 − − −
5 5 − − −
• − −
• • −
Communication Number of inputs Number of outputs Modbus BACnet Serial interface for parameters and configuration Application Supply temperature control Supply air cascade control Air-conditioning control Further information
114
Page 115
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | flexotron controllers for ventilation and air-conditioning
RDT 405, 410: Electronic controller for simple applications, flexotron400 Features • Five different control models for each device, for temperature, pressure, CO2, supply air cascade, heating • Easy to operate with large, illuminated LCD and rotary knob • Fast commissioning due to simple operating concept • Weekly programme (depending on variant) • External setpoint
RDT4**F*01
Power supply
Power supply
RDT 405 RDT 410
Power consumption Power consumption Start-up current
24 V~, ±15%, 50...60 Hz (RDT4**F201 230 V~, +10%/-15% 50…60 Hz (RDT4**F301) 4 VA, 2 W 7.5 VA, 5 W 16 A (2 ms) 24V~ devices 23 A (2 ms) 230 V~ devices
C
Y10188
PI
Technical data
RDT405F201 PI
RDT410F*01
Parameters
Control characteristics P-band Xp Integral action time
P/PI 0...99 K 0...990 s
Measuring range, temperature Measuring range, temperature Input for external setpoint Humidity Humidity CO2
-20...60, 20…100, 60…140°C 5…80, -30…50°C 0…40°C 0...100% rh 0...100% rh 10...9900 ppm for 100% signal
Ambient temperature Ambient humidity Storage and transport temperature
0...50 °C 5...95% rh, no condensation –20...70 °C
Universal inputs Digital inputs Analogue inputs
Digital outputs
Ni1000 (DIN 43760) Potential-free contacts Ni1000 (DIN 43760) for temperature, setpoint 0...10 V, 2 mA, protected against short circuit RDT410F201: Triac 2 × 24 V~, 0.3 A 1 × 230 V~, 5 A RDT410F301: Triac 2 × 24 V~, 0.16 A 1 × 230 V~, 5 A
Dimensions W × H × D Screw terminals Fitting Housing material
123 × 99 × 64 mm For electrical cables of up to 1.5 mm² Top-hat rail, wall, panel PC+ABS
Setting and measuring ranges
RDT 405 RDT 410
Ambient conditions
Inputs/outputs
Analogue outputs
Construction
Right of amendment reserved © 2024 Fr. Sauter AG
115
Single-room, heating and air-conditioning controllers | flexotron controllers for ventilation and air-conditioning
Standards and directives
IP20 (EN 60529) II (RDT410F301 only) EN 61000-6-1, EN61000-6-3
Type of protection1) Protection class EMC Directive 2014/30/EU
CE conformity according to
Overview of types
C
Type
Analogue inputs
Digital inputs
Universal inputs
Analogue outputs
Digital out- Input for ex- Week time- Weight puts ternal set- switch point
RDT405F201
1
1
1
2
0
1
−
0.2 kg
RDT410F201
2
2
1
2
3
1
•
0.3 kg
RDT410F301
2
2
1
2
3
1
•
0.45 kg
A
Week time-switch: only RDT410F*01 (number of switching commands: 8)
Accessories Type
Description
XYE460F001
flexotron400 demo case
0460240001
flexotron400/800 pluggable terminal strips
0460240010
Cabinet fitting kit for flexotron400
EGT388F102
External setpoint adjuster, room operating unit with potentiometer and temperature sensor, recessed
EGT333F102
External setpoint adjuster, room operating unit with potentiometer and temperature sensor, surfacemounted
1)
116
When installed
Right of amendment reserved © 2024 Fr. Sauter AG
VAV compact controller for laboratory and pharmaceutical applications SAUTER VAV controllers enable the air volume to be regulated in accordance with demand in order to optimise energy consumption in ventilation systems. They are used in laboratories, clean rooms, hospital wards and operating theatres. In combination with additional sensors and monitoring facilities, they ensure that fume cupboards are regulated in accordance with the relevant standards.
Overview of VAV compact controllers
Type designation Technical data Adm. dimensions of damper shaft (mm) Running time (s) Power supply (V) Communication/protocol Further information
ASV205BF132*, ASV215BF132*
ASV215BF152*
Ø 8...16 30...105 60...105 24 RS-485 SLC / BACnet MS/TP Page 118
Ø 8...16 3...15
Right of amendment reserved © 2024 Fr. Sauter AG
24 RS-485 SLC / BACnet MS/TP Page 121
117
Single-room, heating and air-conditioning controllers | VAV compact controllers
ASV205BF132E, ASV215BF132E: VAV compact controller Features • Supply and return air control for individual rooms such as offices, conference rooms and hotel rooms, in
conjunction with a VAV box or a damper and flow probe Pressure control in supply and return air ducts for low-noise, energy-efficient air distribution • • Static measurement of differential pressure with MEMS sensor • Can be used for measuring in areas with dirty or contaminated return air • Low energy consumption and long serviceable life thanks to low-wear stepping motor • Electromechanical, torque-based switch-off for safe operation
C
• Extremely simple installation due to self-centring shaft adapter
ASV205BF132E
• Disengageable gear unit for manual adjustment and positioning of damper • Integrated second control loop for the following applications : 1)
• Duct pressure and zone control • Room climate regulation • 2 x RS-485 bus interface on RJ12 and connection terminal • Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol +
• Communication within network via BACnet MS/TP
+
• Input and output signals for integrating: • Setpoints and actual values • Power outputs for reheaters and recoolers • EY-RU 3** digital room operating units • Analogue output • Easy programming of the following applications using the SAUTER CASE VAV software : 2)
• Volume flow control • Room pressure control • Duct pressure control • Adjustable end values of the differential pressure measuring range
3)
• 100...300 Pa • Efficient control algorithm for fast control loops • Priority control via switching contacts • Zero point can be calibrated
Technical data Power supply
Power supply4) Power consumption at nominal voltage Rated power 50/60 Hz (~/=) during continuous operation5) Power consumption when idle6)
1)
2)
3) 4)
5) 6)
118
24 V~, +/-20%, 50...60 Hz 24 V=, -10%/+20% 4.7 VA/2.5 W 1.5 VA/0.7 W
Application support depending on hardware and software version in CASE VAV manual D100316836 (German), D100316957 (English), D100316878 (French) Application support depending on hardware and software version in CASE VAV manual D100316836 (German), D100316957 (English), D100316878 (French) Available measuring ranges depending on hardware/type 24 V=: Analogue inputs that are not connected are rated 0 V. The nominal torque is achieved within the specified tolerances. Power specified without operating units FCCP 200, EY-RU 3* Holding torque ASV205*: 4 Nm ASV215*: 8 Nm
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | VAV compact controllers Parameters
Integrated damper actuator
∆p sensor
90° Angle of rotation7) Admissible dimensions of damper shaft Ø 8...16 mm, □ 6.5...12.7 mm Admissible damper shaft (hardness) Max. 300 HV Surge-voltage resistance 500 V (EN 60730) Operating noise < 35 dB (A) 0...500 Pa Measuring range ∆p (gain = 1)8) Linearity error 2% (at 25 °C) Time constant 0.2 s < 1 Pa Influence of position9) Reproducibility 0.2% FS Zero point stability 0.2% for 1 year Admissible positive pressure ±12.5 kPa Admissible operating pressure pstat10) ±7 kPa Low-pressure connections11)
Ø i = 3.5...6 mm
Operating temperature Storage and transport temperature Air humidity
0...55 °C –20...55 °C < 85% rh, no condensation
Analogue inputs Analogue outputs Digital inputs12)
0...10 V (Ri = 100 kΩ) 0...10 V, load > 10 kΩ Closed 1 V=, 1 mA, open > 2 V= 0.3 A at 24 V ~/= 0 to 50 °C Ni1000 (DIN 43760), NTC10k (10k3A1), Pt1000 (EN 60751) 0.3 °C (Ni1000/Pt1000), 0.1 °C (NTC) +/- 0.6 °C 0.3 A at 24 V ~/= Period duration 1 s....15 minutes 0...100%
C
Ambient conditions
Inputs/outputs
Digital output Resistive input
Resolution Measuring difference PWM
Interfaces and communication
RS-485 not electrically isolated Communication protocols Access method Topology Number of participants13) Bus termination
115 kBaud SAUTER Local Communication (SLC), BACnet MS/TP, ¼ load Master/slave Line 31 (32) with SLC 120 Ω (both ends)
Weight Fitting
0.8 kg Self-centring spindle adapter
Type of protection
IP00, IP30 (EN 60529) (with protection set) III (EN 60730)
Construction
Standards and directives
Protection class
7)
Maximum rotation angle 102° (without end stop) Available measuring ranges depending on hardware/type 9) Zero adjustment recommended during commissioning 10) Short-term overload; zero adjustment of sensor is recommended 11) Recommended hardness of tubing < 40 Sha (e.g. silicone) 12) Digital inputs for external potential-free contacts (gold-plated recommended) 13) One participant is always also the parametering tool, hence the maximum number of 31 connectible devices 8)
Right of amendment reserved © 2024 Fr. Sauter AG
119
Single-room, heating and air-conditioning controllers | VAV compact controllers Conformity
Machine directive 2006/42/EC, appendix II 1.B EN 61000-6-1, EN 61000-6-3, EN 61000-6-4, EN 61000-6-2
EMC Directive 2014/30/EU
Overview of types Type
Measuring range ∆p
Running time for 90°
Rotational torque
Holding torque
ASV205BF132E
0...300 Pa
30, 45, 60, 75, 90, 105 s
5 Nm
4 Nm
ASV215BF132E
0...300 Pa
60, 75, 90, 105 s
10 Nm
8 Nm
A A
C
For a running time of 105 s and an ambient temperature of ≥ 55 °C, the specified torque is reduced by 0.5 Nm. Current-free holding torque by means of interlocking in gear unit.
Accessories
120
Type
Description
0372301001
Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.
XAFP100F001
Flow probe to measure the air volume in ventilation ducts
0300360001
USB-RS-485 converter
0297867001
Reference pressure container
0430360100
IP30 protection set
0430360200
Replacement LP connector
0372129001
Torsion protection
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | VAV compact controllers
ASV215BF152*: VAV compact controller for laboratory and pharmaceutical applications Features • Controlling the return air in fume cupboards and controlling the supply and return air in laboratories, clean
rooms, hospital wards and operating theatres using a VAV box or a damper and flow probe • Static measurement of differential pressure based on the capacitive method of measurement • Zero point can be calibrated using software • Adjustable end values of the differential pressure measuring range
1)
• 50...150 Pa
C
• 100...300 Pa • Can be used for measuring in areas with dirty or contaminated return air • Brushless DC motor guarantees minimum energy consumption and a long service life
ASV215BF152D
• Electromechanical, torque-based switch-off for safe operation • Extremely simple installation due to self-centring shaft adapter • Disengageable gear unit for manual adjustment and positioning of damper • Easy programming of the following applications using SAUTER CASE Components:
2)
• Volume flow control • Room pressure control
+
+
• Duct pressure control • Flow control for fume cupboards • Efficient control algorithm for fast control loops • Integrated second control loop for:
3)
• Room-pressure control: can be ideally combined with EGP 100 with symmetrical measuring range • Fume-cupboard control ideally combined with SVU 100, SGU 100 and FCCP 200 • 2 x RS-485 bus interface on RJ12 and connection terminal • Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol • Communication within network via BACnet MS/TP
4)
• Integration of EY-RU 3** digital room operating units • FCCP 200 display and alarm unit for fume-cupboard control or room monitoring • Input and output signals for integrating: • Setpoints and actual values • Analogue output • Priority control via switching contacts
Technical data Power supply
Rotational torque Power supply5) Power consumption at nominal voltage Rated power 50/60 Hz (~/=) after 3 s running time during continuous operation Power consumption when idle6)
1) 2) 3) 4) 5)
6)
10 Nm 24 V~, ±20%, 50...60 Hz 24 V=, -10%/+20% Approx. 19 VA/10 W (10 Nm) Approx. 20 VA/11 W with FCCP 200 Approx. 6 VA/2 W
Available measuring ranges depending on hardware/type Application support depending on hardware and software version in CASE VAV manual Application support depending on hardware and software version in CASE VAV manual Support of BACnet MS/TP interface 24 V=: Analogue inputs that are not connected are rated 0 V. The nominal torque is achieved within the specified tolerances. Holding torque approx. 5 Nm
Right of amendment reserved © 2024 Fr. Sauter AG
121
Single-room, heating and air-conditioning controllers | VAV compact controllers Parameters
Integrated damper actuator
∆p sensor
C
Rotational torque 10 Nm 2 Nm Holding torque7) 90° Angle of rotation8) 3...15 s Running time for 90°9) Admissible dimensions of damper shaft Ø 8...16 mm, □ 6.5...12.7 mm Admissible damper shaft (hardness) Max. 300 HV Surge-voltage resistance 500 V (EN 60730) Operating noise < 49 dB (A) at 3 s Measuring range ∆p (gain = 1) 0...150/300 Pa Pressure range, types D/E10) Linearity error 2% FS Time constant 0.1 s Typically ±1 Pa Influence of position11) Reproducibility 0.2% FS Zero point stability 0.2% FS (at 20 °C) Admissible positive pressure ±10 kPa Admissible operating pressure pstat12) ±3 kPa Low-pressure connections13)
Ø i = 3.5...6 mm
Operating temperature Storage and transport temperature Air humidity
0...55 °C –20...55 °C < 85% rh, no condensation
Analogue inputs14) Digital inputs15)
0...10 V (Ri = 100 kΩ) Closed 1 V=, 1 mA, open > 2 V= 0...10 V, load > 10 kΩ max. cable length 30 m max. adm. external voltage ±24 V 0.3 A at 24 V ~/=
Ambient conditions
Inputs/outputs
Analogue outputs16)
Digital output Interfaces and communication
RS-485 not electrically isolated Communication protocols17) Access method Topology Number of participants18) Bus termination
115 kBaud SAUTER Local Communication (SLC), BACnet MS/TP, ¼ load Master/slave Line 31 (32) with SLC 120 Ω (both ends)
Weight Fitting
0.8 kg Self-centring spindle adapter
Type of protection
IP00, IP30 (EN 60529) (with protection set) III (EN 60730)
Construction
Standards and directives
Protection class 7)
Current-free holding torque by means of interlocking in gear unit Maximum rotation angle 102° (without end stop) 9) Running time can be set via software 10) Available measuring ranges depending on hardware/type 11) Zero adjustment recommended during commissioning 12) Short-term overload; zero adjustment of sensor is recommended 13) Recommended hardness of tubing < 40 Sha (e.g. silicone) 14) Depending on the application, can be parameterised as an analogue input or output using SAUTER CASE Components 15) Digital inputs for external potential-free contacts (gold-plated recommended) 16) Depending on the application, can be parameterised as an analogue input or output using SAUTER CASE Components 17) Available protocols switched using software 18) One participant is always also the parametering tool, hence the maximum number of 31 connectible devices 8)
122
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | VAV compact controllers Conformity EMC Directive 2014/30/EU
Machine directive 2006/42/EC, appendix II 1.B EN 61000-6-1, EN 61000-6-3, EN 61000-6-4, EN 61000-6-2
Overview of types Type
Measuring range ∆p
ASV215BF152D 0...150 Pa ASV215BF152E
0...300 Pa
C
Accessories Type
Description
0372301001
Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.
XAFP100F001
Flow probe to measure the air volume in ventilation ducts
0300360001
USB-RS-485 converter
0297867001
Reference pressure container
0430360100
IP30 protection set
0430360200
Replacement LP connector
0372129001
Torsion protection
Right of amendment reserved © 2024 Fr. Sauter AG
123
Single-room, heating and air-conditioning controllers | VAV compact controllers
FCCP 200: Fume cupboard indicator and monitor Features • Measured value display and indication of operating statuses for a range of ambient conditions such as
pressure, temperature, relative humidity etc. in combination with an EY-RC 504/505 room automation station or an ASV 2*5 VAV compact controller Monitoring fume cupboards as per EN 14175-2 to check that they are functioning correctly and that the • ventilation is operated to provide maximum safety for the laboratory staff • Indication when the front sash is open > 500 mm • Switching the fume cupboard lighting on and off
C
• Up to two function indicators for double-sided fume cupboards • Indication of day/night change-over
FCCP200F010
International Design
• Audible alarm can be delayed or muted via configuration • Demand-controlled regulation of fume cupboards as per EN 14175-6 in combination with the
ASV 2*5 VAV compact controller
Award
• Function indicator with visual and audible notification as per EN 14175-2 • Storage of all defined parameters with protection from power failure • Interface for easy configuration of the connected VAV ASV 2*5 • Five freely configurable push-buttons
1)
• Chemical-resistant glass surface • Units that can be displayed: m/s, fps, l/s, m3/h, cfm, Pa, °C, °F, %rh, ppm
Technical data Power supply
Power supply Power consumption
5 V, ±10% 0.4 VA
Sound pressure level Frequency Alarm duration2) Start-up delay Brightness Field of view Measuring range of temperature sensor3)
80 dB (A) 4 kHz 60 s Adjustable from 0 to 3200 s EN 842, punctiform > 120° −5…50 °C
Operating temperature Storage temperature Humidity without condensation
5…45 °C −20…80 °C < 5…85% rh
Dimensions W × H × D
169 × 36 × 12 mm
Protection class Protection class (when installed) EMC Directive 2014/30/EU
III (EN 60730) IP41 installed vertically EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Parameters
Audible alarm
Optical alarm Temperature sensor
Admissible ambient conditions
Construction
Standards and directives
1) 2) 3)
124
In combination with the EY-RC 504/505 room automation station and CASE Engine. Can be set using software. After it is installed, the temperature sensor must be calibrated using CASE Engine software during the commissioning.
Right of amendment reserved © 2024 Fr. Sauter AG
Single-room, heating and air-conditioning controllers | VAV compact controllers Overview of types Type
Features
FCCP200F010
Fume cupboard monitor and indicator
Accessories Type
Description
0300360001
USB-RS-485 converter
0430600100
USB-C RJ12 cable FCCP 200
C
Right of amendment reserved © 2024 Fr. Sauter AG
125
Valves, control valves, dampers, actuators
A high degree of flexibility for optimum results. SAUTER valves and actuators each come in a few basic versions that cover all needs for reliable and long-lasting control elements. The valve and the actuator are perfectly matched to each another as a basis for optimum control quality. The new Smart Actuator allows autonomous control of heating, ventilation and air conditioning. Cloud-based applications and an app simplify commissioning as well as optimisation during operation. 126
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators Smart actuators AKM 115SA: Smart Actuator for ball valve
131
SAIO 100: I/O module for smart actuators
140
AVM 115SA: Smart Actuator for 2- and 3-way valves
134
Power and connecting cables for Smart Actuators
142
ASM 115SA: Smart Actuator for ventilation dampers
137
Unit valves and actuators for unit valves Overview of unit valves
145
AXT 301, 311: Thermal actuator for unit valves
163
VUL: 2-way valves, PN 16
146 149
AXS 315S: Continuous thermal actuator for unit valves with stroke indicator
166
BUL: 3-way unit valve, PN 16 VUT: 2-way valve, PN 16
154
AXF 217S: Motorised actuator for unit valves with positioner
169
BUT: 3-way unit valve
156
AXM 217: Motorised actuator for unit valves
171
AXM 217S: Motorised actuator for unit valves with positioner
172
BXL: 3-way unit valve, PN 16
159
Overview of actuators for unit valves
161
Regulating valves and valve actuators VUN: 2-way valve with male thread, PN 16
177
BUS: 3-way flanged valve, PN 40
225
BUN: 3-way valve, PN 16
180
Overview of valve actuators
228
V6R: 2-way valve, PN 16
183
AVM 105, 115: Valve actuator
230
B6R: 3-way valve, PN 16
186
AVM 105S, 115S: Valve actuator (SUT)
232
VUD: 2-way flanged valve, PN 6
189
AVM 215: Valve actuator
234
VQD: 2-way flanged valve, PN 6
192
AVM 215S: Valve actuator with SAUTER Universal Technology (SUT)
236
BUD: 3-way flanged valve, PN 6
194
AVM 321, 322: Valve actuator
238
BQD: 3-way flanged valve, PN 6
197
AVM 321S, 322S: SUT valve actuator
241
VUE: 2-way flanged valve, PN 16/10
199
AVM 322-R: Retrofit actuator
244
VQE: 2-way flanged valve, PN 16
203
AVM 322S-R: Retrofit actuator
246
BUE: 3-way flanged valve, PN 16/10
205
AVM 234S: SUT valve actuator
249
BQE: 3-way flanged valve, PN 16
209
AVF 124: Valve actuator
252
VUG: 2-way flanged valve, PN 25/16
212
AVF 125S: SUT valve actuator
254
BUG: 3-way flanged valve, PN 25/16
216
AVF 234S: SUT valve actuator
256
VUP: Pressure-relieved 2-way flanged valve, PN 25
220
AVN 224S: SUT valve actuator
259
VUS: 2-way flanged valve, PN 40
222
Multi-function valves Overview of dynamic regulating valves
262
VDL 010...050: 2-way regulating valve, PN 25, Valveco compact
269
UVC 106: Dynamic flow control system with 6-way ball valve, eValveco
264
VDL 050…100: 2-way regulating valve, PN 16, Valveco flange
274
UVC102MF065…100: Dynamic flow control system with 2-way valve and energy monitoring, eValveco
266
292
Ball valves and ball valve actuators Overview of ball valves
276
VKAI: 2-way cut-off ball valve, PN 40
VKR: 2-way regulating ball valve, PN 40
278
VKAI: 2-way cut-off ball valve, PN 40
294
VKRA: 2-way regulating ball valve, PN 40
282
BKLI: 3-way changeover ball valve (L) with female thread, PN 40
297
BKR: 3-way regulating ball valve, PN 40
286
BKTI: 3-way changeover ball valve with female thread, PN 40
300
BKRA: 3-way regulating ball valve, PN 40
289
BKTA: 3-way changeover ball valve with male thread, PN 40
303
Right of amendment reserved © 2024 Fr. Sauter AG
127
V
Overview of 6-way ball valves
306
AKM 105S, 115S: Rotary actuator
313
B2KL: 6-way ball valve with male thread, PN 16
307
AKM 115S F152: High-speed rotary actuator
315
Overview of actuators for ball valves
309
AKF 112, 113: Rotary actuator
317
AKM 105, 115: Rotary actuator
311
AKF 113S: Rotary actuator
318
Overview of control valves and butterfly valves
319
MH32F, MH42F: Control valve, PN 6
322
M3R, M4R: Control valve, PN 10
320
DEF: Tight-sealing butterfly valve, PN 16
324
Control valves and rotary and damper actuators
Damper and rotary actuators
V
Overview of damper and rotary actuators
327
ADM 322: Rotary actuator
329
ADM 322S: Rotary actuator with positioner
331
ASM 105, 115: Damper actuator
334
ASM 105S, 115S F132: Damper actuator, SUT
336
ASM 105S, 115S F152: High-speed damper actuator, SUT
338
ASM 124: Damper actuator
340
ASM 134: Damper actuator
342
ASM 124S, 134S: Damper actuator, SUT
344
ASF 112, 113: Damper actuator
346
ASF 113S: Damper actuator
348
ASF 122, 123: Damper actuator
350
ASF 123S: Damper actuator
352
128
Right of amendment reserved © 2024 Fr. Sauter AG
Valve specification – calculating made easy SAUTER valve slide rule [1] Use SAUTER´s practical valve slide rule to specify the valve nominal diameter depending on the flow rate for liquids and saturated steam. You can order the slide rule at your sales partner or sales consultant.
SAUTER VALVEDIM software [2] A tried and tested tool for convenient valve and actuator specification, SAUTER provides installers and project engineers with its SAUTER VALVEDIM PC software. The tool comprises three function levels: 1. Valve and actuator specification • using recommended values for a rough specification of the required versions and variables; • based on the existing or stipulated installation values for the definitive specification of the required versions and variables. 2. Selection of the valve and the suitable actuator based on characteristics. 3. Direct transfer of the results to the project documentation. VALVEDIM is available from your SAUTER subsidiary or as a download at https://www.sauter-controls.com/produkt/case-suite/
1,5
30
2
4
1,5 1,6
2
40 50
70
30
40 50
5
3 4 5 6 7 8 9 10
100 70 50 30 20 1 0,7 0,5 0,3 0,2 1
0,4 0,5 0,63
20 20
3
70
100 100
10 7 5 3 2 0,1 0,05 0,03 0,02
2,5 3
4
5
150 200
5 7 10 15 20
30
1,5
300 400 500 2 40 50
3 70
700
4 5 100
1000
6 7 8 9 10 6,3
40 50 63 70 80 100
1,0
1,6
2,5
4
6,3
10
16
22
25
28
40
63
100
160
220
250
320
340
15
15
15
15
15
20
25
32
40
40
50
50
65
80
100 125 AVM
125
150
150
4 6 10 6
4 6 VUN 10 6
4 6 10 6 4 6 10 6
4 6 10 6 4 6 10 6 4 6 6 6
AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 10 321(S) 10 AVF 6 124/125S 6 AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 10 321(S) 10 AVF 6 124/125S 6 AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 6 321(S) 6 AVF 6 124/125S 6 AVM 322(S) AVM 234S AVF 234S AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 10 321(S) 10 AVF 6 124/125S 6 AVM 322(S) AVM 234S AVF 234S AVM 16 322(S) 16 AVM 16 234S 16 AVF 16 234S16 AVM ? 322(S) ? AVM 40 234S 40 AVF 40 234S40
4 5 10 5 4 5 10 6 4 6 6 6
4 4 10 4 3 4 10 5 2,8 6 6 6
3 3,5 10 3,5 2 3,7 10 4 2,1 5,2 6 5,2
1,9 3 6 3 1,2 2,7 230 V AC 6 24 V AC 3,7
BUN
VUD BUD VQD BQD 4* 4* 6* VUE* 6* 10* BUE 10* PN16 6* 6* EN-JL 1040 VQE
4 6 10 6
4 6 10 6
BQE 16* 16* 16* 16* VUG* PN25 16* 16* 16* 16* EN-JS 102 16* 16* 16* BUG 16* ? ? ? ? VUS* PN40 40* 40* 40* 40* 1.0619 40* 40* 40* BUS 40*
16 16 16 ? 40* 40*
16 16 16 40 40
24 V DC 1,2 3,3 2-Pt 6 3-Pt 3,3 0...10 V 4...20mA
4 6 10 6
16 16 16 ? 40 40
2,8 6 10 6
2,1 second 1,4 5,2 3,3 9 5,7 Newton 5,2 3,3
SF132
SF132
F112
F110
F122
2)
1000
5
160 200
300 400 250 320 340
F
2)
124
125
1)
234
1)
1)
A 96 48
40/80 40/80 40/80 48 120 120 120 60 60 60 60 80/160 80/160 80/160 32 240 240 80 120 120 120 120 120/240 120/240 120/240 1000
2,5 3 3
1,5 3 3
2 2
1,5 1,5
7,1 5,6 ? 6,1 4,7
4,7 3,4 ? 3,9 3
3 2,2 ? 1,5 1,5
? 1 1
www.sauter-controls.com
234
322 F120
F122
321
2,5 1,5 3 3 2 3 2 35 3 0,9 60 120 120 60 96 300,9 120 120 120 48 2 2 120 3,4 3,4 250 500 2 2
15,2 9,4 6,1 4 16 1) Module 16 230V-24V:160372332 001 11 16 2) Module 16 230V-24V 13,5 8,5 ? ? ? ? ? ? 37,8 28,7 16,4 10,5 29,6 22,5 12,8 8,2
5000 3 700
AVF
SF132
F120
F122
115 SF132
F120
F100
PN16 CC752S-GM
3000
F
15 20 25 30 16 22 28
15
1 1 2,4 1052,4 4 4 2,4 2,4 0,8 0,8 1,8 1,8 4 4 2,7 2,7 0,9 0,9 2 2 4 4 2 2
2000
7 106 1,5 2 150 200 300 400 500
1 0,01
SF132
)15DN 15
15 15 4
F230
0,15 0,2 0,3 0,16 0,25
[m3/h]0,40 0,63 ( kvs 0,25 0,16
PN6 EN-JL 1040
10 10
5000 7000 10 1,5 2
F130
[m3/h] 0,1
7 7
1
SF132
[bar]
kvs
5 5
2 1,5 1 0,7 0,5 2000 1000 500 300 200 20 10 7 5 3 2
& pv [kPa] / kv
4 3000 0,7
SF132
[kg/dm3]
SF132
%p
SF132
4
! t [K] " Q [kW] 1 0,7 1,5 2 3 § Q [kcal/h] 400 500 700 1000 1500 2000 0,1 0,2 0,3 0,4 0,5 $ V 0,15 [kcal/h]
0,5
2500
500
2000
A
1 1 2 1,6 ?
? 0,7 0,7
1,5 1,2 ?
[1]
[3]
[2]
SAUTER CASE ValveDim mobile app With the new CASE ValveDim mobile app, finding the right parts and the ideal valve/actuator combinations is impressively convenient and very efficient: Intuitive operation makes it easier to search for individual products and combine them. Selected valve/actuator combinations can be stored in projects. Personal
[3]
lists with valve/actuator combinations can be exported from the app as a project table in PDF format so that they can be shared with contacts. What’s more, CASE ValveDim can also be used offline.
Right of amendment reserved © 2024 Fr. Sauter AG
129
Valve specification – manual calculation Here you will find all the necessary information for the manual valve specification. Variables, constants and formulas
[1]
Variable Description
Value
V̇
Volume flow
Q̇ to
Supplied heat per unit of time (heat flow)
Unit
Q̇ from Supplied heat per unit of time (heat flow) Temperature difference Specific thermal capacity of water Density of water
Supposition:
Pressure difference across the valve Calculated flow rate for the valve Actual flow rate for the valve at nominal stroke, selected according to table or chart
Calculation formula for kv
[2]
kv = V̇·
1 bar Δpv
Diagram
[3]
[4]
Calculations The following are given:
1000
Q̇ to = 70 kW ≈ 250 000 kJ/h Δt = 20 K
Δpv = 45 mbar = 4.5 kPa (corresponds to 450 mm water column) To be found:
100
V̇, kv Approximate calculation of V̇ Assumption: Q̇ to = Q̇ from
10
Q̇ to = Q̇ from = V̇ · cw · Δt · ρw Q̇ to
V̇ =
3
V̇ =
1
cw · Δt · ρw
70
1.164 · 10 · 20 · 1 000 –3
·
kW·(kg·K)·m3
kWh·K·kg·h
≈ 3 m3/h
Calculation of Kv kv = 3 m3/h ·
0.1
1 bar 0.045 bar
≈ 14.1 m3/h
Determination of flow rate Determination of kv from the diagram kvs = 16 m3/h
0.01 10
100 35.2
1000
10 000
100 000
45
Example plotted: Given are the volume flow (3 m³/h) and a desired Δpv of 45 mbar, which results in a Kv value of 14.1 m³/h. The Kvs values entered are deliverable values. Selected: A valve with kvs = 16 m³/h, which results in a pressure difference Δpv of 35.2 mbar.
130
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Smart actuators
AKM 115SA: Smart Actuator for ball valve Features • Smart Actuator as an intelligent IoT solution for autonomous control of heating and air-conditioning
applications in smart buildings • Ready-made HVAC standard applications enable efficient installation and commissioning of small systems • Applications are selected from the library via smartphone app and installed on the Smart Actuator • BACnet, Bluetooth LE and WLAN interface for flexible system integration • Commissioning, parameterisation and remote access to the system are conveniently carried out via a
AKM115SAF232
smartphone app As an IoT device, the cloud connection for remote access takes place via MQTT using TLS encryption • • Extensive diagnostic data from the actuator enables predictive maintenance of installations • Enables creation of Smart Actuator networks with distributed intelligence
V
• Optionally, the Smart Actuator can be used flexibly in BA networks due to free programmability via
CASE Suite • Real-time clock for calendar functions and time programmes • Two universal I/Os for connecting external sensors and actuators • Direct connection of a room operating unit • Flexibly expandable with up to two Smart Actuator SAIO 100 I/O modules for comprehensive control
tasks • Pre-assembled cables, with colour- and mechanically-coded connectors, allow fast and error-free wiring • Fitting without tools using a bayonet ring made of glass-fibre reinforced plastic • BLDC motor technology enables extensive diagnostic functions • Intelligent angle of rotation adaptation and detection incl. feedback signal • Electronic, torque-dependent cut-off
Smart Actuator app
• Gear unit can be disengaged for manual adjustment • For operating the 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI and BKTA, as
well as 6-way ball valve B2KL Technical data Power supply
Power supply
24 VAC, −10%/+20%, 50…60 Hz 24 VDC, −10%/+20%
Surge-voltage resistance Rotational torque Holding torque1) Angle of rotation Response time Running time for 90° Characteristic Operating noise (unloaded)
500 V (EN 60730) 8 Nm 8 Nm 90° 200 ms 35/60/120 sec. Linear, (inverse) equal percentage, (inverse) quadratic, free characteristic < 30 dB (A)
Media temperature2) Ambient temperature Ambient humidity Storage and transport temperature
Max. 100 °C −10…55 °C 5…85% rh, no condensation −20…70 °C
Parameters
Ambient conditions
1) 2)
Holding torque energised and de-energised At media temperatures < 5 °C or > 100 °C, appropriate accessory must be used
Right of amendment reserved © 2024 Fr. Sauter AG
131
Valves, control valves, dampers, actuators | Smart actuators Inputs/outputs
Type of inputs
Number of universal I/O Analogue input U Analogue input I
Ni1000 Pt1000 Resistance Analogue output U
2 0…10 V (Ri = 100 kΩ, ±0.05 V) 4…20 mA (with ext. resistor 500 Ω or accessory 053060311**) Closed: ≤ 1 VDC, 1 mA Open: ≥ 4 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 200…3000 Ω 0…10 V (±0.1 V)
BACnet data point objects BACnet client links Control Active COV subscription Time programmes Calendar
Max. 100 (from firmware 1.1.0b58) 16 6 loops 64 4 (Schedule) 3 (Calendar)
Processor RAM (memory) Flash
ARM Cortex-M7 (528 MHz) 1024 kB 2 × 16 MB external, for data and system 128-bit AES Via CASE Engine or mobile app Zephyr 100 ms For commissioning and maintenance Via MQTT to IoT hub For time programmes and calendars
Digital input3)
Type of output Function
V
Dynamic objects
Architecture
Flash encryption Application data Operating system Cycle time Mobile app Cloud Real-time clock Interfaces, communication
RS-485 A connection4)
RS-485 B connection5)
Bluetooth
WLAN Indicator/display
Communication protocol Connection Termination/Pull-Up/Pull-Down Communication protocol Use Connection Termination Version Range Radiation Standard LED indicator
BACnet MS/TP, ¼ load 2 × 3-pin connector, coded, daisy chain Internal, switchable via software SLC master 2 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, switchable via software BLE 4.2 < 10 m 4 mW IEEE 802.11 b/g 2 status LEDs (green/red and blue)
Construction
Fitting position
Housing material
Connections at the bottom or side, not at the top 168 × 137 × 74 mm 0.7 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS
Type of protection Protection class
IP54 (EN 60529) III (IEC 60730-1)
Dimensions W × H × D Weight Housing
Standards, directives
3) 4) 5)
132
Switching thresholds: 2.28 V (0 to 1) and 2.69 V (1 to 0) or 2.19 kΩ (0 to 1) and 2.69 kΩ (1 to 0) Not electrically isolated Not electrically isolated
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Smart actuators
CE/UKCA conformity6)
Environment class RED 2014/53/EU (CE)
3K3 (IEC 60721) EN 60730-1:2011 EN 60730-2-14:1997 + A1:2001, A11:2005; A2:2008 EN 62479:2010 EN 301 489-1 V1.9.2 EN 61000-6-2:2005; AC:2005 EN 61000-6-3:2007 + A1:2011; AC 2012 EN 300 328 V2.2.2 See RED EN IEC 63000
RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
EN IEC 63000
Overview of types Type
Features
AKM115SAF232 Smart Actuator for ball valve, RS-485
A
V
Power consumption
Max. 5 W / 10 VA (without peripherals)
Power consumption: Without connected peripheral devices (room operating units, sensors, actuators or I/O modules)
Accessories Type
Description
SAIO100F020
I/O module, 5 × UI/AO, 3 × relay
0510420001
Adaptor required when temperature of the medium > 100 °C
0510240011
Adaptor required when temperature of the medium < 5 °C
05393601000
Dummy plug spare part set IP54
EY-PS031F011
Power supply unit, 110…240 VAC / 24 VDC, 1.25 A, 30 W, DIN rail mounting
EY-PS031F021
Power supply unit, 110…240 VAC / 24 VDC, 2.5 A, 60 W, DIN rail mounting
EY-PS031F041
Power supply unit, 110…240 VAC / 24 VDC, 4 A, 100 W, DIN rail mounting
A
6)
Order the device cables separately; see the section entitled “Accessories − power and connecting cables”
Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
133
Valves, control valves, dampers, actuators | Smart actuators
AVM 115SA: Smart Actuator for 2- and 3-way valves Features • Smart Actuator as an intelligent IoT solution for autonomous control of heating and air-conditioning
applications in smart buildings Ready-made HVAC standard applications enable efficient installation and commissioning of small systems • • Applications are selected from the library via smartphone app and installed on the Smart Actuator
AVM115SAF232
• BACnet, Bluetooth LE and WLAN interface for flexible system integration • Commissioning, parameterisation and remote access to the system are conveniently carried out via a
smartphone app As an IoT device, the cloud connection for remote access takes place via MQTT using TLS encryption • • Extensive diagnostic data from the actuator enables predictive maintenance of installations • Enables creation of Smart Actuator networks with distributed intelligence
V
• Optionally, the Smart Actuator can be used flexibly in BA networks due to free programmability via
CASE Suite • Real-time clock for calendar functions and time programmes • Two universal I/Os for connecting external sensors and actuators • Direct connection of a room operating unit • Flexibly expandable with up to two Smart Actuator SAIO 100 I/O modules for comprehensive control
tasks • Pre-assembled cables, with colour- and mechanically-coded connectors, allow fast and error-free wiring • Toolless assembly by means of automatic valve stem connection and brass cap nut • BLDC motor technology enables extensive diagnostic functions
Smart Actuator app
• Intelligent stroke adaptation and detection incl. feedback signal • Electronic, torque-dependent cut-off • Gear unit can be disengaged for manual adjustment • For activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series
Technical data Power supply
Power supply
24 VAC, −10%/+20%, 50…60 Hz 24 VDC, −10%/+20%
Surge-voltage resistance Actuating power Actuator stroke Response time Running time Characteristic Operating noise (unloaded)
500 V (EN 60730) 500 N 0...10 mm 200 ms 35/60/120 sec. Linear, (inverse) equal percentage, (inverse) quadratic, free characteristic < 30 dB (A)
Media temperature1) Ambient temperature Ambient humidity Storage and transport temperature
Max. 100 °C −10…55 °C 5…85% rh, no condensation −20…70 °C
Number of universal I/O
2
Parameters
Ambient conditions
Inputs/outputs
1)
134
At media temperature > 100 °C, appropriate accessory must be used
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Smart actuators Type of inputs
Analogue input U Analogue input I
Ni1000 Pt1000 Resistance Analogue output U
0…10 V (Ri = 100 kΩ, ±0.05 V) 4…20 mA (with ext. resistor 500 Ω or accessory 053060311**) Closed: ≤ 1 VDC, 1 mA Open: ≥ 4 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 200…3000 Ω 0…10 V (±0.1 V)
BACnet data point objects BACnet client links Control Active COV subscription Time programmes Calendar
Max. 100 (from firmware 1.1.0b58) 16 6 loops 64 4 (Schedule) 3 (Calendar)
Processor RAM (memory) Flash
ARM Cortex-M7 (528 MHz) 1024 kB 2 × 16 MB external, for data and system 128-bit AES Via CASE Engine or mobile app Zephyr 100 ms For commissioning and maintenance Via MQTT to IoT hub For time programmes and calendars
Digital input2)
Type of output Function
Dynamic objects
V
Architecture
Flash encryption Application data Operating system Cycle time Mobile app Cloud Real-time clock Interfaces, communication
RS-485 A connection3)
RS-485 B connection4)
Bluetooth
WLAN Indicator/display
Communication protocol Connection Termination/Pull-Up/Pull-Down Communication protocol Use Connection Termination Version Range Radiation Standard LED indicator
BACnet MS/TP, ¼ load 2 × 3-pin connector, coded, daisy chain Internal, switchable via software SLC master 2 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, switchable via software BLE 4.2 < 10 m 4 mW IEEE 802.11 b/g 2 status LEDs (green/red, blue)
Construction
Fitting position
Housing material
Connections at the bottom or side, not at the top 168 × 119 × 74 mm 0.7 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS
Type of protection Protection class Environment class
IP54 (EN 60529) III (IEC 60730-1) 3K3 (IEC 60721)
Dimensions W × H × D Weight Housing
Standards, directives
2) 3) 4)
Switching thresholds: 2.28 V (0 to 1) and 2.69 V (1 to 0) or 2.19 kΩ (0 to 1) and 2.69 kΩ (1 to 0) Not electrically isolated Not electrically isolated
Right of amendment reserved © 2024 Fr. Sauter AG
135
Valves, control valves, dampers, actuators | Smart actuators CE/UKCA conformity5)
RED 2014/53/EU (CE)
RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
EN 60730-1:2011 EN 60730-2-14:1997 + A1:2001, A11:2005; A2:2008 EN 62479:2010 EN 301 489-1 V1.9.2 EN 61000-6-2:2005; AC:2005 EN 61000-6-3:2007 + A1:2011; AC 2012 EN 300 328 V2.2.2 See RED EN IEC 63000 EN IEC 63000
Overview of types Type
V
Features
Power consumption
AVM115SAF232 Smart Actuator for globe valves, RS-485, BACnet Max. 5 W / 10 VA (without peripherals) MS/TP
A
Power consumption: Without connected peripheral devices (room operating units, sensors, actuators or I/O modules)
Accessories Type
Description
SAIO100F020
I/O module, 5 × UI/AO, 3 × relay
0372249001
Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50
0372273001
Adapter for Siemens valve VVG/VXG 44, 48
05393601000
Dummy plug spare part set IP54
EY-PS031F011
Power supply unit, 110…240 VAC / 24 VDC, 1.25 A, 30 W, DIN rail mounting
EY-PS031F021
Power supply unit, 110…240 VAC / 24 VDC, 2.5 A, 60 W, DIN rail mounting
EY-PS031F041
Power supply unit, 110…240 VAC / 24 VDC, 4 A, 100 W, DIN rail mounting
A
5)
136
Order the device cables separately; see the section entitled “Accessories − power and connecting cables”
Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Smart actuators
ASM 115SA: Smart Actuator for ventilation dampers Features • Smart Actuator as an intelligent IoT solution for autonomous control of heating and air-conditioning
applications in smart buildings Ready-made HVAC standard applications enable efficient installation and commissioning of small systems • • Applications are selected from the library via smartphone app and installed on the Smart Actuator
ASM115SAF232
• BACnet, Bluetooth LE and WLAN interface for flexible system integration • Commissioning, parameterisation and remote access to the system are conveniently carried out via a
smartphone app • As an IoT device, the cloud connection for remote access takes place via MQTT using TLS encryption • Extensive diagnostic data from the actuator enables predictive maintenance of installations • Enables creation of Smart Actuator networks with distributed intelligence
V
• Optionally, the Smart Actuator can be used flexibly in BA networks due to free programmability via
CASE Suite • Real-time clock for calendar functions and time programmes • Two universal I/Os for connecting external sensors and actuators • Direct connection of a room operating unit • Flexibly expandable with up to two Smart Actuator SAIO 100 I/O modules for comprehensive control
tasks • Pre-assembled cables, with colour- and mechanically-coded connectors, allow fast and error-free wiring • Easy fitting using self-centring spindle adapters
Smart Actuator app
• BLDC motor technology enables extensive diagnostic functions • Intelligent angle of rotation adaptation and detection incl. feedback signal • Electronic, torque-dependent cut-off • Gear unit can be disengaged for manual adjustment
Technical data Power supply
Power supply
24 VAC, −10%/+20%, 50…60 Hz 24 VDC, −10%/+20%
Surge-voltage resistance Rotational torque Holding torque1) Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Response time Running time for 90° Characteristic Operating noise (unloaded)
500 V (EN 60730) 10 Nm 10 Nm Max. 95° Ø 8...16 mm, □ 6.5...12.5 mm Max. 300 HV 200 ms 35/60/120 sec. Linear, (inverse) equal percentage, (inverse) quadratic, free characteristic < 30 dB (A)
Ambient temperature Ambient humidity Storage and transport temperature
−10…55 °C 5…85% rh, no condensation −20…70 °C
Number of universal I/O
2
Parameters
Ambient conditions
Inputs/outputs
1)
Holding torque energised and de-energised
Right of amendment reserved © 2024 Fr. Sauter AG
137
Valves, control valves, dampers, actuators | Smart actuators Type of inputs
Analogue input U Analogue input I
Ni1000 Pt1000 Resistance Analogue output U
0…10 V (Ri = 100 kΩ, ±0.05 V) 4...20 mA (with ext. resistor 500 Ω or accessory 053060311**) Closed: ≤ 1 VDC, 1 mA Open: ≥ 4 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 200…3000 Ω 0…10 V (±0.1 V)
BACnet data point objects BACnet client links Control Active COV subscription Time programmes Calendar
Max. 100 (from firmware 1.1.0b58) 16 6 loops 64 4 (Schedule) 3 (Calendar)
Processor RAM (memory) Flash
ARM Cortex-M7 (528 MHz) 1024 kB 2 × 16 MB external, for data and system 128-bit AES Via CASE Engine or mobile app Zephyr 100 ms For commissioning and maintenance Via MQTT to IoT hub For time programmes and calendars
Digital input2)
Type of output Function
Dynamic objects
V
Architecture
Flash encryption Application data Operating system Cycle time Mobile app Cloud Real-time clock Interfaces, communication
RS-485 A connection3)
RS-485 B connection4)
Bluetooth
WLAN Indicator/display
Communication protocol Connection Termination/Pull-Up/Pull-Down Communication protocol Use Connection Termination Version Range Radiation Standard LED indicator
BACnet MS/TP, ¼ load 2 × 3-pin connector, coded, daisy chain Internal, switchable via software SLC master 2 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, switchable via software BLE 4.2 < 10 m 4 mW IEEE 802.11 b/g 2 status LEDs (green/red, blue)
Construction
Fitting position
Housing material
Connections at the bottom or side, not at the top 168 × 62 × 74 mm 0.7 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS
Type of protection Protection class Environment class
IP54 (EN 60529) III (IEC 60730-1) 3K3 (IEC 60721)
Dimensions W × H × D Weight Housing
Standards, directives
2) 3) 4)
138
Switching thresholds: 2.28 V (0 to 1) and 2.69 V (1 to 0) or 2.19 kΩ (0 to 1) and 2.69 kΩ (1 to 0) Not electrically isolated Not electrically isolated
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Smart actuators CE/UKCA conformity5)
RED 2014/53/EU (CE)
RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
EN 60730-1:2011 EN 60730-2-14:1997 + A1:2001, A11:2005; A2:2008 EN 62479:2010 EN 301 489-1 V1.9.2 EN 61000-6-2:2005; AC:2005 EN 61000-6-3:2007 + A1:2011; AC 2012 EN 300 328 V2.2.2 See RED EN IEC 63000 EN IEC 63000
Overview of types Type
Features
ASM115SAF232 Smart Actuator for dampers, RS-485, BACnet MS/TP
A
Power consumption
V
Max. 5 W / 10 VA (without peripherals)
Power consumption: Without connected peripheral devices (room operating units, sensors, actuators or I/O modules)
Accessories Type
Description
SAIO100F020
I/O module, 5 × UI/AO, 3 × relay
0361977002
Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115
0372300001
Torsion protection, long (230 mm)
05393601000
Dummy plug spare part set IP54
0372301001
Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.
0372320001
Hexagon key as visualisation for position indicator
EY-PS031F011
Power supply unit, 110…240 VAC / 24 VDC, 1.25 A, 30 W, DIN rail mounting
EY-PS031F021
Power supply unit, 110…240 VAC / 24 VDC, 2.5 A, 60 W, DIN rail mounting
EY-PS031F041
Power supply unit, 110…240 VAC / 24 VDC, 4 A, 100 W, DIN rail mounting
A
5)
Order the device cables separately; see the section entitled “Accessories − power and connecting cables”
Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
139
Valves, control valves, dampers, actuators | Smart actuators
SAIO 100: I/O module for smart actuators Features • Extends the inputs and outputs of the smart actuator for extensive control tasks • Connection of sensors or actuators via five integrated universal inputs and outputs
SAIO100F010
• Three changeover relays for fan or pump control • Connection to the smart actuator via plug-in I/O module cable (SLC) • Direct connection of a room operating unit • Housing according to IP54 enables use without cabinet • Separate 24 V power supply for sensors and actuators with total power requirement up to 1 A
Technical data
V
Power supply
Power supply
24 VAC/DC (via smart actuator) 24 VAC/DC for terminals T4...T7 (via separate power supply) 1.2 VA at 24 VDC (without sensors and actuators)
Power consumption
Ambient conditions
Ambient temperature Ambient humidity Storage and transport temperature
−10…55 °C 5...95% rh, no condensation −20…70 °C
Number of universal I/O Number of relays Rating
Ni1000 Pt1000 Resistance Analogue output U
5 (+1 from smart actuator) 3 10 A (resistive) 5 A (inductive) Change-over 0…10 V (Ri = 100 kΩ, ±0.05 V) 4...20 mA (with ext. resistor 500 Ω) Closed: 1 VDC, 1 mA Open: > 2 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 100…2500 Ω (±25 Ω) 0…10 V (±0.4 V)
Communication protocol Use Connection Termination LED indicator
SLC slave 1 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, DIP switch 1 status LED (green, red)
Fitting
Housing material
On DIN rail 35 × 7.5/15 (EN 60715) or on supplied rail 200 × 107 × 55 mm 0.5 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS
Type of protection Protection class Environment class
IP54 (EN 60529) III (IEC 60730-1) 3K3 (IEC 60721)
Inputs/outputs
Type of inputs
Type of output
Type Analogue input U Analogue input I Digital input
Interfaces, communication
RS-485 connection
Indicator/display Construction
Dimensions W × H × D Weight Housing
Standards, directives
140
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Smart actuators CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
EN 61000-6-1, EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14
Overview of types Type
Features
SAIO100F020
I/O module for smart actuator, 6 pcs. UI/AO, 3 Max. 1.7 W / 3.6 VA (without peripherals) pcs. relay
Power consumption
Accessories Type
Description
05393601000
Dummy plug spare part set IP54
A
For power cables or connecting cables (053060*****), see order code in PDS 53.950
V
Right of amendment reserved © 2024 Fr. Sauter AG
141
Valves, control valves, dampers, actuators | Smart actuators
Power and connecting cables for Smart Actuators Features • For connection to the power supply, to cable temperature sensors, and for connecting the actuators • Pre-assembled cables in various lengths from 0.5 to 30 metres • Robust XLPE sheathed cables
1)
With mechanically and colour-coded connectors
• Silicone- and halogen-free • Can also be laid under plaster, in and on masonry and non-reinforced concrete
2)
Technical data Parameters
V
Bending radius
Min. 10 × outer diameter for fixed installation
Ambient temperature
Max. +70 °C
Material
Silicone- and halogen-free according to EN 60754-1/2 Flame retardant according to EN 60332-1-2 Conductor stranded bare copper wires, open ends ultrasonically welded Black (plug and sheath)
Ambient conditions
Construction
Type Colour Standards, directives
CE/UKCA conformity according to
RoHS Directive 2011/65/EU & 2015/863/EU Restriction of Hazardous Substances Regulations 2012 (RoHS UKCA)
Overview of types Type
Cable type
Cable length
Connector type
05306020000
24 V power supply, open cable end
0.5 m
2-pin
05306020001
24 V power supply, open cable end
1.0 m
2-pin
05306020005
24 V power supply, open cable end
5.0 m
2-pin
05306020010
24 V power supply, open cable end
10.0 m
2-pin
05306020020
24 V power supply, open cable end
20.0 m
2-pin
05306020030
24 V power supply, open cable end
30.0 m
2-pin
05306020201
24 V power supply, Y-connector
1.0 m
2-pin
05306031001
I/O signals, open cable end, 3-core
1.0 m
3-pin
05306031005
I/O signals, open cable end, 3-core
5.0 m
3-pin
05306031010
I/O signals, open cable end, 3-core
10.0 m
3-pin
05306031020
I/O signals, open cable end, 3-core
20.0 m
3-pin
05306031030
I/O signals, open cable end, 3-core
30.0 m
3-pin
05306031105
I/O signals (I), open cable end, 3-core
5.0 m
3-pin
05306032001
I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 1.0 m ready to plug in
3-pin
05306032005
I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 5.0 m ready to plug in
3-pin
05306032010
I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 10.0 m ready to plug in
3-pin
1) 2)
142
XLPE: Cross-linked polyethylene National regulations must be observed
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Smart actuators Type
Cable type
05306032020
I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 20.0 m ready to plug in
3-pin
05306032101
I/O signals, cable temperature sensor Pt1000 (−50...180 °C) 1.0 m ready to plug in
3-pin
05306032105
I/O signals, cable temperature sensor Pt1000 (−50...180 °C) 5.0 m ready to plug in
3-pin
05306034000
RS-485, daisy chain, open cable end, 3-core
0.5 m
3-pin
05306034001
RS-485, daisy chain, open cable end, 3-core
1.0 m
3-pin
05306034005
RS-485, daisy chain, open cable end, 3-core
5.0 m
3-pin
05306034010
RS-485, daisy chain, open cable end, 3-core
10.0 m
3-pin
05306034020
RS-485, daisy chain, open cable end, 3-core
20.0 m
3-pin
05306034030
RS-485, daisy chain, open cable end, 3-core
30.0 m
3-pin
05306034100
RS-485, daisy chain, connection of two actuators, ready to plug in
0.5 m
3-pin
05306034101
RS-485, daisy chain, connection of two actuators, ready to plug in
1.0 m
3-pin
05306034105
RS-485, daisy chain, connection of two actuators, ready to plug in
5.0 m
3-pin
05306034110
RS-485, daisy chain, connection of two actuators, ready to plug in
10.0 m
3-pin
05306034120
RS-485, daisy chain, connection of two actuators, ready to plug in
20.0 m
3-pin
05306034130
RS-485, daisy chain, connection of two actuators, ready to plug in
30.0 m
3-pin
05306051000
I/O signals, open cable end, 3-core
0.5 m
5-pin
05306051001
I/O signals, open cable end, 3-core
1.0 m
5-pin
05306051005
I/O signals, open cable end, 3-core
5.0 m
5-pin
05306051010
I/O signals, open cable end, 3-core
10.0 m
5-pin
05306051020
I/O signals, open cable end, 3-core
20.0 m
5-pin
05306051030
I/O signals, open cable end, 3-core
30.0 m
5-pin
05306053000
I/O signals, connection of actuator with I/O module SAIO100, 0.5 m ready to plug in
5-pin
05306053001
I/O signals, connection of actuator with I/O module SAIO100, 1.0 m ready to plug in
5-pin
05306053005
I/O signals, connection of actuator with I/O module SAIO100, 5.0 m ready to plug in
5-pin
05306053010
I/O signals, connection of actuator with I/O module SAIO100, 10.0 m ready to plug in
5-pin
05306053020
I/O signals, connection of actuator with I/O module SAIO100, 20.0 m ready to plug in
5-pin
05306053030
I/O signals, connection of actuator with I/O module SAIO100, 30.0 m ready to plug in
5-pin
05306053500
SLC connection, open cable end, 5-core
0.5 m
5-pin
05306053501
SLC connection, open cable end, 5-core
1.0 m
5-pin
05306053505
SLC connection, open cable end, 5-core
5.0 m
5-pin
05306053510
SLC connection, open cable end, 5-core
10.0 m
5-pin
05306053520
SLC connection, open cable end, 5-core
20.0 m
5-pin
05306053530
SLC connection, open cable end, 5-core
30.0 m
5-pin
A
Cable length
Connector type
V
Other models and lengths on request. For order numbers, see order code below
Example Order no. 05306020000
Designation Power cable, 2-pin, 24 V power supply, open cable end, 2-core, 0.5 m
Right of amendment reserved © 2024 Fr. Sauter AG
143
Valves, control valves, dampers, actuators | Smart actuators Order code (1) Product type 053060…
A
(2) Model …200…
(3) Cable length …00
Not all theoretically possible combinations can be ordered
(1) Product type Order no. 053060…
Type Power and connecting cables for Smart Actuator
(2) Model
V
Order no. …200… …201… …202… …310… …510… …311…
Plug 2-pin 2-pin 2-pin 3-pin 5-pin 3-pin
…320…
3-pin
…321…
3-pin
…340… …341… …530…
3-pin 3-pin 5-pin
…535…
5-pin
Function and connection 24 V power supply, open cable end 24 V power supply, daisy chain 24 V power supply, Y-connector I/O signals, 3-core open cable end I/O signals for current measurement with integrated 500 Ω resistor, 3-core open cable end I/O signals, cable temperature sensor Ni1000 (−35...100 °C), ready to plug in I/O signals, cable temperature sensor Pt1000 (−50...180 °C), ready to plug in RS-485, daisy chain, 3-core open cable end RS-485, daisy chain, connection of two actuators, ready to plug in I/O signals, connection of actuator with I/O module SAIO100, ready to plug in SLC connection, 5-core open cable end
(3) Cable length Order no.
3)
144
Length (m) …00 0.5 …01 1.0 …05 5.0 …10 10.0 …20 20.0 …30 30.0
Conductor cross-section (mm²)3) 0.5 / 0.75 0.5 / 0.75 0.5 / 0.75 0.75 0.75 0.75
Conductor cross-section depends on cable type and cable length
Right of amendment reserved © 2024 Fr. Sauter AG
Unit valves In combination with thermal actuators, unit valves are used to control radiators, air reheaters and recoolers as well as fan coil units.
Overview of unit valves
Type designation
VUL
BUL
VUT
BUT
BXL
Application Single-room control Chilled ceiling, underfloor heating Radiator Underfloor device
• • • •
• • • •
• • • •
• • • •
• • • •
• − 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 146
− • 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 149
• − 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 154
− • 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 156
− • 25...40 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 159
Version 2-way 3-way Nominal diameter (DN) Nominal pressure Combination options with actuator Further information
Right of amendment reserved © 2024 Fr. Sauter AG
145
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
VUL: 2-way valve, PN 16 Features • Control of heating zones, air secondary treatment units and fan coil units in combination with unit valve
actuators AXM 217(S), AXT 301 or AXS 315S • Flat-sealing standard version or version with clamping-ring screw fitting for pipe Ø 15 mm with DN 10 • Valve with male thread as per DIN EN ISO 228-1, class B • Stuffing box can be replaced under system pressure
VUL010F310
• Control passage A–AB is closed when the spindle is moved in • Closing procedure against the pressure • Valve body made of nickel-plated cast brass for DN 10 and gunmetal for DN 15 and DN 20 • Plug with EPDM soft seal
V
• Stainless-steel spindle • Stuffing box with double O-ring seal
Technical data Parameters
Nominal pressure Operating pressure Operating temperature Valve characteristic Valve stroke1) Leakage rate
PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Equal-percentage 4 mm 0.002% of Kvs value
Operating temperature at valve
Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)
Ambient conditions
Standards, directives
ValveDim app
Overview of types Type
Nominal diame- Kvs value ter
Connection
Weight
VUL010F340
DN 10
VUL010F330
DN 10
0.16 m³/h
G½" B
0.19 kg
0.4 m³/h
G½" B
VUL010F320
0.18 kg
DN 10
0.63 m³/h
G½" B
0.18 kg
VUL010F310
DN 10
1 m³/h
G½" B
0.18 kg
VUL010F300
DN 10
1.6 m³/h
G½" B
0.18 kg
VUL015F310
DN 15
2.5 m³/h
G¾" B
0.28 kg
VUL015F300
DN 15
3.5 m³/h
G¾" B
0.28 kg
VUL020F300
DN 20
4.5 m³/h
G1" B
0.33 kg
VUL010F630
DN 10
0.4 m³/h
Clamping ring vers. Ø15 mm
0.18 kg
VUL010F620
DN 10
0.63 m³/h
Clamping ring vers. Ø15 mm
0.18 kg
VUL010F610
DN 10
1 m³/h
Clamping ring vers. Ø15 mm
0.18 kg
VUL010F600
DN 10
1.6 m³/h
Clamping ring vers. Ø15 mm
0.18 kg
1)
146
The valve stroke is limited by the actuator
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Accessories Type
Description
0378133010
1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜
0378133015
1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½
0378133020
1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾
0378134010
1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½
0378134015
1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾
0378134020
1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1
0378135010
1 clamping-ring screw fitting for pipe Ø 15 mm, DN 10
0378145015
1 clamping-ring screw fitting for pipe Ø 15 mm, DN 15, flat-sealing, G¾
0378145020
1 clamping-ring screw fitting for pipe Ø 22 mm, DN 20, flat-sealing, G1
0378128001
Stuffing box for VUL valves, can be replaced under pressure
Combination of VUL with electric actuators
/ /
V
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences with motorised actuators Actuator
AXM217F200
AXM217F202
Page
171
171
AXM217SF402 AXM217SF404 173
Voltage
230 VAC
24 VAC/DC
24 VAC/DC
Control signal
2-/3-point
2-/3-point
0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA
Running time
13 s/mm
13 s/mm
8 s/mm
Closes against the pressure VUL010F340 VUL010F330 VUL010F320 VUL010F630 VUL010F620
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
4.0
4.0
4.0
VUL010F310 VUL010F300 VUL010F610 VUL010F600
3.8
3.8
3.8
VUL015F310 VUL015F300 VUL020F300
1.1
1.1
1.1
Cannot be used to close with the pressure
Right of amendment reserved © 2024 Fr. Sauter AG
147
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Pressure differences with thermal actuators Actuator
AXT301F102 AXT301F112 164
AXT301F210
AXT301F212
Page
AXT301F100 AXT301F110 164
164
164
164
164
Voltage
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
Control signal
2-point
2-point
2-point
2-point
2-point
2-point
Running time
48 s/mm
48 s/mm
48 s/mm
48 s/mm
52 s/mm
52 s/mm
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
VUL010F340 VUL010F330 VUL010F320 VUL010F630 VUL010F620
4.0
6.0
4.0
6.0
VUL010F310 VUL010F300 VUL010F610 VUL010F600
4.0
4.0
4.0
VUL015F310 VUL015F300 VUL020F300
1.1
1.1
1.1
Closes against the pressure
V
AXT301HF110
AXT301HF112
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
4.0
4.0
4.0
6.0
4.0
6.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
1.1
1.1
1.1
1.1
1.1
1.1
1.1
Cannot be used to close with the pressure
Pressure differences with thermal, continuous actuators Actuator Page
AXS315SF102 167
AXS315SF202 167
Voltage
24 VAC/DC
24 VAC/DC
Control signal
0…10 V
0…10 V
Running time
30 s/mm
30 s/mm
Closes against the pressure
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
VUL010F340 VUL010F330 VUL010F320 VUL010F630 VUL010F620
4.0
6.0
4.0
VUL010F310 VUL010F300 VUL010F610 VUL010F600
4.0
4.0
4.0
VUL015F310 VUL015F300 VUL020F300
1.1
1.1
1.1
Cannot be used to close with the pressure
148
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
BUL: 3-way unit valve, PN 16 Features • Ideally suited for unit valve actuators AXM 217(S), AXT 301 and AXS 315S • Flat-sealing standard version or version with clamping-ring screw fitting for pipe Ø 15 mm with DN 10 • Valve with male thread as per DIN EN ISO 228-1, class B • Special model for fan coil units with cast-on by-pass T-piece • Control passage A–AB is closed when the spindle is moved in • Can be used as a control valve and, thanks to its tight-sealing third passage, as a distribution valve • Nickel-plated valve body made of cast brass
BUL015F310
• Plug with EPDM soft seal for control passage and mixing passage • Stainless-steel spindle
V
• Stuffing box with double O-ring seal
Technical data Parameters
Nominal pressure Operating pressure Operating temperature Control passage valve characteristic Mixing passage valve characteristic Valve stroke Leakage rate of control passage A-AB Leakage rate of mixing passage B-AB
PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Equal-percentage Linear 3.7 mm 0.0001% of Kvs value Approx. 0.1% of Kvs value
Operating temperature at valve
Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)
BUL010F410
Ambient conditions
Standards, directives
Control valve
Overview of types
/ /
The BUL 3-way valve must not be used as a 2-way valve Kvs value: The Kvs value of the mixing passage (B-AB) is reduced by approx. 30%
Type
Nominal diame- Kvs value ter
Connection
Weight
BUL010F330
DN 10
0.4 m³/h
G½" B
0.30 kg
BUL010F320
DN 10
0.63 m³/h
G½" B
0.30 kg
BUL010F310
DN 10
1 m³/h
G½" B
0.30 kg
BUL010F300
DN 10
1.6 m³/h
G½" B
0.30 kg
BUL015F310
DN 15
2.5 m³/h
G¾" B
0.33 kg
BUL015F300
DN 15
4 m³/h
G¾" B
0.33 kg
BUL020F300
DN 20
5 m³/h
G1" B
0.36 kg
BUL010F430
DN 10
0.4 m³/h
G½" B
0.38 kg
BUL010F420
DN 10
0.63 m³/h
G½" B
0.38 kg
BUL010F410
DN 10
1 m³/h
G½" B
0.38 kg
BUL010F400
DN 10
1.6 m³/h
G½" B
0.38 kg
BUL015F410
DN 15
2.5 m³/h
G¾" B
0.42 kg
BUL015F400
DN 15
4 m³/h
G¾" B
0.42 kg
Right of amendment reserved © 2024 Fr. Sauter AG
Distribution valve
149
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Type
Nominal diame- Kvs value ter
Connection
Weight
BUL020F400
DN 20
5 m³/h
G1" B
0.50 kg
BUL010F630
DN 10
0.4 m³/h
Clamping ring vers. Ø 15 mm
0.38 kg
BUL010F620
DN 10
0.63 m³/h
Clamping ring vers. Ø 15 mm
0.38 kg
BUL010F610
DN 10
1 m³/h
Clamping ring vers. Ø 15 mm
0.38 kg
BUL010F600
DN 10
1.6 m³/h
Clamping ring
0.38 kg
A
BUL0**F4**: Version with by-pass T-piece
Accessories
V
Type
Description
0378133010
1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜
0378133015
1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½
0378133020
1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾
0378134010
1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½
0378134015
1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾
0378134020
1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1
0378135010
1 clamping-ring screw fitting for pipe Ø 15 mm, DN 10
0378145015
1 clamping-ring screw fitting for pipe Ø 15 mm, DN 15, flat-sealing, G¾
0378145020
1 clamping-ring screw fitting for pipe Ø 22 mm, DN 20, flat-sealing, G1
0378126001
Stuffing box for BUL valves
0378126002
Stuffing box for BUL valves as of manufacturing date 1501
Combination of BUL with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences with motorised actuators
150
Actuator
AXM217F200
AXM217F202
Page
171
171
AXM217SF402 AXM217SF404 173
Voltage
230 VAC
24 VAC/DC
24 VAC/DC
Control signal
2-/3-point
2-/3-point
0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA
Running time
48 s
48 s
48 s
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600
1.7
1.7
1.7
BUL015F310 BUL015F410
1.4
1.4
1.4
BUL015F300 BUL015F400
1.2
1.2
1.2
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Actuator
AXM217F200
AXM217F202
Page
171
171
AXM217SF402 AXM217SF404 173
BUL020F300 BUL020F400
1.0
1.0
1.0
As distribution valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600
1.9
1.9
1.9
BUL015F310 BUL015F300 BUL020F300 BUL015F410 BUL015F400 BUL020F400
1.2
V 1.2
1.2
Pressure differences with thermal actuators Actuator
AXT301F102 AXT301F112 164
AXT301F210
AXT301F212
Page
AXT301F100 AXT301F110 164
AXT301HF110
AXT301HF112
164
164
164
164
Voltage
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
Control signal
2-point
2-point
2-point
2-point
2-point
2-point
Running time
48 s/mm
48 s/mm
48 s/mm
48 s/mm
52 s/mm
52 s/mm
As control valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600
1.7
1.8
1.7
1.8
BUL015F310 BUL015F410
1.4
1.5
1.4
BUL015F300 BUL015F400
1.2
1.3
BUL020F300 BUL020F400
1.0
1.1
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
1.7
1.7
1.7
1.8
1.7
1.8
1.5
1.4
1.4
1.4
1.5
1.4
1.5
1.2
1.3
1.2
1.2
1.2
1.3
1.2
1.3
1.0
1.1
1.0
1.0
1.0
1.1
1.0
1.1
Right of amendment reserved © 2024 Fr. Sauter AG
151
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Actuator Page
V
AXT301F100 AXT301F110 164
As distribution valve
∆pmax [bar]
BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600
AXT301F102 AXT301F112 164
AXT301F210
AXT301F212
AXT301HF110
AXT301HF112
164
164
164
164
∆ps [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
1.9
4.0
1.9
4.0
1.9
1.9
1.9
4.0
1.9
4.0
BUL015F310 BUL015F410
1.6
2.1
1.6
2.1
1.6
1.6
1.6
2.1
1.6
2.1
BUL015F300 BUL015F400
1.4
2.1
1.4
2.1
1.4
1.4
1.4
2.1
1.4
2.1
BUL020F300 BUL020F400
1.2
2.0
1.2
2.0
1.2
1.2
1.2
2.0
1.2
2.0
Pressure differences with thermal, continuous actuators
152
Actuator Page
AXS315SF102 167
AXS315SF202 167
Voltage
24 VAC/DC
24 VAC/DC
Control signal
0…10 V
0…10 V
Running time
30 s/mm
30 s/mm
As control valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600
1.7
1.8
1.7
BUL015F310 BUL015F410
1.4
1.5
1.4
BUL015F300 BUL015F400
1.2
1.3
1.2
BUL020F300 BUL020F400
1.0
1.1
1.0
As distribution valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600
1.9
4.0
1.9
BUL015F310 BUL015F410
1.6
2.1
1.6
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Actuator Page
AXS315SF102 167
AXS315SF202 167
BUL015F300 BUL015F400
1.4
2.1
1.4
BUL020F300 BUL020F400
1.1
1.2
1.2
V
Right of amendment reserved © 2024 Fr. Sauter AG
153
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
VUT: 2-way valve, PN 16 Features • Regulation of fan coil units, air secondary-treatment units, heating zones and two-pipe systems with heat
exchanger in combination with AXM 217(S), AXT 301 or AXS 315S unit valve actuators Standard version flatsealing • • Adjustable Kvs value • When the spindle is pushed in, the valve is closed • Closing procedure against the pressure
VUT015F200
• Valve with male thread as per DIN EN ISO 228-1, class B • Valve body made of cast brass • Stainless-steel spindle
V
• Plug with EPDM soft seal • Stuffing box with O-ring seal • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Operating pressure Operating temperature Valve characteristic Leakage rate
PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Almost linear ≤ 0.0001% of Kvs value
Operating temperature at valve
Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 EN 60534, page 3 Fluid group II, No CE label (article 4.3)
Kvs range
Valve stroke (mm)
Connection
Weight (kg)
Ambient conditions
ValveDim app
Standards, directives
Overview of types Type
Nominal diameter (DN)
VUT010F200
10
0.2…1.6 m³/h
3
G½ B
0.18
VUT010F210
10
0.2…1.0 m³/h
3
G½ B
0.18
VUT010F220
10
0.2…0.63 m³/h
3
G½ B
0.18
VUT015F200
15
1.0…3.5 m³/h
4
G¾ B
0.28
VUT015F210
15
0.3…2.5 m³/h
3
G¾ B
0.28
VUT020F200
20
4.5 m³/h
4
G1 B
0.33
Accessories Type
154
Description
0378133010
1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜
0378133015
1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½
0378133020
1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾
0378134010
1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½
0378134015
1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾
0378134020
1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Combination of VUT with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences with motorised actuators Actuator
AXM217F200
AXM217F202
Page
171
171
AXM217SF402 AXM217SF404 173
Voltage
230 VAC
24 VAC/DC
24 VAC/DC
Control signal
2-/3-point
2-/3-point
0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA
Laufzeit
13 s/mm
13 s/mm
8 s/mm
Closes against the pressure VUT010F200 VUT010F210 VUT010F220
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
2.5
2.5
2.5
VUT015F200 VUT015F210
1.8
1.8
1.8
VUT020F200
1.0
1.0
1.0
V
Cannot be used to close with the pressure
Pressure differences with thermal actuators Actuator
AXT301F102 AXT301F112 164
AXT301F210
AXT301F212
Page
AXT301F100 AXT301F110 164
164
164
164
164
Voltage
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
Control signal
2-point
2-point
2-point
2-point
2-point
2-point
Laufzeit
48 s/mm
48 s/mm
48 s/mm
48 s/mm
52 s/mm
52 s/mm
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
VUT010F200 VUT010F210 VUT010F220
2.3
2.3
2.3
2.3
VUT015F200 VUT015F210
1.6
1.6
1.6
VUT020F200
0.9
0.9
0.9
Closes against the pressure
AXT301HF110
AXT301HF112
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
2.3
2.3
2.3
2.3
2.3
2.3
1.6
1.6
1.6
1.6
1.6
1.6
1.6
0.9
0.9
0.9
0.9
0.9
0.9
0.9
Cannot be used to close with the pressure
Pressure differences with thermal, continuous actuators Actuator Page
AXS315SF102 167
AXS315SF202 167
Voltage
24 VAC/DC
24 VAC/DC
Control signal
0…10 V
0…10 V
Laufzeit
30 s/mm
30 s/mm
Closes against the pressure
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
VUT010F200 VUT010F210 VUT010F220
2.5
2.5
2.5
VUT015F200 VUT015F210
1.8
1.8
1.8
VUT020F200
1.0
1.0
1.0
Cannot be used to close with the pressure
Right of amendment reserved © 2024 Fr. Sauter AG
155
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
BUT: 3-way unit valve, PN 16 (el.) Features • Regulation of fan coil units, air secondary-treatment units, heating zones and two-pipe systems with heat
exchanger in combination with AXM 217(S), AXT 301 or AXS 315S unit valve actuators Standard version flatsealing • • Special model for fan coil units with cast-on by-pass T-piece • Control passage closed when spindle is pushed in • Used as a control valve • Valve with male thread as per DIN EN ISO 228-1, class B
BUT015F210
• Valve body in cast brass • Stainless-steel spindle
V
• Plug with soft seal made of EPDM for control passage and mixing passage • Stuffing box with O-ring seal • Water quality as per VDI 2035
Technical data Parameters
BUT015F400
Nominal pressure Operating pressure Operating temperature Control passage valve characteristic Mixing passage valve characteristic Leakage rate of control passage A-AB Leakage rate of mixing passage B-AB
PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Almost linear Linear (not reduced) 0.0001% of Kvs Approx. 0.1% of Kvs
Operating temperature at valve
Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)
Ambient conditions
Standards, directives
Overview of types
/
The BUT control valve must not be used as a through valve or diverting valve; mixing passage is not reduced.
Type
ValveDim app
156
Nominal diameter (DN)
Valve stroke (mm)
Kvs value
Connection
Weight (kg)
BUT010F200
10
3
1 m³/h
G½ B
0.3
BUT010F400
10
3
1.6 m³/h
G½ B
0.38
BUT010F410
10
3
1 m³/h
G½ B
0.38
BUT010F420
10
3
0.63 m³/h
G½ B
0.38
BUT015F210
15
3
2.5 m³/h
G¾ B
0.33
BUT015F410
15
3
2.5 m³/h
G¾ B
0.42
BUT015F400
15
4
3.5 m³/h
G¾ B
0.42
BUT020F200
20
4
4.5 m³/h
G1 B
0.36
BUT020F400
20
4
4.5 m³/h
G1 B
0.5
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
A
BUT0**F4**: Version with by-pass T-piece
Accessories Type
Description
0378133010
1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜
0378133015
1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½
0378133020
1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾
0378134010
1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½
0378134015
1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾
0378134020
1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1
0378145015
1 clamping-ring screw fitting for pipe Ø 15 mm, DN 15, flat-sealing, G¾
0378145020
1 clamping-ring screw fitting for pipe Ø 22 mm, DN 20, flat-sealing, G1
V
Combination of BUT with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.
/
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve. Data for a static pressure of 6 bar.
/
Definition for close/off pressure: Max. admissible differential pressure when closing the valve. Calculation, see below.
Pressure differences with motorised actuators Actuator
AXM217F200
AXM217F202
Page
171
171
AXM217SF402 AXM217SF404 173
Voltage
230 VAC
24 VAC/DC
24 VAC/DC
Control signal
2-/3-point
2-/3-point
0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA
Laufzeit
13 s/mm
13 s/mm
8 s/mm
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BUT010F200 BUT010F400 BUT010F410 BUT010F420
1.7
1.7
1.7
BUT015F210 BUT015F410
1.4
1.4
1.4
BUT015F400
1.2
1.2
1.2
BUT020F200 BUT020F400
1.0
1.0
1.0
Cannot be used as distribution valve
Right of amendment reserved © 2024 Fr. Sauter AG
157
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
A
Close/off pressure = ∆pmax + 0.1 bar
Pressure differences with thermal actuators Actuator
V
AXT301F102 AXT301F112 164
AXT301F210
AXT301F212
Page
AXT301F100 AXT301F110 164
AXT301HF110
AXT301HF112
164
164
164
164
Voltage
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
Control signal
2-point
2-point
2-point
2-point
2-point
2-point
Laufzeit
33 s/mm
33 s/mm
33 s/mm
33 s/mm
40 s/mm
40 s/mm
As control valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
BUT010F200 BUT010F400 BUT010F410 BUT010F420
1.5
1.8
1.5
1.8
1.5
1.5
1.5
1.8
1.5
1.8
BUT015F210 BUT015F410
1.2
1.5
1.2
1.5
1.2
1.2
1.2
1.5
1.2
1.5
BUT015F400
1.0
1.3
1.0
1.3
1.0
1.0
1.0
1.3
1.0
1.3
BUT020F200 BUT020F400
0.9
1.1
0.9
1.1
0.9
0.9
0.9
1.1
0.9
1.1
Cannot be used as distribution valve
A
Close/off pressure = ∆pmax + 0.3 bar
Pressure differences with thermal, continuous actuators Actuator Page
AXS315SF102 167
AXS315SF202 167
Voltage
24 VAC/DC
24 VAC/DC
Control signal
0…10 V
0…10 V
Laufzeit
30 s/mm
30 s/mm
As control valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
BUT010F200 BUT010F400 BUT010F410 BUT010F420
1.7
1.8
1.7
BUT015F210 BUT015F410
1.4
1.5
1.4
BUT015F400
1.2
1.3
1.2
BUT020F200 BUT020F400
1.0
1.1
1.0
Cannot be used as distribution valve
A
158
Close/off pressure = ∆pmax + 0.1 bar
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
BXL: 3-way unit valve, PN 16 Features • Ideally suited as control valve for unit valve actuators AXM 217(S), AXT 301 and AXS 315S • Valve with male thread as per DIN EN ISO 228-1, class A • Control passage A–AB open when the spindle is moved in • Used as a control valve • Valve body made of gunmetal • Plug with EPDM soft seal
BXL025F200
• Stainless-steel spindle • Stuffing box with double O-ring seal • Version with cap nut and flat seal
V
Technical data Parameters
Nominal pressure Operating pressure Operating temperature Control passage valve characteristic Mixing passage valve characteristic Valve stroke Control passage leakage rate Mixing passage leakage rate
PN 16 Max. 16 bar at 130 °C 2…130 °C Linear Complementary, reduced 2.9 mm Approx. 0.05% of Kvs value Approx. 0.2% of Kvs value
Operating temperature at valve
Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)
Ambient conditions
Standards, directives
ValveDim app
Overview of types
/
The BXL 3-way valve must not be used as a 2-way valve
Type
Nominal diameter
Kvs value
Weight
BXL025F200
DN 25
6.5 m³/h
1200 g
BXL040F200
DN 40
9.5 m³/h
2350 g
Accessories Type
Description
0361824025
3 threaded sleeves, R 1", flat-sealing
0361824040
3 threaded sleeves, R 5/4", flat-sealing
0361825028
3 solder nipple, Ø 28; flat-sealing, DN 25
0361825035
3 solder nipple, Ø 35; flat-sealing, DN 40
0361825042
3 solder nipple, Ø 42; flat-sealing, DN 40
Right of amendment reserved © 2024 Fr. Sauter AG
159
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Combination of BXL with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve. Data for a static pressure of 6 bar.
Pressure differences with motorised actuators
V
Actuator
AXM217F200
AXM217F202
Page
171
171
AXM217SF402 AXM217SF404 173
Voltage
230 VAC
24 VAC/DC
24 VAC/DC
Control signal
2-/3-point
2-/3-point
0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA
Running time
13 s/mm
13 s/mm
8 s/mm
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BXL025F200
0.5
0.5
0.5
BXL040F200
0.2
0.2
0.2
Cannot be used as distribution valve
Pressure differences with thermal actuators Actuator
AXT301F102 AXT301F112 164
AXT301HF110
AXT301HF112
Page
AXT301F100 AXT301F110 164
164
164
Voltage
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
Control signal
2-point
2-point
2-point
2-point
Running time
48 s/mm
48 s/mm
52 s/mm
52 s/mm
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BXL025F200
0.5
0.5
0.5
0.5
BXL040F200
0.2
0.2
0.2
0.2
Cannot be used as distribution valve
Pressure differences with thermal, continuous actuators Actuator Page
AXS315SF102 AXS315SF202 167
Voltage
24 VAC/DC
Control signal
0…10 V
Running time
30 s/mm
As control valve
∆pmax [bar]
BXL025F200
0.5
BXL040F200
0.2
Cannot be used as distribution valve
160
Right of amendment reserved © 2024 Fr. Sauter AG
Actuators for unit valves SAUTER actuators for unit valves provide reliable and accurate control. Pulsepause activation (with pulse widths of a few seconds) or continuous activation guarantees accurate control characteristic.
Overview of actuators for unit valves
AXS315SF102
AXS315SF202
AXT301F***
AXT301HF11*
AXT311F11*
Technical data Max. nominal stroke (mm) Max. closing force (N) Direction of closure Running time Power supply (V)
Type designation
6.5 125 NC 30 s/mm 24
6.5 125 NO 30 s/mm 24
5 100 NC/NO 4.0 min. 24/230
4 100 NC 3.5 min. 24/230
6.5 125 NC 4.5 min. 24/230
Method of operation Stroke indicator Thermal Motor
• • −
• • −
• • −
• • −
• • −
• − −
• − − VUL, BUL, VDL, VXL, VUT, BUT, BXL
• − −
Page 163
Page 163
Page 163
Control 2-point 3-point Positioner (0...10 V) Combination options with valve Further information
− − − − • • VUL, BUL, VDL, VXL, VUT, BUT, BXL Page 166
Right of amendment reserved © 2024 Fr. Sauter AG
Page 166
161
Type designation
AXF 217S
AXM 217
AXM 217S
Technical data Max. nominal stroke (mm) Max. pushing force (N) Direction of closure Running time Power supply (V)
6 160 − 8 s/mm 24
6.3 120 − 13 s/mm 24/230
5.5 120 − 8 s/mm 24
Method of operation Stroke indicator Status indicator Thermal Motor Reset function
− • − • •
− − − • −
− • − • −
− − • VUL, BUL, VDL, VXL, VUT, BUT, BXL
• • − VUL, BUL, VDL, VXL, VUT, BUT, BXL
− − • VUL, BUL, VDL, VXL, VUT, BUT, BXL
Page 169
Page 171
Page 172
Control 2-point 3-point Positioner Combination options with valve Further information
162
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
AXT 301, 311: Thermal actuator for unit valves with stroke indicator Features • Actuation of unit valves and valves in surface heating and cooling systems as well as fan coils • Low-force fitting on the valve using adapter ring • NC “normally closed” and NO “normally open” versions • NC version with first-open function • Adaptation to valve using plastic adapter M30 × 1.5 or M28 × 1.5
AXT301F***
• Max. closing force 125 N • With 230 V or 24 V thermal expansion element • Large visible and tactile position indicator
V
• Low-noise and maintenance-free • Contemporary design • High functional quality and service life • Version with integrated auxiliary contact • Standard version with 1-metre cable permanently connected • Version with 2 m or 5 m plug-in cable • Can be mounted in any position, even suspended under the valve
AXT301HF11*
Technical data Power supply
AXT301HF110/112
Power supply 230 VAC Power supply 24 VAC/DC Power consumption during operation1) Start-up current 230 VAC Start-up current 24 VAC/DC Power for auxiliary contacts 230 V Power for auxiliary contacts 24 V Changeover point of auxiliary contact
±10% 50…60 Hz +20%…−10% Approx. 1 W < 550 mA after max. 100 ms < 300 mA after max. 2 min. 5(1) A, 50/60 Hz 3(1) A, 50/60 Hz For approx. 2 mm stroke
Ambient temperature Storage and transport temperature Operating temperature at valve Air humidity
0…60 °C −25…60 °C Max. 100 °C < 85% rh, no condensation
Housing
Weight
White (RAL 9003), surface structured according to VDI 3400 Ref. 27 Polyamide PVC hose line (H03V2V2-F), Ø 0.75 mm², fixed mounting, light grey (RAL 7035) 0.1 kg (with 1 m power cable)
Type of protection Protection class 230 V Protection class 24 V
IP54 II (EN 60730-1) III (EN 60730-1)
AXT311F11*
Ambient conditions
Construction
Housing material Power cable2)
Standards, directives
1) 2)
ValveDim app
Power consumption after expansion element has reached steady temperature state AXT301F100 and F102 without pre-assembled cable
Right of amendment reserved © 2024 Fr. Sauter AG
163
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves CE/UKCA conformity3)
LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE)
EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN IEC 63000
EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
EN IEC 63000
Overview of types
V
Type
Voltage
Stroke
AXT301F110
230 VAC
5.0 mm
100 N
4.0 min
NC
1m
–
AXT301F112
24 VAC/DC 5.0 mm
100 N
4.0 min
NC
1m
–
AXT301F210
230 VAC
5.0 mm
100 N
4.0 min
NO
1m
–
AXT301F212
24 VAC/DC 5.0 mm
100 N
4.0 min
NO
1m
–
AXT301F100
230 VAC
5.0 mm
100 N
4.0 min
NC
Without cable –
AXT301F102
24 VAC/DC 5.0 mm
100 N
4.0 min
NC
Without cable –
AXT301HF110
230 VAC
4.0 mm
100 N
3.5 min
NC
1m
Auxiliary contacts
AXT301HF112
24 VAC/DC 4.0 mm
100 N
3.5 min
NC
1m
Auxiliary contacts
AXT311F110
230 VAC
6.5 mm
125 N
4.5 min
NC
1m
–
AXT311F112
24 VAC/DC 6.5 mm
125 N
4.5 min
NC
1m
–
A A A
Closing force Running time
NC/NO
Cable length
Function
AXT301F100/102: Connection cable available as optional accessory AXT301F*1*: Including adapter ring 0550389K008 M30 × 1.5 for closing dimension 10.5 mm, pack of one AXT311F11*: Including adapter ring 0550389K008 M30 × 1.5 for closing dimension 8.5 mm in combination with Frese or Siemens PICV valves
Accessories
/
Type
Delivery quantity Description
0550389K001
Set of 5
VA 10 adapter, plastic, light grey, M30 × 1.5 Suitable for: Dumser, Beulco (from 2005), Purmo, Strawa, Oventrop (also Cocon, Cocon 4, Hycocon,), Oventrop stainless steel distributor, Vescal (Metaplast), Cronatherm, eht Siegmund, Gampper, KaMo (H) before Sept. 2005, Aquatherm (brass distributor), Valvex brass distributor, Viega stainless steel distributor (Fonterra & pro Radiant), Thermotech, KaMo INOX distributor, Bianchi valves (series 401T & 403T) and brass distributor (series 332T), Unipipe (ECO distributor), CronaTech, Fränkische, Zehnder, ATS stainless steel distributor, Frese Optima (2.5 mm), Hesag/Herb (Profi-Line distributor), Luxor (CD distributor), TECE stainless steel (Strawa), Watts brass distributor (HKV-T), Tiemme valves, Watts (Vogel & Noot, Cosmo Objektline), Acome (Strawa), Multibeton HKV (Oventrop)
0550389K101
Set of 100
Adapter like 0550389K001
0550389K002
Set of 5
VA 16 adapter, plastic, red, M28 × 1.5 Suitable for: Polytherm (H), Buderus, Thermoval, KAN-Therm (brass distributor)
8.25 mm
0550389K102
Set of 100
Adapter like 0550389K002
8.25 mm
0550389K003
Set of 5
VA 17 adapter, plastic, dusty grey, M28 × 1.5 Suitable for: MMA (EDVH 25, FVXR 15, VXR 20), ICMA (BAS), industry technology Italy (DB VZ2)
11.5 mm
0550389K103
Set of 100
Adapter like 0550389K003
11.5 mm
3)
164
Valve adapters: The names of the manufacturers are provided for information purposes. Manufacturers may change the closing dimensions without prior notice. Closing dimension
11 mm
11 mm
Explanation of abbreviations in the “Additional technical information” section of this product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Type
Delivery quantity Description
0550389K004
Set of 5
VA 26 adapter, plastic, dusty grey, M30 × 1.5 Suitable for: Giacomini
Closing dimension
0550389K104
Set of 100
Adapter like 0550389K004
4 mm
0550389K005
Set of 5
VA 50 adapter, plastic, dark grey, M30 × 1.5 Suitable for: Honeywell & Braukmann, Broen (type: Ballorex Dynamic), Böhnisch/SBK (before 1998), Cazzaniga, Reich, MNG (before 1998), Frese, Schütz, Seppelfricke, Cufix, KaMo (from Sept. 2005), FAR (from 2007), Pantherm, Unicor, emcal (stainless steel from March 2013), Comap HKV module, black (H)
10 mm
0550389K105
Set of 100
Adapter like 0550389K005
0550389K006
Set of 5
VA 64 adapter, plastic, pure white Suitable for: Pettinaroli
17.8 mm
0550389K106
Set of 100
Adapter like 0550389K006
17.8 mm
0550389K007
Set of 5
VA 78 adapter, plastic, pure white Suitable for: Danfoss RA, Oventrop type: V3D, GD & GDF, Jaga
28.8 mm
0550389K107
Set of 100
Adapter like 0550389K007
28.8 mm
0550389K008
Set of 5
VA 80 adapter, plastic, pure white, M30 × 1.5 Suitable for: Heimeier, Herb, Onda, IVAR, Thermoval, Schlösser (from 1993), Kermi, Cazzaniga, Oventrop, Multiblock (from 1997), Frank (from 2003), Athe-Therm (brass up to Feb. 2005), Athe-Therm (stainless steel), BHS distributor, Jupiter, Böhnisch/SBK (from 1998), Simplex, RBM, Emmeti, Cosmo, Watts, Roth, Delphis-Therm, GC distributor, Cuprotherm, Caleffi distributor series 670 (plastic), Wieland, Caleffi, SKV distributor, Aquatechnik Italy (Multirapid, before 2007, from 2009), Brugman, TKM, Bianchi, Jaga, Gomacal, Nereus angle valve DN 10, Strasshofer, Taco (Vogel & Noot, Cosmo stainless steel and CMV module distributor), Caleffi (with thread ring on manufacturer side), Watts, Vogel & Noot (Cosmo brass distributor), RDZ (brass distributor), VIR (series 9520), Herz regulating valve and distributor
10.5 mm
0550389K108
Set of 100
Adapter like 0550389K008
10.5 mm
0550389K009
Set of 5
VA 90 adapter, plastic, crimson, M30 × 1.5 Suitable for: Chemidro, TECE (plastic distributor), KWH Pipe, Prandelli (brass HKV), Athe-Therm (brass from Feb. 2005), Roth DE (H) (type: Universal HK2), Uponor stainless steel distributor, Reliance stainless steel, SAS brass distributor, Luxor, Tiemme brass distributor (series: ‘Floor’), Honeywell VSMF, Afriso pro Calida EF1 (plastic)
11.5 mm
0550389K109
Set of 100
Adapter like 0550389K009
11.5 mm
0550389K010
Set of 5
VA 41 adapter, plastic, dark green, M30 × 1.5 Suitable for: Danfoss AB-QM (DN 10–DN 20) (4 mm actuator), Danfoss AB-QM (DN 25–DN 32) (5 mm actuator), RDZ (plastic distributor), Vescal (Cazzaniga), Frese Optima Compact and EVA (from 2016) + 5 mm actuator
9.5 mm
0550389K110
Set of 100
Adapter like 0550389K010
0550600202
1x 2 metres
PVC flat cable H03V2V2H2-F, 2-core, 0.75 mm²
–
0550600212
1x 2 metres
Thermoplastic cable H03Z1Z1-F, 2-core, 0.75 mm², halogen-free
–
0550600502
1x 5 metres
PVC flat cable H03V2V2H2-F, 2-core, 0.75 mm²
–
0550600512
1x 5 metres
Thermoplastic cable H03Z1Z1-F, 2-core, 0.75 mm², halogen-free
–
4 mm
10 mm
9,5 mm
A
The cables for the AXT301F100 and AXT301F102 actuators must be ordered separately and can be fitted as required on site. It is not possible to install the cables at the factory
A
Special covers to prevent theft or vandalism, for example, are available on request
Right of amendment reserved © 2024 Fr. Sauter AG
V
165
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
AXS 315S: Continuous thermal actuator for unit valves with stroke indicator Features • Actuation of unit valves and valves in surface heating and cooling systems as well as fan coils • First-open function for low-force fitting on the valve using adapter ring • NC “normally closed” and NO “normally open” versions • NC version with first-open function • Adaptation to valve using plastic adapter M30 × 1.5 or M28 × 1.5 • Max. closing force 125 N • With 24 V thermal expansion element
AXS315SF*02
V
• Large visible and tactile position indicator • Low-noise and maintenance-free • Contemporary design • High functional quality and serviceable life • Version with 1m, 2m or 5m plug-in cable • PVC or halogen-free cable, with or without position feedback signal, available as an accessory • Can be mounted in any position, even suspended under the valve
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power consumption during operation1) Start-up current
−10%, +20%, 50…60 Hz −20%…+20% 1.2 W < 320 mA after max. 2 minutes
Parameters
6.5 mm Stroke2) Closing force 125 N +5% 30 s/mm Running time3) Control signal 0…10 V Control signal input resistance 100 kΩ Position feedback signal 0…10 V (0.1 V resolution) Position feedback signal output impe- 10 kΩ dance Position feedback signal output current 0.1 mA (1 mA if shorted) Output load impedance 100 kΩ…1000 kΩ
ValveDim app
Ambient conditions
Ambient temperature Storage and transport temperature Operating temperature at valve Air humidity
0…50 °C −25…60 °C Max. 100 °C < 85% rh, no condensation
Housing
White (RAL 9003), surface structured according to VDI 3400 Ref. 27 Polyamide Ø 0.22 mm², 3- or 4-core, signal white (RAL 9003) 0.15 kg (without power cable)
Construction
Housing material Power cable4) Weight 1) 2) 3) 4)
166
Power consumption after expansion element has reached steady temperature state Stroke, incl. 0.5 mm overstroke range; see “Initialisation” Running time, see “Runtime behaviour” Order the power cable separately
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
Standards, directives
CE/UKCA conformity5)
Type of protection LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
IP54 EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN IEC 63000 EN IEC 63000
Overview of types Type
Features
AXS315SF102
Actuator for unit valves with first-open function, normally closed (NC)
AXS315SF202
Actuator for unit valves, normally open (NO)
A A A
V
Order the power cable 0550600*** separately, see accessories Includes adapter ring 0550389K010 suitable for SAUTER VUL, VDL, VUT, BUT and BXL valves Adapter ring 0550389K008 suitable for SAUTER BUL valve must be ordered separately
Accessories
/
The names of the manufacturers in the following list are provided for information purposes. Manufacturers may change the closing dimensions without prior notice.
Type
Delivery quantity Description
0550389K001
Set of 5
VA 10 adapter, plastic, light grey, M30 × 1.5 Suitable for: Dumser, Beulco (from 2005), Purmo, Strawa, Oventrop (also Cocon, Cocon 4, Hycocon,), Oventrop stainless steel distributor, Vescal (Metaplast), Cronatherm, eht Siegmund, Gampper, KaMo (H) before Sept. 2005, Aquatherm (brass distributor), Valvex brass distributor, Viega stainless steel distributor (Fonterra & pro Radiant), Thermotech, KaMo INOX distributor, Bianchi valves (series 401T & 403T) and brass distributor (series 332T), Unipipe (ECO distributor), CronaTech, Fränkische, Zehnder, ATS stainless steel distributor, Frese Optima (2.5 mm), Hesag/Herb (Profi-Line distributor), Luxor (CD distributor), TECE stainless steel (Strawa), Watts brass distributor (HKV-T), Tiemme valves, Watts (Vogel & Noot, Cosmo Objektline), Acome (Strawa), Multibeton HKV (Oventrop)
11 mm
0550389K101
Set of 100
Adapter like 0550389K001
11 mm
0550389K002
Set of 5
VA 16 adapter, plastic, red, M28 × 1.5 Suitable for: Polytherm (H), Buderus, Thermoval, KAN-Therm (brass distributor)
8.25 mm
0550389K102
Set of 100
Adapter like 0550389K002
8.25 mm
0550389K003
Set of 5
VA 17 adapter, plastic, dusty grey, M28 × 1.5 Suitable for: MMA (EDVH 25, FVXR 15, VXR 20), ICMA (BAS), industry technology Italy (DB VZ2)
11.5 mm
0550389K103
Set of 100
Adapter like 0550389K003
11.5 mm
0550389K004
Set of 5
VA 26 adapter, plastic, dusty grey, M30 × 1.5 Suitable for: Giacomini
4 mm
0550389K104
Set of 100
Adapter like 0550389K004
4 mm
5)
Closing dimension
Explanation of abbreviations in the “Additional technical information” section of this product data sheet and in the appendix to SAUTER product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
167
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
V
Type
Delivery quantity Description
0550389K005
Set of 5
VA 50 adapter, plastic, dark grey, M30 × 1.5 Suitable for: Honeywell & Braukmann, Broen (type: Ballorex Dynamic), Böhnisch/SBK (before 1998), Cazzaniga, Reich, MNG (before 1998), Frese, Schütz, Seppelfricke, Cufix, KaMo (from Sept. 2005), FAR (from 2007), Pantherm, Unicor, emcal (stainless steel from March 2013), Comap HKV module, black (H)
0550389K105
Set of 100
Adapter like 0550389K005
0550389K006
Set of 5
VA 64 adapter, plastic, pure white Suitable for: Pettinaroli
17.8 mm
0550389K106
Set of 100
Adapter like 0550389K006
17.8 mm
0550389K007
Set of 5
VA 78 adapter, plastic, pure white Suitable for: Danfoss RA, Oventrop type: V3D, GD & GDF, Jaga
28.8 mm
0550389K107
Set of 100
Adapter like 0550389K007
28.8 mm
0550389K008
Set of 5
VA 80 adapter, plastic, pure white, M30 × 1.5 Suitable for: Heimeier, Herb, Onda, IVAR, Thermoval, Schlösser (from 1993), Kermi, Cazzaniga, Oventrop, Multiblock (from 1997), Frank (from 2003), Athe-Therm (brass up to Feb. 2005), Athe-Therm (stainless steel), BHS distributor, Jupiter, Böhnisch/SBK (from 1998), Simplex, RBM, Emmeti, Cosmo, Watts, Roth, Delphis-Therm, GC distributor, Cuprotherm, Caleffi distributor series 670 (plastic), Wieland, Caleffi, SKV distributor, Aquatechnik Italy (Multirapid, before 2007, from 2009), Brugman, TKM, Bianchi, Jaga, Gomacal, Nereus angle valve DN 10, Strasshofer, Taco (Vogel & Noot, Cosmo stainless steel and CMV module distributor), Caleffi (with thread ring on manufacturer side), Watts, Vogel & Noot (Cosmo brass distributor), RDZ (brass distributor), VIR (series 9520), Herz regulating valve and distributor
10.5 mm
0550389K108
Set of 100
Adapter like 0550389K008
10.5 mm
0550389K009
Set of 5
VA 90 adapter, plastic, crimson, M30 × 1.5 Suitable for: Chemidro, TECE (plastic distributor), KWH Pipe, Prandelli (brass HKV), Athe-Therm (brass from Feb. 2005), Roth DE (H) (type: Universal HK2), Uponor stainless steel distributor, Reliance stainless steel, SAS brass distributor, Luxor, Tiemme brass distributor (series: ‘Floor’), Honeywell VSMF, Afriso pro Calida EF1 (plastic)
11.5 mm
0550389K109
Set of 100
Adapter like 0550389K009
11.5 mm
0550389K010
Set of 5
VA 41 adapter, plastic, dark green, M30 × 1.5 Suitable for: Danfoss AB-QM (DN 10–DN 20) (4 mm actuator), Danfoss AB-QM (DN 25–DN 32) (5 mm actuator), RDZ (plastic distributor), Vescal (Cazzaniga), Frese Optima Compact and EVA (from 2016) + 5 mm actuator
9.5 mm
0550389K110
Set of 100
Adapter like 0550389K010
9,5 mm
0550600103
1x 1 metre
Power cable, 0…10 V, 3-core, 0.22 mm², type LiYY, PVC
−
0550600203
1x 2 metres
Power cable, 0…10 V, 3-core, 0.22 mm², type LiYY, PVC
−
0550600503
1x 5 metres
Power cable, 0…10 V, 3-core, 0.22 mm², type LiYY, PVC
−
0550600113
1x 1 metre
Power cable, 0…10 V, 3-core, 0.22 mm², type LiZ1Z1, halogen-free
−
0550600213
1x 2 metres
Power cable, 0…10 V, 3-core, 0.22 mm², type LiZ1Z1, halogen-free
−
0550600513
1x 5 metres
Power cable, 0…10 V, 3-core, 0.22 mm², type LiZ1Z1, halogen-free
−
0550600114
1x 1 metre
Power cable, 0…10 V, 4-core, 0.22 mm², type LiZ1Z1, halogen-free, position feedback
−
0550600214
1x 2 metres
Power cable, 0…10 V, 4-core, 0.22 mm², type LiZ1Z1, halogen-free, position feedback
−
0550600514
1x 5 metres
Power cable, 0…10 V, 4-core, 0.22 mm², type LiZ1Z1, halogen-free, position feedback
−
A
168
Closing dimension
10 mm
10 mm
Special covers to prevent theft or vandalism, for example, are available on request
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
AXF 217S: Motorised actuator for unit valves with positioner Features • Stepping motor with electronic activation and cut-out • Attached to valve with M30 × 1.5 thread • Version with direction of operation 1 (direct acting) or 2 (reverse acting), adjustable • Adjustable valve strokes • Automatic stroke adjustment
AXF217SF404
• Electrical reset function
AXF217SF405
• Maintenance-free gear unit • Suitable for retrofitting existing installations using the appropriate adapters • Status and diagnostic indicator via integrated bi-colour LED
V 2
Power supply
Power supply Power consumption
24 V~ ±15%, 50…60 Hz 24 V= ±15% 5 VA while charging, 2,5 VA during operation, 1 W at standstill
of o
Technical data
n n io tio ct ra ire e D f op o
100%
pe Dire ra ct tio io n n 1
• Fitting position vertically upright to horizontal, not suspended
0% 0V
Output signal y
10 V
Parameters1)
Direction of operation Nominal stroke
Feedback signal Charging time
1 or 2 (adjustable) Max. 6 mm Automatic stroke adjustment 8 s/mm H0:10 mm 160 N < 30 dB (A) 0(2)…10 V; 5…10 V; 0…5 V Ri > 100 kΩ; 0(4)…20 mA Ri = 500 Ω 0…10 V=, ±5% 150 s (supercapacitor)
Ambient temperature Max. operating temperature at valve Storage and transport temperature Ambient humidity
0...50 °C, no condensation 95 °C −20…65 °C < 90% rh
Weight Housing Housing material Thread Power cable
0.2 kg Two-piece, light grey (RAL 7035) Plastic Nickel-plated brass M30 × 1.5 1.50 m long, halogen-free 4 × 0.5 mm², light grey, insertable
Type of protection
IP54 (EN 60529)
Running time Closing dimension Actuating power Sound pressure level Control signal
Ambient conditions
Construction
Standards, directives
1)
The direction of operation and the control voltage can be set using accessory 0550360010 (configurator); factory setting “1” (DA). Direction of operation 1: Control signal increasing = actuator moves out (valve VUT, VUL, VXL, VDL, BUL, BUT closes, valve BXL (control passage) opens). Direction of operation2: Control signal increasing = actuator moves in (valve VUT, VUL, VXL, VDL, BUL, BUT opens, valve BXL (control passage) closes)
Right of amendment reserved © 2024 Fr. Sauter AG
169
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
CE conformity according to
Protection class EMC Directive 2014/30/EU
III (IEC 60730) 60730-1, 60730-2-14
Overview of types Type
Features
AXF217SF404
Motorised actuator for unit valves with positioner, automatic stroke adjustment, electrical reset function:Spindle extends (EFSD)
AXF217SF405
Motorised actuator for unit valves with positioner, automatic stroke adjustment, electrical reset function:Spindle retracts (EFSU)
Accessories Type
Description
0550360010
Configurator for changing control signal, direction of operation, characteristic, direction of reset function
V
170
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
AXM 217: Motorised actuator for unit valves Features • Reliable actuation in efficient control systems • For 2-point or 3-point controllers in conjunction with single-room control systems • Stepping motor with electronic activation and cut-out • Attached to valve with M30 × 1.5 thread • Maintenance-free gear unit
AXM217F20
• Suitable for retrofitting existing installations using the appropriate adapters • Operating status indicated by integrated LED • Fitting position vertically upright to horizontal, not suspended
V
Technical data Parameters
Nominal stroke Running time Actuating power1) Sound pressure level
6.3 mm 13 s/mm 120 N < 30 dB (A)
Max. operating temperature at valve Ambient temperature Ambient humidity
90 °C 0...50 °C < 75% rh
Weight Housing Housing material Thread Power cable
0.15 kg Two-piece, light grey RAL 7035 Plastic Nickel-plated brass M30 × 1.5 1.50 m long, 3 × 0,5 mm², light grey, insertable
Type of protection EMC Directive 2014/30/EU
IP43 (EN 60529) CE as per EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 CE as per EN 60730-1 and EN 60730-2-14
Ambient conditions
Construction
Standards and directives
Low-Voltage Directive 2014/35/EU
Overview of types Type
Power supply
Power consumption
Protection class
AXM217F200
230 V~, ±10%, 50...60 Hz
6.5 VA, 2 W
II (IEC 60730)
AXM217F202
24 V~, ±15%, (50...60 Hz)
2.5 VA, 1.5 W
III (IEC 60730)
A
AXM217F202: Voltage 24V= with relay circuit only
Accessories Type
Description
0550603001
Cable: 24 V, PVC, pluggable, 3 m long
0550603005
Cable: 24 V, halogen-free, pluggable, 3 m long
1)
Actuating power min. 100 N, max. 150 N
Right of amendment reserved © 2024 Fr. Sauter AG
171
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves
AXM 217S: Motorised actuator for unit valves with positioner Features • Stepping motor with electronic activation and cut-out • Attached to valve with M30 × 1.5 thread • Version with direction of operation 1 (direct acting) or 2 (reverse acting), adjustable • Adjustable valve strokes • Automatic stroke adjustment (AXM217SF404)
AXM217SF402
• Maintenance-free gear unit
AXM217SF404
• Suitable for retrofitting existing installations using the appropriate adapters • Status and diagnostic indicator via integrated bi-colour LED
V
• Fitting position vertically upright to horizontal, not suspended
2
Power supply Power consumption
24 VAC/DC ±15 %, 50...60 Hz 2.5 VA / 1.5 W
Direction of operation Nominal stroke Running time Sound pressure level Control signal
1 or 2 (adjustable) 3.2 mm, 4.3 mm, 5.5 mm (adjustable) Automatic stroke adjustment (F404) 8 s/mm < 30 dB (A) 0(2)...10 V; 5...10 V; 0...5 V Ri > 100 kΩ; 0(4)...20 mA Ri = 500 Ω
Ambient temperature Max. operating temperature at valve Storage and transport temperature Ambient humidity
0…50 °C, no condensation 95 °C −20…65 °C < 75% rh
Weight Housing Housing material Thread Power cable
0.15 kg Two-piece, light grey (RAL 7035) Plastic Nickel-plated brass M30 × 1.5 1.50 m long, 3 × 0.5 mm², light grey, pluggable 3.0 m long, halogen-free (F404)
Type of protection Protection class EMC Directive 2014/30/EU
IP43 (EN 60529) III (IEC 60730) 61000-6-1, 61000-6-2, 61000-6-3 and EN 61000-6-4
Parameters1)
0% 0V
Power supply
of o
pe Dire ra ct tio io n n 1
Technical data n n io tio ct ra ire e D f op o
100%
Output signal y
10 V
Ambient conditions
Construction
Standards, directives
CE conformity according to
1)
172
Direction of operation and control signal can be adjusted using DIP switches. Direction of operation 1: Control signal increasing = actuator moves out (valve VUT, VUL, VCL, VDL, BUL closes and valve BXL (control passage) opens). Direction of operation 2: Control signal increasing = actuator moves in (valve VUT, VUL, VCL, VDL, BUL opens and valve BXL (control passage) closes). Factory setting: Direction of operation 2 (RA)
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Overview of types Type
Features
Actuating power
AXM217SF402
Motorised actuator for unit valves with positioner
120 N
AXM217SF404
Motorised actuator for unit valves with positioner and au- 160 N tomatic stroke adjustment
A
AXM217SF402: Actuating power min. 100 N, max. 150 N
Accessories Type
Description
0550603009
Cable: 24 V, PVC, pluggable, 3 m long
0550603010
Cable: 24 V, PVC, pluggable, 7 m long
0550603011
Cable: 24 V, halogen-free, pluggable, 3 m long
0550603012
Cable: 24 V, halogen-free, pluggable, 7 m long
V
Right of amendment reserved © 2024 Fr. Sauter AG
173
Regulating valves SAUTER regulating valves provide flexible combinations for all requirements. The wide product range at SAUTER comprises threaded valves made of DZR cast brass and flanged valves made of grey cast iron, ductile cast iron or cast steel, ensuring that you will find products that suit your requirements perfectly. These regulating valves can be used for the continuous control of hot and cold water in closed circuits.
Overview of regulating valves
Type designation Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Version 2-way 3-way Female thread Male thread Nominal diameter (DN) Nominal pressure Combination options with actuator Further information
174
VUN
BUN
V6R
B6R
• • −
• − −
• • −
• − −
• • • • • • −
• • • • − • −
• − • • • • −
• − • • − • −
• − − • 15...50 PN 16 AVM 105(S), AVM 115(S), AVF 124 AVF 125S AVM 321(S) Page 177
− • − • 15...50 PN 16 AVM 105(S), AVM 115(S), AVF 124 AVF 125S AVM 321(S) Page 180
• − • − 15...50 PN 16 AVM 234S, AVF 234S AVM 322(S)
− • • − 15...50 PN 16 AVM 234S, AVF 234S AVM 322(S)
Page 183
Page 186
Right of amendment reserved © 2024 Fr. Sauter AG
Type designation
VUD
VQD
BUD
BQD
• • −
• • −
• − −
• − −
• • • − • • −
• • • − • • −
• • • − • • −
• • • − • • −
Further information
• − • 15...50 PN 6 AVM 105(S), AVM 115(S), AVM 321(S) Page 189
• − • 65...100 PN 6 AVM 234S, AVM 322(S), AVF 234S Page 192
− • • 15...50 PN 6 AVM 105(S), AVM 115(S), AVM 321(S) Page 194
− • • 65...100 PN 6 AVM 234S, AVM 322(S), AVF 234S Page 197
Type designation
VUE
VQE
BUE
BQE
• • −
• • −
• − −
• − −
• • • − • • −
• • • − • • −
• • • − • • −
• • • − • • −
• − • 15...50 PN 16/10 AVM 105, AVM 115, AVM 321(S) Page 199
• − • 65...150 PN 16 AVM 234S, AVM 322(S), AVF 234S Page 203
− • • 15...50 PN 16/10 AVM 105, AVM 115, AVM 321(S) Page 205
− • • 65...150 PN 16 AVM 234S, AVM 322(S), AVF 234S Page 209
Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator
Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator Further information
Right of amendment reserved © 2024 Fr. Sauter AG
175
Type designation Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Steam Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator Further information
Type designation Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Steam Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator Further information
176
VUG
BUG
VUP
• • •
• − −
• • −
• − • − • • • •
• − • − • • • −
• − • − • • • •
• − • 15...150 PN 25/16 AVM 234S, AVF 234S, AVN 224S, AVM 322(S)
− • • 15...150 PN 25/16 AVM 234S, AVF 234S, AVN 224S, AVM 322(S)
• − • 40...150 PN 25 AVM 234S, AVF 234S, AVN 224S, AVM 322(S)
Page 212
Page 216
Page 220
VUS
BUS
• • •
• − •
• − • − • • • •
• − • − • • • −
• − • 15...100 PN 40 AVM 234S, AVF 234S, AVM 322(S)
− • • 15...100 PN 40 AVM 234S, AVF 234S, AVM 322(S)
Page 222
Page 225
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VUN: 2-way valve with male thread, PN 16 Features • Regulating valve free of silicone grease with male thread (DIN EN ISO 228-1) for cold or hot water in
closed and open circuits In combination with valve actuators AVM 105(S), 115(S), 321(S) and AVF 124, 125S as a control unit • • Equal-percentage (F300) / linear (F200) characteristic, can be set with SUT valve actuators
(SAUTER Universal Technology) • The valve is closed when the spindle is moved out • Closing procedure against the pressure or with the pressure • Stainless-steel spindle
VUN032F300
• Valve body and valve seat in dezincification-resistant (DZR) cast brass • Plug made of dezincification-resistant cast brass (DZR) with EPDM sealing ring
V
• Stuffing box with wiper ring made of dezincification-resistant (DZR) cast brass and double O-ring seal
made of EPDM Technical data Parameters
Nominal pressure Control ratio Valve characteristic Nominal stroke Leakage rate
16 bar > 50:1 F200 = linear F3*0 = equal-percentage 8 mm ≤ 0.02% of Kvs value
Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C
−10...130 °C 16 bar 13 bar
Ambient conditions
Overview of types Type
Nominal diameter
Kvs value
Connection
Weight
VUN015F350
DN 15
0.4 m³/h
G1" B
0.82 kg
VUN015F340
DN 15
0.63 m³/h
G1" B
0.82 kg
VUN015F330
DN 15
1 m³/h
G1" B
0.82 kg
VUN015F320
DN 15
1.6 m³/h
G1" B
0.82 kg
VUN015F310
DN 15
2.5 m³/h
G1" B
0.82 kg
VUN015F300
DN 15
4 m³/h
G1" B
0.82 kg
VUN020F300
DN 20
6.3 m³/h
G1¼" B
1 kg
VUN025F300
DN 25
10 m³/h
G1½" B
1.3 kg
VUN032F300
DN 32
16 m³/h
G2" B
1.74 kg
VUN040F300
DN 40
22 m³/h
G2¼" B
2.52 kg
VUN050F300
DN 50
28 m³/h
G2¾" B
3.44 kg
VUN050F200
DN 50
40 m³/h
G2¾" B
3.44 kg
Accessories Type
Description
0361951015
Screw fitting for male thread with flat seal DN 15
0361951020
Screw fitting for male thread with flat seal DN 20
0361951025
Screw fitting for male thread with flat seal DN 25
0361951032
Screw fitting for male thread with flat seal DN 32
1)
Use stuffing box heater at temperatures below 0 °C; use temperature adapter (accessory) at temperatures above 100 °C
Right of amendment reserved © 2024 Fr. Sauter AG
177
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Description
0361951040
Screw fitting for male thread with flat seal DN 40
0361951050
Screw fitting for male thread with flat seal DN 50
0372240001
Manual adjustment for valves with 8 mm stroke
0372249001
Adaptor required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)
0372249002
Adaptor required when temperature of the medium is 130...150 °C
0378284100
Stuffing box heater 230V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24V~, 15 W for medium below 0 °C
0378368001
Complete replacement stuffing box for DN 15...50
Combination of VUN with electric actuators
/
V
/
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM105F100
AVM105SF132
230
AVM105F120 AVM105F122 230
Page
AVM115SF132
233
AVM115F120 AVM115F122 231
Actuating power
250 N
Control signal
2-/3-point
250 N
250 N
500 N
500 N
2-/3-point
2-/3-point, 0...10 V 2-/3-point
Running time
30 s
2-/3-point, 0...10 V
120 s
35/60/120 s
60/120 s
120 s
233
Closes against the pressure
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
VUN015F350 VUN015F340 VUN015F330 VUN015F320 VUN015F310 VUN015F300
4.0
4.0
4.0
6.0
6.0
VUN020F300
4.0
4.0
4.0
5.0
5.0
VUN025F300
4.0
4.0
4.0
4.0
4.0
VUN032F300
3.0
3.0
3.0
3.5
3.5
VUN040F300
1.9
1.9
1.9
3.0
3.0
VUN050F300 VUN050F200
1.0
1.0
1.0
2.4
2.4
Cannot be used to close with the pressure Actuator
AVM321SF132
Page
AVM321F110 AVM321F112 239
242
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
Actuating power
1000 N
1000 N
500 N
500 N
Control signal
2-/3-point
2-/3point, 0...10 V, 4...20 m 3-point A
2-/3pt., 0...10 V, 4...20 mA
Running time
48/96 s
32/96 s
60/120 s
Closes against the pressure VUN015F350 VUN015F340 VUN015F330 VUN015F320 VUN015F310 VUN015F300 VUN020F300
178
60/120 s
∆pmax [bar]
∆pmax [bar]
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]
10.0
10.0
6.0
16.0
6.0
16.0
10.0
10.0
5.0
12.0
5.0
12.0
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page
AVM321F110 AVM321F112 239
AVM321SF132 242
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
VUN025F300
10.0
10.0
4.0
8.0
4.0
8.0
VUN032F300
10.0
10.0
3.5
6.0
3.5
6.0
VUN040F300
6.0
6.0
3.0
3.5
3.0
3.5
VUN050F300 VUN050F200
4.0
4.0
2.4
2.4
2.4
2.4
Closes with the pressure
∆pmax [bar]
∆pmax [bar]
VUN015F350 VUN015F340 VUN015F330 VUN015F320 VUN015F310 VUN015F300
6.0
6.0
4.0
16.0
4.0
16.0
VUN020F300
6.0
6.0
2.8
16.0
2.8
16.0
VUN025F300
5.0
5.0
2.8
8.0
2.8
16.0
VUN032F300
4.0
4.0
2.0
16.0
2.0
16.0
VUN040F300
2.5
2.5
1.5
16.0
1.5
16.0
VUN050F300 VUN050F200
2.0
2.0
0.8
16.0
0.8
16.0
A
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]
V
At temperatures above 100 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
179
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
BUN: 3-way valve with male thread, PN 16 Features • Regulating valve free of silicone grease with male thread (DIN EN ISO 228-1) for cold and hot water in
closed and open circuits In combination with valve actuators AVM 105(S), 115(S), 321(S) and AVF 124, 125S as a control unit • • Equal-percentage (F300) / linear (F200) characteristic, can be set with SUT valve actuators
(SAUTER Universal Technology) • The valve is closed when the spindle is moved out • Can be used as a control valve or a distribution valve
BUN032F300
• Stainless-steel spindle • Valve body with valve seat made from dezincification-resistant cast brass (DZR) • Plug made of dezincification-resistant cast brass (DZR) with EPDM sealing ring
V
• Stuffing box with wiper ring made from dezincification-resistant cast brass (DZR) and double O-ring seal
made from EPDM Technical data Parameters
Nominal pressure Valve characteristic, control passage
Distribution valve
Control valve
Mixing passage valve characteristic Control ratio Control passage leakage rate Mixing passage leakage rate Nominal stroke
16 bar F200 = linear F3*0 = equal percentage Linear > 50:1 ≤ 0.05% of kvs value ≤ 1% of Kvs value 8 mm
Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C
–10...130 °C 16 bar 13 bar
Ambient conditions
Overview of types Type
Nominal diameter
Kvs value
Connection
Weight
BUN015F330
DN 15
1 m³/h
G1" B
0.82 kg
BUN015F320
DN 15
1.6 m³/h
G1" B
0.82 kg
BUN015F310
DN 15
2.5 m³/h
G1" B
0.82 kg
BUN015F300
DN 15
4 m³/h
G1" B
0.82 kg
BUN020F300
DN 20
6.3 m³/h
G1¼" B
1 kg
BUN025F300
DN 25
10 m³/h
G1½" B
1.3 kg
BUN032F300
DN 32
16 m³/h
G2" B
1.74 kg
BUN040F300
DN 40
22 m³/h
G2¼" B
2.52 kg
BUN050F300
DN 50
28 m³/h
G2¾" B
3.44 kg
BUN050F200
DN 50
40 m³/h
G2¾" B
3.44 kg
Accessories Type
Description
0361951015
Screw fitting for male thread with flat seal DN 15
0361951020
Screw fitting for male thread with flat seal DN 20
0361951025
Screw fitting for male thread with flat seal DN 25
0361951032
Screw fitting for male thread with flat seal DN 32
1)
180
Use stuffing box heater at temperatures below 0 °C; use temperature adapter (accessory) at temperatures above 100 °C
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Description
0361951040
Screw fitting for male thread with flat seal DN 40
0361951050
Screw fitting for male thread with flat seal DN 50
0372240001
Manual adjustment for valves with 8 mm stroke
0372249001
Adaptor required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)
0372249002
Adaptor required when temperature of the medium is 130...150 °C
0378284100
Stuffing box heater 230V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24V~, 15 W for medium below 0 °C
0378368001
Complete replacement stuffing box for DN 15...50
Combination of BUN with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
V
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM105F100
AVM105SF132
230
AVM105F120 AVM105F122 230
Page
AVM115SF132
233
AVM115F120 AVM115F122 231
Actuating power
250 N
Control signal
2-/3-point
250 N
250 N
500 N
500 N
2-/3-point
2-/3-point, 0...10 V 2-/3-point
Running time
30 s
2-/3-point, 0...10 V
120 s
35/60/120 s
60/120 s
120 s
233
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BUN015F330 BUN015F320 BUN015F310 BUN015F300
4.0
4.0
4.0
6.0
6.0
BUN020F300
4.0
4.0
4.0
5.0
5.0
BUN025F300
3.0
3.0
3.0
4.0
4.0
BUN032F300
2.0
2.0
2.0
3.7
3.7
BUN040F300
1.2
1.2
1.2
2.7
2.7
BUN050F300 BUN050F200
0.8
0.8
0.8
1.8
1.8
Cannot be used as distribution valve Actuator
AVM321SF132
Page
AVM321F110 AVM321F112 239
242
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3point, 0...10 V, 4...20 m 3-point A
500 N
500 N 2-/3pt., 0...10 V, 4...20 mA
Running time
48/96 s
32/96 s
60/120 s
60/120 s
As control valve
∆pmax [bar]
∆pmax [bar]
BUN015F330 BUN015F320 BUN015F310 BUN015F300
10.0
10.0
6.0
16.0
6.0
16.0
BUN020F300
10.0
10.0
5.0
9.5
5.0
9.5
BUN025F300
10.0
10.0
4.0
6.5
4.0
6.5
BUN032F300
10.0
10.0
3.7
4.3
3.7
4.3
BUN040F300
6.0
6.0
2.7
2.7
2.7
2.7
Right of amendment reserved © 2024 Fr. Sauter AG
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]
181
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page
V
AVM321SF132 242
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
BUN050F300 BUN050F200
4.0
4.0
As distribution valve
∆pmax [bar]
∆pmax [bar]
BUN015F330 BUN015F320 BUN015F310 BUN015F300
6.0
6.0
4.0
16.0
4.0
16.0
BUN020F300
6.0
6.0
2.8
16.0
2.8
16.0
BUN025F300
5.0
5.0
2.8
16.0
2.8
16.0
BUN032F300
4.0
4.0
2.0
16.0
2.0
16.0
BUN040F300
2.5
2.5
1.5
16.0
1.5
16.0
BUN050F300 BUN050F200
2.0
2.0
0.8
16.0
0.8
16.0
A
182
AVM321F110 AVM321F112 239
1.8
1.8
1.8
1.8
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]
At temperatures above 100 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
V6R: 2-way valve with female thread, PN 16 (el.) Features • Regulating valve free of silicone grease with female thread DIN EN ISO 228-1 G for the control of
cold/hot water in closed and open circuits • In combination with valve actuators AVM 322, AVM 322S, AVM 234S, AVF 234S • Equal-percentage or linear characteristic, can be set with SUT valve actuators (SAUTER Universal
Technology) to linear or equal-percentage • Control passage A–AB closed when the spindle is moved out • Closing procedure against the pressure or with the pressure
V6R15F300
• Valve body and seat made of gunmetal • Stainless-steel spindle • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM
V
Technical data Parameters
Control ratio Leakage rate Valve stroke Nominal pressure
> 50:1 ≤ 0.05% of Kvs value 14 mm 16 bar
Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C
−15...130 °C 16 bar 13 bar
Pressure and temperature data Flow parameters
DIN 2401 VDI/VDE 2173
Ambient conditions
Standards, directives
ValveDim app
Overview of types Type
Nominal di- Kvs value ameter
Valve characteristic Materials for valve plug
V6R15F350
DN 15
0.4 m³/h
Equal-percentage Stainless steel
G½"
1.2 kg
V6R15F340
DN 15
0.63 m³/h Equal-percentage Stainless steel
G½"
1.2 kg
V6R15F330
DN 15
1 m³/h
Equal-percentage Stainless steel
G½"
1.2 kg
V6R15F320
DN 15
1.6 m³/h
Equal-percentage Stainless steel
G½"
1.2 kg
V6R15F310
DN 15
2.5 m³/h
Equal-percentage Brass
G½"
1.2 kg
V6R15F300
DN 15
4 m³/h
Equal-percentage Brass
G½"
1.2 kg
V6R15F200
DN 15
4 m³/h
Linear
Brass
G½"
1.2 kg
V6R25F310
DN 25
6.3 m³/h
Equal-percentage Brass
G1"
1.6 kg
V6R25F300
DN 25
10 m³/h
Equal-percentage Brass
G1"
1.6 kg
V6R25F210
DN 25
6.3 m³/h
Linear
Brass
G1"
1.6 kg
V6R25F200
DN 25
10 m³/h
Linear
Brass
G1"
1.6 kg
V6R40F310
DN 40
16 m³/h
Equal-percentage Brass
G1½"
3.4 kg
V6R40F300
DN 40
25 m³/h
Equal-percentage Brass
G1½"
3.4 kg
V6R40F210
DN 40
16 m³/h
Linear
Brass
G1½"
3.4 kg
V6R40F200
DN 40
25 m³/h
Linear
Brass
G1½"
3.4 kg
V6R50F300
DN 50
35 m³/h
Equal-percentage Brass
G2"
4.6 kg
V6R50F200
DN 50
35 m³/h
Linear
G2"
4.6 kg
1)
Brass
Type of Weight connection
At temperatures below 0 °C, use stuffing box heater (accessory)
Right of amendment reserved © 2024 Fr. Sauter AG
183
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0217268001
Stuffing box heater 15 W, 24 V
0217268004
Stuffing box heater 15 W, 230 V
0360391015
Screw fitting, DN 15, incl. seal, 2 pcs. required
0360391025
Screw fitting, DN 25, incl. seal, 2 pcs. required
0360391040
Screw fitting incl. seal, 2 pcs. required, Rp1½ - G1½
0360391050
Screw fitting incl. seal, 2 pcs. required, Rp2 - G2
0360427000
Stuffing box, complete with O-ring, max. 130 °C
A
0217268*** Stuffing box heater 15 W, light alloy housing, IP54, 3 × 0.75 mm² power cable, earth connector, length 1 m, ferrule
Combination of V6R with electrical actuators
V
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM234SF132
AVM322F120 AVM322F122 239
AVM322SF132
250
AVF234SF132 AVF234SF232 257
Page Actuating power
2500 N
2000 N
1000 N
1000 N
Control signal
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
Running time
28/56/84 s
28/56/84 s
120/240 s
120/80 s
Closes against the pressure
∆pmax [bar] ∆ps [bar]
∆pmax [bar]
∆pmax [bar]
V6R15F350 V6R15F340 V6R15F330 V6R15F320 V6R15F310 V6R15F300 V6R15F200 V6R25F310 V6R25F300 V6R25F210 V6R25F200
4.0
4.0
16.0
4.0
4.0
V6R40F310 V6R40F300 V6R40F210 V6R40F200
3.0
3.0
11.5
3.0
3.0
V6R50F300 V6R50F200
2.0
2.0
8.6
2.0
2.0
∆pmax [bar]
∆pmax [bar]
Closes with the pressure V6R15F350 V6R15F340 V6R15F330 V6R15F320 V6R15F310 V6R15F300 V6R15F200 V6R25F310 V6R25F300 V6R25F210 V6R25F200
184
∆pmax [bar]
242
∆pmax [bar]
∆pmax [bar] ∆ps [bar]
3.0
3.0
16.0
4.0
4.0
2.0
2.0
16.0
4.0
4.0
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator
AVM234SF132
Page
250
AVF234SF132 AVF234SF232 257
AVM322F120 AVM322F122 239
AVM322SF132 242
V6R40F310 V6R40F300 V6R40F210 V6R40F200
1.5
1.5
16.0
3.0
3.0
V6R50F300 V6R50F200
1.0
1.0
16.0
2.0
2.0
A A
Accessories required: Mounting set 0372338001 for AVM 234 and AVF 234 Accessories required: Mounting set 0510240012 for AVM 322(S)
V
Right of amendment reserved © 2024 Fr. Sauter AG
185
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
B6R: 3-way valve with female thread, PN 16 (el.) Features • Regulating valve free of silicone grease with female thread DIN EN ISO 228-1 G for the control of
cold/hot water in closed and open circuits • In combination with valve actuators AVM 322, AVM 322S, AVM 234S, AVF 234S • Equal-percentage or linear characteristic, can be set with SUT valve actuators (SAUTER Universal
Technology) to linear or equal-percentage • Control passage A–AB closed when the spindle is moved out
B6R25F300
• Can be used as a control valve or a distribution valve • Valve body and seat made of gunmetal • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM • Stainless-steel spindle
V
Technical data Parameters
Control ratio Leakage rate of control passage A-AB Leakage rate of mixing passage B-AB Valve stroke Mixing passage valve characteristic
> 50:1 ≤ 0.05% of Kvs value ≤ 1% of Kvs value 14 mm Linear
Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C
−15...130 °C 16 bar 13 bar
Pressure and temperature data Flow parameters
DIN 2401 VDI/VDE 2173
Ambient conditions
Standards, directives
ValveDim app
Overview of types Type
Nominal di- Kvs value ameter
B6R15F330
DN 15
1 m³/h
Equal-percentage Stainless steel
G½"
1.2 kg
B6R15F320
DN 15
1.6 m³/h
Equal-percentage Stainless steel
G½"
1.2 kg
B6R15F310
DN 15
2.5 m³/h
Equal-percentage Brass
G½"
1.2 kg
B6R15F300
DN 15
4 m³/h
Equal-percentage Brass
G½"
1.2 kg
B6R15F200
DN 15
4 m³/h
Linear
Brass
G½"
1.2 kg
B6R25F310
DN 25
6.3 m³/h
Equal-percentage Brass
G1"
1.6 kg
B6R25F300
DN 25
10 m³/h
Equal-percentage Brass
G1"
1.6 kg
B6R25F210
DN 25
6.3 m³/h
Linear
Brass
G1"
1.6 kg
B6R25F200
DN 25
10 m³/h
Linear
Brass
G1"
1.6 kg
B6R40F310
DN 40
16 m³/h
Equal-percentage Brass
G1½"
3.4 kg
B6R40F300
DN 40
25 m³/h
Equal-percentage Brass
G1½"
3.4 kg
B6R40F210
DN 40
16 m³/h
Linear
Brass
G1½"
3.4 kg
B6R40F200
DN 40
25 m³/h
Linear
Brass
G1½"
3.4 kg
B6R50F300
DN 50
35 m³/h
Equal-percentage Brass
G2"
4.6 kg
B6R50F200
DN 50
35 m³/h
Linear
G2"
4.6 kg
1)
186
Valve characteristic Materials for valve plug
Brass
Type of Weight connection
At temperatures below 0 °C, use stuffing box heater (accessory)
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0217268001
Stuffing box heater 15 W, 24 V
0217268004
Stuffing box heater 15 W, 230 V
0360391015
Screw fitting, DN 15, incl. seal, 3 pcs. required
0360391025
Screw fitting, DN 25, incl. seal, 3 pcs. required
0360391040
Screw fitting, DN 40, incl. seal, 3 pcs. required
0360391050
Screw fitting, DN 50, incl. seal, 3 pcs. required
0360427000
Stuffing box, comlete with o-ring, max. 130 °C
0360429000
Adhesive label for distribution valve
A
0217268*** Stuffing box heater 15 W, light alloy housing, IP54, 3 × 0.75 mm² power cable, earth connector, length 1 m, ferrule
A
0360429 Sheet with 21 adhesive labels for flow change; see combinations
V
Combination of B6R with electrical actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM234SF132
AVM322F120 AVM322F122 239
AVM322SF132
250
AVF234SF132 AVF234SF232 257
Page Actuating power
2500 N
2000 N
1000 N
1000 N
Control signal
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
Running time
28/56/84 s
28/56/84 s
120/240 s
120/80 s
As control valve
∆pmax [bar]
B6R15F330 B6R15F320 B6R15F310 B6R15F300 B6R15F200 B6R25F310 B6R25F300 B6R25F210 B6R25F200
∆pmax [bar] ∆ps [bar]
4.0
4.0
B6R40F310 B6R40F300 B6R40F210 B6R40F200
3.0
B6R50F300 B6R50F200
2.0
As distribution valve
∆pmax [bar]
B6R15F330 B6R15F320 B6R15F310 B6R15F300 B6R15F200
3.0
3.0
B6R25F310 B6R25F300 B6R25F210 B6R25F200
2.0
2.0
242
∆pmax [bar]
∆pmax [bar]
16.0
4.0
4.0
3.0
11.5
3.0
3.0
2.0
8.6
2.0
2.0
∆pmax [bar]
∆pmax [bar]
16.0
4.0
4.0
16.0
4.0
4.0
∆pmax [bar] ∆ps [bar]
Right of amendment reserved © 2024 Fr. Sauter AG
187
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator
AVM234SF132
Page
250
AVF234SF132 AVF234SF232 257
AVM322F120 AVM322F122 239
AVM322SF132 242
B6R40F310 B6R40F300 B6R40F210 B6R40F200
1.5
1.5
16.0
3.0
3.0
B6R50F300 B6R50F200
1.0
1.0
16.0
2.0
2.0
A A
Accessories required: Mounting set 0372338001 for AVM 234 and AVF 234 Accessories required: Mounting set 0510240012 for AVM 322(S)
V
188
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VUD: 2-way flanged valve, PN 6 (el.) Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and
AVF 125(S) as a control unit • Not suitable for steam or drinking water or potentially explosive atmospheres • Valve with flange connection as per EN 1092-2, seal form B
VUD032F300
• Regulating valve, free of silicone grease, painted black • Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-
percentage or quadratic • The valve is closed when the spindle is moved out
V
• Closing procedure against the pressure or with the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM
Technical data Parameters
Nominal pressure Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Control ratio from valve Stuffing box Leakage rate Valve stroke
PN 6 Flange as per EN 1092-2, form B Linear
Operating temperature2) Operating pressure
−10...150 °C Up to 120 °C; 6 bar At 150 °C; 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed
Pressure and temperature data Flow parameters Pressure Equipment Directive
EN 764, EN 1333 EN 60534 (page 3) 97/23/EC (fluid group II) No CE label Article 3.3
Equal-percentage > 50:1 2 EPDM O-rings ≤ 0.05% of Kvs value 8 mm
Ambient conditions1)
Standards, directives
Overview of types Type
Nominal diameter
Kvs value
Weight
VUD015F320
DN 15
1.6 m³/h
3.2 kg
VUD015F310
DN 15
2.5 m³/h
3.2 kg
VUD015F300
DN 15
4 m³/h
3.2 kg
VUD020F300
DN 20
6.3 m³/h
4.1 kg
VUD025F300
DN 25
10 m³/h
4.7 kg
1) 2)
Humidity must not exceed 75% At temperatures below 0 °C, use stuffing box heater. Use adapter (accessory) at temperatures above 100 °C
Right of amendment reserved © 2024 Fr. Sauter AG
189
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Nominal diameter
Kvs value
Weight
VUD032F300
DN 32
16 m³/h
7.3 kg
VUD040F300
DN 40
22 m³/h
8.6 kg
VUD050F300
DN 50
28 m³/h
11.2 kg
VUD050F200
DN 50
40 m³/h
11.2 kg
Accessories
V
Type
Description
0372240001
Manual adjustment for valves with 8 mm stroke
0372249001
Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50
0372249002
Adaptor required when temperature of the medium is 130...150 °C, DN 15...50
0378284100
Stuffing box heater 230 VAC, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 VAC, 15 W for medium below 0 °C
0378368001
Complete replacement stuffing box for DN 15...50
Combination of VUD with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Combination of VUD with electric actuator, actuating power 250 N, 500 N Actuator
AVM105F100
AVM105SF132
230
AVM105F120 AVM105F122 230
Page Actuating power
250 N
250 N
Control signal
2-/3-point
2-/3-point
2-/3-point, 0...10 V 2-/3-point
2-/3-point, 0...10 V
Running time
30 s
120 s
35/60/120 s
60/120 s
Closes against the pressure VUD015F320 VUD015F310 VUD015F300 VUD020F300
AVM115SF132
233
AVM115F120 AVM115F122 231
250 N
500 N
500 N
120 s
233
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
4.0
4.0
4.0
6.0
6.0
VUD025F300
2.8
2.8
2.8
6.0
6.0
VUD032F300
2.1
2.1
2.1
5.2
5.2
VUD040F300
1.2
1.2
1.2
3.3
3.3
VUD050F300 VUD050F200
0.9
0.9
0.9
2.0
2.0
Cannot be used to close with the pressure
190
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of VUD with electric actuator with spring return, actuating power 500 N Actuator Page
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
Actuating power
500 N
500 N
Control signal
3-point
2-/3-pt., 0...10 V, 4...20 mA
Running time
60/120 s
60/120 s
Closes against the pressure
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
VUD015F320 VUD015F310 VUD015F300 VUD020F300 VUD025F300
6.0
6.0
6.0
6.0
VUD032F300
5.2
5.2
5.2
5.2
VUD040F300
3.3
3.3
3.3
3.3
VUD050F300 VUD050F200
2.0
2.0
2.0
2.0
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
6.0
6.0
6.0
6.0
VUD025F300
5.0
6.0
5.0
6.0
VUD032F300
4.0
6.0
4.0
6.0
VUD040F300
2.5
6.0
2.5
6.0
VUD050F300 VUD050F200
1.5
6.0
1.5
6.0
Closes with the pressure VUD015F320 VUD015F310 VUD015F300 VUD020F300
A
V
At temperatures above 100 °C, accessories are required
Combination of VUD with electric actuator, actuating power 1000 N Actuator Page
AVM321F110 AVM321F112 239
AVM321SF132 242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0...10 V, 4...20 mA
Running time
48/96 s
32/96 s
Closes against the pressure
∆pmax [bar]
∆pmax [bar]
VUD015F320 VUD015F310 VUD015F300 VUD020F300 VUD025F300 VUD032F300 VUD040F300
6.0
6.0
VUD050F300 VUD050F200
4.0
4.0
∆pmax [bar]
∆pmax [bar]
6.0
6.0
Closes with the pressure VUD015F320 VUD015F310 VUD015F300 VUD020F300 VUD025F300
5.0
5.0
VUD032F300
4.0
4.0
VUD040F300
2.5
2.5
VUD050F300 VUD050F200
1.5
1.5
A
At temperatures above 100 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
191
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VQD: 2-way flanged valve, PN 6 Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for steam or drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black
VQD
• Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-
percentage or quadratic • The valve is closed when the spindle is moved out
V
• Closing procedure against the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of stainless steel with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM
Technical data Parameters
Nominal pressure Connection Valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke
PN 6 Flange as per EN 1092-2, form B Equal-percentage > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65...80) 40 mm (DN 100)
Ambient conditions1)
Operating temperature2) Operating pressure
−10...150 °C Up to 120 °C 6 bar At 150 °C 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed
Pressure and temperature data Flow parameters Pressure Equipment Directive
EN 764, EN 1333 EN 60534, (page 3) 2014/68/EU (fluid group II) No CE label as per article 4.3
Standards, directives
Overview of types Type
Nominal diameter
Kvs value
Weight
VQD065F300
DN 65
63 m³/h
18.0 kg
VQD080F300
DN 80
100 m³/h
25.3 kg
VQD100F300
DN 100
160 m³/h
37.1 kg
1) 2)
192
Humidity must not exceed 75% At temperatures below 0 °C, use stuffing box heater
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0372336180
Intermediate piece (required when temperature of the medium is 130...180 °C)
0378284100
Stuffing box heater 230 VAC, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 VAC, 15 W for medium below 0 °C
0378369101
Complete replacement stuffing box for DN 65...150
Combination of VQD with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the
V
valve.
Combination of VQD with electric actuator, actuating power 1000 N Actuator Page
AVM322F120 AVM322F122 239
242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
Running time
120/240 s
120/80 s
Closes against the pressure VQD065F300
AVM322SF132
∆pmax [bar]
VQD080F300
∆pmax [bar]
2.5
2.5
1.5
1.5
Cannot be used to close with the pressure
A
Maximum media temperature: 100 °C
Combination of VQD with electric actuator, actuating power 2500 N, 2000 N Actuator Page
AVF234SF132 AVF234SF232 257
AVM234SF132
Actuating power
2000 N
2500 N
Control signal
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 65, DN 80
40/80/120 s
40/80/120 s
Running time for DN 100...150
80/160/240 s
80/160/240 s
250
Closes against the pressure
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
VQD065F300
3.0
5.1
1.2
VQD080F300
3.0
3.4
3.0
VQD100F300
2.0
2.2
2.0
Cannot be used to close with the pressure
A A
Spring return: AVF234SF132 normally closed (NC); AVF234SF232 normally open (NO) At temperatures above 130 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
193
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
BUD: 3-way flanged valve, PN 6 (el.) Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and
AVF 125(S) as a control unit • Not suitable for drinking water
BUD032F300
• Valve with flange connection as per EN 1092-2, seal form B, for PN 16 and PN 10 • Regulating valve, free of silicone grease, painted black • Characteristic can be set with SUT valve actuators to linear, equal-percentage or quadratic • The control passage is closed when the spindle is moved out
V
• Used as control valve or as distribution valve • Valve body with seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM
Control valve
Technical data Parameters
Nominal pressure Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Mixing passage valve characteristic Control ratio from valve Stuffing box Control passage leakage rate Mixing passage leakage rate Valve stroke
Distribution valve
PN 6 Flange as per EN 1092-2, form B Linear Equal-percentage Linear > 50:1 2 EPDM O-rings < 0.05% of Kvs value < 1% of Kvs value 8 mm
Ambient conditions1)
Operating temperature2) Operating pressure
−10...150 °C Up to 120 °C; 6 bar At 150 °C; 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 EN 60534 (page 3) Fluid group II, liquid or steam pressure, no CE label as per article 4.3
Standards, directives
Overview of types Type
Nominal diameter
Kvs value
Weight
BUD015F320
DN 15
1.6 m³/h
3200 g
BUD015F310
DN 15
2.5 m³/h
3200 g
BUD015F300
DN 15
4 m³/h
3200 g
BUD020F300
DN 20
6.3 m³/h
4100 g
1) 2)
194
Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 100 °C
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Nominal diameter
Kvs value
Weight
BUD025F300
DN 25
10 m³/h
4700 g
BUD032F300
DN 32
16 m³/h
7100 g
BUD040F300
DN 40
22 m³/h
8400 g
BUD050F300
DN 50
28 m³/h
10900 g
BUD050F200
DN 50
40 m³/h
11200 g
Accessories Type
Description
0372240001
Manual adjustment for valves with 8 mm stroke
0372249001
Adapter required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)
0372249002
Adapter required when temperature of the medium is 130...150 °C
0378284100
Stuffing box heater 230 V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 V~, 15 W for medium below 0 °C
0378368001
Complete replacement stuffing box for DN 15...50
V
Combination of BUD with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Combination of BUD with electric actuator, actuating power 250 N, 500 N Actuator
AVM105F100
AVM105SF132
230
AVM105F120 AVM105F122 230
Page Actuating power
AVM115SF132
233
AVM115F120 AVM115F122 231
250 N
250 N
250 N
500 N
Control signal
2-/3-point
2-/3-point
2-/3-point, 0...10 V 2-/3-point
500 N 2-/3-point, 0...10 V
Running time
30 s
120 s
35/60/120 s
60/120 s
120 s
233
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BUD015F320 BUD015F310 BUD015F300 BUD020F300
4.0
4.0
4.0
6.0
6.0
BUD025F300
2.8
2.8
2.8
6.0
6.0
BUD032F300
2.1
2.1
2.1
5.2
5.2
BUD040F300
1.2
1.2
1.2
3.3
3.3
BUD050F300 BUD050F200
0.9
0.9
0.9
2.0
2.0
Cannot be used as distribution valve
Right of amendment reserved © 2024 Fr. Sauter AG
195
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of BUD with electric actuator with spring return, actuating power 500 N Actuator
V
Page
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
Actuating power
500 N
500 N
Control signal
3-point
2-/3-pt., 0...10 V, 4...20 mA
Running time
60/120 s
60/120 s
As control valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
BUD015F320 BUD015F310 BUD015F300 BUD020F300 BUD025F300
6.0
6.0
6.0
6.0
BUD032F300
5.2
5.2
5.2
5.2
BUD040F300
3.3
3.3
3.3
3.3
BUD050F300 BUD050F200
2.0
2.0
2.0
2.0
As distribution valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
BUD015F320 BUD015F310 BUD015F300 BUD020F300
6.0
6.0
6.0
6.0
BUD025F300
5.0
6.0
5.0
6.0
BUD032F300
4.0
6.0
4.0
6.0
BUD040F300
2.5
6.0
2.5
6.0
BUD050F300 BUD050F200
1.5
6.0
1.5
6.0
A
At temperatures above 100 °C, accessories are required
Combination of BUD with electric actuator, actuating power 1000 N Actuator Page
AVM321F110 AVM321F112 239
242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0...10 V, 4...20 mA
Running time
48/96 s
32/96 s
As control valve
∆pmax [bar]
∆pmax [bar]
BUD015F320 BUD015F310 BUD015F300 BUD020F300 BUD025F300 BUD032F300 BUD040F300
6.0
6.0
BUD050F300 BUD050F200
4.0
4.0
As distribution valve
∆pmax [bar]
∆pmax [bar]
BUD015F320 BUD015F310 BUD015F300 BUD020F300
6.0
6.0
BUD025F300
5.0
5.0
BUD032F300
4.0
4.0
BUD040F300
2.5
2.5
BUD050F300 BUD050F200
1.5
1.5
A
196
AVM321SF132
At temperatures above 100 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
BQD: 3-way flanged valve, PN 6 Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black • Equal-percentage control passage characteristic, can be set with SUT (SAUTER Universal Technology)
BQD
valve actuators to linear or quadratic • Mixing passage, linear characteristic
V
• The control passage is closed when the spindle is moved out • Used as control valve or as distribution valve • Valve body with seat made of grey cast iron • Stainless-steel spindle • Plug made of stainless steel with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM
Control valve
Technical data Parameters
Nominal pressure Connection Control passage valve characteristic Mixing passage valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke
PN 6 Flange as per EN 1092-2, form B Equal-percentage Linear > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65...80) 40 mm (DN 100)
Distribution valve
Ambient conditions1)
Operating temperature2) Operating pressure
−10...150 °C Up to 120 °C 6 bar At 150 °C 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed
Pressure and temperature data Flow parameters Pressure Equipment Directive
EN 764, EN 1333 EN 60534, (page 3) 2014/68/EU (fluid group II) No CE label as per article 4.3
Standards, directives
Overview of types Type
Nominal diameter
Kvs value
Weight
BQD065F300
DN 65
63 m³/h
14.8 kg
BQD080F300
DN 80
100 m³/h
21 kg
BQD100F300
DN 100
160 m³/h
31 kg
1) 2)
Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater
Right of amendment reserved © 2024 Fr. Sauter AG
197
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0372336180
Adapter (required when temperature of the medium is 130...150 °C)
0378284100
Stuffing box heater 230 V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 V~, 15 W for medium below 0 °C
0378369101
Complete replacement stuffing box
Combination of BQD with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
V
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Combination of BQD with electric actuator, actuating power 1000 N Actuator Page
AVM322F120 AVM322F122 239
AVM322SF132 242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
Running time
120/240 s
120/80 s
As control valve
∆pmax [bar]
BQD065F300
2.5
2.5
BQD080F300
1.5
1.5
∆pmax [bar]
∆pmax [bar]
As distribution valve BQD065F300 BQD080F300
A
∆pmax [bar]
1.0
1.0
0.7
0.7
At media temperature above 100 °C, accessories are required.
Combination of BQD with electric actuator, actuating power 2500 N, 2000 N Actuator Page
AVF234SF132 AVF234SF232 257
Actuating power
2000 N
2500 N
Control signal
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 65, DN 80
40/80/120 s
40/80/120 s
Running time for DN 100...150
80/160/240 s
80/160/240 s
250
As control valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
BQD065F300
3.0
5.1
3.0
BQD080F300
3.0
3.4
3.0
BQD100F300
2.0
2.2
2.0
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
As distribution valve BQD065F300
1.0
6.0
1.0
BQD080F300
0.8
6.0
0.8
BQD100F300
0.5
6.0
0.5
A
198
AVM234SF132
At temperatures above 130 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VUE: 2-way flanged valve, PN 16/10 (el.) Features • Continuous control of cold/hot water and low-pressure steam up to 115 °C in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and
AVF 125(S) as a control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B, for PN 16 and PN 10 • Regulating valve, free of silicone grease, painted black
VUE032F300
• Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-
percentage or quadratic • The valve is closed when the spindle is moved out
V
• Closing procedure against the pressure or with the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM
Technical data Parameters
Nominal pressure Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Control ratio from valve Stuffing box Leakage rate Valve stroke
PN 16/10 Flange as per EN 1092-2, form B Linear
Operating temperature2) Operating pressure
-10…150 °C PN 16: Up to 120 °C, 16 bar At 150 °C, 14.4 bar PN 10: Up to 120 °C, 10 bar At 150 °C, 9 bar Between 120 °C and 150 °C, a linear interpolation can be performed
Equal-percentage > 50:1 2 EPDM O-rings < 0.05% of Kvs value 8 mm
Ambient conditions1)
ValveDim app
Standards, directives
Pressure and temperature data Flow parameters Pressure Equipment Directive
EN 764, EN 1333 EN 60534 (page 3) 97/23/EC (fluid group II) No CE label Article 3.3
Overview of types Type
Nominal diameter
Kvs value
Weight
VUE015F350
DN 15
0.4 m³/h
3.2 kg
VUE015F340
DN 15
0.63 m³/h
3.2 kg
1) 2)
Humidity must not exceed 75%. At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 100 °C
Right of amendment reserved © 2024 Fr. Sauter AG
199
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Nominal diameter
Kvs value
Weight
VUE015F330
DN 15
1 m³/h
3.2 kg
VUE015F320
DN 15
1.6 m³/h
3.2 kg
VUE015F310
DN 15
2.5 m³/h
3.2 kg
VUE015F300
DN 15
4 m³/h
3.2 kg
VUE020F300
DN 20
6.3 m³/h
4.1 kg
VUE025F300
DN 25
10 m³/h
4.7 kg
VUE032F300
DN 32
16 m³/h
7.3 kg
VUE040F300
DN 40
22 m³/h
8.6 kg
VUE050F300
DN 50
28 m³/h
11.2 kg
VUE050F200
DN 50
40 m³/h
11.2 kg
Accessories
V
Type
Description
0372240001
Manual adjustment for valves with 8 mm stroke
0372249001
Adapter required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)
0372249002
Adapter required when temperature of the medium is 130...150 °C
0378284100
Stuffing box heater 230 V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 V~, 15 W for medium below 0 °C
0378368001
Complete replacement stuffing box for DN 15...50
Combination of VUE with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Combination of VUE with electric actuator, actuating power 250 N, 500 N Actuator
AVM105F100
AVM105SF132
230
AVM105F120 AVM105F122 230
Page Actuating power
250 N
250 N
Control signal
2-/3-point
2-/3-point
2-/3-point, 0...10 V 2-/3-point
2-/3-point, 0...10 V
Running time
30 s
120 s
35/60/120 s
60/120 s
Closes against the pressure VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300
AVM115SF132
233
AVM115F120 AVM115F122 231
250 N
500 N
500 N
120 s
233
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
4.0
4.0
4.0
6.0
6.0
VUE025F300
2.8
2.8
2.8
6.0
6.0
VUE032F300
2.1
2.1
2.1
5.2
5.2
VUE040F300
1.4
1.4
1.4
3.3
3.3
VUE050F300 VUE050F200
0.9
0.9
0.9
2.0
2.0
Cannot be used to close with the pressure
200
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of VUE with electric actuator with spring return, actuating power 500 N Actuator Page
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
Actuating power
500 N
500 N
Control signal
3-point
2-/3-pt., 0...10 V, 4...20 mA
Running time
60/120 s
60/120 s
Closes against the pressure
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300
6.0
16.0
6.0
16.0
VUE020F300
6.0
11.0
6.0
11.0
VUE025F300
6.0
6.8
6.0
6.8
VUE032F300
5.2
5.2
5.2
5.2
VUE040F300
3.3
3.3
3.3
3.3
VUE050F300 VUE050F200
2.0
2.0
2.0
2.0
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
6.0
16.0
6.0
16.0
VUE025F300
5.0
16.0
5.0
16.0
VUE032F300
4.0
16.0
4.0
16.0
VUE040F300
2.5
16.0
2.5
16.0
VUE050F300 VUE050F200
1.5
16.0
1.5
16.0
Closes with the pressure VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300
A
V
At temperatures above 100 °C, accessories are required
Combination of VUE with electric actuator, actuating power 1000 N Actuator Page
AVM321F110 AVM321F112 239
242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0...10 V, 4...20 mA
Running time
48/96 s
32/96 s
Closes against the pressure VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300 VUE025F300 VUE032F300
AVM321SF132
∆pmax [bar]
∆pmax [bar]
10.0
10.0
VUE040F300
6.0
6.0
VUE050F300 VUE050F200
4.0
4.0
Right of amendment reserved © 2024 Fr. Sauter AG
201
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page
V
AVM321SF132 242
Closes with the pressure
∆pmax [bar]
∆pmax [bar]
VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300
6.0
6.0
VUE025F300
5.0
6.0
VUE032F300
4.0
6.0
VUE040F300
2.5
2.5
VUE050F300 VUE050F200
1.5
1.5
A
202
AVM321F110 AVM321F112 239
At temperatures above 100 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VQE: 2-way flanged valve, PN 16 Features • Continuous control of cold and hot water and low-pressure steam up to 115 °C in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black • Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-
VQE
percentage or quadratic • The valve is closed when the spindle is moved out
V
• Closing procedure against the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of stainless steel with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM
Technical data Parameters
Nominal pressure Connection Valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke
PN 16 Flange as per EN 1092-2, form B Equal-percentage > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65, 80) 40 mm (DN 100...150)
Ambient conditions1)
Operating temperature2) Operating pressure
−10…150 °C Up to 120 °C 16 bar At 150 °C 14.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed
Pressure and temperature data Flow parameters Pressure Equipment Directive
EN 764, EN 1333 EN 60534-3 2014/68/EU (fluid group II) No CE label as per article 4.3
Standards, directives
Overview of types Type
Nominal diameter
Kvs value
Weight
VQE065F300
DN 65
63 m³/h
23.8 kg
VQE080F300
DN 80
100 m³/h
30.2 kg
VQE100F300
DN 100
160 m³/h
41.3 kg
VQE125F300
DN 125
220 m³/h
62 kg
VQE150F300
DN 150
320 m³/h
89 kg
1) 2)
Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 130 °C
Right of amendment reserved © 2024 Fr. Sauter AG
203
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0372336180
Adapter (required when temperature of the medium is 130...150 °C)
0378284100
Stuffing box heater 230 V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 V~, 15 W for medium below 0 °C
0378369101
Complete replacement stuffing box
Combination of VQE with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
V
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Combination of VQE with electric actuators, actuating power 1000 N Actuator Page
AVM322F120 AVM322F122 239
242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
Running time
120/240 s
120/80 s
Closes against the pressure VQE065F300
AVM322SF132
∆pmax [bar]
VQE080F300
∆pmax [bar]
2.5
2.5
1.5
1.5
Cannot be used to close with the pressure
A
At media temperature above 100 °C, accessories are required.
Combination of VQE with electric actuators, actuating power 2500 N, 2000 N Actuator Page
AVF234SF132 AVF234SF232 257
AVM234SF132
Actuating power
2000 N
2500 N
Control signal
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 65, DN 80
40/80/120 s
40/80/120 s
Running time for DN 100...150
80/160/240 s
80/160/240 s
250
Closes against the pressure
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
VQE065F300
3.0
5.1
3.0
VQE080F300
3.0
3.4
3.0
VQE100F300
2.0
2.2
2.0
VQE125F300
1.4
1.4
1.5
VQE150F300
1.0
1.1
1.0
Cannot be used to close with the pressure
A A
204
Spring return: AVF234SF132 normally closed (NC); AVF234SF232 normally open (NO) At temperatures above 130 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
BUE: 3-way flanged valve, PN 16/10 (el.) Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and AVF
125(S) as a control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B, for PN 16 and PN 10 • Regulating valve, free of silicone grease, painted black
BUE032F300
• Equal-percentage characteristic with F300, can be set with SUT valve actuators (SAUTER Universal
Technology) to linear or quadratic • Valve passage A–AB is closed when the spindle is moved out
V
• Can be used as a control valve or a distribution valve • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM
Control valve
Technical data Parameters
Connection Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Mixing passage valve characteristic Control ratio from valve Stuffing box Control passage leakage rate Mixing passage leakage rate Valve stroke
PN 16/10 Flange as per EN 1092-2, form B Linear Equal-percentage
Distribution valve
Linear > 50:1 2 EPDM O-rings < 0.05% of Kvs value < 1% of Kvs value 8 mm
Ambient conditions1)
Operating temperature2) Operating pressure
−10...150 °C PN 16: Up to 120 °C, 16 bar At 150 °C, 14.4 bar PN 10: Up to 120 °C, 10 bar At 150 °C, 9 bar Between 120 °C and 150 °C, a linear interpolation can be performed
Pressure and temperature data Flow parameters Pressure Equipment Directive
EN 764, EN 1333 EN 60534 (page 3) 97/23/EC (fluid group II) No CE label Article 3.3
Standards, directives
1) 2)
Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 100 °C
Right of amendment reserved © 2024 Fr. Sauter AG
205
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Overview of types Type
Nominal diameter
Kvs value
Weight
BUE015F330
DN 15
1 m³/h
3.2 kg
BUE015F320
DN 15
1.6 m³/h
3.2 kg
BUE015F310
DN 15
2.5 m³/h
3.2 kg
BUE015F300
DN 15
4 m³/h
3.2 kg
BUE020F300
DN 20
6.3 m³/h
4.1 kg
BUE025F300
DN 25
10 m³/h
4.7 kg
BUE032F300
DN 32
16 m³/h
7.1 kg
BUE040F300
DN 40
22 m³/h
8.4 kg
BUE050F300
DN 50
28 m³/h
11.2 kg
BUE050F200
DN 50
40 m³/h
11.2 kg
Accessories
V
Type
Description
0372240001
Manual adjustment for valves with 8 mm stroke
0372249001
Adapter required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)
0372249002
Adapter required when temperature of the medium is 130...150 °C
0378284100
Stuffing box heater 230 V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 V~, 15 W for medium below 0 °C
0378368001
Complete replacement stuffing box for DN 15...50
Combination of BUE with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Combination of BUE with electric actuator, actuating power 250 N, 500 N Actuator
AVM105F100
AVM105SF132
230
AVM105F120 AVM105F122 230
Page Actuating power
AVM115SF132
233
AVM115F120 AVM115F122 231
250 N
250 N
250 N
500 N
Control signal
2-/3-point
2-/3-point
2-/3-point, 0...10 V 2-/3-point
500 N 2-/3-point, 0...10 V
Running time
30 s
120 s
35/60/120 s
60/120 s
120 s
233
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BUE015F330 BUE015F320 BUE015F310 BUE015F300 BUE020F300
4.0
4.0
4.0
6.0
6.0
BUE025F300
2.8
2.8
2.8
6.0
6.0
BUE032F300
2.1
2.1
2.1
5.2
5.2
BUE040F300
1.4
1.4
1.4
3.3
3.3
BUE050F300 BUE050F200
0.9
0.9
0.9
2.0
2.0
Cannot be used as distribution valve
206
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of BUE with electric actuator with spring return, actuating power 500 N Actuator Page
AVF124F130 AVF124F230 252
AVF125SF132 AVF125SF232 255
Actuating power
500 N
500 N
Control signal
3-point
2-/3-pt., 0...10 V, 4...20 mA
Running time
60/120 s
60/120 s
As control valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
BUE015F330 BUE015F320 BUE015F310 BUE015F300
6.0
16.0
6.0
16.0
BUE020F300
6.0
11.0
6.0
11.0
BUE025F300
6.0
6.8
6.0
6.8
BUE032F300
5.2
5.2
5.2
5.2
BUE040F300
3.3
3.3
3.3
3.3
BUE050F300 BUE050F200
2.0
2.0
2.0
2.0
As distribution valve
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
BUE020F300
6.0
16.0
6.0
16.0
BUE025F300
5.0
16.0
5.0
16.0
BUE032F300
4.0
16.0
4.0
16.0
BUE040F300
2.5
16.0
2.5
16.0
BUE050F300 BUE050F200
1.5
16.0
1.5
16.0
A A
V
Spring return: 18 ± 10 s At temperatures above 100 °C, accessories are required
Combination of BUE with electric actuator, actuating power 1000 N Actuator Page
AVM321F110 AVM321F112 239
AVM321SF132 242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0...10 V, 4...20 mA
Running time
48/96 s
32/96 s
As control valve
∆pmax [bar]
∆pmax [bar]
BUE015F330 BUE015F320 BUE015F310 BUE015F300 BUE020F300 BUE025F300 BUE032F300
10.0
10.0
BUE040F300
6.0
6.0
BUE050F300 BUE050F200
4.0
4.0
∆pmax [bar]
∆pmax [bar]
6.0
6.0
As distribution valve BUE015F330 BUE015F320 BUE015F310 BUE015F300 BUE020F300 BUE025F300
6.0
5.0
BUE032F300
6.0
4.0
BUE040F300
2.5
2.5
BUE050F300 BUE050F200
1.5
1.5
Right of amendment reserved © 2024 Fr. Sauter AG
207
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
A
At temperatures above 100 °C, accessories are required
V
208
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
BQE: 3-way flanged valve, PN 16 Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black • Equal-percentage control passage characteristic, can be set with SUT (SAUTER Universal Technology) valve
BQE
actuators to linear or quadratic • Mixing passage, linear characteristic
V
• The control passage is closed when the spindle is moved out • Used as control valve or as distribution valve • Valve body with seat made of grey cast iron • Spindle and plug made of stainless steel; plug with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM
Control valve
Technical data Parameters
Nominal pressure Connection Control passage valve characteristic Mixing passage valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke
PN 16 Flange as per EN 1092-2, form B Equal-percentage Linear > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65, 80) 40 mm (DN 100...150)
Distribution valve
Ambient conditions
Operating temperature1) Operating pressure
Air humidity
−10…150 °C Up to 120 °C 16 bar At 150 °C 14.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed Max. 75% rh, no condensation
Standards, directives
Pressure and temperature data Flow parameters Pressure Equipment Directive
EN 764, EN 1333 EN 60534, (page 3) 2014/68/EU (fluid group II) With CE label
ValveDim app
Overview of types Type
Nominal diameter
Kvs value
Weight
BQE065F300
DN 65
63 m³/h
19 kg
BQE080F300
DN 80
100 m³/h
24 kg
BQE100F300
DN 100
160 m³/h
34 kg
BQE125F300
DN 125
220 m³/h
52 kg
BQE150F300
DN 150
320 m³/h
76 kg
1)
At temperatures below 0 °C, use a stuffing box heater. Use adapter at temperatures above 130 °C (see accessories)
Right of amendment reserved © 2024 Fr. Sauter AG
209
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0372336180
Adapter (required when temperature of the medium is 130...150 °C)
0378284100
Stuffing box heater 230 V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 V~, 15 W for medium below 0 °C
0378369101
Complete replacement stuffing box
Combination of BQE with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
V
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Combination of BQE with electric actuators, actuating power 1000 N Actuator Page
AVM322F120 AVM322F122 239
AVM322SF132 242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
Running time
120/240 s
120/80 s
As control valve
∆pmax [bar]
BQE065F300
2.5
2.5
BQE080F300
1.5
1.5
∆pmax [bar]
∆pmax [bar]
As distribution valve BQE065F300 BQE080F300
A
∆pmax [bar]
1.0
1.0
0.7
0.7
At media temperature above 100 °C, accessories are required.
Combination of BQE with electric actuators, actuating power 2000 N and 2500 N Actuator
AVF234SF132 AVF234SF232 257
Page
250
Actuating power
2500 N
2000 N
Control signal
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 65, DN 80
40/80/120 s
40/80/120 s
Running time for DN 100...150
80/160/240 s
80/160/240 s
As control valve
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
BQE065F300
3.0
3.0
5.1
BQE080F300
3.0
3.0
3.4
BQE100F300
2.0
2.0
2.2
BQE125F300
1.5
1.4
1.4
BQE150F300
1.0
1.0
1.1
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
As distribution valve BQE065F300
210
AVM234SF132
1.0
1.0
16.0
BQE080F300
0.8
0.8
16.0
BQE100F300 BQE125F300 BQE150F300
0.5
0.5
16.0
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
A
At temperatures above 130 °C, accessories are required.
V
Right of amendment reserved © 2024 Fr. Sauter AG
211
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VUG: 2-way flanged valve, PN 25/16 (el.) Features • Continuous control of cold and hot water in closed circuits, and of steam • In combination with valve actuators AVM 322(S), AVM 234S, AVN 234S and AVF 234S as a control unit • Water quality as per VDI 2035 • Valve with flange connection as per EN 1092-2, seal form B • Nominal pressure 25 bar (VUG065F316: 16 bar) • Not suitable for drinking water • Standard compliance for control units according to DIN EN 14597 (VUG065F316 does not have TÜV
approval) VUG032F304
V
• Regulating valve, free of silicone grease, painted black • Equal-percentage characteristic, can be set with SUT (SAUTER Universal Technology) valve actuators to
linear or quadratic • The valve is closed when the spindle is moved out • Closing procedure against the pressure or with the pressure • Valve body made of ductile cast iron; seat and spindle made of stainless steel • Plugs of nominal diameter DN 15...50 made of stainless steel with glass-fibre-reinforced PTFE sealing ring • Plugs of nominal diameter DN 65...150 made of stainless steel with metal-to-metal seal • Maintenance-free stuffing box in brass with spring-loaded PTFE washer
Technical data Parameters
Nominal pressure Connection Valve characteristic Control ratio from valve Leakage rate at max. ∆ps
PN 16/25 Flange as per EN 1092-2, form B Equal-percentage > 50:1 ≤ 0.05% of Kvs value
Operating temperature1) Operating pressure2)
−10…200 °C PN 16: –16 bar at 30…120 °C 14 bar at 200 °C PN 25: 25 bar at 30…120 °C 21.7 bar at 200 °C
Pressure and temperature data Flow parameters Test mark3)
EN 764, EN 1333 EN 60534 TÜV ID: 14392
Ambient conditions
Standards, directives
1)
ValveDim app
2) 3)
212
For cold water applications from −20...30 °C, the VUG***F3**S versions with a stuffing box containing silicone (e.g. VUG015F304S) must be used. The VUG***F3**S valves do not comply with the standard for control units as per DIN EN 14597. VUG***F3**S are only available up to DN 125. VUG***F3**S do not have TÜV approval and must not be combined with AVN224 actuators. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution For operating pressures, see diagram “Pressure / temperature assignment” VUG065F316 does not have TÜV approval. The valve does not bear the test centre identification number and falls under category I of the Pressure Equipment Directive. The valve can be used with the AVN224SF*** actuator, but not as a safety device. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution. For use as per DIN EN 14597. When the VUG065F316 is combined with the AVN224S actuator, the permissible media temperature is > 0 °C.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators PED 2014/68/EU (CE) PESR-2016 (UKCA)
Fluid group II, liquid or steam pressure Fluid group II, liquid or steam pressure
Overview of types Type
Nominal diame- Kvs value ter
Valve stroke
Connection
Weight
Approval
VUG015F374
DN 15
20 mm
PN 25/16
4 kg
CE, TÜV
VUG015F364
DN 15
0.25 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
VUG015F354
DN 15
0.4 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
VUG015F344
DN 15
0.63 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
VUG015F334
DN 15
1 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
VUG015F324
DN 15
1.6 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
VUG015F314
DN 15
2.5 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
VUG015F304
DN 15
4 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
VUG020F304
DN 20
6.3 m³/h
20 mm
PN 25/16
5 kg
CE, TÜV
VUG025F304
DN 25
10 m³/h
20 mm
PN 25/16
5.6 kg
CE, TÜV
VUG032F304
DN 32
16 m³/h
20 mm
PN 25/16
9.1 kg
CE, TÜV
VUG040F304
DN 40
25 m³/h
20 mm
PN 25/16
11.2 kg
CE, TÜV
VUG050F304
DN 50
40 m³/h
20 mm
PN 25/16
13.8 kg
CE, TÜV, UKCA
VUG065F316
DN 65
63 m³/h
40 mm
PN 16
25 kg
CE, UKCA
VUG065F304
DN 65
63 m³/h
40 mm
PN 25
25 kg
CE, TÜV, UKCA
VUG080F304
DN 80
100 m³/h
40 mm
PN 25/16
37 kg
CE, TÜV, UKCA
VUG100F304
DN 100
160 m³/h
40 mm
PN 25
50 kg
CE, TÜV, UKCA
VUG125F304
DN 125
250 m³/h
40 mm
PN 25
75 kg
CE, TÜV, UKCA
VUG150F304
DN 150
340 m³/h
40 mm
PN 25
100 kg
CE, TÜV
A
0.16 m³/h
V
VUG with DN 150: Not used in the United Kingdom of Great Britain and Northern Ireland (UK)
Markets for valve-actuator combinations AVM322F120 AVM322F122
AVM322SF132 AVM234SF132
AVF234SF132 AVF234SF232
AVN224SF132
AVN224SF232
1, 3
1, 3
1, 3
2, 3, 4
2, 3
1, 3 2, 3
1, 3 2, 3
1, 3 2, 3
2, 3 2, 3, 4
2, 3 2, 3
VUG015F374 VUG015F364 VUG015F354 VUG015F344 VUG015F334 VUG015F324 VUG015F314 VUG015F304 VUG020F304 VUG025F304 VUG032F304 VUG040F304 VUG050F304 VUG065F304 VUG080F304 VUG100F304 VUG125F304 VUG065F316 VUG150F304 Key:
1 2 3 4
Intended for the United Kingdom of Great Britain and Northern Ireland (UK) Combination not allowed in UK Intended for the European Union (EU) for control functions Approval in the EU for safety functions. Cat. IV of the PED. TÜV certificate
Right of amendment reserved © 2024 Fr. Sauter AG
213
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0372336180
Intermediate piece (required when temperature of the medium is 130...180 °C)
0372336240
Adapter (required when temperature of the medium is 180...200 °C)
0378284100
Stuffing box heater 230 VAC, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 VAC, 15 W for medium below 0 °C
0378384001
Torsion protection DN 65...150
0560260001
Stuffing box for VUG/BUG for cold water application with grease containing silicone
Combination of VUG with electric actuators
/ /
V
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM322SF132
AVM234SF132
Page
AVM322F120 AVM322F122 239
242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 15...50
120/240 s
Running time for DN 65...150
–
Closes against the pressure VUG015F374 VUG015F364 VUG015F354 VUG015F344 VUG015F334 VUG015F324 VUG015F314 VUG015F304 VUG020F304
250
AVF234SF132 AVF234SF232 257
AVN224SF132 AVN224SF232 260
2500 N
2000 N
1100 N
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
80/120 s
40/80/120 s
40/80/120 s
40/80/120 s
–
80/160/240 s
80/160/240 s
80/160/240 s
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
16.0
16.0
16.0
16.0
25.0
16.0
25.0
VUG025F304
15.2
15.2
16.0
16.0
25.0
16.0
17.0
VUG032F304
9.4
9.4
16.0
16.0
21.0
10.5
10.5
VUG040F304
6.1
6.1
16.0
13.5
13.5
6.5
6.5
VUG050F304
4.0
4.0
11.0
8.5
8.5
4.0
4.0
VUG065F316
–
–
7.1
5.6
5.6
–
–
VUG065F304
–
–
7.1
5.6
5.6
3.0
3.0
VUG080F304
–
–
4.7
3.4
3.4
2.0
2.0
VUG100F304
–
–
3.0
2.2
2.2
1.1
1.1
VUG125F304
–
–
2.0
1.6
1.6
0.8
0.8
VUG150F304
–
–
1.5
1.2
1.2
0.6
0.6
214
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page
AVM322F120 AVM322F122 239
AVM322SF132
AVM234SF132
242
250
AVF234SF132 AVF234SF232 257
AVN224SF132 AVN224SF232 260
Closes with the pressure
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
VUG015F374 VUG015F364 VUG015F354 VUG015F344 VUG015F334 VUG015F324 VUG015F314 VUG015F304 VUG020F304 VUG025F304 VUG032F304
6.0
6.0
6.0
6.0
25.0
6.0
25.0
VUG040F304
5.5
5.5
6.0
6.0
25.0
6.0
25.0
VUG050F304
3.5
3.5
6.0
6.0
25.0
4.0
25.0
VUG065F316
–
–
4.5
4.5
25.0
–
–
VUG065F304
–
–
4.5
4.5
25.0
2.6
25.0
VUG080F304
–
–
3.5
3.4
25.0
1.7
25.0
VUG100F304
–
–
3.0
2.2
25.0
1.1
25.0
VUG125F304
–
–
2.0
1.6
25.0
0.8
25.0
VUG150F304
–
–
1.5
1.0
25.0
0.6
25.0
A A
At temperatures above 130 °C, accessories are required Combination with AVN 224S: with safety function as per DIN EN 14597
Right of amendment reserved © 2024 Fr. Sauter AG
215
V
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
BUG: 3-way flanged valve, PN 25/16 (el.) Features • Continuous control of cold and hot water in closed circuits • In combination with valve actuators AVM 322(S), AVM 234S, AVN 234S and AVF 234S as a control unit • Water quality as per VDI 2035 • Valve with flange connection as per EN 1092-2, seal form B • Nominal pressure 25 bar (BUG065F316: 16 bar) • Not suitable for drinking water • Standard compliance for control units according to DIN EN 14597 (BUG065F316 does not have TÜV
BUG032F304
V
approval) • Regulating valve, free of silicone grease, painted black • Equal-percentage characteristic, can be set with SUT valve actuators to linear or quadratic • The control passage is closed when the spindle is moved out • Can be used as a control valve or a distribution valve • Valve body made of ductile cast iron • Stainless-steel seat and spindle • Plugs of nominal diameter DN 15...50 made of stainless steel with glass-fibre-reinforced PTFE sealing ring • Plugs of nominal diameter DN 65...150 made of stainless steel with metal-to-metal seal • Maintenance-free stuffing box in brass with spring-loaded PTFE washer
Technical data Parameters
Leakage rate at max. ∆ps
Nominal pressure Connection Control ratio Control passage valve characteristic Mixing passage valve characteristic Control passage leakage rate Mixing passage leakage rate
PN 16/25 Flange as per EN 1092-2, form B > 50: 1 Equal-percentage Linear ≤ 0.05% of Kvs value ≤ 1.0% of Kvs value
Operating temperature1) Operating pressure2)
−10…200 °C PN 16: 16 bar at 30…120 °C 14 bar at 200 °C PN 25: 25 bar at 30…120 °C 21.7 bar at 200 °C
Pressure and temperature data Flow parameters
EN 764, EN 1333 EN 60534
Ambient conditions
Standards, directives
ValveDim app
1)
2)
216
For cold water applications from –20...30 °C, use versions BUG***F3**S with a stuffing box containing silicone (e.g.: BUG015F304S). The BUG***F3**S valves do not comply with the standard for control units as per DIN EN 14597. BUG***F3**S are only available up to DN 125. BUG***F3**S do not have TÜV approval and must not be combined with AVN224 actuators. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution. For operating pressures, see diagram “Pressure / temperature assignment”
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators TÜV ID: 18388 Fluid group II, liquid or steam pressure Fluid group II, liquid or steam pressure
Test mark3) PED 2014/68/EU (CE) PESR-2016 (UKCA)
Overview of types Type
Nominal diame- Kvs value ter
Valve stroke
BUG015F334
DN 15
1 m³/h
20 mm
PN 25/16
3.1 kg
CE, TÜV
BUG015F324
DN 15
1.6 m³/h
20 mm
PN 25/16
3.1 kg
CE, TÜV
BUG015F314
DN 15
2.5 m³/h
20 mm
PN 25/16
3.1 kg
CE, TÜV
BUG015F304
DN 15
4 m³/h
20 mm
PN 25/16
3.1 kg
CE, TÜV
BUG020F304
DN 20
6.3 m³/h
20 mm
PN 25/16
4 kg
CE, TÜV
BUG025F304
DN 25
10 m³/h
20 mm
PN 25/16
4.7 kg
CE, TÜV
BUG032F304
DN 32
16 m³/h
20 mm
PN 25/16
7.2 kg
CE, TÜV
BUG040F304
DN 40
25 m³/h
20 mm
PN 25/16
9.2 kg
CE, TÜV
BUG050F304
DN 50
40 m³/h
20 mm
PN 25/16
11.9 kg
CE, TÜV UKCA
BUG065F316
DN 65
63 m³/h
40 mm
PN 16
26.8 kg
CE, UKCA
BUG065F304
DN 65
63 m³/h
40 mm
PN 25
27.1 kg
CE, TÜV UKCA
BUG080F304
DN 80
100 m³/h
40 mm
PN 25/16
36.3 kg
CE, TÜV UKCA
BUG100F304
DN 100
160 m³/h
40 mm
PN 25
53 kg
CE, TÜV UKCA
BUG125F304
DN 125
250 m³/h
40 mm
PN 25
79.1 kg
CE, TÜV UKCA
BUG150F304
DN 150
340 m³/h
40 mm
PN 25
108.7 kg
CE, TÜV
A
Connection
Weight
Approval
V
BUG with DN 150: Not used in the United Kingdom of Great Britain and Northern Ireland (UK)
Markets for valve-actuator combinations AVM322F120 AVM322F122
AVM322SF132 AVM234SF132
AVF234SF132 AVF234SF232
AVN224SF132
AVN224SF232
1, 3
1, 3
1, 3
2, 3, 4
2, 3
1, 3 2, 3
1, 3 2, 3
1, 3 2, 3
2, 3 2, 3, 4
2, 3 2, 3
BUG015F334 BUG015F324 BUG015F314 BUG015F304 BUG020F304 BUG025F304 BUG032F304 BUG040F304 BUG050F304 BUG065F304 BUG080F304 BUG100F304 BUG125F304 BUG065F316 BUG150F304 Key:
3)
1 2 3 4
Intended for the United Kingdom of Great Britain and Northern Ireland (UK) Combination not allowed in UK Intended for the European Union (EU) for control functions Approval in the EU for safety functions. Cat. IV of the PED. TÜV certificate
BUG065F316 does not have TÜV approval. The valve does not bear the test centre identification number and falls under category I of the Pressure Equipment Directive. The valve can be used with the AVN224SF*** actuator, but not as a safety device. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution. For use as per DIN EN 14597. When the BUG065F316 is combined with the AVN224S actuator, the permissible media temperature is > 0 °C.
Right of amendment reserved © 2024 Fr. Sauter AG
217
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type
Description
0372336180
Intermediate piece (required when temperature of the medium is 130...180 °C)
0372336240
Adapter (required when temperature of the medium is 180...200 °C)
0378284100
Stuffing box heater 230 VAC, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24 VAC, 15 W for medium below 0 °C
0378384001
Torsion protection DN 65...150
0560260001
Stuffing box for VUG/BUG for cold water application with grease containing silicone
Combination of BUG with electric actuators
/ /
V
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM322SF132
AVM234SF132
Page
AVM322F120 AVM322F122 239
250
AVF234SF132 AVF234SF232 257
AVN224SF132 AVN224SF232 260
242
Actuating power
1000 N
1000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
2500 N
2000 N
1100 N
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 15...50
120/240 s
80/120 s
40/80/120 s
40/80/120 s
40/80/120 s
Running time for DN 65...150
–
–
80/160/240 s
80/160/240 s
80/160/240 s
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
BUG015F334 BUG015F324 BUG015F314 BUG015F304 BUG020F304
16.0
16.0
16.0
16.0
25.0
16.0
25.0
BUG025F304
15.2
15.2
16.0
16.0
25.0
16.0
17.0
BUG032F304
9.4
9.4
16.0
16.0
21.0
10.5
10.5
BUG040F304
6.1
6.1
16.0
13.5
13.5
6.5
6.5
BUG050F304
4.0
4.0
11.0
8.5
8.5
4.0
4.0
BUG065F316
–
–
7.1
5.6
5.6
–
–
BUG065F304
–
–
7.1
5.6
5.6
3.0
3.0
BUG080F304
–
–
4.7
3.4
3.4
2.0
2.0
BUG100F304
–
–
3.0
2.2
2.2
1.1
1.1
BUG125F304
–
–
2.0
1.6
1.6
0.8
0.8
BUG150F304
–
–
1.5
1.2
1.2
0.6
0.6
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
6.0
6.0
6.0
6.0
25.0
6.0
25.0
As distribution valve BUG015F334 BUG015F324 BUG015F314 BUG015F304 BUG020F304 BUG025F304 BUG032F304 BUG040F304
5.5
5.5
4.0
6.0
25.0
6.0
25.0
BUG050F304
3.5
3.5
6.0
6.0
25.0
4.0
25.0
BUG065F316
–
–
4.5
4.5
25.0
–
–
BUG065F304
–
–
4.5
4.5
25.0
2.6
25.0
BUG080F304
–
–
3.5
3.4
25.0
1.7
25.0
218
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page
AVM322F120 AVM322F122 239
AVM322SF132
AVM234SF132
242
250
AVF234SF132 AVF234SF232 257
AVN224SF132 AVN224SF232 260
BUG100F304
–
–
3.0
2.2
25.0
1.1
25.0
BUG125F304
–
–
2.0
1.6
25.0
0.8
25.0
BUG150F304
–
–
1.0
1.0
25.0
0.6
25.0
A A
At temperatures above 130 °C, accessories are required Combination with AVN 224S: with safety function as per DIN EN 14597
V
Right of amendment reserved © 2024 Fr. Sauter AG
219
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VUP: Pressure-relieved 2-way flanged valve, PN 25 (el.) Features • Continuous control of cold and hot water in closed circuits, and of steam • In combination with valve actuators AVM 322(S), AVM 234S, AVF 234S and AVN 224S as a control unit • Water quality as per VDI 2035 • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, with pressure compensation, galvanised and painted black
VUP040F304
• Equal-percentage characteristic, can be set with SUT (SAUTER Universal Technology) valve actuators to
linear or quadratic • The valve is closed when the spindle is moved in
V
• Valve body made of ductile cast iron • Valve seat, plug and spindle made of stainless steel A
AB
• Closing procedure only against the pressure • Maintenance-free stuffing box in brass with spring-loaded PTFE-FKM-PTFE washer
Technical data Parameters
Nominal pressure Connection Valve characteristic Control ratio Leakage rate at max. ∆ps
PN 25 Flange as per EN 1092-2, form B Equal-percentage > 100:1 < 0.05% of Kvs value
Operating temperature1) Operating pressure
−20...200 °C Up to 120 °C, 25 bar Up to 200 °C, 20 bar
Test mark
TÜV ID: 06973
Admissible ambient conditions
Standards and directives
Overview of types Type
Nominal diameter
Kvs value
Valve stroke
Weight
VUP040F304
DN 40
25 m³/h
14 mm
10000 g
VUP050F304
DN 50
40 m³/h
25 mm
14000 g
VUP065F304
DN 65
63 m³/h
25 mm
18000 g
VUP080F304
DN 80
100 m³/h
25 mm
25500 g
VUP100F304
DN 100
160 m³/h
40 mm
36500 g
VUP125F304
DN 125
250 m³/h
40 mm
56500 g
VUP150F304
DN 150
350 m³/h
40 mm
84500 g
Accessories Type
Description
0372336180
Adaptor (required when temperature of the medium is 130...180 °C)
0372336240
Adaptor (required when temperature of the medium is 180...200 °C)
0378284100
Stuffing box heater 230V~, 15 W for medium below 0 °C
0378284102
Stuffing box heater 24V~, 15 W for medium below 0 °C
1)
220
Use stuffing box heater at temperatures below 0 °C; use the relevant adapter (accessory) at temperatures above 130 °C or 180 °C. Valve combined with AVN 224S: For use as per DIN EN 14597, the admissible media temperature is > 0 °C.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Description
0378356001
Replacement pack for stuffing box DN 40…80
0378357001
Replacement pack for stuffing box DN 100…150
Combination of VUP with electrical actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM322SF132
AVM234SF132
Page
AVM322F120 AVM322F122 239
242
Actuating power
1000 N
Control signal
V
250
AVF234SF132 AVF234SF232 257
AVN224SF132 AVN224SF232 260
1000 N
2500 N
2000 N
1100 N
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 40
84/168 s
56/84 s
28/56/84 s
28/56/84 s
28/56/84 s
Running time for DN 50...80
–
–
50/100/150 s
50/100/150 s
50/100/150 s
Running time for DN 100...150
–
–
80/160/240 s
80/160/240 s
80/160/240 s
Closes against the pressure
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
VUP040F304
25.0
25.0
25.0
25.0
25.0
25.0
25.0
VUP050F304
–
–
25.0
25.0
25.0
20.0
25.0
VUP065F304
–
–
25.0
25.0
25.0
16.0
17.0
VUP080F304
–
–
25.0
25.0
25.0
12.0
15.0
VUP100F304
–
–
25.0
20.0
22.0
9.0
12.0
VUP125F304
–
–
19.0
14.0
20.0
6.0
6.0
VUP150F304
–
–
15.0
10.0
15.0
4.0
4.0
Cannot be used to close with the pressure
A
Combination with AVN 224S: with safety function as per DIN EN 14597
Right of amendment reserved © 2024 Fr. Sauter AG
221
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
VUS: 2-way flanged valve, PN 40 (el.) Features • Continuous control of cold, warm and hot water in closed circuits, and of steam • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Water quality as per VDI 2035 • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B
VUS040F305
• Regulating valve, free of silicone grease, matt black • Equal-percentage characteristic, can be set with SUT valve actuators to linear or quadratic • The valve is closed when the spindle is moved in. Closing procedure only against the pressure • Valve body made of cast steel; spindle, seat and plug of stainless steel
V
• Maintenance-free stuffing box, made of stainless steel, with spring-loaded PTFE washer up to 220 °C, with
graphite seal up to 260 °C Technical data Parameters
Nominal pressure Operating pressure
Connection Valve characteristic Control ratio Leakage rate
PN 40 40 bar at −10...50 °C 36.3 bar at 120 °C 29.4 bar at 220 °C 27.8 bar at 260 °C Flange as per EN 1092-2, form B Equal-percentage > 50: 1 ≤ 0.05% of Kvs value
Operating temperature1)
−10...260 °C
Pressure and temperature data Flow parameters PED 2014/68/EU (CE)
EN 764, EN 1333 EN 60534 VdTÜV pressure information sheet 100, sheet 1, cat. IV EN 12952-11, EN 12953-9 Article 4.3 AD 2000 Rulebook
Ambient conditions
CE/UKCA conformity2)
ValveDim app
PESR-2016 (UKCA)
Overview of types Type
Nominal diameter
Kvs value
Valve stroke
Weight
VUS015F375
DN 15
0.16 m³/h
20 mm
5.1 kg
VUS015F365
DN 15
0.25 m³/h
20 mm
5.1 kg
VUS015F355
DN 15
0.4 m³/h
20 mm
5.1 kg
VUS015F345
DN 15
0.63 m³/h
20 mm
5.1 kg
VUS015F335
DN 15
1 m³/h
20 mm
5.1 kg
VUS015F325
DN 15
1.6 m³/h
20 mm
5.1 kg
VUS015F315
DN 15
2.5 m³/h
20 mm
5.1 kg
VUS015F305
DN 15
4 m³/h
20 mm
5.1 kg
VUS020F305
DN 20
6.3 m³/h
20 mm
5.9 kg
VUS025F305
DN 25
10 m³/h
20 mm
6.8 kg
VUS032F305
DN 32
16 m³/h
20 mm
8.4 kg
1)
2)
222
No stuffing box heater required down to –10 °C. Above 130 °C or 180 °C, use the relevant adapter (accessory). Above 200 °C and up to 260 °C, use stuffing box with graphite seal (accessory) Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Nominal diameter
Kvs value
Valve stroke
Weight
VUS040F305
DN 40
25 m³/h
20 mm
10.6 kg
VUS050F305
DN 50
40 m³/h
20 mm
13.2 kg
VUS065F305
DN 65
63 m³/h
30 mm
18.6 kg
VUS080F305
DN 80
100 m³/h
30 mm
25.1 kg
VUS100F305
DN 100
160 m³/h
30 mm
36.4 kg
CE/UKCA conformity
VUS015F375 VUS015F365 VUS015F355 VUS015F345 VUS015F335 VUS015F325 VUS015F315 VUS015F305 VUS020F305 VUS025F305 VUS032F305 VUS040F305 VUS050F305 VUS065F305 VUS080F305 VUS100F305
EU PED 2014/68/EU
Label
UK PESR-2016 (UKCA)
Label
Art. 4.3
Without CE
Art. 8.3
Without UKCA
Category I
CE
Category I
UKCA
V
Accessories Type
Description
0372336180
Adaptor (required when temperature of the medium is 130...180 °C)
0372336240
Adaptor (required when temperature of the medium is 180...260 °C)
0378373001
Stuffing box with graphite seal for temperatures of 220...260 °C; DN 15…50
0378373002
Stuffing box with graphite seal for temperatures of 220...260 °C; DN 65…100
Right of amendment reserved © 2024 Fr. Sauter AG
223
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of VUS with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
V
AVM322SF132
AVM234SF132
Page
AVM322F120 AVM322F122 239
242
250
AVF234SF132 AVF234SF232 257
Actuating power
1000 N
1000 N
2500 N
2000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 15...50
120/240 s
80/120 s
40/80/120 s
40/80/120 s
Running time for DN 65...100
–
–
60/120/180 s
60/120/180 s
Closes against the pressure
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
VUS015F375 VUS015F365 VUS015F355 VUS015F345 VUS015F335 VUS015F325 VUS015F315 VUS015F305 VUS020F305
35.0
35.0
40.0
40.0
25.0
VUS025F305
17.4
17.4
37.8
29.6
25.0
VUS032F305
12.2
12.2
28.7
22.5
21.0
VUS040F305
6.2
6.2
16.4
12.8
13.5
VUS050F305
3.7
3.7
10.5
8.2
8.5
VUS065F305
–
–
6.1
4.7
5.6
VUS080F305
–
–
3.9
3.0
3.4
VUS100F305
–
–
1.5
1.5
2.2
Cannot be used to close with the pressure
A
224
At temperatures above 130 °C, accessories are required
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
BUS: 3-way flanged valve, PN 40 (el.) Features • Continuous control of cold/warm/hot water in HVAC installations in closed circuits • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Water quality as per VDI 2035 • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, matt black • Control passage, linear characteristic, DN 15...100; adjustable with SUT (SAUTER Universal Technology)
BUS015F2*5
valve actuators to equal-percentage • Mixing passage, linear characteristic
V
• The control passage is closed when the spindle is moved out • For use only as a control valve • Valve body made of cast steel • Stainless-steel seat and plug • Stainless-steel spindle • Maintenance-free stuffing box, made of stainless steel, with spring-loaded PTFE washer up to 220 °C, with
graphite seal up to 260 °C Technical data Parameters
Nominal pressure Operating pressure
Connection Control ratio Mixing passage valve characteristic Control passage leakage rate Mixing passage leakage rate
PN 40 40 bar at −10...50 °C 36.3 bar at 120 °C 29.4 bar at 220 °C 27.8 bar at 260 °C Flange as per EN 1092-2, form B > 30: 1 Linear ≤ 0.05% of Kvs value ≤ 1.0% of Kvs value ValveDim app
Ambient conditions
Operating temperature1)
−10...260 °C
Pressure and temperature data Flow parameters PED 2014/68/EU (CE) PESR-2016 (UKCA)
EN 764, EN 1333 EN 60534 Fluid group II (liquids only) Fluid group II (liquids only)
CE/UKCA conformity2)
Overview of types Type
Nominal diame- Kvs value ter
Control passage valve characteristic
Valve stroke
Weight
BUS015F225
DN 15
1.6 m³/h
Linear
20 mm
7.2 kg
BUS015F215
DN 15
2.5 m³/h
Linear
20 mm
7.2 kg
BUS015F205
DN 15
4 m³/h
Linear
20 mm
7.2 kg
BUS020F205
DN 20
6.3 m³/h
Linear
20 mm
8.4 kg
1)
2)
No stuffing box heater required down to –10 °C. At temperatures below −10 °C and down to −60 °C, use special version with bellows seal (available on request, only to DN 100). Application: Water with anti-freeze (glycol up to 55% and brine solution), max. operating pressure 30 bar. Above 130 °C or 180 °C, use the relevant adapter (accessory). Above 220 °C and up to 260 °C, use stuffing box with graphite seal (accessory) Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
225
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Nominal diame- Kvs value ter
Control passage valve characteristic
Valve stroke
Weight
BUS025F205
DN 25
10 m³/h
Linear
20 mm
9.4 kg
BUS032F205
DN 32
16 m³/h
Linear
20 mm
12.4 kg
BUS040F205
DN 40
25 m³/h
Linear
20 mm
15.5 kg
BUS050F205
DN 50
40 m³/h
Linear
20 mm
19.2 kg
BUS065F205
DN 65
63 m³/h
Linear
30 mm
27.6 kg
BUS080F205
DN 80
100 m³/h
Linear
30 mm
36.5 kg
BUS100F205
DN 100
160 m³/h
Linear
30 mm
61.2 kg
CE/UKCA conformity
BUS015F225 BUS015F215 BUS015F205 BUS020F205 BUS025F205 BUS032F205 BUS040F205 BUS050F205 BUS065F205 BUS080F205 BUG100F205
V
EU PED 2014/68/EU
Label
UK PESR-2016 (UKCA)
Label
Art. 4.3
Without CE
Art. 8.3
Without UKCA
Category I
CE
Category I
UKCA
Accessories Type
Description
0372336180
Adaptor (required when temperature of the medium is 130...180 °C)
0372336240
Adaptor (required when temperature of the medium is 180...260 °C)
0378373001
Stuffing box with graphite seal for temperatures of 220...260 °C; DN 15…50
0378373002
Stuffing box with graphite seal for temperatures of 220...260 °C; DN 65…100
Combination of BUS with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AVM322SF132
AVM234SF132
Page
AVM322F120 AVM322F122 239
242
250
AVF234SF132 AVF234SF232 257
Actuating power
1000 N
1000 N
2500 N
2000 N
Control signal
2-/3-point
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
2-/3-point, 0…10 V, 4…20 mA
Running time for DN 15...50
120/240 s
80/120 s
40/80/120 s
40/80/120 s
Running time for DN 65...100
–
–
60/120/180 s
60/120/180 s
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆ps [bar]
BUS015F225 BUS015F215 BUS015F205
35.0
35.0
40.0
40.0
40.0
BUS020F205
35.0
35.0
40.0
34.7
40.0
BUS025F205
17.4
17.4
37.8
29.6
37.0
226
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page
AVM322F120 AVM322F122 239
AVM322SF132
AVM234SF132
242
250
AVF234SF132 AVF234SF232 257
BUS032F205
12.2
12.2
27.0
21.1
27.0
BUS040F205
6.2
6.2
16.4
12.8
16.0
BUS050F205
3.7
3.7
10.5
8.2
10.0
BUS065F205
–
–
6.1
4.7
6.1
BUS080F205
–
–
3.9
3.0
3.9
BUS100F205
–
–
2.5
1.9
2.5
Cannot be used as distribution valve
A
At temperatures above 130 °C, accessories are required
V
Right of amendment reserved © 2024 Fr. Sauter AG
227
Valve actuators SAUTER actuators adapt themselves automatically to the valve. Their accurate control provides a high degree of energy efficiency and a low noise level. Furthermore, they can adjust the regulating valves themselves. To save energy, it is possible to include an electric cut-off. SAUTER valve actuators can be used for controllers with a switching or continuous output.
Overview of valve actuators
Type designation Technical data Max. nominal stroke (mm) Max. pushing force (N) Running time s Power supply (V) Control 2-point 3-point Positioner Spring return Combination options with valve Further information
228
AVM 105, 115
AVM 105S, 115S
AVM 215
AVM 215S
8 250, 500 30, 120 24/230
8 250, 500 35, 60, 120 24
8...20 mm 500 7.5 230 V~
10...20 mm 500 7.5 24 V~/=
• • − − VUN/BUN, VUD/BUD, VUE/BUE
• • • − VUN/BUN, VUD/BUD, VUE/BUE
• • − − VUG/BUG, VUS/BUS to DN 025
• • • − VUG/BUG, VUS/BUS to DN 025
Page 230
Page 232
Page 234
Page 236
Right of amendment reserved © 2024 Fr. Sauter AG
Type designation
AVM 321, 322
AVM 321S, 322S
8, 20 1000 6, 12 s/mm 24 / 230
8, 20 1000 4, 12 s/mm 24 / (230)
• • − − VUD/BUD/VQD/BQD, VUE/BUE/VQE/BQE, VUG/BUG VUN/BUN, VUS/BUS, VUP, V6R/B6R
• • • − VUD/BUD/VQD/BQD, VUE/BUE/VQE/BQE, VUG/BUG, VUN/BUN, VUS/BUS, VUP, V6R/B6R
Page 238
Page 241
Technical data Max. nominal stroke (mm) Max. pushing force (N) Running time Power supply (V) Control 2-point 3-point Positioner Spring return Combination options with valve Further information
Type designation
AVM 234S
AVF 234S
AVN 224S
Technical data Max. nominal stroke (mm) Max. pushing force (N) Running time Power supply (V)
40 2500 2, 4, 6, s/mm 24 / (230)
40 2000 2, 4, 6 s/mm 24 / (230)
40 1100 2, 4, 6 s/mm 24 / (230)
• • • − VQD/BQD, VQE/BQE, VUG/BUG, VUS/BUS, VUP, V6R/B6R Page 249
• • • • VQD/BQD, VQE/BQE, VUG/BUG, VUS/BUS, VUP, V6R/B6R Page 256
• • • • VQE/BQE, VUG/BUG, VUS/BUS, VUP, V6R/B6R
Control 2-point 3-point Positioner Spring return Combination options with valve Further information
Right of amendment reserved © 2024 Fr. Sauter AG
Page 259
229
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 105, 115: Valve actuator Features • Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series • For controllers with a switching (2-/3-point) output • Synchronous motor with electronic control unit and time-dependent cut-off • Direction of operation can be selected directly on the cable • Maintenance-free gearbox with magnetic coupling
AVM1*5F***
• Gear unit can be disengaged to position the valve by hand (hexagon key provided) • Connection with valve spindle performed automatically • Cap nut for valve fitting made of brass • Fitting vertically upright to horizontal, not suspended
V
Technical data Power supply
Power supply 24 VAC Power supply 230 VAC
±20%, 50...60 Hz ±15%, 50...60 Hz
Actuator stroke1) Response time
0...8 mm 200 ms
Ambient temperature Media temperature Ambient humidity
−10...55 °C Max. 100 °C 5...95% rh, no condensation
Control
2-/3-point
Weight Housing
0.7 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 3 × 0.75 mm²
Parameters
Ambient conditions
Function
Construction
Housing material Power cable Standards, directives
CE conformity according to
Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
Directive 2006/95/EC Machinery Directive 2006/42/EC (according to Appendix II, 1B)
IP54 (EN 60529), horizontal III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1 EN 60730-2-14 Over-voltage category III Degree of contamination II EEC (II B) EN ISO 12100:2018
Overview of types Type
Voltage
Actuating power
Running time
Power consumption
AVM105F100
230 V~
250 N
30.0 s
2.4 W, 4.5 VA
AVM105F120
230 V~
250 N
120.0 s
2.0 W, 4.0 VA
1)
230
Stroke 10 mm for AVM115F901
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Voltage
Actuating power
Running time
Power consumption
AVM105F122
24 V~
250 N
120.0 s
1.6 W, 1.7 VA
AVM115F120
230 V~
500 N
120.0 s
2.0 W, 4.0 VA
AVM115F122
24 V~
500 N
120.0 s
1.6 W, 1.7 VA
AVM115F901
230 V~
500 N
160.0 s
2.0 W, 4.0 VA
A
AVM115F901: For SAUTER Valveco VCL040 and VCL050, inverse scale, inverse connection
Accessories Type
Description
0372145001
Auxiliary change-over contacts, single
0372145002
Auxiliary change-over contacts, double
0372249001
Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C
0372273001
Adapter for Siemens valve VVG/VXG 44, 48
0372286001
Potentiometer 130 Ω
0372286002
Potentiometer 1000 Ω
0372286003
Potentiometer, 5000 Ω
0372320001
Hexagon key as visualisation for position indicator
A A
V
Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator
Right of amendment reserved © 2024 Fr. Sauter AG
231
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 105S, 115S: Valve actuator with SAUTER Universal Technology (SUT) Features • Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series • For controllers with a switching (2- and 3-point) or continuous (0...10 V) output • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic,
force-dependent cut-off • Automatic recognition of applied control signal (continuous or switched) • Coding switches for selecting characteristic and running time
AVM1*5SF***
• Type of characteristic (linear/equal-percentage) can be set on the actuator • Automatic adaptation to valve stroke
V
• Maintenance-free gear unit • Gear unit can be disengaged in order to position the valve by hand (hexagon key provided) • Connection with valve spindle performed automatically after control voltage is applied • Brass cap nut for fitting the valve • Fitting vertically upright to horizontal, not suspended
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC
±20%, 50...60 Hz -10...20%
Actuator stroke1) Response time Control signal Positional feedback signal Starting point U0 Control span ΔU Switching range Xsh
0...8 mm 200 milliseconds 0…10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 or 10 V 10 V 200 mV
Ambient temperature Ambient humidity Media temperature
-10...55 °C 5…95% rh, no condensation Max. 100 °C
Weight Housing
0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m, 5 × 0.75 mm²
Parameters
Positioner
Ambient conditions
Construction
Housing material Power cable Standards, directives
CE conformity
1)
232
Type of protection Protection class EMC Directive 2014/30/EU
IP54 (EN 60529), horizontal III (IEC 60730) EN 61000-6-1, EN 61000-6-3, EN 61000-6-4
Stroke 10 mm for AVM115SF901
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Overview of types Type
Voltage
Actuating power
Running time
Power consumption
AVM105SF132
24 V~/=
250 N
35/60/120 s
4.8 W, 8.5 VA
AVM115SF132
24 V~/=
500 N
60/120 s
4.9 W, 8.7 VA
AVM115SF901
24 V~/=
500 N
80/160 s
4.9 W, 8.7 VA
A A
AVM105SF132, AVM115SF132: Equal-percentage characteristic, can be converted to linear AVM115SF901: For SAUTER Valveco VCL040 and VCL050, inverse scale, inverse connection
Accessories Type
Description
0313529001
Split-range unit for adjusting sequences, fitted in separate junction box
0372145001
Auxiliary change-over contacts, single
0372145002
Auxiliary change-over contacts, double
0372249001
Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C
0372249002
Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 130… 150 °C
0372273001
Adapter for Siemens valve VVG/VXG 44, 48
0372286001
Potentiometer 130 Ω
0372286002
Potentiometer 1000 Ω
0372286003
Potentiometer, 5000 Ω
A A
V
Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator
Right of amendment reserved © 2024 Fr. Sauter AG
233
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 215: Valve actuator Features • Actuation of 2- and 3-way valves • For controllers with a switching (2-/3-point) output
AVM215F120R
• Synchronous motor with electronic control unit and cut-off • Maintenance-free gear unit • Gear unit can be disengaged in order to position the valve by hand with the provided hexagon key
(load-free) Connection with valve spindle performed semi-automatically • • Fitting vertically upright to horizontal, not suspended
V
Technical data Power supply
Power supply
230 V~ ±15%, 50...60 Hz
Actuator stroke Response time
8...20 mm 200 ms
Ambient temperature Media temperature Ambient humidity
-10...55 °C Max. 100 °C 5...85% rh, no condensation
Control
2-/3-point
Weight Housing
1 kg Lower section black, upper section yellow Flame-retardant plastic
Parameters
Ambient conditions
Function
Construction
Housing material Power cable
1.2 m long, 3 × 0.75 mm2
Standards and directives
CE conformity according to
Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
Machinery Directive 2006/42/EC (according to Appendix II, 1B)
IP54 (EN 60529), horizontal 230 V: II (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 Over-voltage category III Degree of contamination II EN ISO 12100:2018
Overview of types Type
Voltage
Actuating power
Running time
Power consumption
AVM215F120R
230 V~
400 N
7.5 s/mm
3.2 W 7.0 VA
Accessories
234
Type
Description
0510390029
Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM215(S)F***R
0510390030
Mounting set for SAUTER VU*/BU* valves with 8 mm stroke for AVM215(S)F***R
0510390031
Mounting set for SAUTER VU*/BU* valves with 20 mm stroke for AVM215(S)F***R
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Description
0510390032
Mounting set for SAUTER V6*/B6* and VX*/BX* valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390033
Mounting set for IMI TA-Fusion valves, thread DN 32 to DN 50 for AVM215(S)F***R
0510390034
Mounting set for IMI TA-Fusion valves, thread DN 65 to DN 80 for AVM215(S)F***R
0510390035
Mounting set for IMI CV valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390036
Mounting set for IMI KTM 512 valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390037
Mounting set for IMI KTM 512 valves, thread DN 65 to DN 100 for AVM215(S)F***R
0510390038
Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM215(S)F***R
0510390039
Mounting set for Danfoss VFS/VL/VF valves: thread DN 15 to DN 50, VEFS2: DN 25 to DN 50 for AVM215(S)F***R
0510390040
Mounting set for Danfoss VRB/VRG valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390060
Adapter set for AVM 2*5 for Schneider V241/V341
0510480003
Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke
0510480004
Dual auxiliary switch unit
0372320001
Hexagon key as visualisation for position indicator
A A
V
Auxiliary change-over contacts: infinitely variable 0...100%, admissible load 3(1.5) A, 24...230 V Accessory 0510390029 can also be used for SAUTER Valveco compact DN 40 and DN 50
Right of amendment reserved © 2024 Fr. Sauter AG
235
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 215S: Valve actuator with SAUTER Universal Technology (SUT) Features • Actuation of 2- and 3-way valves • For controllers with a switching (2- and 3-point) or continuous (0...10 V) output
AVM215SF132
• Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-
dependent cut-off Automatic recognition of applied control signal (continuous or switched) • • Coding switches for selecting characteristic and running time • Type of characteristic (linear/equal-percentage) can be set on the actuator • Automatic adaptation to valve stroke
V
• Direction of operation can be selected directly on the cable • Maintenance-free gear unit • Gear unit can be disengaged in order to position the valve by hand with the hexagon key provided (load-
free) • Connection with valve spindle performed semi-automatically after control voltage is applied • Fitting vertically upright to horizontal, not suspended
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC
±20%, 50…60 Hz −10...20%
Actuator stroke Response time Control signal Position feedback signal Starting point U0 Control span ΔU Switching range Xsh
8...20 mm 200 milliseconds 0...10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 or 10 V 10 V 200 mV
Ambient temperature Ambient humidity Media temperature
−10…55 °C 5…85% rh, no condensation Max. 100 °C
Weight Housing
1 kg Lower section black, upper section yellow Flame-retardant plastic
Parameters
Positioner
Ambient conditions
Construction
Housing material Power cable
1.2 m, 5 × 0.5 mm2
Standards, directives
CE conformity according to
236
Type of protection Protection class EMC Directive 2014/30/EU
IP54 (EN 60529), horizontal III (IEC 60730) EN 61000-6-1, EN 61000-6-3, EN 61000-6-4
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Overview of types Type
Actuating power
Running time
Power consumption
AVM215SF132R 24 VAC/DC
500 N
7.5 s/mm 15 s/mm
3.5 W, 6.6 VA 2.7 W, 5.3 VA
AVM215SF132-7 24 V~/=
500 N
7.5 s/mm
3.5 W, 6.6 VA
A
Voltage
AVM215SF132-7 including adapter set for VDL flanged valves DN 50, DN 65 and DN 80
Accessories Type
Description
0510390029
Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM215(S)F***R
0510390030
Mounting set for SAUTER VU*/BU* valves with 8 mm stroke for AVM215(S)F***R
0510390031
Mounting set for SAUTER VU*/BU* valves with 20 mm stroke for AVM215(S)F***R
0510390032
Mounting set for SAUTER V6*/B6* and VX*/BX* valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390033
Mounting set for IMI TA-Fusion valves, thread DN 32 to DN 50 for AVM215(S)F***R
0510390034
Mounting set for IMI TA-Fusion valves, thread DN 65 to DN 80 for AVM215(S)F***R
0510390035
Mounting set for IMI CV valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390036
Mounting set for IMI KTM 512 valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390037
Mounting set for IMI KTM 512 valves, thread DN 65 to DN 100 for AVM215(S)F***R
0510390038
Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM215(S)F***R
0510390039
Mounting set for Danfoss VFS/VL/VF valves: thread DN 15 to DN 50, VEFS2: DN 25 to DN 50 for AVM215(S)F***R
0510390040
Mounting set for Danfoss VRB/VRG valves, thread DN 15 to DN 50 for AVM215(S)F***R
0510390060
Adapter set for AVM 2*5 for Schneider V241/V341
0510480003
Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke
0510480004
Dual auxiliary switch unit
0372320001
Hexagon key as visualisation for position indicator
A A
V
Auxiliary change-over contacts: infinitely variable 0...100%, admissible load 3(1.5) A, 24...230 V Accessory 0510390029 can also be used for SAUTER Valveco compact DN 40 and DN 50
Right of amendment reserved © 2024 Fr. Sauter AG
237
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 321, 322: Valve actuator Features • In ventilation air conditioning units
for actuation of 2- and 3-way valves of type series AVM 321: VUD, VUE, VUN, BUD, BUE, BUN and AVM 322: V6R, VQD, VQE, VUG, VUP, VUS, B6R, BQD, BQE, BUG, BUS For controllers with a switching output (2-point or 3-point control) • 1)
• Synchronous motor with electronic control unit and load-dependent cut-off • Direction of operation and running time can be set using coding switches
AVM32*F1**
• Crank handle for external manual adjustment with motor cut-off • Low operating noise • Simple assembly onto valve; spindle is automatically connected after nominal voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves
V
• Electrical parallel operation of five actuators • Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Mounting column made of aluminium • Fixing bracket made of cast light alloy for valve fitting with 20 mm stroke and made of plastic for valve
fitting with 8 mm stroke • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable gland made of plastic M20 × 1.5 • Fitting vertically upright to horizontal, not suspended
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption2)
±20%, 50...60 Hz −10...20% ±15% < 2.4 W, < 4.0 VA (at nominal voltage, with movement)
Nominal force3) Operating noise4) Response time Media temperature5)
1000 N < 30 dB (A) at nominal force > 200 ms 0...100 °C
Operating temperature Storage and transport temperature Humidity without condensation
−10...55 °C −40...80 °C 5...85% rh
Type of protection Protection class
IP54 (EN 60529) II (EN 60730), III (EN 60730)
Parameters
Ambient conditions
Standards, directives
1) 2)
3)
4) 5)
238
To be used outside HVAC applications only after consultation with the manufacturer For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V or 230 V, 25 °C ambient temperature, 50 Hz). With boundary conditions (19.2 V~ / 28.8 V~ / 21. V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and running time, the actuating/tensile force is minimised to 800 N Operating noise with the slowest running time, measuring distance 1 m At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater)
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)
EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 (AVM32*F110 and F120) III II 2000 m EN ISO 12100:2018
Overview of types Type
Voltage
Nominal stroke Running time
Power consump- DimenWeight tion sions W × H × D
AVM322F120
230 V~
20 mm
6 (12) s/mm
< 2.4 W, < 4.0 VA
160 × 241 × 88 mm
1.6 kg
AVM322F122
24 V~/=
20 mm
6 (12) s/mm
< 2.0 W, < 3.0 VA
160 × 241 × 88 mm
1.6 kg
AVM321F110
230 V~
8 mm
12 (6) s/mm
< 2.4 W, < 4.0 VA
160 × 187 × 88 mm
1.5 kg
AVM321F112
24 V~/=
8 mm
12 (6) s/mm
< 2.0 W, < 3.0 VA
160 × 187 × 88 mm
1.5 kg
A
AVM32*F1*2: CSA-certified actuators on request (only for devices with supply voltage 24 V~/=). Accessory is not CSA-certified.
A
Power consumption: at nominal voltage and with movement; for more power consumption data, see table “Power consumption for supply voltage”.
V
Accessories AVM 321, 322 Type
Description
0500570001
Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122
0510600001
Cable module, 1.2 m, 3-wire, PVC
0510600002
Cable module, 1.2 m, 3-wire, halogen-free
0510600003
Cable module, 1.2 m, 6-wire, PVC
0510600004
Cable module, 1.2 m, 6-wire, halogen-free
0510600005
Cable module, 5 m, 3-wire, PVC
0510600006
Cable module, 5 m, 3-wire, halogen-free
0510600007
Cable module, 5 m, 6-wire, PVC
0510600008
Cable module, 5 m, 6-wire, halogen-free
AVM 321 Type
Description
0372249001
Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50
0372249002
Adaptor required when temperature of the medium is 130...150 °C, DN 15...50
0510480003
Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke
AVM 322 Type
Description
0372336180
Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)
0372336240
Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)
0510240012
Mounting set for SAUTER V6** / B6** and VX*/BX* valves with 14 mm stroke for AVM322(S)
0510390006
Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)
0510390007
Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)
0510390008
Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)
0510390009
Mounting set for LDM valves up to 20 mm stroke for AVM322(S)
0510390010
Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)
Right of amendment reserved © 2024 Fr. Sauter AG
239
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Description
0510390012
Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)
0510390028
Adapter set for non-SAUTER valves (Frese), stroke 20 mm
0510480004
Double auxiliary contact
A
Accessory is not CSA-certified.
V
240
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 321S, 322S: Valve actuator Features • In ventilation and air conditioning units for actuating 2- and 3-way valves of type series AVM 321S:
VUD, VUE, VUN, BUD, BUE, BUN and AVM 322S: V6R, VQD, VQE, VUG, VUP, VUS, B6R, BQD, BQE, BUG, BUS For controllers with constant output (0...10 V / 4...20 mA) or switching output (2-point or 3-point control) • • BLDC motor (brushless DC) with SUT (SAUTER Universal Technology) electronic control unit of the third
generation and electronic load-dependent cut-off • Automatic detection of applied control signal (continuous or switching), operating indicator using bi-colour
LED • Automatic adaptation to the stroke of the valve, between 8 and 20 mm
AVM32*SF132
• Low operating noise
V
• With the built-in absolute distance measurement system, the position is always maintained in the case of
power failure The direction of operation, characteristic (linear/equal percentage), running time and control signal • (voltage/current) can be adjusted via coding switches • Integrated forced operation can be set via coding switches (with selectable direction of operation) • Easy re-initialisation using a coding switch • Crank handle for external manual adjustment with motor cut-off • Simple assembly onto valve; spindle is automatically connected after control voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Electrical parallel operation of five actuators • Parameterisation option via the BUS interface • Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Mounting column made of aluminium • Fixing bracket made of cast light alloy for valve fitting with 20 mm stroke and made of plastic for valve
fitting with 8 mm stroke • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable glands made of plastic M20 × 1.5 • Fitting vertically upright to horizontal, not suspended • Nominal actuating power 1000 N
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption1)
±20%, 50...60 Hz −10...20% ±15% < 1.7 W, < 3.5 VA (at nominal voltage, with movement)
Nominal force2) Operating noise3) Response time
1000 N < 30 dB (A) at nominal force > 200 ms
Parameters
1)
2)
3)
For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V, 25 °C ambient temperature, 50 Hz). With boundary conditions (19.2 V~ / 28.8 V~ / 21.6 V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and running time, the actuating/tensile force is minimised to 800 N Noise level at the slowest running time, measuring distance 1 m
Right of amendment reserved © 2024 Fr. Sauter AG
241
Valves, control valves, dampers, actuators | Regulating valves and valve actuators 0...100 °C
Media temperature4) Nominal voltage Characteristic Control signal y5)
Linear/equal percentage 0...10 V, Ri ≥ 50 kΩ 4...20 mA, Ri ≤ 50 Ω 0...10 V, load ≥ 5 kΩ 0 or 10 V 4 or 20 mA 10 V 16 mA 160 mV 0.22 mA
Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Control span ΔI Hysteresis Xsh
Ambient conditions
V
Operating temperature Storage and transport temperature Air humidity without condensation
−10...55 °C −40...80 °C 5...85% rh
Type of protection Protection class EMC Directive 2014/30/EU
IP54 (EN 60529) III (EN 60730-1), EN 60730-2-14 EN 610000-6-1, EN 610000-6-2, EN 610000-6-3, EN 610000-6-4 EN 60730-1, EN 60730-2-14 (AVM32*F110 and F120) III II 2000 m EN ISO 12100:2018
Standards, directives
CE conformity according to
Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)
Overview of types Type
Voltage
Nominal stroke
Running time
Dimensions W × H × D
Weight
AVM321SF132
24 V~/=
8 mm
12 (4) s/mm
160 × 187 × 88 mm
1.5 kg
AVM322SF132
24 V~/=
20 mm
6 (4) s/mm
160 × 241 × 88 mm
1.6 kg
A
CSA-certified actuators on request (only for devices with supply voltage 24 V~/=). Accessory is not CSA-certified.
Accessories AVM 321S, 322S Type
Description
0500570003
Constant 230 V module for valve actuators AVM321S and AVM322S
0500420001
Split-range unit module for setting sequences for valve actuators AVM321S and AVM322S
0500420002
4...20 mA feedback module
0500570001
Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122
0510600001
Cable module, 1.2 m, 3-wire, PVC
0510600002
Cable module, 1.2 m, 3-wire, halogen-free
0510600003
Cable module, 1.2 m, 6-wire, PVC
0510600004
Cable module, 1.2 m, 6-wire, halogen-free
0510600005
Cable module, 5 m, 3-wire, PVC
0510600006
Cable module, 5 m, 3-wire, halogen-free
4)
5)
242
At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater) Positional feedback signal: also for 2- or 3-point, depending on type of connection
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Description
0510600007
Cable module, 5 m, 6-wire, PVC
0510600008
Cable module, 5 m, 6-wire, halogen-free
AVM 321S Type
Description
0372249001
Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50
0372249002
Adaptor required when temperature of the medium is 130...150 °C, DN 15...50
0510480003
Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke
AVM 322S Type
Description
0500240001
Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)
0500240002
Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)
0510240012
Mounting set for SAUTER V6** / B6** and VX*/BX* valves with 14 mm stroke for AVM322(S)
0510390006
Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)
0510390007
Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)
0510390008
Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)
0510390009
Mounting set for LDM valves up to 20 mm stroke for AVM322(S)
0510390010
Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)
0510390012
Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)
0510390028
Adapter set for non-SAUTER valves (Frese), stroke 20 mm
0510480004
Double auxiliary contact
A A
V
Accessory is not CSA-certified. The CASE Components configuration tool can be downloaded from the CASE Suite product page (GZS 100, 150) on the SAUTER homepage.
Right of amendment reserved © 2024 Fr. Sauter AG
243
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 322-R: Retrofit actuator Features • In ventilation and air conditioning units
1)
For actuation of 2- and 3-way valves
• For controllers with a switching output (2-point or 3-point control) • Synchronous motor with electronic control unit and load-dependent cut-off
AVM322F12*R
• Direction of operation and positioning time can be set using coding switches • Crank handle for external manual adjustment with motor cut-off • Low operating noise • Simple assembly onto valve; spindle is automatically connected after nominal voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Electrical parallel operation of five actuators
V
• Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable gland made of plastic M20 × 1.5 • Fitting position vertically upright to horizontal, not suspended
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption2)
±20%, 50...60 Hz -10...20% ±15% < 2.4 W, < 4.0 VA (at nominal voltage, with movement)
Nominal force3) Operating noise4) Response time Media temperature5)
1000 N < 30 dB (A) at nominal force > 200 ms 0...100 °C max.
Operating temperature Storage and transport temperature Humidity without condensation
-10...55 °C -40...80 °C 5...85% rh
Dimensions W × H × D Weight
160 × 114 × 88 0.94
Type of protection Protection class
IP54 (EN 60529) II (EN 60730), III (EN 60730)
Parameters
Ambient conditions
Construction
Standards and directives
1) 2)
3)
4) 5)
244
To be used outside HVAC applications only after consultation with the manufacturer For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V or 230 V, 25 °C ambient temperature, 50 Hz). With boundary conditions (19.2 V~ / 28.8 V~ / 21.6 V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and positioning time, the actuating/tensile force is minimised to 800 N Operating noise with the slowest positioning time, measuring distance 1 m At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater)
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)
EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 (AVM322F120R) III II 2,000 m EN ISO 12100:2018
Overview of types Type
Voltage
Nominal stroke
Running time
Power consumption
AVM322F120R
230 V~
20 mm
6 (12) s/mm
< 2.4 W, < 4.0 VA
AVM322F122R
24 V~/=
20 mm
6 (12) s/mm
< 2.4 W, < 4.0 VA
A
V
Power consumption: at nominal voltage and with movement; for more power consumption data, see table “Power consumption for supply voltage”
Accessories Type
Description
0500240001
Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)
0500240002
Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)
0500570001
Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122
0510390020
Mounting set for SAUTER VU*/BU* and VQ*/BQ* valves with 20 mm stroke for AVM322(S)***R
0510390021
Mounting set for SAUTER V6*/B6* and VX*/BX* valves with 14 mm stroke for AVM322(S)***R
0510390022
Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)***R
0510390023
Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)***R
0510390024
Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)***R
0510390025
Mounting set for LDM valves up to 20 mm stroke for AVM322(S)***R
0510390026
Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)***R
0510390027
Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)***R
0510390028
Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM322(S)***R
0510390041
Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM322(S)***R
0510390061
Mounting set for Schneider V241/V341 valves, DN 15 to DN 50 for AVM322(S)***R
0510480004
Dual auxiliary switch unit
Right of amendment reserved © 2024 Fr. Sauter AG
245
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 322S-R: Retrofit actuator Features • In ventilation and air conditioning units
1)
For actuation of 2- and 3-way valves
• For controllers with constant output (0...10 V / 4...20 mA) or switching output (2-point or 3-point control) • BLDC motor (brushless DC) with SUT (SAUTER Universal Technology) electronic control unit of the third
AVM322SF132R
generation and electronic load-dependent cut-off • Automatic detection of applied control signal (continuous or switching), operating indicator using bi-colour
LED • Automatic adaptation to the stroke of the valve, between 8 and 20 mm • Low operating noise • With the built-in absolute distance measurement system, the position is always maintained in the case of
power failure • The direction of operation, characteristic (linear/equal percentage), positioning time and control signal (voltage/current) can be adjusted via coding switches Integrated forced operation can be set via coding switches (with selectable direction of operation) •
V
• Easy re-initialisation using a coding switch • Crank handle for external manual adjustment with motor cut-off • Simple assembly onto valve; spindle is automatically connected after control voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Electrical parallel operation of five actuators • Parameterisation option via the BUS interface • Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable glands made of plastic M20 × 1.5 • Fitting position vertically upright to horizontal, not suspended • Nominal actuating power 1000 N
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption2)
±20%, 50...60 Hz -10...20% ±15% < 1.7 W, < 3.5 VA (at nominal voltage, with movement)
Positioning time (s/mm) Nominal force3) Nominal stroke Operating noise4) Response time Media temperature5)
6 (4) 1000 N 20 mm < 30 dB (A) at nominal force > 200 ms 0...100 °C
Parameters
1) 2)
3)
4) 5)
246
To be used outside HVAC applications only after consultation with the manufacturer For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V, 25 °C ambient temperature, 50 Hz); With boundary conditions (19.2 V~ / 28.8 V~ / 21.6 V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and positioning time, the actuating/tensile force is minimised to 800 N Noise level with the slowest positioning time, measuring distance 1m At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater)
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Nominal voltage Characteristic Control signal y6)
24 V~/= Linear/equal percentage 0...10 V, Ri ≥ 50 kΩ 4...20 mA, Ri ≤ 50 Ω 0...10 V, load ≥ 5 kΩ 0 or 10 V 4 or 20 mA 10 V 16 mA 160 mV 0.22 mA
Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Control span ΔI Hysteresis Xsh
Ambient conditions
Operating temperature Storage and transport temperature Air humidity without condensation
-10...55 °C -40...80 °C 5...85% rh
Dimensions W × H × D Weight
160 × 114 × 88 0.94
Type of protection Protection class EMC Directive 2014/30/EU
IP54 (EN 60529) II (EN 60730-1), EN 60730-2-14 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 III II 2,000 m EN ISO 12100:2018
V
Construction
Standards and directives
CE conformity according to
Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)
Overview of types Type
Voltage
AVM322SF132R 24 V~/=
Nominal stroke
Running time
Power consumption
20 mm
6 (4) s/mm
< 1.7 W, < 3.5 VA
Accessories Type
Description
0500240001
Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)
0500240002
Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)
0500420001
Split-range unit module for setting sequences for valve actuators AVM321S and AVM322S
0500420002
4…20 mA feedback module for valve actuators AVM321S and AVM322S
0500570001
Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122
0500570003
Constant 230 V module for valve actuators AVM321S and AVM322S
0510390020
Mounting set for SAUTER VU*/BU* and VQ*/BQ* valves with 20 mm stroke for AVM322(S)***R
0510390021
Mounting set for SAUTER V6*/B6* and VX*/BX* valves with 14 mm stroke for AVM322(S)***R
0510390022
Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)***R
0510390023
Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)***R
0510390024
Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)***R
0510390025
Mounting set for LDM valves up to 20 mm stroke for AVM322(S)***R
0510390026
Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)***R
0510390027
Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)***R
0510390028
Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM322(S)***R
6)
Positional feedback signal: also for 2- or 3-point, depending on type of connection
Right of amendment reserved © 2024 Fr. Sauter AG
247
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type
Description
0510390041
Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM322(S)***R
0510390061
Mounting set for Schneider V241/V341 valves, DN 15 to DN 50 for AVM322(S)***R
0510480004
Dual auxiliary switch unit
A A
Accessory is not CSA-certified. The CASE Components configuration tool can be downloaded from the CASE Suite product page (GZS 100, 150) on the SAUTER homepage.
V
248
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVM 234S: SUT valve actuator with positioner Features • Activation of 2-way and 3-way valves of the VQD/BQD and VQE/BQE series, as well as VUG/BUG,
VUS/BUS, VUP, V6R/B6R and VDL • For controllers with constant output (0...10 V or 4...20 mA) or switching output (2-point or 3-point control) • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-
dependent cut-off • Simple assembly with valve; spindle is automatically connected after control voltage is applied (patented
system) • Automatic detection of applied control signal (constant or switched); indicated by two LEDs
AVM234SF132
• Coding switches for selecting characteristic and running time • Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator
V
• Automatic adaptation to the stroke of the valve (min. valve stroke 8 mm, max. valve stroke 49 mm). The
measured stroke is saved and is not lost even in the event of a power failure • Direction of operation can be selected via screw terminals when making the electrical connection • Crank handle for external manual adjustment with motor cut-off and as trigger for a re-initialisation • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Power supply 230 V with module or direct connection for 24 VAC / 24 VDC; continuous activation also
admissible with 230 V • Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel • Mounting column made of stainless steel; mounting bracket made of cast light alloy for fitting the valve • Electrical connections (max. 2.5 mm²) with screw terminals • Three pre-scored cable inlets for M20 × 1.5 (2×) and M16 × 1.5 • Fitting vertically upright to horizontal, not suspended
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption1)
±20%, 50…60 Hz ±15% ±15%, 50...60 Hz (with accessories) 24 VAC/24 VDC 10 W/20 VA 230 VAC (with accessories) 13 W/28 VA
Running time Actuator stroke Response time for 3-point Control signal 1 Control signal 2 Position feedback signal Starting point U0 Control span ΔU Switching range Xsh
2/4/6 s/mm 0...49 mm 200 milliseconds 0...10 V, Ri >100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V, load > 10 kΩ 0 or 10 V 10 V 300 mV
Ambient temperature Ambient humidity Media temperature2)
−10…55 °C < 95% rh, no condensation Max. 120 °C
Parameters
Positioner
ValveDim app
Ambient conditions
1) 2)
Choose transformers for this value, otherwise malfunctions may occur For higher temperatures of the medium (180 °C or 240 °C), use an adapter (see accessories)
Right of amendment reserved © 2024 Fr. Sauter AG
249
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Construction
Weight Housing Housing material
4.1 kg Two-part, yellow Flame-retardant plastic
Type of protection Protection class Over-voltage categories Degree of contamination LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA)4) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
IP66 (EN 60529) III (IEC 60730) III III EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 61000-6-2, EN 61000-6-4 EN 61000-6-2, EN 61000-6-4 EN IEC 63000:2018
Standards, directives
CE/UKCA conformity3)
V
EN IEC 63000:2018
Overview of types
/ /
Actuator for valves: VQD/BQD, VQE/BQE, VUG/BUG, VUP, VUS/BUS Actuator with mounting set (see accessories) for valves: V6R, B6R
Type
Voltage
Actuating power
Running time
Power consumption
AVM234SF132
24 VAC/DC
2500 N
2/4/6 s/mm
10 W, 20 VA
AVM234SF132-5 24 VAC/DC
2500 N
2/4/6 s/mm
10 W, 20 VA
AVM234SF132-6 24 VAC/DC
2500 N
2/4/6 s/mm
10 W, 20 VA
AVM234SF132-7 24 VAC/DC
1700 N
2/4/6 s/mm
10 W, 20 VA
Accessories Type
Description
0313529001
Split-range unit for setting sequences
Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA Type
Description
0372332001
230 V ±15%, supply voltage
0372332002
100 V ±15%, supply voltage
Auxiliary change-over contacts (2 each) 12...250 VAC Type
Description
0372333001
Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A
0372333002
Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A
Potentiometers Type
Description
0372334001
Potentiometer, 2000 Ω, 1 W, 24 V
0372334006
Potentiometer, 1000 Ω, 1 W, 24 V
Adapters for high temperatures Type
Description
0372336180
Intermediate piece (required when temperature of the medium is 130...180 °C)
0372336240
Adapter (required when temperature of the medium is 180...200 °C)
3)
4)
250
Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues EN 61000-6-2: (HF immunity limitation. Feedback signal between 80 MHz and 1000 MHz criterion B, otherwise criterion A)
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Mounting set for AVM234SF132 on SAUTER valves (no adapter needed for 0372338 002) Type
Description
0372338001
V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm
0372338002
V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm
0372338003
Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132
0372338004
Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132
Adapter set for non-SAUTER valves Type
Description
0372376010
Siemens with 20 mm stroke or 10 mm spindle diameter
0372376014
Siemens with 40 mm stroke or 14 mm spindle diameter
0372376015
Siemens VXF32, PN 10, DN 100…150; VXF22, PN 6, DN 100
0372377001
Johnson Controls DN 15…150, 14, 25, 40 mm stroke, spindle diameter 10, 12, 14 mm
0372378001
Honeywell with 20 mm stroke
0372378002
Honeywell with 38 mm stroke
0372386001
LDM type RY113 R/M
0372389001
ITT-Dräger, DN 15…32
0372389002
ITT-Dräger, DN 40…50
0378263001
End stop (needed for V/BXD, V/BXE DN 15…50, V/B6 DN 15 with kvs ≤ 1 m³/h)
0386263001
Cable gland M16 × 1.5
0386263002
Cable gland M20 × 1.5
0372461001
Forced operation for AV×2×4S
0372387001
SAUTER Satchwell VZF1727 mounting set
0510390052
Adapter set for non-SAUTER valves (Frese), stroke 20 mm
0510390053
Adapter set for non-SAUTER valves (Frese), stroke 40/43 mm
A
V
Adapter: Not needed for version AV*2*4SF132-6
Right of amendment reserved © 2024 Fr. Sauter AG
251
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVF 124: Valve actuator with spring return Features • Activation of 2- and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series, DN 15 to DN 50. • For controllers with a switching output (3-point control) • Spring return moves the unit to the end position in the event of a power failure or when a limit controller is
activated • Stepping motor with electronic control unit and electronic, force-dependent cut-off • Maintenance-free gear unit
AVF124F130
• LED display • Coding switch for changing the running time • Electrical connections (max. 1.5 mm²) with screw terminals
V
• Cable inlet M20 × 1.5
AVF124F130
• Fitting vertically upright to horizontal, not suspended
Technical data Power supply
AVF124F230
Power supply Power consumption
230 V~, ±15%, 50...60 Hz 4 W, 7.6 VA
Running time of motor Running time of spring Actuating power Actuator stroke Response time
60/120 s 18 s ±10 500 N 0...8 mm 200 ms
Ambient temperature Media temperature Ambient humidity
5...60 °C Max. 100 °C < 95% rh, no condensation
Weight Housing Housing material Materials for gearbox and fitting bracket
2.4 kg Lower section black, cover transparent Fire-retardant plastic Pressure-cast zinc
Type of protection1) Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Software Mode of operation
IP54 as per EN 60529 II (IEC 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III III A (EN 60730) Type 1 AA (200 ms, EN 60730)
Parameters
Ambient conditions
Construction
Standards and directives
Overview of types Type
Voltage
Nominal stroke
Running time
Power consumption Reset function
AVF124F130
230 V~
8 mm
60/120 s
4 W, 7.6 VA
Spindle retracted
AVF124F230
230 V~
8 mm
60/120 s
4 W, 7.6 VA
Spindle extended
1)
252
Type of protection IP54 only with cable gland
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
A A
AVF124F130: Valve normally closed (NC) with: VUD, BUD, VUE, BUE, VUN, BUN AVF124F230: Valve normally open (NO) with: VUD, BUD, VUE, BUE, VUN, BUN
Accessories Type
Description
0370881001
Auxiliary change-over contacts, single
0372249001
Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C
0372249002
Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 130… 150 °C
0372460001
Cable screw fitting (plastic M20 × 1,5) incl. locking nut and seal
A
Auxiliary change-over contacts: Infinitely variable, admissible load 2(1) A, 12...250 V~, min. load 250 mA, 12 V~
V
Right of amendment reserved © 2024 Fr. Sauter AG
253
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVF 125S: SUT valve actuator with spring return Features • Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series • For controllers with switching (2- and 3-point) or continuous output (0…10 V, 4…20 mA) • Spring return moves the unit to the end position in the event of a power failure or when a limit controller is
activated • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic,
force-dependent cut-off AVF125SF132
• Automatic recognition of applied control signal (continuous or switched) • Coding switches for selecting characteristic and running time • Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator • Direction of operation can be selected via screw terminals when making the electrical connection
V
• Maintenance-free gear unit
AVF125SF132
• LED display • Electrical connections (max. 1.5 mm²) with screw terminals • Cable inlet M20 × 1.5 • Fitting vertically upright to horizontal, not suspended
AVF125SF232
Technical data Power supply
Power supply Power consumption Power consumption on starting1)
24 V~, ±20%, 50...60 Hz 5 W, 8.4 VA 30 VA (max. 1 s)
Running time of motor Running time of spring Actuating power Actuator stroke Control signal 1 Control signal 2 Positional feedback signal Starting point U0 Control span ΔU Switching range Xsh
60/120 s 18 s ±10 500 N 0...8 mm 0...10 V, Ri = 100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V; load > 2.5 kΩ 0 or 10 V 10 V 200 mV
Ambient temperature Ambient humidity Media temperature
–10...55 °C < 95% rh, no condensation Max. 100 °C
Weight Housing Housing material Materials for gearbox and fitting bracket
2.4 kg Lower section black, cover transparent Fire-retardant plastic Pressure-cast zinc
Type of protection2) Protection class
IP54 as per EN 60529 III (IEC 60730)
Parameters
Positioner
Ambient conditions
Construction
Standards and directives
1) 2)
254
Only in the event of a restart or after a spring return Type of protection IP54 only with M20 cable gland
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators EMC Directive 2014/30/EU Software Mode of operation Machinery Directive 2006/42/EC (according to Appendix II, 1B)
EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 A (EN 60730) Type 1 AA (200 ms, EN 60730) EN ISO 12100:2018
Overview of types
/
For valves with equal-percentage characteristic; can be changed to linear
Type
Voltage
Nominal stroke
Running time
Power consumption Reset function
AVF125SF132
24 V~
8 mm
60/120 s
5 W, 8.4 VA
Spindle retracted
AVF125SF232
24 V~
8 mm
60/120 s
5 W, 8.4 VA
Spindle extended
A
AVF125SF132: Actuator spindle normally retracted; valve normally closed (NC) with: VUD, BUD, VUE, BUE, VUN, BUN
A
AVF125SF232: Actuator spindle normally extended; valve normally open (NO) with: VUD, BUD, VUE, BUE, VUN, BUN
V
Accessories Type
Description
0313529001
Split-range unit for adjusting sequences, fitted in separate junction box
0370881001
Auxiliary change-over contacts, single
0372249001
Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C
0372249002
Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 130… 150 °C
0372460001
Cable screw fitting (plastic M20 × 1,5) incl. locking nut and seal
A
Auxiliary change-over contacts: Infinitely variable, admissible load 2(1) A, 12...250 V~, min. load 250 mA, 12 V~
Right of amendment reserved © 2024 Fr. Sauter AG
255
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVF 234S: SUT valve actuator with spring return Features • Activation of 2-way and 3-way valves of the VQD/BQD, VQE/BQE, VUG/BUG, VUP, VUS/BUS and
V6R/B6R series • For controllers with switching (2- and 3-point) and continuous (0...10 V, 4...20 mA) output • Spring return moves to end position in the event of a power failure/interruption or when a limit controller is
activated • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-
AVF234SF132
dependent cut-off • Simple assembly with valve; spindle is automatically connected after control voltage is applied (patented
system) • Automatic detection of applied control signal (constant or switched); indicated by two LEDs • Coding switches for selecting characteristic and running time
V
• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator
AVF234SF132
• Automatic adaptation to the stroke of the valve (min. valve stroke 8 mm, max. valve stroke 49 mm). The
measured stroke is saved and is not lost even in the event of a power failure • Direction of operation can be selected via screw terminals when making the electrical connection • Crank handle for external manual adjustment with motor cut-off and as trigger for a re-initialisation • Numerous adapters enable the unit to be fitted onto non-SAUTER valves
AVF234SF232
• Power supply 230 V with module or direct connection for 24 VAC or 24 VDC; continuous activation also
admissible with 230 V Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel • • Spring pack and mounting column made of stainless steel; mounting bracket made of cast light alloy for
valve fitting Electrical connections (max. 2.5 mm²) with screw terminals • • Three pre-scored cable inlets for M20 × 1.5 (2×) and M16 × 1.5 • Fitting vertically upright to horizontal, not suspended
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption1)
±20%, 50...60 Hz ±15% ±15%, 50...60 Hz (with accessories) 24 VAC/24 VDC 10 W, 20 VA 230 VAC (with accessories) 13 W/28 VA
Running time of motor Running time of spring2) Actuating power Response time for 3-point Number of spring returns Control signal 1 Control signal 2 Positional feedback 0...10 V Starting point U0 Control span ΔU Switching range Xsh
2/4/6 s/mm 15...30 s 2000 N 200 ms > 40 000 0...10 V, Ri = 100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V, load > 10 kΩ 0 V or 10 V 10 V 300 mV
Parameters
ValveDim app
Positioner
1) 2)
256
Choose transformers for this value, otherwise malfunctions may occur Return time equates to a stroke of 14...40 mm and does not depend on the set running time
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Ambient conditions
Ambient temperature Ambient humidity Media temperature3)
−10...55 °C < 95% rh, no condensation Max. 130 °C (180 °C or 240 °C with accessories)
Weight Housing Housing material
5.6 kg Two-part, yellow Flame-retardant plastic
Type of protection Protection class Over-voltage categories Degree of contamination LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA)5) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
IP66 (EN 60529) III (IEC 60730) III III EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 61000-6-2, EN 61000-6-4 EN 61000-6-2, EN 61000-6-4 EN IEC 63000:2018
Construction
Standards, directives
CE/UKCA conformity4)
V
EN IEC 63000:2018
Overview of types Type
Voltage
Stroke
Running time
Power consumption Direction of operation of spring
AVF234SF132
24 VAC/DC
14...40 mm
2/4/6 s/mm
10 W, 20 VA
Spindle retracted
AVF234SF132-5 24 VAC/DC
14 mm
2/4/6 s/mm
10 W, 20 VA
Spindle retracted
AVF234SF232
0...40 mm
2/4/6 s/mm
10 W, 20 VA
Spindle extended
24 VAC/DC
A
AVF234SF132: Valve normally closed (NC) with: VQD/BQD, VQE/BQE, VUG/BUG, BUS; valve normally open (NO) with: VUS, VUP
A A
AVF234SF132-5: Valve normally closed (NC) with: V6R, B6R AVF234SF232: Valve normally open (NO) with: VQD/BQD, VQE/BQE, VUG/BUG, BUS; valve normally closed (NC) with: VUS, VUP
Accessories Type
Description
0313529001
Split-range unit for setting sequences
Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA Type
Description
0372332001
230 V ±15%, supply voltage
0372332002
100 V ±15%, supply voltage
Auxiliary change-over contacts (2 each) 12...250 VAC Type
Description
0372333001
Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A
0372333002
Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A
3) 4) 5)
An adapter is needed for higher temperatures (180 °C or 240 °C) (see accessories) Explanation of abbreviations in “Additional technical data” section EN 61000-6-2: HF immunity, limitation of feedback signal between 80 MHz and 1000 MHz criterion B, otherwise criterion A
Right of amendment reserved © 2024 Fr. Sauter AG
257
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Potentiometers Type
Description
0372334001
Potentiometer, 2000 Ω, 1 W, 24 V
0372334006
Potentiometer, 1000 Ω, 1 W, 24 V
Adapters for high temperatures Type
Description
0372336180
Intermediate piece (required when temperature of the medium is 130...180 °C)
0372336240
Adapter (required when temperature of the medium is 180...200 °C)
Mounting set for AVF234SF*32 onto SAUTER valves (no adapter needed for 0372338 002)
V
Type
Description
0372338001
V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm
0372338002
V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm
0372338003
Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132
0372338004
Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132
Adapter set for non-SAUTER valves Type
Description
0372376010
Siemens with 20 mm stroke or 10 mm spindle diameter
0372376014
Siemens with 40 mm stroke or 14 mm spindle diameter
0372376015
Siemens VXF32, PN 10, DN 100…150; VXF22, PN 6, DN 100
0372377001
Johnson Controls DN 15…150, 14, 25, 40 mm stroke, spindle diameter 10, 12, 14 mm
0372378001
Honeywell with 20 mm stroke
0372378002
Honeywell with 38 mm stroke
0372386001
LDM type RY113 R/M
0372389001
ITT-Dräger, DN 15…32
0372389002
ITT-Dräger, DN 40…50
0378263001
End stop (needed for V/BXD, V/BXE DN 15…50, V/B6 DN 15 with kvs ≤ 1 m³/h)
0386263001
Cable gland M16 × 1.5
0386263002
Cable gland M20 × 1.5
0372387001
SAUTER Satchwell VZF1727 mounting set
0372461001
Forced operation for AV×2×4S
0510390052
Adapter set for non-SAUTER valves (Frese), stroke 20 mm
0510390053
Adapter set for non-SAUTER valves (Frese), stroke 40/43 mm
A A
258
Adapter: Not needed for version AV*2*4SF132-6 Potentiometer 130 Ω: This potentiometer must only be used as a voltage divider.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators
AVN 224S: SUT valve actuator with safety function Features • Actuation of 2-way or 3-way valves of type series VUG/BUG and VUP as per DIN EN 14597 • For controllers with constant output (0...10 V or 4...20 mA) and switching output (2-point or 3-point control) • Valve actuator with safety function (as per DIN EN 14597) and pushing force of 1100 N, in normally
closed (NC) or normally open (NO) version • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-
dependent cut-off • Simple assembly with valve; spindle is automatically connected after control voltage is applied (patented
system) • Automatic recognition of applied control signal (constant or switched); indicated by two LEDs
AVN224SF132
• Coding switches for selecting characteristic and running time
V
• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator • Automatic adaptation to the valve stroke (min. valve stroke 8 mm, max. valve stroke 49 mm); the measured
stroke is stored and is not lost in the event of a power failure • Direction of operation can be selected via screw terminals when making the electrical connection
AVN224SF132
• Push-buttons on outside of housing for manual adjustment with motor cut-off and as trigger for re-
initialisation • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel
AVN224SF232
• Spring pack and mounting column made of stainless steel; mounting bracket made of cast light alloy for valve fitting Electrical connections (max. 2.5 mm2) with screw terminals • • Three break-out cable inlets for M20 × 1.5 (2×) and M16 × 1.5 • Fitting vertically upright to horizontal, not suspended
The following features and certifications do not apply to the United Kingdom of Great Britain and Northern Ireland (UK): • TÜV certification
The product is not designed for use in the United Kingdom. Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption
±20%, 50...60 Hz ±15% ±15%, 50...60 Hz (with accessories) 24 VAC/24 VDC 10 W, 18 VA 230 VAC (with accessories) 11 W / 24 VA
Running time of motor Running time of spring1) Actuating power Number of spring returns Response time for 3-point Control signal 1 Control signal 2 Position feedback signal Starting point U0 Control span ΔU
2/4/6 s/mm 15...30 s 1100 N > 40 000 200 ms 0...10 V, Ri = 100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V, load > 10 kΩ 0 V or 10 V 10 V
Parameters
Positioner
1)
ValveDim app
Spring return time equates to a stroke of 14...40 mm and does not depend on the set running time
Right of amendment reserved © 2024 Fr. Sauter AG
259
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Switching range Xsh
300 mV
Ambient temperature Ambient humidity Media temperature
−10...55 °C < 95% rh, no condensation Max. 130 °C
Weight Housing Housing material
5.6 kg Two-part, yellow Flame-retardant plastic
Type of protection Protection class EMC Directive 2014/30/EU2) Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination PED 2014/68/EU, cat. IV3)
IP66 (EN 60529) III (IEC 60730) EN 61000-6-2, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III III Category IV, fluid group II, liquid or steam pressure modules B+D TÜV ID: 18388
Ambient conditions
Construction
Standards, directives
V
Test mark4)
Overview of types Type
Voltage
Nominal stroke
Running time
Power consumption Direction of operation of spring
AVN224SF132
24 VAC/DC
40 mm
2/4/6 s/mm
10 W, 18 VA
Spindle retracted
AVN224SF232
24 VAC/DC
40 mm
2/4/6 s/mm
10 W, 18 VA
Spindle extended
A
AVN224SF132: Valve normally closed (NC) with: VUG, BUG (as per DIN EN 14597); valve normally open (NO) with: VUP
A
AVN224SF232: Valve normally open (NO) with: VUG, BUG; valve normally closed (NC) with: VUP (as per DIN EN 14597)
Accessories Type
Description
0313529001
Split-range unit for setting sequences
Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA Type
Description
0372332001
230 V ±15%, supply voltage
0372332002
100 V ±15%, supply voltage
Auxiliary change-over contacts (2 each) 12...250 VAC Type
Description
0372333001
Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A
0372333002
Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A
Potentiometers Type
Description
0372334001
Potentiometer, 2000 Ω, 1 W, 24 V
0372334006
Potentiometer, 1000 Ω, 1 W, 24 V
2)
3) 4)
260
EN 61000-6-2: HF immunity, limitation of feedback signal between 80 MHz and 1000 MHz criterion B, otherwise criterion A Only for VUP, VUG and BUG valves. See PDS for the valves. For the United Kingdom of Great Britain and Northern Ireland (UK): Use is not permitted.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Regulating valves and valve actuators Adapters for high temperatures Type
Description
0372336180
Intermediate piece (required when temperature of the medium is 130...180 °C)
0372336240
Adapter (required when temperature of the medium is 180...200 °C)
Mounting set for AVN224SF*32 onto SAUTER valves (no adapter needed for 0372338 002) Type
Description
0372338001
V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm
0372338002
V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm
0372338003
Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132
0372338004
Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132
Adapter set for non-SAUTER valves Type
Description
0372376010
Siemens with 20 mm stroke or 10 mm spindle diameter
0372376014
Siemens with 40 mm stroke or 14 mm spindle diameter
0372377001
Johnson Controls DN 15…150, 14, 25, 40 mm stroke, spindle diameter 10, 12, 14 mm
0372378001
Honeywell with 20 mm stroke
0372378002
Honeywell with 38 mm stroke
0372386001
LDM type RY113 R/M
0372389001
ITT-Dräger, DN 15…32
0372389002
ITT-Dräger, DN 40…50
0378263001
End stop (needed for V/BXD, V/BXE DN 15…50, V/B6 DN 15 with kvs ≤ 1 m³/h)
0386263001
Cable gland M16 × 1.5
0386263002
Cable gland M20 × 1.5
0372387001
SAUTER Satchwell VZF1727 mounting set
0372461001
Forced operation for AVx2xS
0510390052
Adapter set for non-SAUTER valves (Frese), stroke 20 mm
0510390053
Adapter set for non-SAUTER valves (Frese), stroke 40/43 mm
A A
V
Adapter: Not needed for version AV*2*4SF132-6 Potentiometer 130 Ω: This potentiometer must only be used as a voltage divider.
Right of amendment reserved © 2024 Fr. Sauter AG
261
Dynamic regulating valves The automatic hydronic balancing of water distribution networks using dynamic SAUTER valves provides correct supply to air-conditioning, cooling and heating devices. These include fan coil units, chilled ceilings, central underfloor heating systems, remote heating, air recirculation devices and plant segments. SAUTER Valveco and eValveco prevent under- or oversupply and the resulting temperature variations caused by pressure changes in the distribution network.
Overview of dynamic regulating valves
Type designation Application Preheater for ventilation / air-conditioning, cooler Chilled ceiling, underfloor heating Static heating District heating Version 2-way 3-way 6-way Female thread Male thread Flange Temperature measurement Electronic control Nominal pressure Communication Interfaces Protocols Combination options with actuator Further information
262
UVC 106 eValveco
UVC102MF065…100 eValveco
−
•
• − −
− • −
− − • − • − • • PN 16
• − − − − • • • PN 16
− Modbus RTU, BACnet MS/TP integrated
Bluetooth Modbus RTU, BACnet MS/TP integrated
Page 264
Page 266
Right of amendment reserved © 2024 Fr. Sauter AG
Type designation
VDL 010…032 Valveco compact
VDL 040, 050 Valveco compact
VDL 050…100 Valveco flange
•
•
•
• • −
• • −
− • •
• − − − • − − − PN 25 AXM 217(S) AXT 301, 311, AXS 315S AXF 217S, AVM 215(S) Page 269
• − − • − − − − PN 25 AXM 217(S) AXT 301, 311, AXS 315S AXF 217S, AVM 215(S) Page 269
• − − − − • − − PN 16 AVM 215, AVM 234
Application Preheater for ventilation / air-conditioning, cooler Chilled ceiling, underfloor heating Static heating District heating Version 2-way 3-way 6-way Female thread Male thread Flange Temperature measurement Electronic control Nominal pressure Combination options with actuator Further information
Right of amendment reserved © 2024 Fr. Sauter AG
Page 274
263
Valves, control valves, dampers, actuators | Multi-function valves
UVC 106: Dynamic flow control system with 6-way ball valve, eValveco Features • Patented pressure-independent, variable flow control (EP 2307938) • Integrated flow measurement with feedback • Easy integration into every building management system • Variable flow rate setpoint for heating and cooling modes • For climate ceilings with changeover (4-pipe) • Integration into the building management system via BACnet MS/TP or Modbus/RTU with RS-485 interface
UVC106MF0*5
V
UVC106BF0*5
Technical data Electronic power supply
~
Power supply Rated power during continuous operation Power consumption when idle Peak inrush current Input signal
M Feedback signal1) Feedback signal resolution
24 VAC, ±20%, 50 Hz 3 W (4 VA) 1.5 W (2 VA) 5 A [3 ms] Xs: 0…10 VDC (0.17 mA), split-range 0.5…4.5 VDC heating 5.5…9.5 VDC cooling Ri ≥ 60 kΩ Xi: 0…10 VDC (max. 2 mA) Approx. 100 mV
Parameters
Setpoint adjustment Type of sensor Unit of measurement2)
Valve and actuator
Measuring accuracy Minimum controllable flow3) Readiness for operation Nominal pressure Differential pressure ∆p4) Medium5) Media temperature Leakage rate in % of Kvs Control characteristic Operating noise (unloaded)6)
Analogue (Y1) or via Modbus/RTU or BACnet MS/TP TTM ultrasonic sensor, no moving parts [m3/h], l/s, l/min, gpm (UK), gpm (US) ±3% of actual value 3 l/h 3…5 minutes after switching on PN16 Max. 2 bar (200 kPa) Water (glycol-free) 5…90 °C 0.001 % Equal-percentage (factory setting) or linear < 30 dB (A)
ValveDim app Interfaces, communication
BMS integration
Interface Protocol Connection7) Cable type
1) 2) 3) 4) 5) 6) 7)
264
STP cable, 1 × 2-wire, twisted Modbus/RTU, slave (MF) or BACnet MS/TP (BF) RS-485, 2-core twisted (with shared lead) Shielded 2-core cable, STP or FTP
In relation to the measured actual flow. Unit in [ ]: Factory setting In relation to the measured actual flow No minimum differential pressure required In accordance with VDI 2035 sheet 2 Measuring distance 1 m, actuator not under load Not electrically isolated
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Multi-function valves Baud rate8) Terminating resistor
9600, 19200, 38400 baud At both ends 120 Ω
Power cable
PVC cable, 7 × 0.5 mm2 (length 1 m) Flow sensor: ABS Actuator: Flame retardant plastic 6-way ball valve: CW617N Flow meter: CW617N DN 15 ISO228/1: 5 × G½" + 1 × G¾" (male thread) DN 25 ISO228/1: 6 × G1" (male thread)
Construction
Housing material
Connection
Ambient conditions
Ambient temperature Storage temperature Ambient humidity
10…45 °C −20…50 °C Max. 85% rh, non-condensing
Type of protection9) EMC Directive 2014/30/EU
IP54 (EN 60529), horizontal EN 61000-6-1 (2007) EN 61000-6-3 (2007) (A1: 2011 / AC: 2012) Fluid group II, no CE label (Art. 4.3)
V
Standards and directives
CE conformity according to
PED 2014/68/EU
Overview of types Type
Description
Kvs value
Weight
UVC106MF015
Flow control valve with 6-way ball Modbus/RTU 0...1400 l/h valve, DN 15
Protocol
Flow range
1.4 m3
2.5 kg
UVC106BF015
Flow control valve with 6-way ball BACnet MS/TP 0...1400 l/h valve, DN 15
1.4 m3
2.5 kg
UVC106MF025
Flow control valve with 6-way ball Modbus/RTU 0...2500 l/h valve, DN 25
2.5 m3
4 kg
UVC106BF025
Flow control valve with 6-way ball BACnet MS/TP 0...2500 l/h valve, DN 25
2.5 m3
4 kg
Accessories Type
Description
0560284015
Screw fitting in brass, flat-sealing, female thread/male thread for DN 15
0560284025
Screw fitting in brass, flat-sealing, female thread/male thread for DN 25
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
8) 9)
Factory setting: 38400 baud, 8 data bits, even parity, 1 stop bit See fitting instructions P100017045
Right of amendment reserved © 2024 Fr. Sauter AG
265
Valves, control valves, dampers, actuators | Multi-function valves
UVC102MF065…100: Dynamic flow control system with 2way valve and energy monitoring, eValveco Features • Patented pressure-independent variable flow control • Dynamic hydronic balancing at full and partial load • Integrated flow measurement with feedback and temperature measurement • Energy monitoring
UVC102MF065
• Remote commissioning and troubleshooting • Bluetooth interface for commissioning and maintenance via smartphone app • Available as 2-way globe valve, version DN 65...DN 100
V
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power consumption UVC102MF100
Power consumption when idle
UVC102
Input signal
M T
Feedback signal1) Additional sensor input Feedback signal resolution
~
T
±10%, 50 Hz ±10% DN 65: 6.5 W / 8 VA DN 80: 9.5 W / 11 VA DN 100: 13.5 W / 19 VA DN 65: 5.5 W / 6 VA DN 80: 8.5 W / 9 VA DN 100: 8.5 W / 9 VA Y1: 0…10 V= (0.17 mA) Ri ≥ 60 kΩ X1: 0…10 V= (max. 2 mA) Y2: 0…10 V= (0.17 mA) Approx. 100 mV
Parameters
Volume flow control
Setpoint adjustment2) Type of sensor Unit of measurement3) Readiness for operation Control characteristic4) Control accuracy Measuring accuracy
Valve
Temperature sensor
Analogue (Y1) or via Modbus RTU (can be switched to BACnet MS/TP) TTM ultrasonic sensor, no moving parts
Cable length
[m3/h], l/s, l/min, gpm (UK) 5…10 min. after switching on [Equal percentage] or linear 5% of setpoint ±3% (in relation to the measured actual flow) 4 s/mm PN 16 (16 bar) Water (glycol-free) According to VDI 2035 5…130 °C Class III as per DIN EN 60534-4 (0.001 × kvs) 2 × Pt1000 as per EN 60751, class B 2 m per sensor
Wireless
Bluetooth (max. range 10 m)
Actuator running time Nominal pressure Medium Media quality Media temperature5) Leakage rate Type of sensor
Interfaces, communication
ValveDim app 1) 2) 3) 4) 5)
266
In relation to the measured actual flow In relation to the measured actual flow Factory setting in [ ] Factory setting in [ ] For media temperatures above 100 °C, use temperature adapter (DN 65 and DN 80).
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Multi-function valves Electric wiring (incl. bus connection) Protocol Connection6) Cable type Baud rate7)
Topology Terminating resistor Indicator/display
PVC cable, 7 × 0.5 mm2, cable length 2 m Modbus RTU/TCP, slave BACnet MS/TP, slave RS-485 twisted pair cable with shared lead Shielded 2-core cable, STP or FTP 9600, 19 200 or [38 400] 1 start bit Parity [even]/odd/no parity 8 data bits 1 stop bit Multi-drop bus, max. length 1000 m At both ends 120 Ω Status LEDs
V
Construction
Material of water-bearing parts
Material of flow meter housing Material of actuator housing Connections
Brass, bronze, EPDM, stainless steel (1.4401, 1.4122,1.4301), thermoplastic, ceramic Steel, polypropylene Flame-retardant plastic PN16, flange as per EN 1092-2 type 21
Ambient conditions
Operating temperature Storage and transport temperature Air humidity Maintenance / calibration Max. altitude
10…45 °C −20…50 °C 5…85% rh (non-condensing) Maintenance-free / factory calibrated 2000 m above sea level
Type of protection Protection class Measuring Instruments Directive 2014/32/EU EMC Directive 2014/30/EU
IP54 (EN 60529), horizontal III EN 1434-4:2007
Standards, directives
CE conformity according to
PED 2014/68/EU Low-Voltage Directive 2014/35/EU Pressure and temperature data Flow parameters
Volume flow sensor: EN 61000-3-2, EN 61000-3-3 EN 61000-6-1, EN 61000-6-3 AVM234: EN 61000-6-2, EN 61000-6-4 AVM322: EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 Fluid group II, no CE label AVM 322 and AVM 234 EN 60730-1, EN 60730-2-14 EN 764, EN 1333 EN 60534
Overview of types Type
Nominal diam- Volume flow range eter
Volume flow at 30 kPa pressure drop
Kvs value
Weight
UVC102MF065
DN 65
0.175…48.8 m³/h
26.7 m³/h
48.8 m³/h
37.4 kg
UVC102MF080
DN 80
0.280…70.7 m³/h
38.7 m³/h
70.7 m³/h
46.1 kg
UVC102MF100
DN 100
0.420…118.7 m³/h
65 m³/h
118.7 m³/h
69.5 kg
6) 7)
Not electrically isolated Standard factory setting in [ ]
Right of amendment reserved © 2024 Fr. Sauter AG
267
Valves, control valves, dampers, actuators | Multi-function valves Accessories UVC102MF065, UVC102MF080 Type
Description
0510480004
Dual auxiliary switch unit
0500240001
Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)
0378369101
Complete replacement stuffing box for DN 65...150
UVC102MF100
V
Type
Description
0372333001
Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A
0372333002
Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A
0378369101
Complete replacement stuffing box for DN 65...150
Flow rate DN [mm] UVC102MF065 UVC102MF080 UVC102MF100 Δp VMin
65 80 100
Kvs [m3/h] 48.8 70.7 118.7
VMin [m3/h] 0.175 0.280 0.420
V5 [m3/h] 10.9 15.8 26.5
V10 [m3/h] 15.4 22.3 37.5
V20 [m3/h] 21.8 31.6 53.0
V30 [m3/h] 26.7 38.7 65.0
VMax [m3/h] 48.8 70.7 118.7
Maximum closing pressure Minimum controllable flow
Kvs
Actual flow rate with valve fully open and 1 bar (100 kPa) pressure difference
V5
Flow range at Δp 5 kPa
V10
Flow range at Δp 10 kPa
V20
Flow range at Δp 20 kPa
V30
Flow range at Δp 30 kPa
VMax Maximum controllable flow. The maximum flow is reached at a differential pressure of 1 bar (100 kPa). The target flow can be set to a value that is equal to or less than the maximum flow
268
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Multi-function valves
VDL 010...050: 2-way regulating valve for dynamic hydronic balancing, PN 25, Valveco compact Features • Dynamic volume flow control in closed water circuits in conjunction with AXM 217(S), AXT 301, 311 or
AXS 315S unit valve actuators • Range 30…11500 l/h • Easy to preset the max. required volume flow • Automatic flow regulation • Versions with and without pressure measurement nipple • The valve is closed when the spindle is moved in
VDL015F210
• Closing procedure against the pressure
V
• Slight adaptation of the proven SAUTER actuator technology • Regulating valve with male (DN 10...DN 32) or female thread (DN 40 and DN 50) according to
DIN EN ISO 228-1 • Flat-sealing regulating valve • Differential pressure across the control unit is kept constant; valve authority 1 • Valve body and plug made of dezincification-resistant (DZR) brass • Stainless-steel spindle • Temperature range of medium 0…120 °C
Technical data Parameters
Nominal pressure Operating pressure Operating temperature Valve characteristic Leakage rate
PN 25 Max. 25 bar (up to 120 °C) 0…120 °C Linear 0.01%
Operating temperature at valve
Max. 100 °C in combination with AXM 217(S), AXT 301, 311, AXS 315S or AVM 215(S)
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 EN 60534, page 3 Fluid group II, No CE label (article 4.3)
VDL040F201
Ambient conditions
Standards, directives
Overview of types Type
Nominal Volume flow diameter range (l/h) (DN)
Control range Valve min ∆p...max stroke ∆p (kPa) (mm)
Connection / tolerance class
VDL010F200
10
65...370
14...800
5
G½" B
−
0.36
VDL010F201
10
65...370
14...800
5
G½" B
•
0.45
VDL010F210
10
30...200
14...800
2.5
G½" B
−
0.36
VDL010F211
10
30...200
14...800
2.5
G½" B
•
0.45 0.38
Pressure Weight (kg) measurement nipple
VDL015F200
15
100...575
14...800
2.5
G¾" B
−
VDL015F200H
15
220...1330
8...800
5
G¾" B
−
0.38
VDL015F201
15
100...575
14...800
2.5
G¾" B
•
0.47
VDL015F210
15
65...370
14...800
5
G¾" B
−
0.38
VDL015F201H
15
220...1330
8...800
5
G¾" B
•
0.47
VDL015F211
15
65...370
14...800
5
G¾" B
•
0.47
Right of amendment reserved © 2024 Fr. Sauter AG
ValveDim app
269
Valves, control valves, dampers, actuators | Multi-function valves
V
Type
Nominal Volume flow diameter range (l/h) (DN)
Control range Valve min ∆p...max stroke ∆p (kPa) (mm)
Connection / tolerance class
VDL015F220
15
30...200
14...800
2.5
G¾" B
−
VDL015F221
15
30...200
14...800
2.5
G¾" B
•
0.47
VDL020F200
20
220...1330
15...800
5
G1" B
−
0.4
VDL020F201
20
220...1330
15...800
5
G1" B
•
0.5
VDL020F210
20
160...990
15...800
4
G1" B
−
0.4
VDL020F210H
20
300...1800
8...800
5.5
G1" B
−
0.4
VDL020F211
20
160...990
15...800
4
G1" B
•
0.5
VDL020F211H
20
300...1800
8...800
5.5
G1" B
•
0.5
VDL020F220
20
100...575
14...800
2.5
G1" B
−
0.4
VDL020F221
20
100...575
14...800
2.5
G1" B
•
0.5
VDL025F200
25
600...3609
8...800
5.5
G 1¼" B
−
1.02
VDL025F201
25
600...3609
8...800
5.5
G 1¼" B
•
1.12
VDL025F210
25
280...1800
8...800
5.5
G 1¼" B
−
0.51
VDL025F211
25
280...1800
8...800
5.5
G 1¼" B
•
0.62
VDL032F200
32
550...4001
8...800
5.5
G 1½" B
−
1.17
VDL032F201
32
550...4001
8...800
5.5
G 1½" B
•
1.27
VDL040F201
40
1370...9500
8...800
15
G 1½" B
•
3.28
VDL050F201
50
1400...11500
8...800
15
G2" B
•
3.71
A
Pressure Weight (kg) measurement nipple
0.38
DN 10…DN 32 valves with male thread DN 40 and DN 50 valves with female thread
Accessories
270
Type
Description
0378133010
1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜
0378133015
1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½
0378133020
1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾
0378134010
1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½
0378134015
1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾
0378134020
1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0510390029
Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM215(S)F***R
0361951015
Screw fitting for male thread with flat seal, G1 - Rp½
0361951020
Screw fitting for male thread with flat seal, G1¼ - Rp¾
0361951025
Screw fitting for male thread with flat seal, G1½ - Rp1
0360391040
Screw fitting incl. seal, 2 pcs. required, Rp1½ - G1½
0360391050
Screw fitting incl. seal, 2 pcs. required, Rp2 - G2
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Multi-function valves Combination of VDL with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences with motorised actuators Actuator
AXM217F200
AXM217F202
Page
171
171
AXM217SF402 AXM217SF404 173
Voltage
230 VAC
24 VAC/DC
24 VAC/DC
Control signal
2-/3-point
2-/3-point
0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA
Laufzeit
13 s/mm
13 s/mm
8 s/mm
Closes against the pressure VDL010F200 VDL010F201 VDL010F210 VDL010F211 VDL015F200 VDL015F200H VDL015F201 VDL015F210 VDL015F201H VDL015F211 VDL015F220 VDL015F221 VDL020F200 VDL020F201 VDL020F210 VDL020F210H VDL020F211 VDL020F211H VDL020F220 VDL020F221 VDL025F210 VDL025F211 VDL025F200 VDL025F201 VDL032F200 VDL032F201
V
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
8.0
6.0
8.0
6.0
8.0
6.0
8.0
8.0
8.0
8.0
8.0
8.0
Cannot be used to close with the pressure Actuator Page
AVM215F120R 234
AVM215SF132R 237
Voltage
230 VAC
24 VAC/DC
Control signal
2-/3-pt.
0…10 V
Laufzeit
7.5 s/mm
7.5 s/mm
Closes against the pressure VDL040F201 VDL050F201
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
8.0
8.0
8.0
8.0
Cannot be used to close with the pressure
Right of amendment reserved © 2024 Fr. Sauter AG
271
Valves, control valves, dampers, actuators | Multi-function valves Pressure differences with thermal actuators Actuator
AXT301F102 AXT301F112 164
AXT301HF110
AXT301HF112
Page
AXT301F100 AXT301F110 164
164
164
Voltage
230 VAC
24 VAC/DC
230 VAC
24 VAC/DC
Control signal
2-point
2-point
2-point
2-point
Laufzeit
33 s/mm
33 s/mm
40 s/mm
40 s/mm
Closes against the ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] pressure
V
VDL010F200 VDL010F201 VDL010F210 VDL010F211 VDL015F200 VDL015F200H VDL015F201 VDL015F210 VDL015F201H VDL015F211 VDL015F220 VDL015F221 VDL020F200 VDL020F201 VDL020F210 VDL020F210H VDL020F211 VDL020F211H VDL020F220 VDL020F221 VDL025F210 VDL025F211
8.0
6.0
8.0
6.0
8.0
6.0
8.0
6.0
VDL025F200 VDL025F201 VDL032F200 VDL032F201
8.0
8.0
8.0
8.0
8.0
6.0
8.0
6.0
Cannot be used to close with the pressure
272
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Multi-function valves
A
In combination with AXT301HF110, the following valves only open up to approx. 60%, including a closing safety tolerance of 0.8 mm: VDL010F20*, VDL015F21*, VDL015F20*H, VDL020F20*, VDL020F21*, VDL020F21*H, VDL025F20*, VDL025F21*, VDL032F20*
Pressure differences with thermal, continuous actuators Actuator Page
AXS315SF102 167
AXS315SF202 167
AXT311F110 164
AXT311F112 164
Voltage
24 VAC/DC
24 VAC/DC
230 VAC
24 VAC/DC
Control signal
0…10 V
0…10 V
2-point
2-point
Laufzeit
30 s/mm
30 s/mm
52 s/mm
52 s/mm
Closes against the ∆pmax [bar] ∆ps [bar] pressure
∆pmax [bar]
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]
VDL010F200 VDL010F201 VDL010F210 VDL010F211 VDL015F200 VDL015F200H VDL015F201 VDL015F210 VDL015F201H VDL015F211 VDL015F220 VDL015F221 VDL020F200 VDL020F201 VDL020F210 VDL020F210H VDL020F211 VDL020F211H VDL020F220 VDL020F221 VDL025F210 VDL025F211
8.0
6.0
8.0
8.0
6.0
8.0
6.0
VDL025F200 VDL025F201 VDL032F200 VDL032F201
8.0
8.0
8.0
8.0
8.0
8.0
8.0
V
Cannot be used to close with the pressure
A
In combination with AXT311F11*, the white spindle extension must be removed from the following valves before fitting: VDL010F20*, VDL015F21*, VDL015F20*H, VDL020F20*, VDL020F21*H, VDL025F20*, VDL025F21*, VDL032F20*
Right of amendment reserved © 2024 Fr. Sauter AG
273
Valves, control valves, dampers, actuators | Multi-function valves
VDL 050…100: 2-way regulating valve for dynamic hydronic balancing, PN 16, Valveco flange Features • Regulating valve with three functions: Control, preset maximum volume flow, automatic flow regulation • Control of low and mean temperature domestic hot water, cooled water, water with anti-freeze in closed
circuits1) • Volume flow range: 3.7…90.9 m3/h • Easy to preset the max. required volume flow • All types with three pressure measurement nipples • The valve is closed when the spindle is moved in
V
• Closing procedure against the pressure
VDL065F501 P1
P2
• Simple connection to SAUTER actuators AVM 215 for DN 50...80 and AVM 234 for DN 100 P3
• Regulating valve with flange connection (DN 50...DN 100) according to EN ISO 7005-2 • Flat-sealing regulating valve • Differential pressure across the control unit is kept constant; valve authority 1 • Valve body DN 50…80 made of grey cast iron (GJL‑250); DN 100 made of ductile cast iron (GJS‑400) • Stainless-steel spindle
Technical data Parameters
Nominal pressure Volume flow setting range
16 bar
Maximum operating pressure Connection Valve characteristic Control ratio Leakage rate
3.7...90.9 m3/h PN 16 (EN 1333) Flange as per ISO 7005-2 Linear (VDI/VDE 2173) 1:100 Max. 0.01% of the volume flow with the valve fully open (Class IV, EN 1349)
Operating temperature for valve
1…120 °C
Pressure measurement nipple
3 pcs, G¼ inch, suitable for 2 × 40 mm probes
Pressure and temperature data Flow parameters PED 2014/68/EU2)
EN 764, EN 1333 EN 60534, page 3 Fluid group 2 as per Art. 13 Pressure equipment as per Art. 1.1 All types EAC-compliant (Eurasian conformity)
Ambient conditions
ValveDim app Construction
Standards, directives
EAC Directive
Overview of types Type
Nominal diameter (DN)
Volume flow range Control range min Valve stroke (mm) ∆p...max ∆p (kPa)
Weight (kg)
VDL050F501
50
3.7…14.3
15
VDL050F501H
50
5.7…24.6
30…600
20
15
VDL065F501
65
4.5…24.4
28…600
20
19
1) 2)
274
13…600
20
Water quality must comply with VDI 2035, water with anti-freeze permissible No special valve test required at operating temperature ≤ 110 °C. This also applies to valves with PS x DN < 1000. In both cases, the valves do not have a CE label
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Multi-function valves Type
Nominal diameter (DN)
Volume flow range Control range min Valve stroke (mm) ∆p...max ∆p (kPa)
Weight (kg)
VDL065F501H
65
6.4…37.7
19
30…600
20
VDL080F501
80
6.8…35.7
18…600
20
28
VDL080F501H
80
8.5…49.0
22…600
20
28
VDL100F501
100
12.2…69.6
18…600
40
46
VDL100F501H
100
14.8…90.9
20…600
40
46
Type VDL050F501 VDL050F501H VDL065F501 VDL065F501H VDL080F501 VDL080F501H VDL100F501 VDL100F501H
Fluid group 2
Average flow accuracy
No CE marking as per PED, Article 4.3 ± 10% of ∆pmin ± 5% up to 70 kPa at 70...600 kPa
With CE marking as per PED, Article 14.2 (conformity assessment procedure: Category I, Module A)
V
± 10% of ∆pmin ± 5% up to 105 kPa at 150...600 kPa
With CE marking as per PED, Article 14.2
Combination of VDL with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
/
Definition of ∆p min: Minimum differential pressure across the control passage of the valve for the differential pressure regulator to operate reliably.
Pressure differences Actuator Page
AVM215SF132-7 237
AVM234SF132-7 250
Voltage
24 V~/=
24 VAC/DC
Control signal
0…10 V
0…10 V
Running time
7.5 s/mm
2/4/6 s/mm
Actuating power
500 N
1700 N
Media temperature Max. 120 °C Closes against the pressure VDL050F501 VDL050F501H VDL065F501 VDL065F501H VDL080F501 VDL080F501H VDL100F501 VDL100F501H
Max. 120 °C
∆pmax [bar]
∆ps [bar]
∆pmax [bar]
∆ps [bar]
6.0
7.0
–
–
–
–
6.0
6.0
Cannot be used to close with the pressure
Right of amendment reserved © 2024 Fr. Sauter AG
275
Ball valves The body of the ball valves from SAUTER is made of top-quality DZR brass. This enables the continuous control of cold or hot water in closed circuits, such as in domestic hot water systems. The dezincification-resistant, chrome-plated brass ball with its polished surface ensures the best possible control precision.
Overview of regulating ball valves
Type designation Application Single-room control Preheater for ventilation & air-conditioning Preheater, cooler for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling Static heating Multi-boiler system Local heating Version 2-way 3-way Female thread Male thread Nominal diameter (DN) Nominal pressure Combination options with actuator
Further information
276
VKR
VKRA
BKR
BKRA
• • •
• • •
• • •
• • •
• • • • •
• • • • •
• • • • •
• • • • •
• − • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 278
• − − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 282
− • • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 286
− • − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 289
Right of amendment reserved © 2024 Fr. Sauter AG
Overview of cut-off and changeover ball valves
Type designation Application Single-room control Preheater for ventilation & air-conditioning Preheater, cooler for ventilation & air-conditioning Reheater for ventilation & air-conditioning Version 2-way 3-way Female thread Male thread Nominal diameter (DN) Nominal pressure Combination options with actuator
Further information
VKAI
VKAA
BKLI
BKTI
BKTA
• • •
• • •
• • •
• • •
• • •
•
•
•
•
•
• − • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 292
• − − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 294
− • • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 297
− • • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 300
− • − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 303
Right of amendment reserved © 2024 Fr. Sauter AG
277
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
VKR: 2-way regulating ball valve with female thread, PN 40 Features • 2-way regulating ball valve for continuous control of cold and hot water in closed circuits • In combination with valve actuators AKM 105(S), 115(S), 115SA and AKF 112, 113(S) as a control unit • Equal-percentage ball valve characteristic; control contour in the ball directly integrated • Characteristic can be set with SUT rotary actuator (SAUTER Universal Technology) to linear or quadratic
VKR040F300
• Spindle with large sliding surface and PTFE glide ring • Low torque due to collar mounted on O-ring • Ball valve with female thread as per ISO 7/1 Rp or NPT • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring
V
• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Valve characteristic Control ratio of ball valve Control ratio with actuator Leakage rate
40 bar Equal-percentage 500:1 > 50:1 Watertight as per EN 60534-4 L/1, better than class 4 90°
Angle of rotation Ambient conditions
Operating temperature1) Operating pressure
−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)
Pressure and temperature data Flow parameters
EN 764, EN 1333 EN 60534 (page 3)
Standards, directives
Overview of types Type
Nominal diameter
Connection ISO 7/1 Rp Kvs value
Weight
VKR015F350-FF
DN 15
Rp ½"
1 m³/h
0.29 kg
VKR015F340-FF
DN 15
Rp ½"
1.6 m³/h
0.29 kg
VKR015F330-FF
DN 15
Rp ½"
2.5 m³/h
0.29 kg
VKR015F320-FF
DN 15
Rp ½"
4 m³/h
0.29 kg
VKR015F310-FF
DN 15
Rp ½"
6.3 m³/h
0.29 kg
VKR015F300-FF
DN 15
Rp ½"
10 m³/h
0.29 kg
VKR020F320-FF
DN 20
Rp ¾"
4 m³/h
0.32 kg
VKR020F310-FF
DN 20
Rp ¾"
6.3 m³/h
0.32 kg
VKR020F300-FF
DN 20
Rp ¾"
10 m³/h
0.32 kg
VKR025F320-FF
DN 25
Rp 1"
6.3 m³/h
0.49 kg
VKR025F310-FF
DN 25
Rp 1"
10 m³/h
0.49 kg
VKR025F300-FF
DN 25
Rp 1"
16 m³/h
0.49 kg
VKR032F320-FF
DN 32
Rp 1¼"
10 m³/h
0.73 kg
1)
278
At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type
Nominal diameter
Connection ISO 7/1 Rp Kvs value
Weight
VKR032F310-FF
DN 32
Rp 1¼"
16 m³/h
0.73 kg
VKR032F300-FF
DN 32
Rp 1¼"
25 m³/h
0.73 kg
VKR040F320-FF
DN 40
Rp 1½"
16 m³/h
1.1 kg
VKR040F310-FF
DN 40
Rp 1½"
25 m³/h
1.1 kg
VKR040F300-FF
DN 40
Rp 1½"
40 m³/h
1.1 kg
VKR050F320-FF
DN 50
Rp 2"
25 m³/h
1.76 kg
VKR050F310-FF
DN 50
Rp 2"
40 m³/h
1.76 kg
VKR050F300-FF
DN 50
Rp 2"
63 m³/h
1.76 kg
Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0560284015
Screw fitting in brass, flat-sealing, female thread/male thread for DN 15
0560284020
Screw fitting in brass, flat-sealing, female thread/male thread for DN 20
0560284025
Screw fitting in brass, flat-sealing, female thread/male thread for DN 25
0560284032
Screw fitting in brass, flat-sealing, female thread/male thread for DN 32
0560284040
Screw fitting in brass, flat-sealing, female thread/male thread for DN 40
0560284050
Screw fitting in brass, flat-sealing, female thread/male thread for DN 50
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
A
V
1 unit delivered in each case, unless otherwise specified. See last page for dimensions and scope of delivery of accessories.
Right of amendment reserved © 2024 Fr. Sauter AG
279
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Combination of VKR with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the ball valve) at which the actuator reliably closes the ball valve using the return spring.
/
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
Pressure differences Actuator
V
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
24 VAC
Operating voltage 230 VAC Closes against the pressure VKR015F350-FF VKR015F340-FF VKR015F330-FF VKR015F320-FF VKR015F310-FF VKR015F300-FF VKR020F320-FF VKR020F310-FF VKR020F300-FF VKR025F320-FF VKR025F310-FF VKR025F300-FF VKR032F320-FF VKR032F310-FF VKR032F300-FF VKR040F320-FF VKR040F310-FF VKR040F300-FF VKR050F320-FF VKR050F310-FF VKR050F300-FF
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
1.8
1.8
3.5
3.5
1.2
1.2
2.4
2.4
Cannot be used to close with the pressure
280
Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
Closes against the pressure
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
VKR015F350-FF VKR015F340-FF VKR015F330-FF VKR015F320-FF VKR015F310-FF VKR015F300-FF VKR020F320-FF VKR020F310-FF VKR020F300-FF VKR025F320-FF VKR025F310-FF VKR025F300-FF
1.8
3.5
3.5
3.5
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page
AKM105SF132 314
VKR032F320-FF VKR032F310-FF VKR032F300-FF VKR040F320-FF VKR040F310-FF VKR040F300-FF VKR050F320-FF VKR050F310-FF VKR050F300-FF
AKM115SF132 314
1.2
AKM115SAF232 133
2.4
2.4
AKM115SF152 316
2.4
Cannot be used to close with the pressure Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC
V
Closes against the ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] pressure VKR015F350-FF VKR015F340-FF VKR015F330-FF VKR015F320-FF VKR015F310-FF VKR015F300-FF VKR020F320-FF VKR020F310-FF VKR020F300-FF VKR025F320-FF VKR025F310-FF VKR025F300-FF
3.5
5.4
3.5
5.4
3.5
5.4
3.5
5.4
VKR032F320-FF VKR032F310-FF VKR032F300-FF VKR040F320-FF VKR040F310-FF VKR040F300-FF VKR050F320-FF VKR050F310-FF VKR050F300-FF
2.4
3.5
2.4
3.5
2.4
3.5
2.4
3.5
Cannot be used to close with the pressure
Right of amendment reserved © 2024 Fr. Sauter AG
281
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
VKRA: 2-way regulating ball valve with male thread, PN 40 Features • 2-way regulating ball valve for continuous control of cold and hot water in closed circuits • In combination with valve actuators AKM 105(S), 115(S), 115SA and AKF 112, 113(S) as a control unit • Equal-percentage ball valve characteristic; control contour in the ball directly integrated
VKRA0**F300
• Characteristic can be set with SUT rotary actuator (SAUTER Universal Technology) to linear or quadratic • Spindle with large sliding surface and PTFE glide ring • Low torque due to collar mounted on O-ring • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring
V
• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Valve characteristic Control ratio of ball valve Control ratio with actuator Leakage rate
40 bar Equal-percentage 500:1 > 50:1 Waterproof as per EN 60534-4 L/1, better than class 5 90°
Angle of rotation Ambient conditions
Operating temperature1) Operating pressure
−10...130 °C, no condensation Liquids: 40 bar (–10...50 °C), 35 bar Gases: 20 bar
Pressure and temperature data Flow parameters
EN 764, EN 1333 EN 60534 (page 3)
Standards, directives
Overview of types Type
Nominal diameter
Connection ISO 228-1
Kvs value
Weight
VKRA015F350
DN 15
G 1" B
1 m³/h
360 g
VKRA015F340
DN 15
G 1" B
1.6 m³/h
360 g
VKRA015F330
DN 15
G 1" B
2.5 m³/h
360 g
VKRA015F320
DN 15
G 1" B
4 m³/h
360 g
VKRA015F310
DN 15
G 1" B
6.3 m³/h
360 g
VKRA020F320
DN 20
G 1¼" B
4 m³/h
440 g
VKRA020F310
DN 20
G 1¼" B
6.3 m³/h
440 g
VKRA020F300
DN 20
G 1¼" B
10 m³/h
440 g
VKRA025F320
DN 25
G 1½" B
6.3 m³/h
570 g
VKRA025F310
DN 25
G 1½" B
10 m³/h
570 g
VKRA025F300
DN 25
G 1½" B
16 m³/h
570 g
VKRA032F320
DN 32
G 2" B
10 m³/h
840 g
VKRA032F310
DN 32
G 2" B
16 m³/h
840 g
1)
282
At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type
Nominal diameter
Connection ISO 228-1
Kvs value
Weight
VKRA032F300
DN 32
G 2" B
25 m³/h
840 g
VKRA040F320
DN 40
G 2¼" B
16 m³/h
1290 g
VKRA040F310
DN 40
G 2¼" B
25 m³/h
1290 g
VKRA040F300
DN 40
G 2¼" B
40 m³/h
1290 g
VKRA050F320
DN 50
G 2¾" B
25 m³/h
1980 g
VKRA050F310
DN 50
G 2¾" B
40 m³/h
1980 g
VKRA050F300
DN 50
G 2¾" B
63 m³/h
1980 g
Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0361951015
Screw fitting for male thread with flat seal, G1 - Rp½
0361951020
Screw fitting for male thread with flat seal, G1¼ - Rp¾
0361951025
Screw fitting for male thread with flat seal, G1½ - Rp1
0361951032
Screw fitting for male thread with flat seal DN 32
0361951040
Screw fitting for male thread with flat seal DN 40
0361951050
Screw fitting for male thread with flat seal DN 50
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
V
Combination of VKRA with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the ball valve) at which the actuator reliably closes the ball valve using the return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
24 VAC
Operating voltage 230 VAC Closes against the pressure VKRA015F350 VKRA015F340 VKRA015F330 VKRA015F320 VKRA015F310 VKRA020F320 VKRA020F310 VKRA020F300 VKRA025F320 VKRA025F310 VKRA025F300
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
1.8
1.8
3.5
3.5
Right of amendment reserved © 2024 Fr. Sauter AG
283
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page
AKM105F100 AKM105F120 311
VKRA032F320 VKRA032F310 VKRA032F300 VKRA040F320 VKRA040F310 VKRA040F300 VKRA050F320 VKRA050F310 VKRA050F300
AKM105F122
AKM115F120
AKM115F122
311
311
311
1.2
1.2
2.4
2.4
Cannot be used to close with the pressure
V
Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
Closes against the pressure
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
VKRA015F350 VKRA015F340 VKRA015F330 VKRA015F320 VKRA015F310 VKRA020F320 VKRA020F310 VKRA020F300 VKRA025F320 VKRA025F310 VKRA025F300
1.8
3.5
3.5
3.5
VKRA032F320 VKRA032F310 VKRA032F300 VKRA040F320 VKRA040F310 VKRA040F300 VKRA050F320 VKRA050F310 VKRA050F300
1.2
2.4
2.4
2.4
Cannot be used to close with the pressure Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC
Closes against the ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] pressure VKRA015F350 VKRA015F340 VKRA015F330 VKRA015F320 VKRA015F310 VKRA020F320 VKRA020F310 VKRA020F300 VKRA025F320 VKRA025F310 VKRA025F300
284
3.5
5.4
3.5
5.4
3.5
5.4
3.5
5.4
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page VKRA032F320 VKRA032F310 VKRA032F300 VKRA040F320 VKRA040F310 VKRA040F300 VKRA050F320 VKRA050F310 VKRA050F300
AKF112F120 317
2.4
AKF112F122 317
3.5
2.4
AKF113F122 317
3.5
2.4
AKF113SF122 318
3.5
2.4
3.5
Cannot be used to close with the pressure
V
Right of amendment reserved © 2024 Fr. Sauter AG
285
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
BKR: 3-way regulating ball valve with female thread, PN 40 Features • 3-way regulating ball valve for continuous control of cold and hot water in closed circuits • In combination with valve actuators AKM 105(S), 115(S), 115SA and AKF 112, 113(S) as a control unit • Control contour in the ball directly integrated • Control passage characteristic can be set to linear or quadratic with SUT rotary actuator
BKR025F310
• Low torque due to collar mounted on O-ring • Spindle with large sliding surface and PTFE ring • Ball valve with female thread as per ISO 7/1 Rp or NPT • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring
V
• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Kvs value, mixing passage Control passage valve characteristic Mixing passage valve characteristic Control ratio of ball valve Control ratio with actuator Control passage leakage rate Mixing passage leakage rate Angle of rotation
40 bar −10...−30% through the control passage Equal-percentage Linear 500:1 Approx. 50:1 Watertight as per EN 60534-4 L/1, better than class 4 < 1% 90°
Ambient conditions
−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)
Operating temperature1) Operating pressure
Overview of types Type
Nominal diameter
Connection ISO 7/1 Rp Kvs value, control pas-
Weight
sage
BKR015F340-FF
DN 15
Rp ½"
1.6 m³/h
0.31 kg
BKR015F330-FF
DN 15
Rp ½"
2.5 m³/h
0.31 kg
BKR015F320-FF
DN 15
Rp ½"
4 m³/h
0.31 kg
BKR015F310-FF
DN 15
Rp ½"
6.3 m³/h
0.33 kg
BKR020F320-FF
DN 20
Rp ¾"
4 m³/h
0.4 kg
BKR020F310-FF
DN 20
Rp ¾"
6.3 m³/h
0.4 kg
BKR025F310-FF
DN 25
Rp 1"
10 m³/h
0.63 kg
BKR032F310-FF
DN 32
Rp 1¼"
16 m³/h
0.97 kg
BKR040F310-FF
DN 40
Rp 1½"
25 m³/h
1.4 kg
BKR050F310-FF
DN 50
Rp 2"
40 m³/h
2.67 kg
1)
286
At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0560284015
Screw fitting in brass, flat-sealing, female thread/male thread for DN 15
0560284020
Screw fitting in brass, flat-sealing, female thread/male thread for DN 20
0560284025
Screw fitting in brass, flat-sealing, female thread/male thread for DN 25
0560284032
Screw fitting in brass, flat-sealing, female thread/male thread for DN 32
0560284040
Screw fitting in brass, flat-sealing, female thread/male thread for DN 40
0560284050
Screw fitting in brass, flat-sealing, female thread/male thread for DN 50
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
A
V
1 unit delivered in each case, unless otherwise specified. See last page for dimensions and scope of delivery of accessories.
Combination of BKR with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
Operating voltage 230 VAC
24 VAC
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKR015F340-FF BKR015F330-FF BKR015F320-FF BKR015F310-FF BKR020F320-FF BKR020F310-FF BKR025F310-FF
1.8
1.8
2.0
2.0
BKR032F310-FF BKR040F310-FF BKR050F310-FF
1.2
1.2
2.0
2.0
Cannot be used as distribution valve
Right of amendment reserved © 2024 Fr. Sauter AG
287
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
V
Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKR015F340-FF BKR015F330-FF BKR015F320-FF BKR015F310-FF BKR020F320-FF BKR020F310-FF BKR025F310-FF
1.8
2.0
2.0
2.0
BKR032F310-FF BKR040F310-FF BKR050F310-FF
1.2
2.0
2.0
2.0
Cannot be used as distribution valve Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC As control valve
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]
BKR015F340-FF BKR015F330-FF BKR015F320-FF BKR015F310-FF BKR020F320-FF BKR020F310-FF BKR025F310-FF
2.0
5.4
2.0
5.4
2.0
5.4
2.0
5.4
BKR032F310-FF BKR040F310-FF BKR050F310-FF
2.0
3.5
2.0
3.5
2.0
3.5
2.0
3.5
Cannot be used as distribution valve
288
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
BKRA: 3-way regulating ball valve with male thread, PN 40 Features • 3-way regulating ball valve for continuous control of cold and hot water in closed circuits • As a control unit in combination with valve actuators AKM105(S), 115(S), 115SA and AKF112, 113(S) • Control contour in the ball directly integrated • Control passage characteristic can be set to linear or quadratic with SUT rotary actuator • Low torque due to collar mounted on O-ring
BKRA0**F3*0
• Spindle with large sliding surface and PTFE ring • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring
V
• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Kvs value, mixing passage Valve characteristic, control passage Mixing passage valve characteristic Control ratio of ball valve Control ratio with actuator Control passage leakage rate Mixing passage leakage rate Angle of rotation
40 bar –10...–30% through the control passage Equal-percentage Linear 500:1 Approx. 50:1 Watertight as per EN 60534-4 L/1, better than class 4 < 1% of the Kvs value 90°
Ambient conditions
−10...130 °C, no condensation 40 bar (–10...50 °C) 35 bar (130 °C) Gases: 20 bar
Operating temperature1) Operating pressure
Overview of types Type
Nominal diameter
Connection ISO 228-1
Kvs value, control pas-
Weight
sage
BKRA015F340
DN 15
G 1" B
1.6 m³/h
0.41 kg
BKRA015F330
DN 15
G 1" B
2.5 m³/h
0.41 kg
BKRA015F320
DN 15
G 1" B
4 m³/h
0.41 kg
BKRA015F310
DN 15
G 1" B
6.3 m³/h
0.45 kg
BKRA020F320
DN 20
G 1¼" B
4 m³/h
0.52 kg
BKRA020F310
DN 20
G 1¼" B
6.3 m³/h
0.4 kg
BKRA025F310
DN 25
G 1½" B
10 m³/h
0.75 kg
BKRA032F310
DN 32
G 2" B
16 m³/h
1.2 kg
BKRA040F310
DN 40
G 2¼" B
25 m³/h
1.84 kg
BKRA050F310
DN 50
G 2¾" B
40 m³/h
2.83 kg
1)
At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.
Right of amendment reserved © 2024 Fr. Sauter AG
289
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories
V
Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0361951015
Screw fitting for male thread with flat seal, G1 - Rp½
0361951020
Screw fitting for male thread with flat seal, G1¼ - Rp¾
0361951025
Screw fitting for male thread with flat seal, G1½ - Rp1
0361951032
Screw fitting for male thread with flat seal DN 32
0361951040
Screw fitting for male thread with flat seal DN 40
0361951050
Screw fitting for male thread with flat seal DN 50
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
Combination of BKRA with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
Operating voltage 230 VAC
24 VAC
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKRA015F340 BKRA015F330 BKRA015F320 BKRA015F310 BKRA020F320 BKRA020F310 BKRA025F310
1.8
1.8
2.0
2.0
BKRA032F310 BKRA040F310 BKRA050F310
1.2
1.2
2.0
2.0
Cannot be used as distribution valve
290
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKRA015F340 BKRA015F330 BKRA015F320 BKRA015F310 BKRA020F320 BKRA020F310 BKRA025F310
1.8
2.0
2.0
2.0
BKRA032F310 BKRA040F310 BKRA050F310
1.2
2.0
2.0
2.0
V
Cannot be used as distribution valve Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC As control valve
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]
BKRA015F340 BKRA015F330 BKRA015F320 BKRA015F310 BKRA020F320 BKRA020F310 BKRA025F310
2.0
5.4
2.0
5.4
2.0
5.4
2.0
5.4
BKRA032F310 BKRA040F310
2.0
3.5
2.0
3.5
2.0
3.5
2.0
3.5
BKRA050F310
1.0
3.5
2.0
3.5
2.0
3.5
2.0
3.5
Cannot be used as distribution valve
Right of amendment reserved © 2024 Fr. Sauter AG
291
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
VKAI: 2-way cut-off ball valve with female thread, PN 40 Features • 2-way cut-off ball valve for use in closed circuits in heating, ventilation and air conditioning systems • As a cut-off device and control unit for 2-point control in combination with valve actuators AKM 105(S),
115(S), 115SA and AKF 112, 113(S) • Fast cut-off in six seconds with the AKM115SF152 valve actuator
VKAI040F300
• Low torque due to collar mounted on O-ring • Ball valve with female thread as per ISO 7/1 Rp • Body made of dezincification-resistant cast brass • Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories
V
• Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Leakage rate Angle of rotation
40 bar 0.0001 x Kvs value 90°
Operating temperature1) Operating pressure
−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)
Ambient conditions
Overview of types Type
Nominal diameter (DN) Connection ISO 7/1 Rp Kvs value
Weight
275 g
VKAI015F300
DN 15
Rp ½"
15 m3/h
VKAI020F300
DN 20
Rp ¾"
22 m3/h
370 g
VKAI025F300
DN 25
Rp 1"
22 m3/h
456 g
VKAI032F300
DN 32
Rp 1¼"
35 m3/h
700 g
VKAI040F300
DN 40
Rp 1½"
68 m3/h
1120 g
VKAI050F300
DN 50
Rp 2"
96 m3/h
1750 g
Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0560284015
Screw fitting in brass, flat-sealing, female thread/male thread for DN 15
0560284020
Screw fitting in brass, flat-sealing, female thread/male thread for DN 20
0560284025
Screw fitting in brass, flat-sealing, female thread/male thread for DN 25
0560284032
Screw fitting in brass, flat-sealing, female thread/male thread for DN 32
0560284040
Screw fitting in brass, flat-sealing, female thread/male thread for DN 40
0560284050
Screw fitting in brass, flat-sealing, female thread/male thread for DN 50
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
1)
292
At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type
Description
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
Combination of VKAI with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
Operating voltage 230 VAC
V
24 VAC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
VKAI015F300 VKAI020F300 VKAI025F300
1.8
1.8
3.5
3.5
VKAI032F300 VKAI040F300 VKAI050F300
1.2
1.2
2.4
2.4
– Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
VKAI015F300 VKAI020F300 VKAI025F300
1.8
3.5
3.5
3.5
VKAI032F300 VKAI040F300 VKAI050F300
1.2
2.4
2.4
2.4
Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
–
Operating voltage 230 VAC
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] VKAI015F300 VKAI020F300 VKAI025F300
3.5
5.4
3.5
5.4
3.5
5.4
3.5
5.4
VKAI032F300 VKAI040F300 VKAI050F300
2.4
5.4
2.4
5.4
2.4
5.4
2.4
5.4
–
Right of amendment reserved © 2024 Fr. Sauter AG
293
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
VKAA: 2-way cut-off ball valve with male thread, PN 40 Features • 2-way cut-off ball valve for use in closed circuits in heating, ventilation and air conditioning systems • As a cut-off device and control unit for 2-point control in combination with valve actuators AKM 105(S),
115(S), 115SA and AKF 112, 113(S) VKAA0**F300
• Fast changeover in six seconds with the AKM115SF152 valve actuator • Low torque due to collar mounted on O-ring • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of dezincification-resistant cast brass • Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories
V
• Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Leakage rate
40 bar Waterproof as per EN 60534-4 L/1, better than class 5 90°
Angle of rotation Ambient conditions
Operating temperature Operating pressure
−10...130 °C, no condensation Liquids: 40 bar (–10...50 °C) 35 bar (130 °C) Gases: 20 bar
Overview of types Type
Nominal diameter (DN) Connection ISO 228-1
Kvs value
Weight
VKAA015F300
DN 15
G 1" B
9 m3
360 g
VKAA020F300
DN 20
G 1¼" B
17 m3
550 g
VKAA025F300
DN 25
G 1½" B
22 m3
570 g
VKAA032F300
DN 32
G 2" B
35 m3
840 g
VKAA040F300
DN 40
G 2¼" B
68 m3
1290 g
VKAA050F300
DN 50
G 2¾" B
96 m3
1980 g
Accessories
294
Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0361951015
Screw fitting for male thread with flat seal, G1 - Rp½
0361951020
Screw fitting for male thread with flat seal, G1¼ - Rp¾
0361951025
Screw fitting for male thread with flat seal, G1½ - Rp1
0361951032
Screw fitting for male thread with flat seal DN 32
0361951040
Screw fitting for male thread with flat seal DN 40
0361951050
Screw fitting for male thread with flat seal DN 50
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type
Description
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
Combination of VKAA with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
/
Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
Operating voltage 230 VAC
V
24 VAC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
VKAA015F300 VKAA020F300 VKAA025F300
1.8
1.8
3.5
3.5
VKAA032F300 VKAA040F300 VKAA050F300
1.2
1.2
2.4
2.4
– Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
VKAA015F300 VKAA020F300 VKAA025F300
1.8
3.5
3.5
3.5
VKAA032F300 VKAA040F300 VKAA050F300
1.2
2.4
2.4
2.4
Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
–
Operating voltage 230 VAC
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] VKAA015F300 VKAA020F300 VKAA025F300
3.5
5.4
3.5
5.4
Right of amendment reserved © 2024 Fr. Sauter AG
3.5
5.4
3.5
5.4
295
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page VKAA032F300 VKAA040F300 VKAA050F300
AKF112F120 317 2.4
AKF112F122 317 5.4
2.4
AKF113F122 317 5.4
2.4
AKF113SF122 318 5.4
2.4
5.4
–
V
296
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
BKLI: 3-way changeover ball valve (L) with female thread, PN 40 Features • 3-way changeover ball valve with L-bore for use in closed circuits in heating, ventilation and air
conditioning systems • For changing over volume flows in combination with valve actuators AKM 105(S), 115(S), 115SA and
AKF 112, 113(S). • Fast changeover in six seconds with the AKM115SF152 valve actuator
BKLI025F300
• Low torque due to collar mounted on O-ring • Spindle with friction ring and double O-ring seal • Ball valve with female thread as per ISO 7/1 Rp • Body made of dezincification-resistant cast brass
V
• Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Leakage rate, through passage Leakage rate, bypass Angle of rotation
40 bar 0.0001 x Kvs value 0.0001 x Kvs value 90°
Operating temperature1) Operating pressure
−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)
Ambient conditions
Overview of types Type
Nominal diameter (DN) Connection ISO 7/1 Rp Kvs value, control pas-
Weight
sage
BKLI015F300
DN 15
Rp ½"
5 m³/h
306 g
BKLI020F300
DN 20
Rp ¾"
9 m³/h
375 g
BKLI025F300
DN 25
Rp 1"
9 m³/h
604 g
BKLI032F300
DN 32
Rp 1¼"
13 m³/h
949 g
BKLI040F300
DN 40
Rp 1½"
25 m³/h
1364 g
BKLI050F300
DN 50
Rp 2"
37 m³/h
2215 g
Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0560284015
Screw fitting in brass, flat-sealing, female thread/male thread for DN 15
0560284020
Screw fitting in brass, flat-sealing, female thread/male thread for DN 20
0560284025
Screw fitting in brass, flat-sealing, female thread/male thread for DN 25
0560284032
Screw fitting in brass, flat-sealing, female thread/male thread for DN 32
0560284040
Screw fitting in brass, flat-sealing, female thread/male thread for DN 40
0560284050
Screw fitting in brass, flat-sealing, female thread/male thread for DN 50
1)
At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.
Right of amendment reserved © 2024 Fr. Sauter AG
297
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type
Description
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
Combination of BKLI with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
V
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
Operating voltage 230 VAC
24 VAC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKLI015F300 BKLI020F300 BKLI025F300
1.8
1.8
2.0
2.0
BKLI032F300 BKLI040F300 BKLI050F300
1.2
1.2
2.0
2.0
– Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKLI015F300 BKLI020F300 BKLI025F300
1.8
2.0
2.0
2.0
BKLI032F300 BKLI040F300 BKLI050F300
1.2
2.0
2.0
2.0
–
298
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] BKLI015F300 BKLI020F300 BKLI025F300 BKLI032F300 BKLI040F300 BKLI050F300
2.0
5.4
2.0
5.4
2.0
5.4
2.0
5.4
–
V
Right of amendment reserved © 2024 Fr. Sauter AG
299
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
BKTI: 3-way changeover ball valve (T) with female thread, PN 40 Features • 3-way changeover ball valve with T-bore for use in closed circuits in heating, ventilation and air
conditioning systems • For changing over volume flows in combination with valve actuators AKM 105(S), 115(S), 115SA and
AKF 112, 113(S) BKTI025F300
• Fast changeover in six seconds with the AKM115SF152 valve actuator • Low torque due to collar mounted on O-ring • Spindle with friction ring and double O-ring seal • Ball valve with female thread as per ISO 7/1 Rp • Body made of dezincification-resistant cast brass
V
• Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Leakage rate, through passage Leakage rate, bypass Angle of rotation
40 bar 0.0001 x Kvs value < 0.01 x Kvs value 90°
Operating temperature1) Operating pressure
−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)
Ambient conditions
Overview of types Type
Nominal diameter
Connection ISO 7/1 Rp Kvs value, control pas-
Weight
sage
BKTI015F300
DN 15
Rp ½"
12 m³/h
306 g
BKTI020F300
DN 20
Rp ¾"
16 m³/h
375 g
BKTI025F300
DN 25
Rp 1"
16 m³/h
604 g
BKTI032F300
DN 32
Rp 1¼"
25 m³/h
949 g
BKTI040F300
DN 40
Rp 1½"
49 m³/h
1364 g
BKTI050F300
DN 50
Rp 2"
73 m³/h
2215 g
Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0560284015
Screw fitting in brass, flat-sealing, female thread/male thread for DN 15
0560284020
Screw fitting in brass, flat-sealing, female thread/male thread for DN 20
0560284025
Screw fitting in brass, flat-sealing, female thread/male thread for DN 25
0560284032
Screw fitting in brass, flat-sealing, female thread/male thread for DN 32
0560284040
Screw fitting in brass, flat-sealing, female thread/male thread for DN 40
0560284050
Screw fitting in brass, flat-sealing, female thread/male thread for DN 50
1)
300
At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type
Description
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
Combination of BKTI with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
V
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
Operating voltage 230 VAC
24 VAC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKTI015F300 BKTI020F300 BKTI025F300
1.8
1.8
2.0
2.0
BKTI032F300 BKTI040F300 BKTI050F300
1.2
1.2
2.0
2.0
– Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKTI015F300 BKTI020F300 BKTI025F300
1.8
2.0
2.0
2.0
BKTI032F300 BKTI040F300 BKTI050F300
1.2
2.0
2.0
2.0
–
Right of amendment reserved © 2024 Fr. Sauter AG
301
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] BKTI015F300 BKTI020F300 BKTI025F300 BKTI032F300 BKTI040F300 BKTI050F300
2.0
5.4
2.0
5.4
2.0
5.4
2.0
5.4
–
V
302
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
BKTA: 3-way changeover ball valve (T) with male thread, PN 40 Features • 3-way changeover ball valve with T-bore for use in closed circuits in heating, ventilation and air
conditioning systems • For changing over volume flows in combination with valve actuators AKM 105(S), 115(S), 115SA and
AKF 112, 113(S) • Fast changeover in six seconds with the AKM115SF152 valve actuator
BKTA0**F300
• Low torque due to collar mounted on O-ring • Spindle with friction ring and double O-ring seal • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of dezincification-resistant cast brass
V
• Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
Technical data Parameters
Nominal pressure Leakage rate, through passage Leakage rate, bypass Angle of rotation
40 bar Waterproof as per EN 60534-4 L/1, better than class 4 < 1% of the Kvs value 90°
Ambient conditions
Operating temperature Operating pressure
−10...130 °C, no condensation 40 bar (–10...50 °C) 35 bar (130 °C) Gases: 20 bar
Overview of types Type
Nominal diameter
Connection ISO 228-1
Kvs value, control pas-
Weight
sage
BKTA015F300
DN 15
G 1" B
8 m³/h
450 g
BKTA020F300
DN 20
G 1¼" B
13 m³/h
680 g
BKTA025F300
DN 25
G 1½" B
13 m³/h
750 g
BKTA032F300
DN 32
G 2" B
25 m³/h
1200 g
BKTA040F300
DN 40
G 2¼" B
49 m³/h
1840 g
BKTA050F300
DN 50
G 2¾" B
73 m³/h
2830 g
Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
0510240011
Adaptor required when temperature of the medium < 5 °C
0510420001
Adaptor required when temperature of the medium > 100 °C
0361951015
Screw fitting for male thread with flat seal, G1 - Rp½
0361951020
Screw fitting for male thread with flat seal, G1¼ - Rp¾
0361951025
Screw fitting for male thread with flat seal, G1½ - Rp1
0361951032
Screw fitting for male thread with flat seal DN 32
0361951040
Screw fitting for male thread with flat seal DN 40
0361951050
Screw fitting for male thread with flat seal DN 50
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
Right of amendment reserved © 2024 Fr. Sauter AG
303
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type
Description
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
0560332032
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32
0560332040
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40
0560332050
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50
Combination of BKTA with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.
/
V
Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.
Pressure differences Actuator
AKM105F122
AKM115F120
AKM115F122
Page
AKM105F100 AKM105F120 311
311
311
311
Rotational torque
4 Nm
4 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point
Running time
30/120 s
30/120 s
120 s
120 s
24 VAC
230 VAC
Operating voltage 230 VAC
24 VAC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKTA015F300 BKTA020F300 BKTA025F300
1.8
1.8
2.0
2.0
BKTA032F300 BKTA040F300 BKTA050F300
1.2
1.2
2.0
2.0
– Actuator Page
AKM105SF132 314
AKM115SF132 314
AKM115SAF232 133
AKM115SF152 316
Rotational torque
4 Nm
8 Nm
8 Nm
7 Nm
Control signal
2-/3-point, 0...10 V
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
2-/3-point, 0...10 V, 4...20 mA
Running time
35/60/120 s
35/60/120 s
35/60/120 s
6s
Operating voltage 24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
BKTA015F300 BKTA020F300 BKTA025F300
1.8
2.0
2.0
2.0
BKTA032F300 BKTA040F300 BKTA050F300
1.2
2.0
2.0
2.0
–
304
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] BKTA015F300 BKTA020F300 BKTA025F300 BKTA032F300 BKTA040F300 BKTA050F300
2.0
5.4
2.0
5.4
2.0
5.4
2.0
5.4
–
V
Right of amendment reserved © 2024 Fr. Sauter AG
305
6-way ball valves The 6-way ball valve from SAUTER is a compact and precise alternative for regulating heated/chilled ceilings and fan coils in four-pipe systems. It doubles as a regulating and changeover ball valve. While conventional solutions operate with up to four 2-way valves, four actuators and two controllers, now only one 6-way ball valve and an actuator are required. Their compact construction enables the devices to be installed in false ceilings without difficulty.
Overview of 6-way ball valves
Type designation Application Single-room control Preheater for ventilation & air-conditioning Preheater, cooler for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling Static heating Multi-boiler system Local heating Version Nominal pressure Combination options with actuator Further information
306
B2KL • • • • • • • • PN 16 AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 307
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
B2KL: 6-way ball valve with male thread, PN 16 Features • 6-way ball valve for changeover or continuous control of heating and cooling circuits in a 4-pipe system • Body made of moulded brass CW602N (dezincification-resistant) or CW617N • With male thread as per ISO 228 • Kvs selection with exchangeable orifice plates • In combination with valve actuators AKM 115(S), 115SA and AKF 112, 113(S) as a control unit • Strainer and screw fitting available as accessories • Water quality as per VDI 2035
B2KL015F400
Technical data
V
Parameters
Nominal pressure Valve characteristic Leakage rate Total angle of rotation
PN 16 Quasi-linear Class A as per EN 12266-1 90° (valve closed at 45°)
Operating temperature
5…90 °C
Pressure and temperature data Flow parameters PED 2014/68/EU
EN 764, EN 1333 EN 60534 Fluid group II, liquid No CE label as per article 4.3
Connection
Material
Weight
M
Ambient conditions
Standards, directives
Overview of types Type
Nominal diameter
Kvs value without orifice plate
B2KL015F400
DN 15
G ¾" B
1.25 m³/h
Moulded brass CW617N
980 g
B2KL015F401
DN 15
G ¾" B
1.25 m³/h
Moulded brass CW602N
980 g
B2KL020F411
DN 20
G ¾" B
2.8 m³/h
Moulded brass CW602N
1870 g
A
Kvs value without orifice plate. Kvs values can be adapted using orifice plates.
Orifice plates for setting the Kvs value Orifice plate set for B2KL DN15 Kvs value 0.25 m3/h
Part number 0589540001 Supplied with the 6-way ball valve
0.4 m3/h 0.63 m3/h 1 m3/h Orifice plate set for B2KL DN20 Kvs value 0.7 m3/h
Part number 0589540002 Supplied with the 6-way ball valve
1 m3/h 1.6 m3/h 2.1 m3/h
Right of amendment reserved © 2024 Fr. Sauter AG
307
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories
V
Type
Description
0378133015
1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½
0378134015
1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾
0580240002
Insulation shell for 6-way ball valve DN 15
0580240003
Insulation shell for 6-way ball valve DN 20
0560284015
Screw fitting in brass, flat-sealing, female thread/male thread for DN 15
0560284020
Screw fitting in brass, flat-sealing, female thread/male thread for DN 20
0580090001
Pliers for changing orifice plate on 6-way ball valve DN 15 and DN 20
0580240001
Fitting bracket for 6-way ball valve DN 15 and DN 20
0560332015
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15
0560332020
Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20
0560332025
Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25
Combination of B2KL with electrical actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the ball valve) at which the actuator reliably closes the ball valve using the return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Pressure differences Actuator Page
AKM115F120 311
AKM115F122 311
AKM115SF132 314
AKM115SAF232 133
Rotational torque
8 Nm
8 Nm
8 Nm
8 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point, 0...10 V
0…10 V, BACnet MS/TP
Running time
120 s
120 s
35/60/120 s
35/60/120 s
24 VAC
24 VAC/DC
24 VAC/DC
Operating voltage 230 VAC ∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
2.0
2.0
2.0
2.0
Actuator Page
AKF112F120 317
AKF112F122 317
AKF113F122 317
AKF113SF122 318
Torque
7 Nm
7 Nm
7 Nm
7 Nm
Control signal
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
24 VAC/DC
24 VAC/DC
24 VAC/DC
B2KL015F400 B2KL015F401 B2KL020F411 –
Operating voltage 230 VAC
∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] B2KL015F400 B2KL015F401 B2KL020F411
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
–
308
Right of amendment reserved © 2024 Fr. Sauter AG
Actuators for ball valves SAUTER actuators for ball valves adapt themselves automatically to the ball valves and enable them to be controlled accurately. The actuators are switched off as a function of the torque. These SAUTER actuators are suitable for operating two- and three-way ball valves. Furthermore, they can be used for controllers with switching or continuous outputs.
Overview of actuators for ball valves
Type designation
AKM 105, 115
AKM105SF132 AKM115SF132
AKM115SAF232
AKM115SF152
Technical data Adjustable characteristic
Equal-percentage
30/120 − 24, 230
Equal-percentage, linear, quadratic 35/60/120 − 24
Equal-percentage, linear, quadratic 35/60/120 − 24
Equal-percentage, linear, quadratic 6 − 24
• • − − − − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL Page 311
• • − • − − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL Page 313
− − • • − − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL Page 131
• • − • • − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA Page 315
Running time (s) Return time (s) Power supply (V) Control 2-point 3-point BACnet MS/TP Positioner High-speed Spring return Combination options with ball valve Further information
Right of amendment reserved © 2024 Fr. Sauter AG
309
Type designation Technical data Adjustable characteristic Running time (s) Return time (s) Power supply (V) Control 2-point 3-point BACnet MS/TP Positioner High-speed Spring return Combination options with ball valve Further information
310
AKF 112, 113
AKF 113S
− 90 15 24, 230
− 90 15 24, 230
• • − − − • VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL
• • − • − • VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL
Page 317
Page 318
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
AKM 105, 115: Rotary actuator for ball valve Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way
ball valve B2KL • For controllers with a switching output (2-/3-point control) • Assembly with ball valves without the use of tools • Synchronous motor with electronic activation and cut-out • Maintenance-free gear unit • Gear unit can be disengaged in order to position the ball valve manually (using the lever)
AKM115F12
• Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve • Fitting vertically upright to horizontal, not suspended
V
Technical data Power supply
Power supply 230 VAC Power supply 24 VAC
±15%, 50...60 Hz ±20%, 50...60 Hz
Power cable Response time Angle of rotation
1.2 m, 3 × 0.75 mm2 Min. 200 ms 90°
Ambient temperature Ambient humidity Media temperature1)
–10...55 °C 5...95% rh, no condensation Max. 100 °C
Control
2-/3-point
Weight Housing
0.7 kg Lower section black, upper section yellow Fire-retardant plastic
Parameters
Ambient conditions
Function
Construction
Housing material Standards and directives
CE conformity according to
IP54 (EN 60529), horizontal III (EN 60730) II (EN 60730) III II EN 60730-1/EN 60730-2-14 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4
Type of protection2) Protection class 24 V Protection class 230 V Over-voltage categories Degree of contamination Directive 2006/95/EC EMC Directive 2014/30/EU
Overview of types Type
Voltage
Running time
Rotational torque
Power consumption
AKM105F100
230 VAC
30.0 s
4 Nm
2.4 W, 4.5 VA
AKM105F120
230 VAC
120.0 s
4 Nm
2.0 W, 4.0 VA
AKM105F122
24 VAC
120.0 s
4 Nm
1.6 W, 1.7 VA
AKM115F120
230 VAC
120.0 s
8 Nm
2.0 W, 4.0 VA
AKM115F122
24 VAC
120.0 s
8 Nm
1.6 W, 1.7 VA
1) 2)
At media temperatures < 5 °C or > 100 °C, appropriate accessory must be used See fitting instructions P100001578
Right of amendment reserved © 2024 Fr. Sauter AG
311
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories Type
Description
0510420001
Adaptor required when temperature of the medium > 100 °C
0510240011
Adaptor required when temperature of the medium < 5 °C
0510480001
Auxiliary change-over contacts, single
0510480002
Auxiliary change-over contacts, double
A
Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V
V
312
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
AKM 105S, 115S: Rotary actuator with SAUTER Universal Technology (SUT) for ball valve Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way
ball valve B2KL • For controllers with constant output (0...10 V) or switching output (2-/3-point control) • Assembly with ball valve without the use of tools • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit • Electronic force-dependent motor cut-off • Automatic recognition of applied control signal (continuous or switched)
AKM115SF132
• Coding switch for selecting characteristic and running time (35 s, 60 s, 120 s)
V
• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator • Direction of operation can be selected directly on the cable • Maintenance-free gear unit • Gear unit can be disengaged in order to position the ball valve manually (using the lever) • Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power consumption
±20%, 50...60 Hz −10%...20% 4.9 W, 8.7 VA
Running time1) Angle of rotation Response time Power cable
35/60/120 s 90° 200 ms
Parameters
Positioner
Positioning signal y Position feedback signal Starting point U0 Control span ΔU Switching range Xsh
1.2 m, 5 × 0.5 mm2 0...10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 V or 10 V 10 V 200 mV
Media temperature2) Ambient temperature Ambient humidity
Max. 100 °C −10...55 °C 5...95% rh, no condensation
Fitting
Vertically upright to horizontal, not suspended 0.7 kg Lower section black, upper section yellow Flame-retardant plastic
Ambient conditions
Construction
Weight Housing Housing material Standards, directives
CE conformity according to
1) 2)
Type of protection Protection class EMC Directive 2014/30/EU
IP54 as per EN 60529 III as per IEC 60730 EN 61000-6-1, EN 61000-6-3 EN 61000-6-4
For a running time of 35 s, the torque is halved At media temperatures < 5 °C or > 100 °C, appropriate accessory must be used
Right of amendment reserved © 2024 Fr. Sauter AG
313
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Overview of types Type
Voltage
Rotational torque
Running time
Power consumption
AKM105SF132
24 VAC/DC
4 Nm
35/60/120 s
4.9 W, 8.7 VA
AKM115SF132
24 VAC/DC
8 Nm
35/60/120 s
4.9 W, 8.7 VA
Accessories Type
Description
0313529001
Split-range unit for setting sequences
0510420001
Adaptor required when temperature of the medium > 100 °C
0510240011
Adaptor required when temperature of the medium < 5 °C
0510480001
Auxiliary change-over contacts, single
0510480002
Auxiliary change-over contacts, double
A
Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V
V
314
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
AKM 115S F152: High-speed rotary actuator with SAUTER Universal Technology (SUT) for ball valve Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way
ball valve B2KL • For controllers with constant output (0...10 V / 4...20 mA) or switching output (2-/3-point control) • Assembly with ball valve without the use of tools • Brushless motor with electronic activation and cut-out • Intelligent adaptation of rotation angle, incl. feedback adjustment • Electronic force-dependent cut-off
AKM115SF152
• Direction of rotation selected with DIP switch
V
• Pulse length correction in 3-point operation, i.e. internal adjustment of start-up time • Gear unit can be disengaged in order to position the ball valve manually (using the lever) • Maintenance-free • Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power consumption
±20%, 50…60 Hz −10%...20% 6.5 W, 9 VA (at nominal voltage)
Rotational torque Operating noise (unloaded) Response time Angle of rotation Running time Characteristic Positioning signal y Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI Switching range Xsh
8 Nm < 49 dB(A) 10 ms 90° 6.0 s linear 0…10 V / 2…10 V, Ri = 100 kΩ, 0…20 mA / 4…20 mA, Ri = 500 Ω 0...10 V, load > 10 kΩ 0 or 10 V / 2 or 10 V 0 or 20 mA / 4 or 20 mA 10 V 100 mV 20 mA 0.1 mA
Operating temperature Media temperature1) Storage and transport temperature Ambient humidity
−20…55 °C Max. 100 °C −30…65 °C 5…85% rh, no condensation
Fitting Dimensions W × H × D Weight Housing
Vertically upright to horizontal 70 × 138 × 127 mm 0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m, 6 × 0.5 mm²
Parameters
Positioner
Ambient conditions
Construction
Housing material Power cable 1)
At media temperature > 100 °C, appropriate accessory must be used
Right of amendment reserved © 2024 Fr. Sauter AG
315
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
Standards and directives
CE conformity according to
Type of protection Protection class EMC Directive 2014/30/EU
IP54 (EN 60529), horizontal III (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4
Overview of types Type
Voltage
Rotational torque
Running time
Power consumption
AKM115SF152
24 VAC/DC
7 Nm
6s
6.5 W, 9 VA
Accessories
V
316
Type
Description
0313529001
Split-range unit for setting sequences
0510420001
Adaptor required when temperature of the medium > 100 °C
0510240011
Adaptor required when temperature of the medium < 5 °C
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
AKF 112, 113: Rotary actuator with spring return for control ball valves Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way
ball valve B2KL • For controllers with a switching output (2-/3-point control) • Returns to the starting position in the event of a power failure or the activation of a safety device • Electronic torque-dependent cut-off • Direction of rotation can be selected during fitting
AKF112F122
Technical data
V
Power supply
Power supply 230 VAC Power supply 24 VAC Power supply 24...48 V=
±10%, 50...60 Hz ±20%, 50...60 Hz ±20%
Rotational torque and holding torque Angle of rotation Power cable Running time for 90° motor Running time for 90° spring
7 Nm Max. 95° 0.9 m, 0.75 mm² (fixed to housing) 90 s 15 s
Ambient temperature Ambient humidity
–32...55 °C 5...95% rh
Weight Housing Housing material
1.2 kg Two-piece Cast aluminium
Type of protection
IP54 as per EN 60529 IP42 depending on fitting position II (EN 60730) III (EN 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 III II
Parameters
Ambient conditions
Construction
Standards and directives
CE conformity according to Only for AKF120F120
Protection class 230 V Protection class 24 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination
Overview of types Type
Power consumption
Control function
Voltage
AKF112F120
4.5 W, 7.0 VA
2-point
230 VAC
AKF112F122
3.5 W, 5.0 VA
2-point
24 VAC / 24…48 VDC
AKF113F122
3.5 W, 5.0 VA
3-point
24 VAC / 24…48 VDC
Accessories Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
Right of amendment reserved © 2024 Fr. Sauter AG
317
Valves, control valves, dampers, actuators | Ball valves and ball valve actuators
AKF 113S: Rotary actuator with spring return and positioner Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and
6‑way ball valve B2KL • For controllers with a continuous output (0…10 V) • Returns to the starting position in the event of a power failure or the activation of a safety device • Electronic torque-dependent cut-off • Direction of rotation can be selected during fitting
AKF113SF122
Technical data Power supply
V
Power supply 24 VAC Power supply 24...48 V= Rated power during continuous operation Power consumption when idle
±20%, 50...60 Hz ±20% 3.5 W, 5 VA
Positioning signal y Position feedback signal Admissible load Starting point U0 Control span ΔU Switching range Xsh Rotational torque and holding torque Angle of rotation Power cable Running time for 90° motor Running time for 90° spring
0...10 V, Ri = 100 kΩ 0...10 V (0...100%) > 10 kΩ 0V 10 V 0.2 V 7 Nm Max. 95° 0.9 m, 4 × 0.75 mm² (fixed to housing) 90 s 15 s
Ambient temperature Ambient humidity
–32...55 °C < 95% rh
Weight Housing Housing material
1.3 kg Two-piece Cast aluminium
Type of protection Protection class EMC Directive 2014/30/EU
IP54 as per EN 60529 III as per IEC 60730 EN 61000-6-2, EN 61000-6-3
2.5 W, 2.5 VA
Parameters
Positioner
Ambient conditions
Construction
Standards and directives
CE conformity according to
Overview of types Type
Features
AKF113SF122
Rotary actuator with spring return and positioner
Accessories
318
Type
Description
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
Right of amendment reserved © 2024 Fr. Sauter AG
Control valves and butterfly valves SAUTER control valves are used to control heating and cooling systems. The 3‑way version is suitable for controlling and change-over functions, while the 4‑way version is employed for higher temperatures in the return circuit. SAUTER butterfly valves are very versatile and are used for control and shut-off functions. Because they close absolutely tightly, they reduce energy consumption.
Overview of control valves and butterfly valves
Type designation
M3R, M4R
MH32F, MH42F
DEF
Application Preheater for ventilation & air-conditioning Static heating Cooling tower Multi-boiler system
• • − −
• • − −
− − • •
Version Control valve Butterfly valve
• −
• −
− •
15...50 PN 10 AR30 W, ASM 105, 115, 124 ADM 322(S)
20...150 PN 6 AR30 W, ASM 105, 115, 124 ADM 322(S)
Page 320
Page 322
25...200 PN 16 AR30 W, A44 W, ASF 122, 123 ASM 124(S) ASM 134(S) ADM 322(S) Page 324
Technical data Nominal diameter (DN) Nominal pressure Combination options with actuator
Further information
Right of amendment reserved © 2024 Fr. Sauter AG
319
Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators
M3R, M4R: Control valve with threaded connection, PN 10 Features • M3R: 3-way valves with nominal diameters DN 15...50 • M4R: 4-way valves with nominal diameters DN 20...50 • Used in combination with the ADM 322 and ASM 105, 115, 124 motorised actuators • Manual adjustment by means of lever and end stops • Body, cover, front gate and spindle made of brass
M3R015F200
Technical data Parameters
V M3R0**F200
Nominal pressure Angle of rotation Valve characteristic Leakage rate
10 bar 90° Linear < 0.1%
Operating temperature Operating pressure
2...110 °C Max. 10 bar
Ambient conditions
M4R0**F200
Overview of types Type
Nominal diameter
Kvs value
Weight
M3R015F200
DN 15 (Rp½)
2.5 m³/h
0.8 kg
M3R020F200
DN 20 (Rp¾)
6 m³/h
0.7 kg
M3R025F200
DN 25 (Rp1)
12 m³/h
1.2 kg
M3R032F200
DN 32 (Rp1¼)
18 m³/h
1.2 kg
M3R040F200
DN 40 (Rp1½)
26 m³/h
2.2 kg
M3R050F200
DN 50 (Rp2)
40 m³/h
2.3 kg
M4R020F200
DN 20 (Rp¾)
6 m³/h
0.8 kg
M4R025F200
DN 25 (Rp1)
12 m³/h
1.2 kg
M4R032F200
DN 32 (Rp1¼)
18 m³/h
1.3 kg
M4R040F200
DN 40 (Rp1½)
26 m³/h
2.3 kg
M4R050F200
DN 50 (Rp2)
40 m³/h
2.5 kg
Accessories
320
Type
Description
0510240013
ADM322 mounting kit with M3R, M4R, MH32, MH42
0361977001
Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124
0361977002
Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Combination of M3R/M4R with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after control valve) at which the actuator reliably closes the valve by means of a return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.
Actuator Page
ASM105F100 334
ASM105F120 334
ASM105F122 334
ASM105SF132 336
ASM115F120 334
ASM115F122 334
ASM115SF132 336
Rotational torque
5 Nm
5 Nm
5 Nm
5 Nm
10 Nm
10 Nm
10 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point, 0...10 V 2-/3-point
2-/3-point
2-/3-point, 0...10 V
Running time
30 s
120 s
120 s
35/60/120 s
120 s
120 s
60/120 s
230 V~
24 V~
24 V =/~
230 V~
24 V~
24 V =/~
Operating voltage 230 V~ As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
M3R015F200
2.0
2.0
2.0
2.0
–
–
–
M3R020F200 M4R020F200
1.0
1.0
1.0
1.0
–
–
–
M3R025F200 M3R032F200 M3R040F200 M3R050F200 M4R025F200 M4R032F200 M4R040F200 M4R050F200
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Cannot be used as distribution valve Actuator
ADM322SF122 ADM322SF152
ASM124F120 ASM124F122
ASM124SF132
Page
ADM322F120 ADM322F122 ADM322HF120 ADM322HF122 ADM322PF120 ADM322PF122 330
332
340
345
Torque
15 Nm
15 Nm
18 Nm
15 Nm
Control signal
3-point
2-/3-point, 0...10 V
2-/3-point
2-/3-point, 0...10 V
Running time
120 s
30/60/120 s
120 s
60/120 s
24 VAC/DC
24 V=/~ / 230 V
24 V=/~ / 230 V
Operating voltage 24 V~/= / 230 V As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
M3R015F200
2.0
2.0
–
–
M3R020F200 M3R025F200 M4R020F200 M4R025F200
1.0
1.0
–
–
M3R032F200 M3R040F200 M3R050F200 M4R032F200 M4R040F200 M4R050F200
1.0
1.0
1.0
1.0
Cannot be used as distribution valve
A
Accessories required: Assembly materials; see accessories. With ASM 124, it is not possible to fit auxiliary contacts or a potentiometer
Right of amendment reserved © 2024 Fr. Sauter AG
321
V
Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators
MH32F, MH42F: Control valve with flange connection, PN 6 Features • MH32F: 3-way valves with nominal diameters DN 20...150 • MH42F: 4-way valves with nominal diameters DN 32...50 • Can be combined with motorised actuators ADM 322 and ASM 105, 115, 124 • Manual adjustment via lever • Body made of grey cast iron; brass gate
MH32F40F200
• Spindle made of brass up to DN 25 and stainless steel from DN 32 • Stuffing box with double O-ring guarantees the tightness of the seal at the spindle
Technical data
V
MH32F**F200
MH42F**F200
Parameters
Nominal pressure Angle of rotation Valve characteristic
6 bar 90° Linear
Operating temperature Operating pressure
2...110 °C Max. 6 bar
Ambient conditions
Overview of types 3-way control valve
4-way control valve
Type
Nominal diameter
Kvs value
Leakage rate in % of Kvs Weight
MH32F20F200
DN 20
12 m³/h
1%
2.7 kg
MH32F25F200
DN 25
18 m³/h
1%
3.5 kg
MH32F32F200
DN 32
28 m³/h
1%
4.6 kg
MH32F40F200
DN 40
44 m³/h
1%
5.6 kg
MH32F50F200
DN 50
66 m³/h
1%
7.9 kg
MH32F65F200
DN 65
100 m³/h
1%
9.2 kg
MH32F80F200
DN 80
150 m³/h
1%
14.2 kg
MH32F100F200 DN 100
225 m³/h
1%
19 kg
MH32F125F200 DN 125
310 m³/h
1%
25.8 kg
MH32F150F200 DN 150
420 m³/h
1%
35.5 kg
MH42F32F200
DN 32
28 m³/h
1.5 %
5.7 kg
MH42F40F200
DN 40
44 m³/h
1.5 %
7.1 kg
MH42F50F200
DN 50
66 m³/h
1.5 %
8.3 kg
A A A
MH32F20...25: 3-way valve: Zinc cover, brass spindle MH32F32...150: 3-way valve: Cover made of grey cast iron, spindle made of stainless steel MH42F32...50: 4-way valve: Cover made of grey cast iron, spindle made of stainless steel
Accessories
322
Type
Description
0360392020
Welding flange, DN 20, smooth, PN 6, incl. asbestos-free seal
0360392025
Welding flange, DN 25, smooth, PN 6, incl. asbestos-free seal
0360392032
Welding flange, DN 32, smooth, PN 6, incl. asbestos-free seal
0360392040
Welding flange, DN 40, smooth, PN 6, incl. asbestos-free seal
0360392050
Welding flange, DN 50, smooth, PN 6, incl. asbestos-free seal
0360392065
Welding flange, DN 65, smooth, PN 6, incl. asbestos-free seal
0360392080
Welding flange, DN 80, smooth, PN 6, incl. asbestos-free seal
0360392100
Welding flange, DN 100, smooth, PN 6, incl. asbestos-free seal
0360392125
Welding flange, DN 125, smooth, PN 6, incl. asbestos-free seal
0360392150
Welding flange, DN 150, smooth, PN 6, incl. asbestos-free seal
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Type
Description
0361977001
Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124
0361977002
Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115
0510240013
ADM322 mounting kit with M3R, M4R, MH32, MH42
Combination of MH32F/MH42F with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Max. admissible pressure drop in the event of a malfunction (pipe break after control valve) at which the actuator reliably closes the control valve using the return spring.
/
Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the control valve.
Pressure differences Actuator Page
ASM105F100 334
ASM105F120 334
ASM105F122 334
ASM105SF132 336
ASM115F120 334
ASM115F122 334
ASM115SF132 336
10 Nm
10 Nm
10 Nm
Rotational torque
5 Nm
5 Nm
5 Nm
5 Nm
Control signal
2-/3-point
2-/3-point
2-/3-point
2-/3-point, 0...10 V 2-/3-point
2-/3-point
2-/3-point, 0...10 V
Running time
30 s
120 s
120 s
35/60/120 s
120 s
120 s
60/120 s
230 V~
24 V~
24 V =/~
230 V~
24 V~
24 V =/~
Operating voltage 230 V~ As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
MH32F20F200 MH32F25F200 MH32F32F200 MH32F40F200
1.0
1.0
1.0
1.0
1.0
1.0
1.0
MH32F50F200 MH32F65F200 MH32F80F200
–
–
–
–
0.5
0.5
0.5
Cannot be used as distribution valve Actuator
ADM322SF122 ADM322SF152
ASM124F120 ASM124F122
ASM124SF132
Page
ADM322F120 ADM322F122 ADM322HF120 ADM322HF122 ADM322PF120 ADM322PF122 330
332
340
345
Torque
15 Nm
15 Nm
18 Nm
15 Nm
Control signal
3-point
2-/3-point, 0...10 V
2-/3-point
2-/3-point, 0...10 V
Running time
120 s
30/60/120 s
120 s
60/120 s
24 VAC/DC
24 V=/~ / 230 V
24 V=/~ / 230 V
Operating voltage 24 V~/= / 230 V As control valve
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
MH32F20F200 MH32F25F200 MH32F32F200 MH32F40F200 MH42F32F200 MH42F40F200
1.0
1.0
1.0
1.0
MH32F50F200 MH32F65F200 MH32F80F200 MH32F100F200 MH32F125F200 MH32F150F200 MH42F50F200
0.5
0.5
0.5
0.5
Cannot be used as distribution valve
A
Accessories required: Assembly materials; see accessories. With ASM 124, it is not possible to fit auxiliary contacts or a potentiometer
Right of amendment reserved © 2024 Fr. Sauter AG
323
V
Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators
DEF: Tight-sealing butterfly valve, PN 16 Features • For cutting off and regulating water and low-pressure steam up to 110 °C • Butterfly valve with 3-way brass bearing bush as spindle bearing • Fits PN 6, PN 10 and PN 16 flanges • Can be combined with motorised actuators of the ADM 322 and A44W type or damper actuators with
spring return of the ASM 124, 134 and ASF 122, 123 type Damper body made of grey cast iron • DEF100F200
• Collar made of ethylene-propylene rubber • Butterfly disc made of stainless steel • Spindle made of stainless steel with two O-rings
V
Technical data Parameters
Nominal pressure Valve characteristic Angle of rotation Leakage rate1)
16 bar Linear 90° < 0,0001% of the Kvs value
Operating temperature Maximum operating pressure
–10...130 °C 16 bar
Ambient conditions
Overview of types Type
Nominal diameter
Kvs value
Weight
DEF025F200
DN 25
36 m³/h
1 kg
DEF032F200
DN 32
40 m³/h
1.15 kg
DEF040F200
DN 40
50 m³/h
2.75 kg
DEF050F200
DN 50
85 m³/h
3.05 kg
DEF065F200
DN 65
215 m³/h
4.05 kg
DEF080F200
DN 80
420 m³/h
4.3 kg
DEF100F200
DN 100
800 m³/h
4.85 kg
DEF125F200
DN 125
1010 m³/h
7.2 kg
DEF150F200
DN 150
2100 m³/h
9.5 kg
DEF200F200
DN 200
4000 m³/h
12 kg
Accessories Type
Description
0361632***
Two welding flanges, complete PN 6 as per EN 1092-1 DN 25, DN 32, DN 40, DN 50, DN 65, DN 80, DN 100, DN 125, DN 150, DN 200
0361633***
Two welding flanges, complete PN 10 (DN 25...100) as per EN 1092-1 and PN 16 (DN 25...200) as per EN 1092-1 DN 25, DN 32, DN 40, DN 50, DN 65, DN 80, DN 100, DN 125, DN 150, DN 200
0361634200
2 welding flanges complete PN 10 (DN 200) as per EN 1092-1
0378110001
Assembly parts; DEF DN 25…65 for A44
0378111001
Assembly parts; DEF DN 80…125 for A44
0378112001
Assembly parts; DEF DN 150…200 for A44
0378113001
Assembly parts; DEF DN 25…100 for ASF122/123
0372455001
Assembly part; DEF DN25...65 for ASM 124/134
0372455002
Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134
0372455003
Assembly part; DEF DN150...200 for ASM 134
1)
324
At Δp 1.5 bar
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Type
Description
0510240014
ADM322 fitting kit with DEF DN20...65
0510240015
ADM322 fitting kit with DEF DN80...100
A
Ordering information: DN 25 = /025, DN 100 = /100
Combination of DEF with electric actuators
/ /
Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.
Definition of ∆p s: Max. admissible pressure drop in the event of a malfunction (pipe break after the damper) at which the actuator reliably closes the damper using the return spring.
/
Definition of ∆p max: Max. admissible pressure drop in control mode at which the actuator reliably opens and closes the damper.
V
Pressure differences Actuator
ADM322SF122 ADM322SF152
ASM124F120 ASM124F122
ASM124SF132
Page
ADM322F120 ADM322F122 ADM322HF120 ADM322HF122 ADM322PF120 ADM322PF122 330
332
340
345
Torque
15 Nm
15 Nm
18 Nm
15 Nm
Control signal
3-point
2-/3-point, 0...10 V
2-/3-point
2-/3-point, 0...10 V
Running time
120 s
30/60/120 s
120 s
60/120 s
24 VAC/DC
24 V=/~ / 230 V
24 V=/~ / 230 V
Operating voltage 24 V~/= / 230 V Closes against the pressure
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
DEF025F200 DEF032F200 DEF040F200 DEF050F200
10.0
10.0
10.0
10.0
DEF065F200
7.0
7.0
7.0
7.0
DEF080F200
4.0
4.0
4.0
4.0
DEF100F200
2.0
2.0
2.0
2.0
Cannot be used to close with the pressure Actuator
ASF122F122
ASF122F222
ASF123F122
ASF123SF122
Page
ASF122F120 ASF122F220 350
350
350
350
352
Torque
18 Nm
18 Nm
18 Nm
18 Nm
18 Nm
Control signal
2-point
2-point
2-point
3-point
0...10 V
Running time
90 s
90 s
90 s
90 s
90 s
Operating voltage 230 V~
24 V~
24V~
24V~
24V~
Closes against the pressure
∆pmax [bar]
∆pmax ∆ps [bar] [bar]
∆pmax ∆ps [bar] [bar]
∆pmax ∆ps [bar] [bar]
DEF025F200 DEF032F200 DEF040F200 DEF050F200
10.0
10.0
10.0
10.0
10.0
10.0
DEF065F200
7.0
7.0
7.0
7.0
7.0
DEF080F200
4.0
4.0
4.0
4.0
DEF100F200
2.0
2.0
2.0
2.0
∆ps [bar]
∆pmax [bar]
∆ps [bar]
10.0
10.0
10.0
10.0
7.0
7.0
7.0
7.0
7.0
4.0
4.0
4.0
4.0
4.0
4.0
2.0
2.0
2.0
2.0
2.0
2.0
Cannot be used to close with the pressure
Right of amendment reserved © 2024 Fr. Sauter AG
325
Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Actuator Page
A44W2F001
A44W2F020
A44W2SF001
ASM134SF132 345
Rotational torque
30 Nm
30 Nm
30 Nm
30 Nm
30 Nm
Control signal
3-point
3-point
0...10 V; 4...20 mA 0...10 V
3-point
Running time
120 s
120 s
120 s
120/240 s
120/240 s
24 V~
24V~
24 V~
230 V~
Operating voltage 230 V~ Closes against the pressure
V
ASM134F130 342
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
∆pmax [bar]
DEF025F200 DEF032F200 DEF040F200 DEF050F200
16.0
16.0
16.0
–
–
DEF065F200
16.0
16.0
16.0
7.0
7.0
DEF080F200 DEF100F200
10.0
10.0
10.0
7.0
7.0
DEF125F200
6.0
6.0
6.0
7.0
7.0
DEF150F200
5.0
5.0
5.0
6.0
6.0
DEF200F200
3.0
3.0
3.0
2.0
2.0
Cannot be used to close with the pressure
A
326
Accessories required: Assembly parts; see accessories
Right of amendment reserved © 2024 Fr. Sauter AG
Damper and rotary actuators SAUTER damper and rotary actuators provide a torque- and time-dependent cut-off facility for efficient energy use. They operate air dampers, shut-off dampers and multi-leaf dampers. The overload protection and the end position detector in the rotary actuators ensures the efficient use of energy. SAUTER rotary actuators can be used for controllers with a switching or continuous output.
Overview of damper and rotary actuators
Type designation
ADM322F12*
ADM322SF1*2
15 120 (240) 24, 230
15 30, 60 24
• − Page 329
• • Page 331
Technical data Torque (Nm) Running time for 90°/(s) Power supply (VAC) Control 3-point Positioner Further information
Type designation
ASM 105, 115
ASM 105S, 115S F132
ASM 105S, 115S F152
ASM 124
Technical data Torque (Nm) Running time (s) Power supply (V)
5, 10 30, 120 24, 230
5, 10 35, 60, 120 24
5, 10 3, 6 24
18 120 24, 230
• • − − − Page 334
• • • − − Page 336
• • • • − Page 338
• • − − − Page 340
Control 2-point 3-point Positioner High-speed Spring return Further information
Right of amendment reserved © 2024 Fr. Sauter AG
327
Type designation
ASM 134
ASM 124S, 134S
ASF 112, 113
ASF 113S
Technical data Torque (Nm) Running time (s) Power supply (V)
30 120, 240 230
15, 30 60, 120, 240 24, 230
7 90 24
7 90 24
− • − − − Page 342
• • • − − Page 344
• • − − • Page 346
− − • − • Page 348
Control 2-point 3-point Positioner High-speed Spring return Further information
Type designation
ASF 122, 123
ASF 123S
Technical data Torque (Nm) Running time (s) Power supply (V)
18 90 24, 230
18 90 230
• • − − • Page 350
− − • − • Page 352
Control 2-point 3-point Positioner High-speed Spring return Further information
328
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators
ADM 322: Rotary actuator Features • For operating control units such as control valves, butterfly valves etc. • For controllers with a switching output (2-point or 3-point control) • 15 Nm nominal torque and holding torque • Synchronous motor with electronic control unit and load-dependent cut-off
ADM322F12*
• Low operating noise • Direction of operation and running time can be set using coding switches • Gear unit can be disengaged for manual adjustment • Electrical parallel operation of up to five actuators possible • Numerous adapters enable the unit to be fitted onto defined non-SAUTER control valves
V
• Maintenance-free gearbox made of plastic and steel, and gearbox base-plates made of steel • Mounting columns made of aluminium
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Connections (screw terminals) ADM322(H, P)F120 ADM322(H, P)F122
± 20%, 50…60 Hz −10%…20% ± 15%
Power consumption Power consumption
Max. 1.5 mm2 < 2.2 W < 2.5 W
Operating noise1) Running time for 90° Response time Angle of rotation Rotational torque and holding torque
< 30 dB(A) (loaded) 120 (240) s < 200 ms Max. 95° 15 Nm
Operating temperature Storage and transport temperature Air humidity without condensation
−20…55 °C −40…80 °C 5…85% rh
Dimensions W × H × D Weight Fitting position
194 × 116 × 86 mm 1.5 Vertically upright to horizontal, not fitted upside down Three-part Flame retardant yellow/black plastic With break-outs, for metric screw fittings M20×1.5
Parameters
Ambient conditions
Construction
Housing Housing material Cable inlet
Standards and directives
Type of protection Protection class CE conformity according to
EMC Directive 2014/30/EU
Low-Voltage Directive 2014/35/EU
1)
IP54 (EN 60529) II (EN 60730-1), EN 60730-2-14 III (EN 60730-1), EN 60730-2-14 EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 60730-1 EN 60730-2-14
Operating noise with the slowest running time
Right of amendment reserved © 2024 Fr. Sauter AG
329
Valves, control valves, dampers, actuators | Damper and rotary actuators Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)
III II 2000 metres EN ISO 12100:2018
Overview of types
V
Type
Nominal voltage
Type
ADM322F120
230 V~
–
ADM322F122
24 V~/=
–
ADM322HF120
230 V~
Auxiliary contacts
ADM322HF122
24 V ~/=
Auxiliary contacts
ADM322PF120
230 V~
Potentiometer
ADM322PF122
24 V~/=
Potentiometer
Accessories
330
Type
Description
0510600001
Cable module, 1.2 m, 3-wire, PVC
0510600002
Cable module, 1.2 m, 3-wire, halogen-free
0510600003
Cable module, 1.2 m, 6-wire, PVC
0510600004
Cable module, 1.2 m, 6-wire, halogen-free
0510600005
Cable module, 5 m, 3-wire, PVC
0510600006
Cable module, 5 m, 3-wire, halogen-free
0510600007
Cable module, 5 m, 6-wire, PVC
0510600008
Cable module, 5 m, 6-wire, halogen-free
0510240013
ADM322 mounting kit with M3R, M4R, MH32, MH42
0510240014
ADM322 fitting kit with DEF DN20...65
0510240015
ADM322 fitting kit with DEF DN80...100
0510390002
Adapter set for control valve, Honeywell, DZ/ZR valves only
0510390003
Adapter set for control valve, Danfoss
0510390004
Adapter set for Caleffi control valve
0510390005
Adapter set for control valve, Coster
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators
ADM 322S: Rotary actuator with positioner Features • For operating control units such as control valves, butterfly valves etc. • For controllers with a continuous output • 15 Nm nominal torque and holding torque • ADM322SF122: Synchronous motor with electronic control unit and load-dependent cut-off
ADM322SF1*2
• ADM322SF152: Brushless DC motor with SUT (SAUTER Universal Technology) electronic control unit and
electronic, load-dependent cut-off • Low operating noise • Automatic recognition of applied control signal • With the built-in absolute distance measurement system, the position is always maintained in the case of
power failure
V
• The direction of operation, running time and control signal (voltage/current) can be adjusted via coding
switches • High-speed variant ADM322SF152 with 30 s or 60 s for angle of rotation 90° • Gear unit can be disengaged for manual adjustment • Easy re-initialisation using a coding switch • Electrical parallel operation of up to five actuators possible • Numerous adapters enable the unit to be fitted onto defined non-SAUTER control valves • ADM322SF152: Integrated forced operation can be set via coding switches (with selectable direction of
operation) • Maintenance-free gearbox made of plastic and steel, and gearbox base-plates made of steel • Mounting columns made of aluminium
Technical data Power supply
Power supply
24 VDC −10%…20% 24 VAC ± 20% (50…60 Hz)
ADM322SF122 positioner
Operating noise1) Response time Angle of rotation Rotational torque and holding torque Control signal y
ADM322SF152 positioner
Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI Max. admissible line resistance Control signal y
< 30 dB(A) (loaded) < 200 ms Max. 95° 15 Nm 0...10 V, Ri ≥ 50 kΩ, 0...20 mA, Ri ≤ 50 Ω 2...10 V (4...20 mA) 0…10 V, load ≥ 5 kΩ 0 or 10 V 0 or 20 mA 10 V 130 mV, 0.26 mA 20 mA 3Ω 0...10 V, Ri ≥ 50 kΩ, 4...20 mA, Ri ≤ 50 Ω 0…10 V, load ≥ 5 kΩ 0 or 10 V 4 or 20 mA 10 V 130 mV, 0.26 mA 20 mA
Parameters
Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI 1)
Operating noise with the slowest running time
Right of amendment reserved © 2024 Fr. Sauter AG
331
Valves, control valves, dampers, actuators | Damper and rotary actuators Max. admissible line resistance
3Ω
Operating temperature Storage and transport temperature Humidity without condensation
−20…55 °C −40…80 °C 5…85% rh
Connection terminals Cable inlet
Screw terminals, max. 1.5 mm² With break-outs, for metric screw fittings M20 × 1.5 Three-part Flame-retardant yellow/black plastic 194 × 166 × 86 mm Vertically upright to horizontal, not fitted upside down 1.5 kg
Ambient conditions
Construction
Housing Housing material Dimensions W × H × D Fitting position
V
Weight Standards and directives
Type of protection Protection class EMC Directive 2014/30/EU
CE conformity according to
Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)
IP54 (EN 60529) III (EN 60730-1), EN 60730-2-14 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1 EN 60730-2-14 III II 2000 m EN ISO 12100:2018
Overview of types Type
Description
ADM322SF122
Rotary actuator, continuous, 24 VDC/AC, running time 120 s, 15 Nm
ADM322SF152
Rotary actuator, continuous, 24 VDC/AC, running time 30 s, 15 Nm
Power consumption at nominal voltage Type ADM322SF122
Running time for 90° [s] 120
ADM322SF152
30 (60)
Status Active power P [W] Operation < 2.5 Standstill < 0.3 Sizing 3.0 Operation < 2.3 Standstill < 0.5 Sizing 3.0
Apparent power S [VA] 5.0 – 6.0 4.5 – 6.0
Accessories
332
Type
Description
0510600001
Cable module, 1.2 m, 3-wire, PVC
0510600002
Cable module, 1.2 m, 3-wire, halogen-free
0510600003
Cable module, 1.2 m, 6-wire, PVC
0510600004
Cable module, 1.2 m, 6-wire, halogen-free
0510600005
Cable module, 5 m, 3-wire, PVC
0510600006
Cable module, 5 m, 3-wire, halogen-free
0510600007
Cable module, 5 m, 6-wire, PVC
0510600008
Cable module, 5 m, 6-wire, halogen-free
0313529001
Split-range unit for setting sequences
0510240013
ADM322 mounting kit with M3R, M4R, MH32, MH42
0510240014
ADM322 fitting kit with DEF DN20...65
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Type
Description
0510240015
ADM322 fitting kit with DEF DN80...100
0510390002
Adapter set for control valve, Honeywell, DZ/ZR valves only
0510390003
Adapter set for control valve, Danfoss
0510390004
Adapter set for Caleffi control valve
0510390005
Adapter set for control valve, Coster
ADM322SF152 only Type
Description
0500420002
4…20 mA feedback module for valve actuators AVM321S and AVM322S
0500570003
Constant 230 V module for valve actuators AVM321S and AVM322S
V
Right of amendment reserved © 2024 Fr. Sauter AG
333
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASM 105, 115: Damper actuator Features • For controllers with switching output (2- and 3-point) • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Synchronous motor with electronic activation and cut-out • Maintenance-free
ASM105F122
• Suitable for all fitting positions
Technical data Parameters
V
Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time
Max. 95° Ø 8...16 mm, □ 6,5...12.5 mm Max. 300 HV < 30 dB (A) 200 ms
Ambient temperature1) Ambient humidity
–20...65 °C 5...85% rh, no condensation
Control
2-/3-point
Weight Housing
0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m long, 3 × 0.75 mm²
Ambient conditions
Function
Construction
Housing material Power cable Standards and directives
CE conformity according to
Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Directive 2006/95/EC Low-Voltage Directive 2014/35/EU2)
IP54 (EN 60529) III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 1050 EN 60730-1, EN 60730-2-14 Over-voltage category III Degree of contamination II
Overview of types Type
Rotational torque and holding torque
Running time for 90°
Power supply
Power consumption
ASM105F100
5 Nm
30 s
230 V~
2.4 W, 5.4 VA
ASM105F120
5 Nm
120 s
230 V~
2.0 W, 5.0 VA
ASM105F122
5 Nm
120 s
24 V~
1.6 W, 1.7 VA
ASM115F120
10 Nm
120 s
230 V~
2.0 W, 5.0 VA
ASM115F122
10 Nm
120 s
24 V~
1.6 W, 1.7 VA
1) 2)
334
Operating time approx. 80% up to 65 °C, 100% up to 55 °C Only for ASM1*5F1*0
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type
Description
0361977002
Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115
0372145001
Auxiliary change-over contacts, single
0372145002
Auxiliary change-over contacts, double
0372286001
Potentiometer, 130 Ω
0372286002
Potentiometer, 1000 Ω
0372286003
Potentiometer, 5000 Ω
0372300001
Torsion protection, long (230 mm)
0372301001
Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.
0372320001
Hexagon key as visualisation for position indicator
A A
Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator
V
Right of amendment reserved © 2024 Fr. Sauter AG
335
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASM 105S, 115S F132: Damper actuator with SAUTER Universal Technology (SUT) Features • For controllers with switching (2- and 3-point) or continuous output (0…10 V) • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Stepping motor with electronic activation and cut-out • Maintenance-free
ASM105SF132
• Intelligent adaptation of rotation angle, incl. feedback adjustment • Free configuration using the CASE Drive PC tool • Suitable for all fitting positions
V
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC
±20%, 51...60 Hz ±20%
Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time Control signal y Positional feedback signal y0 Starting point U0 Control span ΔU Switching range Xsh
Max. 95° Ø 8...16 mm, □ 6,5...12.5 mm Max. 300 HV < 30 dB (A) 200 ms 0...10 V, Ri > 100 kΩ 0...10 V; load > 10 kΩ 0 or 10 V 10 V 200 mV
Ambient temperature Ambient humidity
–20...55 °C < 95% rh, no condensation
Weight Housing
0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m long, 5 × 0.5 mm²
Parameters
Positioner
Ambient conditions
Construction
Housing material Power cable Standards and directives
Type of protection Protection class EMC Directive 2014/30/EU
CE conformity
IP54 (EN 60529) III (IEC 60730) EN 61000-6-1 EN 61000-6-3 EN 61000-6-4 EN 1050
Directive 2006/95/EC
Overview of types
336
Type
Rotational torque and holding tor- Running time for 90° que (Nm)
Power consumption
ASM105SF132
5
35/60/120 s
5.0 W, 9.0 VA
ASM115SF132
10
60/120 s
4.8 W, 8.7 VA
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type
Description
0313529001
Split-range unit for setting sequences
0361977002
Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115
0372145001
Auxiliary change-over contacts, single
0372145002
Auxiliary change-over contacts, double
0372286001
Potentiometer, 130 Ω
0372286002
Potentiometer, 1000 Ω
0372286003
Potentiometer, 5000 Ω
0372300001
Torsion protection, long (230 mm)
0372301001
Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.
0372320001
Hexagon key as visualisation for position indicator
A A
Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V
V
Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator
Right of amendment reserved © 2024 Fr. Sauter AG
337
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASM 105S, 115S F152: High-speed damper actuator with SAUTER Universal Technology (SUT) Features • For controllers with switching (2- and 3-point) or continuous output (0…10 V) • Brushless motor with electronic activation and cut-out • Intelligent adaptation of rotation angle • Electronic force-dependent cut-off • Direction of rotation selection via DIP switch
ASM115SF152
• Pulse length correction in 3-point operation, i.e. internal adjustment of start-up time • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment
V
• Maintenance-free • Fitting: Vertically upright to horizontal, not suspended
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC
±20%, 50…60 Hz +20%, -10%
Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise (unloaded) Response time Positioning signal y Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI Switching range Xsh
Max. 95° Ø 8…16 mm, □ 6.5…12.5 mm Max. 300 HV < 49 dB (A) 10 ms (electrically compensated) 0…10 V / 2…10 V, Ri = 100 kΩ, 0…20 mA / 4…20 mA, Ri = 500 Ω 0...10 V, load > 10 kΩ 0 or 10 V / 2 or 10 V 0 or 20 mA / 4 or 20 mA 10 V 100 mV 20 mA 0.1 mA
Operating temperature Storage and transport temperature Ambient humidity
−20…55 °C −30…65 °C 5…85% rh, no condensation
Dimensions W × H × D Weight Housing Housing material Power cable
70 × 63 × 133 mm 0.7 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 6 × 0.5 mm²
Type of protection Protection class
IP54 (EN 60529) III (EN 60730)
Parameters
Positioner
Ambient conditions
Construction
Standards, directives
338
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators CE conformity
EMC Directive 2014/30/EU
UL and CAN compliance (ASM105SF152U only)
Electrical safety
EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 UL 60730-1 Part 1, UL 60730-2-14 Part 2, CAN/CSA-E60730-1:02 Part 1 and Annex 1
Overview of types
/
Rotational torque and holding torque: Holding torque is typically 1.5 Nm when the actuator is without power
Type
Rotational torque and holding tor- Running time for 90° que
Power consumption
ASM105SF152
5 Nm
3s
6.0 W, 8.5 VA
ASM115SF152
10 Nm
6s
6.5 W, 9.0 VA
ASM105SF152U 3 Nm
3s
6.0 W, 8.5 VA
V
Accessories Type
Description
0313529001
Split-range unit for setting sequences
0361977002
Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115
0372300001
Torsion protection, long (230 mm)
0372301001
Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.
A
The UL compliances of the ASM105SF152U do not apply to the accessories
Right of amendment reserved © 2024 Fr. Sauter AG
339
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASM 124: Damper actuator Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) output • Synchronous motor with electronic activation and cut-out • Maintenance-free gear unit • Electronic end position detector and motor cut-off
ASM124F12*
• Self-centring spindle adapter for fitting onto damper spindle • Gear unit can be disengaged to position the damper and for manual adjustment • Suitable for all fitting positions • Threaded holes (M5) for fitting to bracket
V
• Version with halogen-free cable on demand
Technical data Power supply
Power supply 230 VAC Power supply 24 VAC
±15%, 50...60 Hz ±20%, 50...60 Hz
Rotational torque and holding torque Running time for 90° Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time
18 Nm 120 s Max. 95° Ø 12...20 mm, □ 10...16 mm Max. 300 HV < 30 dB (A) 200 ms
Ambient temperature Ambient humidity
−20...55 °C < 95% rh, no condensation
Weight Housing
1.2 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 3 × 0.75 mm²
Parameters
Ambient conditions
Construction
Housing material Power cable Standards, directives
Type of protection Protection class 230 V Protection class 24 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Mode of operation Software
IP40 (EN 60529), IP43 (EN 60529), IP54 (EN 60529), IP55 (EN 60529) II (EN 60730) III (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III II Type 1 AB (EN 60730) Type 1 C (EN 60730) A (EN 60730)
Overview of types
340
Type
Voltage
Power consumption
ASM124F120
230 V~
2.9 W, 5.6 VA
ASM124F122
24 V~
2.3 W, 2.4 VA
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators
A A A
Power consumption when idle: ASM124F120: 0.5 W, 5.1 VA ASM124F122: 0.03 W, 0.4 VA
Accessories Type
Description
0361977001
Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124
0370059000
Clamping lever for shaft, Ø 8...18 mm
0370990001
Auxiliary change-over contacts, single
0370990002
Auxiliary change-over contacts, double
0370992001
Potentiometer, 2000 Ω, 1 W
0370992002
Potentiometer, 130 Ω, 1 W
0372200001
Fitting bracket
0372201001
Spindle extension with coupling
0372202001
Lever, fitting strip
0372203001
Driver axle for auxiliary contacts
0372204001
Spindle for clamping lever 0370059000
0372455001
Assembly part; DEF DN25...65 for ASM 124/134
0372455002
Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134
A
V
Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V
Right of amendment reserved © 2024 Fr. Sauter AG
341
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASM 134: Damper actuator Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with a switching (3-point) output • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Stepping motor with electronic activation and cut-out
ASM134F130
• Direction of rotation changed by transposing the connections • Suitable for all fitting positions • Maintenance-free • Version with halogen-free cable on demand
V
Technical data Power supply
Power supply Power consumption
230 V~, ±15%, 50 Hz 3.7 W, 4.7 VA
Rotational torque and holding torque Running time for 90° Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time
30 Nm 120/240 s Max. 95° Ø 12...20 mm, □ 10...16 mm Max. 300 HV < 30 dB (A) 200 ms
Ambient temperature Ambient humidity
−20...55 °C < 95% rh, no condensation
Weight Housing
1.8 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 3 × 0.75 mm²
Parameters
Ambient conditions
Construction
Housing material Power cable Standards, directives
Type of protection
Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Mode of operation Software
IP40 (EN 60529) IP54 (EN 60529) IP55 (EN 60529) II (IEC 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III III Type 2 B (EN 60730) A (EN 60730)
Overview of types
342
Type
Rated power during continuous operation
Power consumption when idle
ASM134F130
3.7 W, 4.7 VA
1.1 W, 2.7 VA
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type
Description
0361977001
Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124
0370059000
Clamping lever for shaft, Ø 8...18 mm
0370990001
Auxiliary change-over contacts, single
0370990002
Auxiliary change-over contacts, double
0370992001
Potentiometer, 2000 Ω, 1 W
0370992002
Potentiometer, 130 Ω, 1 W
0372200001
Fitting bracket
0372201001
Spindle extension with coupling
0372202001
Lever, fitting strip
0372203001
Driver axle for auxiliary contacts
0372204001
Spindle for clamping lever 0370059000
0372455001
Assembly part; DEF DN25...65 for ASM 124/134
0372455002
Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134
0372455003
Assembly part; DEF DN150...200 for ASM 134
A
V
Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V
Right of amendment reserved © 2024 Fr. Sauter AG
343
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASM 124S, 134S: Damper actuator with SAUTER Universal Technology (SUT) Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) or continuous output (0…10 V) • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Stepping motor with electronic activation and cut-out
ASM1*4SF132
• Maintenance-free • Intelligent adaptation of rotation angle, incl. feedback adjustment • Direction of rotation changed by transposing the connections
V
• Suitable for all fitting positions • Version with halogen-free cable on demand
Technical data Power supply
Power supply 24 VAC Power supply 24 VDC1)
±20%, 50...60 Hz ±20%
Angle of rotation Admissible damper shaft (hardness) Operating noise Response time Control signal Positional feedback signal Starting point U0 Control span ΔU Switching range Xsh
Max. 95° Max. 300 HV < 30 dB(A) 200 ms 0...10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 or 10 V 10 V 200 mV
Ambient temperature Ambient humidity
−20...55 °C < 95% rh, no condensation
Weight Housing
1.6 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 2 × 0.75 mm²
Parameters
Positioner
Ambient conditions
Construction
Housing material Power cable Standards, directives
Type of protection Protection class EMC Directive 2014/30/EU Mode of operation Software
1)
344
IP40 (EN 60529), IP43 (EN 60529), IP54 (EN 60529) III (IEC 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 Type 1 AB (EN 60730) Type 1 C (EN 60730) A (EN 60730)
24 V= only for control signals 0...10 V
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Overview of types Type
Rotational torque
Holding torque
Running time for 90°
Power consumption Admissible damper shaft
ASM124SF132
15 Nm
15 Nm
60, 120 s
2.4 W, 4.4 VA
Ø 12...20 mm, □ 10...16 mm
ASM134SF132
30 Nm
30 Nm
120, 240 s
2.4 W, 4.3 VA
Ø 12...20 mm, □ 10...16 mm
A A A
Power consumption when idle: ASM124SF132: 0.25 W, 0.46 VA ASM134SF132: 0.26 W, 0.48 VA
Accessories Type
Description
0313529001
Split-range unit for setting sequences
0361977001
Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124
0370059000
Clamping lever for shaft, Ø 8...18 mm
0370990001
Auxiliary change-over contacts, single
0370990002
Auxiliary change-over contacts, double
0370992001
Potentiometer, 2000 Ω, 1 W
0370992002
Potentiometer, 130 Ω, 1 W
0372200001
Fitting bracket
0372201001
Spindle extension with coupling
0372202001
Lever, fitting strip
0372203001
Driver axle for auxiliary contacts
0372204001
Spindle for clamping lever 0370059000
0372455001
Assembly part; DEF DN25...65 for ASM 124/134
0372455002
Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134
0372455003
Assembly part; DEF DN150...200 for ASM 134
A
V
Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V
Right of amendment reserved © 2024 Fr. Sauter AG
345
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASF 112, 113: Damper actuator with spring return Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) output • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Maintenance-free
ASF112F122
• Suitable for all fitting positions
Technical data Power supply
V
Power supply 230 VAC Power supply 24 VAC Power supply 24...48 V=
±10%, 50...60 Hz ±20%, 50...60 Hz ±20%
Rotational torque and holding torque Angle of rotation Admissible damper shaft Running time for 90° motor Running time for 90° spring
7 Nm Max. 95° Ø 6.4...20.5 mm, □ 6.4...13 mm 90 s 15 s
Ambient temperature Ambient humidity
–32...55 °C 5...95% rh, no condensation
Housing Power cable
Cast aluminium 0.9 m, 0.75 mm²
Type of protection
IP54 (EN 60529), suspended IP42 (EN 60529), not suspended III (EN 60730) II (EN 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 II III
Parameters
Ambient conditions
Construction
Standards and directives
Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Degree of contamination Over-voltage categories
Overview of types Type
Control function
Voltage
Power consumption
Weight
ASF112F120
2-point
230 V~
4.5 W, 7.0 VA
1.2 kg
ASF112F122
2-point
24 V~/24...48 V=
3.5 W, 5.0 VA
1.2 kg
ASF112F220
2-point
230 V~
4.5 W, 7.0 VA
1.3 kg
ASF112F222
2-point
24 V~/24...48 V=
3.5 W, 5.0 VA
1.3 kg
ASF113F122
3-point
24 V~/24...48 V=
3.5 W, 5.0 VA
1.2 kg
A
346
ASF112F220, ASF112F222: Double auxiliary contacts 6(2) A; 24...250 V~ with cable 0.9 m; 6 × 0.75 mm²
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type
Description
0372245001
Lever adaptor for converting rotation into stroke
0372245002
Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
V
Right of amendment reserved © 2024 Fr. Sauter AG
347
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASF 113S: Damper actuator with spring return and positioner Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with a continuous output (0...10 V) • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Maintenance-free
ASF113SF122
• Suitable for all fitting positions
Technical data
V
Power supply
Power supply 24 VAC Power supply 24...48 V= Power consumption
±20%, 50...60 Hz ±20% 3.5 W, 5.0 VA
Running time for 90° motor Running time for 90° spring Rotational torque Holding torque Angle of rotation Admissible damper shaft Admissible damper surface area1) Control signal Positional feedback signal Admissible load Switching range Xsh Starting point U0 Control span ΔU
90 s 15 s 7 Nm 7 Nm Max. 95° Ø 6.4...20.5 mm, □ 6.4...13 mm 1.5 m2 0...10 V, Ri = 100 kΩ 0...10 V (0...100%) > 10 kΩ 0.2 V 0V 10 V
Ambient temperature Ambient humidity
–32...55 °C < 95% rh
Weight Housing Power cable
1.3 kg Cast aluminium 0.9 m, 4 × 0.75 mm²
Type of protection
IP54 (EN60529), suspended IP 42 (EN 60529), not suspended III (IEC 60730) II III EN 60730-1, EN 60730-2-14 EN 61000-6-2, EN 61000-6-3
Parameters
Positioner
Setting range
Ambient conditions
Construction
Standards and directives
Protection class Degree of contamination Over-voltage categories Low-Voltage Directive 2014/35/EU EMC Directive 2014/30/EU
Overview of types Type
Features
ASF113SF122
Damper actuator with spring return and positioner
1)
348
Recommended value for smooth-running air dampers
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type
Description
0372245001
Lever adaptor for converting rotation into stroke
0372245002
Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth
0510240001
Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B
V
Right of amendment reserved © 2024 Fr. Sauter AG
349
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASF 122, 123: Damper actuator with spring return Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) output • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Wear-free brushless motor
ASF122F122
• Maintenance-free • Change direction of rotation by simply turning the actuator • Suitable for all fitting positions
V
Technical data Power supply
Power supply 24 VAC Power supply 230 VAC Power supply 24...48 V=
±20%, 50...60 Hz ±10%, 50...60 Hz ±20%
Running time for 90° motor Running time for 90° spring Rotational torque and holding torque Angle of rotation Admissible damper shaft
90 s 15 s 18 Nm Max. 90° Ø 8...25 mm, □ 6...18 mm
Ambient temperature Ambient humidity
−32...55 °C 5...95% rh
Housing Power cable
Cast aluminium 0.9 m, 0.75 mm²
Type of protection
IP54 (EN60529), suspended IP42 (EN 60529), not suspended III (EN 60730) II (EN 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 III II
Parameters
Ambient conditions
Construction
Standards and directives
Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination
Overview of types Type
Control function
Voltage
Power consumption
Weight
ASF122F120
2-point
230 V~
6 W, 8 VA
2 kg
ASF122F122
2-point
24 V~/24...48 V=
5 W, 7 VA
2 kg
ASF122F220
2-point
230 V~
6 W, 8 VA
2.1 kg
ASF122F222
2-point
24 V~/24...48 V=
5 W, 7 VA
2.1 kg
ASF123F122
3-point
24 V~/24...48 V=
5 W, 7 VA
2 kg
A
350
ASF122F220, ASF122F222: With double auxiliary contacts 6(2) A; 24...250 V~; with cable 0.9 m; 6 × 0.75 mm²
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type
Description
0370997001
Lever adaptor for converting rotation into stroke
0370998001
Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth
0378113001
Assembly parts; DEF DN 25…100 for ASF122/123
V
Right of amendment reserved © 2024 Fr. Sauter AG
351
Valves, control valves, dampers, actuators | Damper and rotary actuators
ASF 123S: Damper actuator with spring return and positioner Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with a continuous output (0...10 V) • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Wear-free brushless motor
ASF123SF122
• Maintenance-free • Change direction of rotation by simply turning the actuator • Suitable for all fitting positions
V
Technical data Power supply
Power supply 24...48 V= Power consumption
±20% 5.4 W, 7.5 VA
Running time for 90° motor Running time for 90° spring Rotational torque and holding torque Angle of rotation Admissible damper shaft Control signal Positional feedback signal Admissible load Switching range Xsh Starting point U0 Control span ΔU
90 s 15 s 18 Nm Max. 95° Ø 8...25 mm, □ 6...18 mm 0...10 V, Ri = 100 kΩ 0...10 V (0...100%) > 10 kΩ 0.2 V 0V 10 V
Ambient temperature Ambient humidity
–32...55 °C < 95% rh
Weight Housing Power cable
2 kg Cast aluminium 0.9 m, 4 × 0.75 mm²
Type of protection1)
IP54 (EN60529), suspended IP42 (EN 60529), not suspended III (IEC 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 III II
Parameters
Positioner
Setting range
Ambient conditions
Construction
Standards and directives
Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination
Overview of types Type
Features
ASF123SF122
Damper actuator with spring return and positioner
1)
352
Depending on fitting position, ensure IP54
Right of amendment reserved © 2024 Fr. Sauter AG
Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type
Description
0370997001
Lever adaptor for converting rotation into stroke
0370998001
Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth
0378113001
Assembly parts; DEF DN 25…100 for ASF122/123
V
Right of amendment reserved © 2024 Fr. Sauter AG
353
HVAC automation
6 The new standard in building automation. SAUTER modulo 6 offers unprecedented performance in terms of data points, memory capacity and processing speed, all with minimal space requirements. The app with an augmented reality function shows real-time values and signal labels. Values can be adjusted via the touch screen. As an alternative to smartphone operation, the range also includes a local operating unit (LOI) with a high-resolution graphical colour display. The LOI is compatible with all available I/O modules and offers priority operation decoupled from the station. modulo 6 connects to the cloud and IoT just as securely as with the existing HVAC systems. BACnet/SC adds another security level to the product range. 354
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation HVAC automation EY6AS80: modular BACnet automation station and web server, modu680-AS
357
EY6AS60: modular BACnet automation station, modu660-AS
361
EY6LC01: Module for separate I/O module supply, modu601-LC
366
EY6LC02: Coupling kit for I/O modules in cabinet, modu602-LC
368
EY6LC12: IP coupler for I/O modules with web server, modu612‑LC
370
EY6IO30: 16 × DI/CI inputs I/O module, modu630-IO
373
EY6IO31: 8 × UI (DI/CI/AI), 8 × DI/CI I/O module, modu631-IO
375
EY6IO50: 6 x relay (2A) outputs I/O module, modu650-IO
377
EY6IO70: 8 × DI/CI/DO (OC) and 8 × DI/CI I/O module, modu670‑IO
379
EY6IO71: 8 × AO and 8 × DI/CI I/O module, modu671-IO
381
EY6IO72: 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module, modu672-IO
383
EY6LO00: Operating and indicating unit for I/O modules, modu600-LO
386
EY6CM20: Modbus/RTU (RS‑485) communication module, modu620‑CM
389
EY6CM30: M-Bus communication module, modu630‑CM
391
EY6RT30: BACnet router and SC hub, modu630-RT
394
Right of amendment reserved © 2024 Fr. Sauter AG
¨
355
SAUTER modulo 6 automation stations SAUTER modulo 6 automation stations regulate, control, monitor and optimise the energy efficiency in HVAC installations. The installation network is based on BACnet/IP – the communication protocol for networked building intelligence.
Overview of automation stations
Type designation Product name Parameters Power supply Connection of I/O and COM extension modules Interfaces, communication Interfaces Ethernet/LAN Ethernet/WAN SLC/RS-485 interfaces Modbus/RS-485 interfaces Protocols BACnet profile AMEV profile Objects Data points (BACnet objects) Historical data (Trend Log) Control (Loop) Sequences, scenes (Command) Calendars (Calendar) Time programmes (Schedule) Alarms (Notification Class) Further information
356
EY6AS80 modu680-AS
EY6AS60 modu660-AS
24 VDC ecoLink I/O modules, COM modules, ASV actuators, ecoUnit room operating units, EnOcean wireless interface 24 with modu601-LC (5 of which are COM modules) 2 × RS-485, WAN, LAN, REST API, Bluetooth, USB, microSD 3 × RJ45 (switched) 1 × RJ45
RS-485, LAN, REST API, Bluetooth, USB, microSD 2 × RJ45 (switched) −
1 1 BACnet/IP, SLC, Modbus RTU, HTTP(S), NTP, SMTP, SMPP B-BC AS-B 1600 I/O, 3200 total 1600 96
− BACnet/IP, SLC, HTTP(S), NTP, SMTP, SMPP
800 I/O, 1600 total 800 48 16 32 64 32
Page 357
Page 361
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6AS80: Modular BACnet automation station and web server, modu680-AS Features • Part of the SAUTER modulo 6 system family • Modular automation station, expandable with I/O modules and communication modules • Regulation, control, monitoring and optimisation of operational systems in HVAC • Locally expandable with up to 24 modules via the SAUTER Extension Bus • Can be locally equipped with ecoLink I/O modules and ASV actuators via SLC interface • RS-485 interface for field bus integration (Modbus/RTU / ASCII) • Four RJ45 connections for two separate IP networks (OT/IT; Operational/Information Technology). Three
EY6AS80F021
connections switched for daisy chain • BACnet/IP communication (EN ISO 16484-5) • BACnet profile B-BC • AMEV profile AS-B • REST API interface • MQTT interface (MQTT Broker/Client)
¨
• Integrated web server for local commissioning, visualisation and operation • User administration for identification, authentication and access control • Encryption of communication with TLS • Bluetooth interface for mobile commissioning and maintenance • Programming/parameterisation via PC using CASE Suite (based on IEC 61131-3) • Control libraries • Time and calendar function • Predictive control based on meteorological forecast data • Data recording on removable media (microSD card) • User administration and user identification (web server) • Alive signal output pulsed
Technical data Power supply
Power supply Power consumption1) Dissipated power Peak inrush current2)
24 VDC ± 10% ≤ 2 W without load ≤ 24 W at maximum load ≤ 2 W without load ≤ 4 W at maximum load ≤ 20 A, ≤ 1 ms on the 24 V side
Parameters
Connection
Battery (buffer: RTC) Earth connector
5-pin spring-type terminal, pluggable, 0.5...1.5 mm2 (rigid) 0.5...2.5 mm2, min. 8 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal
Ambient conditions
Operating temperature Storage and transport temperature
1) 2)
0…45 °C −20…70 °C
Maximum load with 12 I/O modules Measured value with EY-PS021F021 power supply unit
Right of amendment reserved © 2024 Fr. Sauter AG
357
HVAC automation | HVAC automation Ambient humidity
10…90% rh, no condensation
BACnet data point objects
Up to 1600 I/O objects, 3200 total 600 (Peer-to-Peer) 96 (Loop) 4800 128 (Structured View) 16 (Command) 64 (Schedule) 32 (Calendar) 32 (Notification Class) intrinsically or extrinsically with Event Enrolment 1600 (Trend Log) up to 4 million entries 32 32 moduWeb Unity, MQTT Commissioning Tool moduWeb Unity Number of topics/alias topics for BACnet objects max. 3200 Number of topics max. ??? (depending on CPU/memory resources) Number of client connections max. ??? SMTP, SMPP NTP client, BACnet master or client, local or UTC With modu615-BM
Function
BACnet
Dynamic objects
BACnet client links Control Active COV subscription Structured view Sequences, scenes Time programmes Calendar Notification Historical data
Services
BBMD in BDT FD in FDT Embedded web server Web API (REST) MQTT Client
¨
MQTT Broker
Notification (client) Time synchronisation Data integrity (client) Architecture
Processor RAM (memory) Flash Application data Processes (BACnet programs)
Cycle time
ARM Cortex A8, 32-bit, 1 GHz 512 MB (DDR3) 512 MB Via CASE Engine Supports separated processes with different cycle times and independent booting Adjustable for each process, min. 50 ms (50, 100, 500, 1000)
Interfaces, communication
Ethernet network #1 (WAN)
Communication protocols
Ethernet network #2 (LAN)
Ethernet network 10/100 BASE-T(X) Communication protocols
Connection, I/O and COM modules
Ethernet network 10/100 BASE-T(X) switched Use3)
RS-485 A connection
Communication protocol Bus physics Bus speed Connection
3)
358
HTTP(S), NTP, SMTP, SMPP, DHCP, MQTT/TCP(TLS), MQTT/WS(S) 1 × RJ45 connector 10/100 Mbit/s BACnet/IP (DIX), HTTP(S), NTP, SMTP, SMPP, DHCP, MQTT/TCP(TLS), MQTT/WS(S) 3 × RJ45 connector 10/100 Mbit/s 1 × integrated iSEB interface for max. 12 modules, expandable with modu601-LC for max. 24 modules in total Modbus/RTU / ASCII Modbus master according to V1.02 1 unit load (UL), electrically isolated 600...115,200 bit/s Parity bit, stop bit, Rx/Tx bus timing Spring-type terminal, pluggable 0.2...1.5 mm2 stiff/flexible
Performance-dependent
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation Line4) Use Participant Functions
RS-485 B connection
120 Ω bus termination and pullup/pull-down Communication protocol Use Participant Power supply
Connection Line Line length
Bluetooth
USB SD memory expansion
120 Ω bus termination and pullup/pull-down Version Range Frequency band Radiation Version Current limitation Type
3-/4-wire (D+/D−/COM reference), twisted, shielded, up to 1000 m Integration of Modbus slaves in an RS-485 segment (line) Up to 31 RS-485 unit loads (UL) Up to 600 Modbus channels for BACnet I/O/V objects for up to 247 Modbus devices; FC01-06, 15, 16, 22; unicast and broadcast; access optimisation Switchable via software (CASE Engine) SLC master ecoLink, ASV, ecoUnit, FCCP200 Max. 8 ecoLink modules and 4 ecoUnit modules, max. 12 ASV units 20…26 V=, max. 1.5 W, protected against short circuit, can be switched on/off (CASE Sun) Spring-type terminal, pluggable 0.2...1.5 mm2 stiff/flexible 4-wire, twisted, shielded Max. 100 m (30 m) with ecoUnit or ASV, up to 500 m, bus termination necessary (120 Ω) Switchable via software (CASE Sun)
¨
BLE 4.0 < 10 m 2.402…2.480 GHz 6 mW 2.0, type A 400 to max. 500 mA microSD, suitable for industrial use
Construction
Fitting
Dimensions W × H × D Weight
On metallic DIN rail 35 × 7.5/15 as per EN 60715. Rail housing as per DIN 43880 92.6 (5 HP) × 100.9 × 58.3 mm 260 g
Standards, directives
Type of protection
Protection class Environment class Software class5) Temperature controller class
CE/UKCA conformity6)
BACnet profile AMEV profile EMC-D 2014/30/EU (CE)
EMC-2016 (UKCA) LV-D 2014/35/EU (CE)
4) 5) 6)
Connections: IP00 Front in DIN cut-out: IP30 (EN 60730-1) I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) I to VIII = up to 5% as per 2009/125/EC, 2010/30/EU & 811/2013 (EU) B-BC (ISO 16484-5) AS-B EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 See EMC Directive EN 60730-1, EN 60730-2-9, EN 60950-1
Performance-dependent The product is not suitable for safety functions Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
359
HVAC automation | HVAC automation EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
See LVD EN 300328 (V2.1.1) EN 300328 (V2.1.1) EN IEC 63000 EN IEC 63000
Overview of types Type
Features
EY6AS80F021
Modular BACnet automation station and web server
Accessories Plug-in I/O modules
¨
Type
Description
EY6IO30F001
modu630-IO 16 × DI/CI inputs I/O module
EY6IO70F001
modu670-IO 8 × DI/CI/DO(OC), 8 × DI/CI I/O module
EY6IO31F001
modu631-IO 8 × UI(DI/CI/AI), 8 × DI/CI I/O module
EY6IO71F001
modu671-IO 8 × AO, 8 × DI/CI I/O module
EY6IO50F001
modu650-IO 6 × relay (2 A) outputs I/O module
EY6IO72F001
modu672-IO 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module
Connection modules Type
Description
EY6LC01F001
Module for separate I/O module supply
EY6LC02F001
Coupling kit for I/O modules in cabinet (P100017761 and P100017762)
EY6LC12F011
IP coupler for I/O modules with web server, modu612‑LC
Spare parts Type
Description
0929360602
AS bus cover with resistor, 5 pcs.
Function expansions Type
Description
Y6WS80F007
Activation code for reporting for modu680-AS
Y6WS80F008
Activation code for the REST API on modu680-AS
Y6WS80F009
Data point extension activation code for moduWeb Unity on modu680-AS
Y6WS80F031
Activation code for network option for modu680-AS
Y6FX02F001
Activation code for MQTT client
Y6FX02F002
Activation code for MQTT client and broker
Y6FX03F001
Activation code for RADIUS Supplicant
Y6FX04F001
Activation code for BACnet/SC DataLink
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
360
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6AS60: Modular BACnet automation station, modu660-AS Features • Part of the SAUTER modulo 6 system family • Modular automation station, expandable with I/O modules and communication modules • Regulation, control, monitoring and optimisation of operational systems in HVAC • Locally expandable with up to 24 modules via the SAUTER Extension Bus • Can be locally equipped with ecoLink I/O modules and ASV actuators via SLC interface • Two RJ45 connections switched for daisy chain • BACnet/IP communication (EN ISO 16484-5)
EY6AS60F011
• BACnet profile B-BC • AMEV profile AS-B • REST API interface • MQTT interface (MQTT Broker/Client) • Integrated web server for local commissioning, expandable with visualisation and operation • User administration for identification, authentication and access control
¨
• Encryption of communication with TLS • Bluetooth interface for mobile commissioning and maintenance • Programming/parameterisation via PC using CASE Suite (based on IEC 61131-3) • Control libraries • Time and calendar function • Predictive control based on meteorological forecast data • Data recording on removable media (microSD card) • User administration and user identification (web server) • Alive signal output pulsed
Technical data Power supply
Power supply Power consumption1) Dissipated power Peak inrush current2)
24 VDC ± 10% ≤ 2 W without load ≤ 24 W at maximum load ≤ 2 W without load ≤ 4 W at maximum load ≤ 20 A, ≤ 1 ms on the 24 V side
Parameters
Connection
Battery (buffer: RTC) Earth connector
5-pin spring-type terminal, pluggable, 0.5...1.5 mm² 0.5...2.5 mm², min. 8 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal
Ambient conditions
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
BACnet data point objects
Up to 800 I/O objects, 1600 total
Function
1) 2)
Maximum load with 12 I/O modules Measured value with EY-PS021F021 power supply unit
Right of amendment reserved © 2024 Fr. Sauter AG
361
HVAC automation | HVAC automation
Dynamic objects
Services
BACnet client links Control Active COV subscription Structured view Sequences, scenes Time programmes Calendar Notification
300 (Peer-to-Peer) 48 (Loop) 2400 128 (Structured View) 16 (Command) 64 (Schedule) 32 (Calendar) 32 (Notification Class) intrinsically or extrinsically with Event Enrolment 800 (Trend Log) up to 2 million entries 32 32 moduWeb Unity, MQTT Commissioning Tool moduWeb Unity Number of topics / alias topics for max. number of BACnet objects (600) Number of topics, depending on CPU/memory resources (> 1000) SMTP, SMPP NTP client, BACnet master or client, local or UTC With modu615-BM
Historical data BBMD in BDT FD in FDT Embedded web server Web API (REST) MQTT Client MQTT Broker Notification (client) Time synchronisation
¨
Data integrity (client) Architecture
Processor RAM (memory) Flash Application data Processes (BACnet programs)
ARM Cortex A8, 32-bit,1 GHz 512 MB (DDR3) 512 MB Via CASE Engine Supports separated processes with different cycle times and independent booting Adjustable via process, min. 50 ms (50, 100, 500, 1000)
Cycle time
Interfaces, communication
Ethernet network (LAN)
Communication protocols
Connection, I/O and COM modules
Ethernet network 10/100 BASE-T(X) switched Use3)
RS-485 B connection
Communication protocol Use Participant Power supply
Connection Line Line length
Bluetooth
3)
362
120 Ω bus termination and pullup/pull-down Version Range Frequency band
BACnet/IP (DIX), HTTP(S), NTP, SMTP, SMPP, DHCP, MQTT/TCP(TLS), MQTT/WS(S) 2 × RJ45 connector 10/100 Mbit/s 1 × integrated iSEB interface for max. 12 modules, expandable with modu601-LC for max. 24 modules in total SLC master ecoLink, ASV, ecoUnit, FCCP 200 Max. 8 ecoLink modules and 4 ecoUnit modules, max. 12 ASV units 20…26 VDC, max. 1.5 W, protected against short circuit, can be switched on/off (CASE Sun) Spring-type terminal, pluggable 0.2...1.5 mm² rigid/flexible 4-wire, twisted, shielded Max. 100 m (30 m) with ecoUnit or ASV, up to 500 m, bus termination necessary (120 Ω) Switchable via software (CASE Sun) BLE 4.0 < 10 m 2.402…2.480 GHz
Performance-dependent
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
USB SD memory expansion
Radiation Version Current limitation Type
6 mW 2.0, type A 400 to max. 500 mA microSD, suitable for industrial use
Fitting
On metallic DIN rail 35 × 7.5/15 as per EN 60715 Rail housing as per DIN 43880 92.6 (5 HP) x 100.9 x 58.3 mm 240 g
Construction
Dimensions W × H × D Weight Standards, directives
Type of protection
Protection class Environment class Software class4) Temperature controller class
CE/UKCA conformity5)
BACnet profile AMEV profile EMC-D 2014/30/EU (CE)
EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
Connections: IP00 Front in DIN cut-out: IP30 (EN 60730-1) I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) I to VIII = up to 5% as per 2009/125/EC, 2010/30/EU & 811/2013 (EU) B-BC (ISO 16484-5) AS-B EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 See EMC Directive EN 60730-1, EN 60730-2-9, EN 60950-1 EN 60730-1, EN 60730-2-9, EN 60950-1 EN 300328 (V2.1.1) EN 300328 (V2.1.1) EN IEC 63000
¨
EN IEC 63000
Overview of types Type
Description
EY6AS60F011
Modular BACnet automation station and web server
Accessories Plug-in I/O modules Type
Description
EY6IO30F001
modu630-IO 16 × DI/CI inputs I/O module
EY6IO31F001
modu631-IO 8 × UI(DI/CI/AI), 8 × DI/CI I/O module
EY6IO50F001
modu650-IO 6 × relay (2 A) outputs I/O module
EY6IO70F001
modu670-IO 8 × DI/CI/DO(OC), 8 × DI/CI I/O module
EY6IO71F001
modu671-IO 8 × AO, 8 × DI/CI I/O module
EY6IO72F001
modu672-IO 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module
4) 5)
The product is not suitable for safety functions Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
363
HVAC automation | HVAC automation Connection modules Type
Description
EY6LC01F001
Module for separate I/O module supply
EY6LC02F001
Coupling kit for I/O modules in cabinet (P100017761 and P100017762)
EY6LC12F011
IP coupler for I/O modules with web server, modu612‑LC
Spare parts Type
Description
0929360602
AS bus cover with resistor, 5 pcs.
Function expansions
¨
Type
Description
Y6WS60F007
Activation code for reporting for modu660-AS (requires Y6WS60F021)
Y6WS60F008
Activation code for the REST API on modu660-AS (requires Y6WS60F021)
Y6WS60F009
Data point extension activation code for moduWeb Unity on modu660 AS (requires Y6WS60F021)
Y6WS60F021
Activation code for visualisation on modu660 AS
Y6FX02F001
Activation code for MQTT client
Y6FX02F002
Activation code for MQTT client and broker
Y6FX03F001
Activation code for RADIUS Supplicant
Y6FX04F001
Activation code for BACnet/SC DataLink
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
364
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
Right of amendment reserved © 2024 Fr. Sauter AG
SAUTER modulo 6 connection modules The SAUTER modulo 6 connection modules offer more flexibility in the cabinet installation (modu602‑LC) and more freedom for a decentralised topology (modu612‑LC). The modu601‑LC ensures the functionality of the I/O modules if the operation of the automation station is interrupted.
Overview of connection modules
Type designation Product name Power supply IP network interfaces I/O and COM extension modules Cloud Connector Further information
EY6LC01F001 modu601-LC 24 VDC − −
EY6LC02F001 modu602-LC − − −
− Page 366
− Page 368
Right of amendment reserved © 2024 Fr. Sauter AG
EY6LC12F011 modu612-LC 24 VDC 2 (switch) Max. 24 (of which 5 are COM modules) MQTT Page 370
365
HVAC automation | HVAC automation
EY6LC01: Module for separated I/O module supply, modu601-LC Features • Part of the SAUTER modulo 6 system family • Enables separate supply between automation station and I/O modules • Power supply of I/O modules and connected LOI units (Local Override and Indication Device) • Allows extension to up to 24 I/O modules • Enables simple wiring tests of the I/O modules without the station, together with modu600-LO on the I/O
modules EY6LC01
Technical data Power supply
¨
Power supply Dissipated power Power consumption Peak inrush current1)
24 V= ± 10% < 0.5 W < 19 W at max. load ≤ 2 A, ≤ 10 ms
Connection
3-pin spring-type terminal, pluggable, 0.5...1.5 mm2 (rigid) 0.5...2.5 mm2, min. 8 mm wire stripped
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C −25...70 °C 10...90% rh, no condensation
Connection, I/O bus
6-pin spring contacts left and 7-pin right Spring contact against DIN rail and PE feed connection
Parameters
Ambient conditions
Interfaces, communication
Earth connector
Construction
Fitting
On metal DIN rail 35 × 7.5/15 as per EN 60715 DIN rail housing as per DIN 43880 56 × 97 × 59 mm 98 g
Dimensions W × H × D Weight Standards, directives
Protection type (as per EN 60730)
CE conformity according to
Protection class Environment class EMC Directive 2014/30/EU
Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Overview of types Type
Description
EY6LC01F001
Module for separate I/O module supply
1)
366
Measured value with EY‑PS021F021 power supply unit
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
¨
Right of amendment reserved © 2024 Fr. Sauter AG
367
HVAC automation | HVAC automation
EY6LC02: Coupling kit for I/O modules in cabinet, modu602LC Features • Part of the SAUTER modulo 6 system family • Arrangement of I/O modules in up to three rows for space-optimised cabinet installation • Minimum space requirement of the transmitter and receiver modules (1.5 HP) • Up to two modu602-LC per station
Technical data EY6LC02
Power supply
Power supply Dissipated power
From AS or LC via I/O bus < 0.3 W incl. 3 m cable
Max. number per station Max. cable length per station
2 3m
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C −25...70 °C 10...90% rh, no condensation
Connection Cable type
RJ45 connector RJ45 type S/FTP, not crossed, at least AWG 24 P100017761: 7-pin spring contacts, only left P100017762: 7-pin spring contacts, only right Spring contact against DIN rail
Parameters
¨
Ambient conditions
Interfaces, communication
Connection, I/O bus
Earth connector Construction
Fitting
On metal DIN rail 35 × 7.5/15 as per EN 60715 DIN rail housing as per DIN 43880 27 × 97 × 59 mm 95 g
Dimensions W × H × D Weight1) Standards, directives
Protection type (as per EN 60730) Protection class Environment class EMC Directive 2014/30/EU
CE conformity according to
Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Overview of types Type
Description
EY6LC02F001
Coupling kit for I/O modules in cabinet (P100017761 and P100017762)
Manuals Document number D100397589 D100408512 1)
368
Language de de
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I
Total weight
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation Document number D100402674 D100410201 D100402676 D100410203
Language en en fr fr
Title SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
¨
Right of amendment reserved © 2024 Fr. Sauter AG
369
HVAC automation | HVAC automation
EY6LC12: IP coupler for I/O modules, with web server, modu612‑LC Features • Part of the SAUTER modulo 6 system family • Enables decentralised installation and connection of the modulo 6 COM and IO modules with the
automation station via IP network • Locally expandable with up to 10 modules • Two RJ45 connections switched for daisy chain • Integrated web server for local commissioning
EY6LC12F011
• Bluetooth interface for mobile commissioning and maintenance • User administration and user identification (web server)
Technical data Power supply
Power supply Power consumption1)
¨
24 VDC ± 10% ≤ 2 W without load ≤ 24 W at maximum load ≤ 2 W without load ≤ 4 W at maximum load ≤ 20 A, ≤ 1 ms on the 24 V side
Dissipated power Peak inrush current2) Parameters
Connection
3-pin spring-type terminal, pluggable, 0.5...1.5 mm² (rigid) 0.5...2.5 mm², min. 8 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal
Battery (buffer: RTC) Earth connector
Ambient conditions
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
Processor Embedded web server Application data
ARM Cortex A8, 32-bit, 600 MHz moduWeb Unity From the automation station
Ethernet network 10/100 BASE-T(X) switched
2 × RJ45 connector, switched 10/100 Mbit/s
Dimensions W × H × D Fitting
92.6 (5 HP) × 97 × 58.3 mm On metal DIN rail 35 × 7.5/15 as per EN 60715. Rail housing as per DIN 43880
Type of protection
Connections: IP00 Front in DIN cut-out: IP30 (EN 60730-1) I (IEC 60730-1) 3K3 (IEC 60721)
Architecture
Interfaces, communication
Ethernet network
Construction
Standards, directives
Protection class Environment class 1) 2)
370
Maximum load with 12 I/O modules Measured value with EY-PS021F021 power supply unit
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation Software class Energy class
CE/UKCA conformity3)
EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
A (EN 60730-1, Appendix H) I to VIII = up to 5% as per EU 811/2013, 2010/30/EU, 2009/125/EC EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 See EMC Directive EN 60730-1, EN 60730-2-9, EN 62479 EN 60730-1, EN 60730-2-9, EN 62479 EN 300328 (V2.1.1) EN 300328 (V2.1.1) EN IEC 63000 EN IEC 63000
Overview of types Type
Description
EY6LC12F011
IP coupler for I/O modules, with web server
¨
Accessories Plug-in I/O modules Type
Description
EY6IO30F001
modu630-IO 16 × DI/CI inputs I/O module
EY6IO31F001
modu631-IO 8 × UI(DI/CI/AI), 8 × DI/CI I/O module
EY6IO50F001
modu650-IO 6 × relay (2 A) outputs I/O module
EY6IO70F001
modu670-IO 8 × DI/CI/DO(OC), 8 × DI/CI I/O module
EY6IO71F001
modu671-IO 8 × AO, 8 × DI/CI I/O module
EY6IO72F001
modu672-IO 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module
Plug-in communication modules (COM) Type
Description
EY6CM20F011
Modbus/RTU (RS-485) communication module
EY6CM30F031
modu630-CM M-Bus communication module
Connection modules Type
Description
EY6LC01F001
Module for separate I/O module supply
EY6LC02F001
Coupling kit for I/O modules in cabinet (P100017761 and P100017762)
3)
Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
371
SAUTER modulo 6 I/O modules SAUTER I/O modules are compatible with the modulo 6 series and are used to capture digital and analogue signals in HVAC installations. They control devices such as contactors, relays and valve actuators.
Overview of I/O modules
Type designation Product name Power supply Control panel optional
EY6IO30F001 modu630 From AS modulo 6 modu600-LO
EY6IO31F001 modu631 From AS modulo 6 modu600-LO
EY6IO50F001 modu650 From AS modulo 6 modu600-LO
Further information
16 − − − − Page 373
8 8 − − − Page 375
− − 6 − − Page 377
Type designation Product name Power supply Control panel optional
EY6IO70F001 modu670 From AS modulo 6 modu600-LO
EY6IO71F001 modu671 From AS modulo 6 modu600-LO
EY6IO72F001 modu672 From AS modulo 6 modu600-LO
8 − − − 8 Page 379
8 − − 8 − Page 381
− 4 4 4 − Page 383
Inputs/outputs Digital inputs Universal inputs Digital outputs Analogue outputs Digital inputs/outputs
Inputs/outputs Digital inputs Universal inputs Digital outputs Analogue outputs Digital inputs/outputs Further information
372
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6IO30: 16 × DI/CI inputs I/O module, modu630-IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC
link coupler • Receiving digital inputs (alarm, status or pulse counter) in operational systems, e.g. in HVAC engineering • 16 digital inputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module
(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)
EY6IO30F001
Technical data Power supply
Power supply Dissipated power1)
From AS or LC via I/O bus ≤ 0.8 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
Number of inputs Power supply for DI Pulse counter2)
16 Internal, ~13 V= ≤ 50 Hz
Connection, LOI Connection, I/O bus Connection terminals
4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail
¨
Ambient conditions
Inputs/outputs
Digital inputs (DI/CI)
Interfaces, communication
Earth connector Construction
Fitting Dimensions W × H × D Weight
On metal DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 130 g
Standards, directives
Protection type (as per EN 60730)
CE conformity according to
Environment class Software class3) EMC Directive 2014/30/EU
Connections and terminals: IP00 Front in DIN cut-out: IP30 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Overview of types Type
Features
EY6IO30F001
16 x DI/CI inputs I/O module
1) 2) 3)
Measured value without accessories 50 Hz only with PC module, otherwise 5 Hz The product is not suitable for safety functions
Right of amendment reserved © 2024 Fr. Sauter AG
373
HVAC automation | HVAC automation Accessories Type
Description
EY6LO00F001
Local operating and indicating unit for I/O modules
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
¨
374
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6IO31: 8 × UI (DI/CI/AI), 8 × DI/CI I/O module, modu631IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC
link coupler • Receiving digital inputs (alarm, status or pulse counter) and analogue inputs (Ni/Pt1000, R, U) in
operational systems, e.g. in HVAC • Eight digital inputs and eight universal inputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module
(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)
EY6IO31F001
Technical data Power supply
Power supply Dissipated power1)
From AS or LC via I/O bus ≤ 0.8 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
Number of inputs Power supply for DI Pulse counter Number of inputs Analogue Digital2)
8 Internal, ~13 V= ≤ 50 Hz 8 0...10 V, Ni1000, Pt1000, R DI/CI: ≤ 50 Hz
Connection, LOI Connection, I/O bus Connection terminals
4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail
¨
Ambient conditions
Inputs/outputs
Digital inputs (DI/CI)
Universal inputs (UI)
Interfaces, communication
Earth connector Construction
Fitting Dimensions W × H × D Weight
On metal DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 131 g
Standards, directives
Protection type (as per EN 60730)
CE conformity according to
1) 2) 3)
Protection class Environment class Software class3) EMC Directive 2014/30/EU
Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Measured value without accessories DI: 50 Hz only with PC module, otherwise 5 Hz The product is not suitable for safety functions
Right of amendment reserved © 2024 Fr. Sauter AG
375
HVAC automation | HVAC automation Overview of types Type
Features
EY6IO31F001
8 x UI(DI/CI/AI) and 8 x DI/CI I/O module
Accessories Type
Description
EY6LO00F001
Local operating and indicating unit for I/O modules
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
¨
376
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6IO50: 6 × relay (2A) outputs I/O module, modu650‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC
link coupler • Activation of displays in operational systems, such as HVAC engineering • Activation of actuators such as contactors or valve actuators, in operational systems • Six digital outputs (relay) • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module
(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)
EY6IO50F001
Technical data Power supply
Power supply Dissipated power1)
From AS or LC via I/O bus ≤ 1,3 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
Number of outputs Type of outputs
6 Relay (0-I), normally-open contact, galvanically isolated 24 VDC, 24...250 VAC Resistive load: 2 A Inductive load: ≤ 1 A, cos φ ≥ 0.8 Start-up current: ≤ 5 A 300,000 cycles for 2 A
¨
Ambient conditions
Inputs/outputs
Digital outputs (DO)
Load
Switching frequency, mechanical Interfaces and communication
Connection, LOI Connection, I/O bus Connection terminals Earth connector
4-pin 7-pin, spring contact 6 x 2-pin spring-loaded plug-in connectors Spring contact against DIN rail
Construction
Fitting Dimensions W × H × D Weight
On metallic DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 124 g
Standards and directives
Protection type (as per EN 60730)
CE conformity according to
Protection class Environment class Software class2) EMC Directive 2014/30/EU
Low-Voltage Directive 2014/35/EU 1) 2)
Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 EN 60730-1
Measured value without accessories The product is not suitable for safety functions
Right of amendment reserved © 2024 Fr. Sauter AG
377
HVAC automation | HVAC automation Overview of types Type
Features
EY6IO50F001
6 x relay (2 A) outputs I/O module
Accessories Type
Description
EY6LO00F001
Local operating and indicating unit for I/O modules
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
¨
378
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6IO70: 8 × DI/CI/DO (OC) and 8 × DI/CI I/O module, modu670‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC
link coupler • Activation of actuators such as relays and displays of operational systems, e.g. in HVAC engineering • Activation of displays in operational systems • Receiving digital inputs (alarm, status or pulse counter) in operational systems • Eight digital inputs and eight digital inputs/outputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module
EY6IO70F001
(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)
Technical data
¨
Power supply
Power supply Dissipated power1)
From AS or LC via I/O bus ≤ 0,8 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
Number of inputs Pulse counter2) Number of inputs/outputs Type of inputs/outputs
8 ≤ 50 Hz 8 Open collector, normally-open contacts (0-I), outputs switched with respect to ground (any arrangement) External, positive ≤ 28 V= 0...100 mA (max. 2 V voltage drop) Internal, ~13 V= ≤ 50 Hz
Ambient conditions
Inputs/outputs
Digital inputs (DI/CI) Digital inputs/outputs (DIO)
Power supply for DO Load Power supply for DI Pulse counter3) Interfaces and communication
Connection, LOI Connection, I/O bus Connection terminals Earth connector
4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail
Construction
Fitting Dimensions W × H × D Weight
On metallic DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 131 g
Standards and directives
Protection type (as per EN 60730) Protection class 1) 2) 3)
Connections and terminals:IP00 Front in DIN cut-out:IP30 I
Measured value without accessories 50 Hz only with PC module, otherwise 5 Hz 50 Hz only with PC module, otherwise 5 Hz
Right of amendment reserved © 2024 Fr. Sauter AG
379
HVAC automation | HVAC automation Environment class Software class4) EMC Directive 2014/30/EU5)
CE conformity according to
3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Overview of types Type
Features
EY6IO70F001
8 x DI/CI/DO(OC) and 8 x DI/CI I/O module
Accessories Type
Description
EY6LO00F001
Local operating and indicating unit for I/O modules
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
¨
4) 5)
380
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
The product is not suitable for safety functions EN 61000-6-2: To comply with the standard, the connecting cables for the digital open collector outputs (DO-OC) may not be longer than 30 m
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6IO71: 8 × AO and 8 × DI/CI I/O module, modu671‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC
link coupler • Activation with a standard signal (0(2)...10 V) in operational systems, such as HVAC engineering • Receiving digital inputs (alarm, status or pulse counter) in operational systems • Eight digital inputs and eight analogue outputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module
(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)
EY6IO71F001
Technical data Power supply1)
Power supply Power consumption Dissipated power
From AS or LC via I/O bus ≤1W ≤ 0,8 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
Number of inputs Power supply for DI Pulse counter2) Number of outputs Analogue Load
8 Internal, ~13 V= ≤ 50 Hz 8 0(2)…10 V= ≤ 2 mA
Connection, LOI Connection, I/O bus Connection terminals
4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail
¨
Ambient conditions
Inputs/outputs
Digital inputs (DI/CI)
Analogue outputs (AO)
Interfaces and communication
Earth connector Construction
Fitting Dimensions W × H × D Weight
On metallic DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 130 g
Standards and directives
Protection type (as per EN 60730)
CE conformity according to
1) 2) 3)
Protection class Environment class Software class3) EMC Directive 2014/30/EU
Connections and terminals:IP00 Front in DIN cut-out:IP30 I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Measured values without accessories 50 Hz only with PC module, otherwise 5 Hz The product is not suitable for safety functions
Right of amendment reserved © 2024 Fr. Sauter AG
381
HVAC automation | HVAC automation Overview of types Type
Features
EY6IO71F001
8 x AO and 8 x DI/CI I/O module
Accessories Type
Description
EY6LO00F001
Local operating and indicating unit for I/O modules
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
¨
382
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6IO72: 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module, modu672‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu612‑LC
link coupler • Activation with a standard signal (0(2)…10 V, 0(4)…20 mA) in operational systems, such as HVAC
engineering • Receiving digital inputs (alarm/status) and analogue inputs (Ni/Pt1000, U, I, R, pot.) in operational
systems • Four universal inputs, four analogue outputs and four digital outputs
EY6IO72F001
• Power supply from automation station (modu6**-AS), link coupler (modu612‑LC) or supply module (modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)
Technical data
¨
Power supply
Power supply Power consumption Dissipated power
From AS or LC via I/O bus ≤ 3.4 W ≤ 0,75 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
Number of inputs Analogue
4 U: 0(2)…10 V I: 0(4)…20 mA R: 200…2500 Ω, Ni/Pt1000, Poti 3 V (potentiometer) DI/CI (≤ 50 Hz) 4 U: 0(2)…10 V I: 0(4)…20 mA 0…10 V / 2…10 V 0…20 mA / 4…20 mA 4 Open collector, NO contacts (0-I), outputs switched with respect to ground External, positive ≤ 28 VDC 0…100 mA (max. 2 V voltage drop)
Ambient conditions
Inputs/outputs
Universal inputs (UI)
Analogue outputs (AO)
Voltage output (U) Current output (I) Digital outputs (DO)
Reference voltage Digital1) Number of outputs Analogue Load > 6 kΩ Load < 500 Ω Number of outputs Type of outputs
Power supply for DO Load Interfaces, communication
Connection, LOI Connection, I/O bus Connection terminals Earth connector
4-pin 7-pin, spring contact 4 × 8-pin spring-loaded plug-in connectors Spring contact against DIN rail
Construction
Fitting Dimensions W × H × D
1)
On DIN rail 35 × 7.5/15 as per EN 60715 55.7 (3 HP) × 100 × 59 mm
50 Hz only with PC module, otherwise 5 Hz
Right of amendment reserved © 2024 Fr. Sauter AG
383
HVAC automation | HVAC automation Weight
130 g
Type of protection
Connections and terminals:IP00 Front in DIN cut-out:IP30 As per 60730-1 I 3K3 (IEC 60721) EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Standards, directives
Protection class Environment class EMC Directive 2014/30/EU
CE conformity according to
Overview of types Type
Features
EY6IO72F001
4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module
Accessories Type
Description
EY6LO00F001
Local operating and indicating unit for I/O modules
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
¨
384
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
Right of amendment reserved © 2024 Fr. Sauter AG
SAUTER modulo 6 operating unit The SAUTER modulo 6 operating unit allows you to display the current status of the inputs and to directly override the outputs of the I/O modules – local priority operation as per EN ISO 16484‑2.
Overview of operating unit
Type designation Product name Power supply Device Function Display Use Further information
Right of amendment reserved © 2024 Fr. Sauter AG
EY6LO00F001 modu600-LO From I/O module Operating device with 4 push-buttons Visualisation, operation Display of analogue, digital and multi-state signals Universally for I/O modules Page 386
385
HVAC automation | HVAC automation
EY6LO00: Operating and indicating unit for I/O modules, modu600-LO Features • Part of the SAUTER modulo 6 system family • Pluggable element for direct operation and visualisation of displays for the modu6** I/O modules • Automatic detection of the current I/O module configuration • Display of values and statuses of the inputs and outputs on an LCD colour display • Detailed display of the individual inputs and outputs including labelling, type, status and graphics • Simple 4-button operation
EY6LO00F001
• LED indicator of I/O module modu6**-IO • Local priority operation • Ready for use without parameterising
Technical data Power supply
¨
Power supply Current consumption Dissipated power
From I/O module modu6**-IO ≤ 12.5 mA ≤ 0,3 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −25…60 °C 10…90% rh, no condensation
Resolution Operation
240 × 240 pixels, colour LCD Four buttons: Back/reject, Reverse/reduce, Forward/increase, Confirm
Connection Protocol
4-pin, spring contacts Proprietary
Type of protection
Connections: IP00 front, plugged in: IP30 (EN 60730-1) III 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3
Ambient conditions
Indicators, display, operation
Interfaces and communication
Standards and directives
CE conformity according to
Protection class Environment class EMC Directive 2014/30/EU
Overview of types Type
Features
EY6LO00F001
modu600-LO, operating and indicating unit for I/O modules
Manuals Document number D100386646 D100397589 D100408512 D100408262 D100402674
386
Language de de de en en
Title modu600‑LO Bedienungsanleitung Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I modu600-LO Operating instructions SAUTER modulo system description
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation Document number D100410201 D100408261 D100402676 D100410203
Language en fr fr fr
Title EY-modulo 6 – Best Practice I modu600-LO Notice d'emploi Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
¨
Right of amendment reserved © 2024 Fr. Sauter AG
387
SAUTER modulo 6 communication modules SAUTER communication modules enable third-party systems to be integrated on the automation level. Field-bus protocols, based on EIA-232 or EIA-485, such as Modbus/RTU and M-Bus, can be integrated directly on the automation station. The data is mapped in BACnet objects and is visible on the BACnet/IP network.
Overview of communication modules
Type designation Product name Interfaces Protocol Further information
388
EY6CM20F011 modu620-CM RS-485 Modbus RTU / ASCII Page 389
EY6CM30F031 modu630-CM RS-232, M-Bus M-Bus Page 391
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6CM20: Modbus/RTU (RS‑485) communication module, modu620‑CM Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu680‑AS and modu660‑AS automation stations or modu612‑LC link
coupler • Up to five COM modules per automation station • Connection to non-SAUTER systems (PLC, chillers, meters etc.) • RS-485, half duplex, electrically isolated interface for Modbus/RTU, Modbus/ASCII • Electrical isolation
EY6CM20F011
• Configurable RS-485 network resistors (software) • Baud rate 600...115 200 bit/s • Modbus master with up to four Modbus communication profiles • Integrated tunnelling function for commissioning and monitoring with serial Modbus master tools
¨
Technical data Power supply
Power supply Power consumption Dissipated power
From AS or LC via I/O bus 30 mA (AS-LC) ≤ 0.7 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −25…70 °C 10…90% rh, no condensation
Communication protocol
Modbus/RTU and Modbus/ASCII master as per V1.02, 2-wire (2W) 1 unit load (unit load (UL)); electrically isolated; integrated RS-485 network resistors (LT, PU, PD) configurable via software 600...115 200 bit/s, parity bit, stop bit, Rx/Tx bus timing Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible 3-/4-wire (D+/D−/COM reference), twisted, shielded, up to 1000 m Integration of Modbus slaves in an RS-485 segment (line) Up to 31 RS-485 unit loads (UL) 600 Modbus channels for BACnet I/O/V objects for up to 247 Modbus devices; FC01-06, 15, 16, 22; unicast and broadcast; access optimisation Switchable via software (CASE Engine)
Ambient conditions
Interfaces, communication
RS-485 (Modbus)
Bus physics
Bus speed Connection
Line Use Participant Functions
120 Ω bus termination and pullup/pull-down Construction
Fitting Dimensions W × H × D Weight
Right of amendment reserved © 2024 Fr. Sauter AG
On metal DIN rail 35 × 7.5/15 as per EN 60715 55.7 (3 HP) × 100 × 59 mm 110 g
389
HVAC automation | HVAC automation Standards, directives
Type of protection Environment class Software class1) EMC Directive 2014/30/EU2)
CE conformity according to
RoHS Directive 2011/65/EU
Connections and terminals: IP00 Front in DIN cut-out: IP30 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 EN IEC 63000
Overview of types Type
Features
EY6CM20F011
Modbus/RTU (RS-485) communication module
Accessories Type
Description
0920360601
Placeholder module for modu6**CM
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203 Additional information P100018041 MD 91.200
¨
1) 2)
390
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
Fitting instructions SAUTER Declaration on materials and the environment
The product is not suitable for safety functions HBES/BACS: 3 metres max. between EY-PS and AS
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation
EY6CM30: M-Bus communication module, modu630‑CM Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu680‑AS and modu660‑AS automation stations or modu612‑LC link
coupler • Up to four COM modules per automation station • M-Bus master • Connection to M-Bus meter networks for the integration of heat meters, electricity meters etc. • 2-wire M-Bus network for up to 80 unit loads, galvanically isolated
EY6CM30F031
• 2-wire RS-232 connection for point-to-point communication • Up to 256 devices and 600 values • M-Bus master with up to four M-Bus communication profiles • Integrated tunnelling function for commissioning and monitoring on the modulo 6 stations
Technical data
¨
Power supply
Power supply Power consumption Power consumption Dissipated power
From AS or LC via I/O bus ≤ 0.35 mA 7.42 W 2.56 W
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −25…70 °C 10…90% rh, no condensation
Communication protocol Bus physics
M-Bus master (EN 13757-3) M-Bus (EN 13757-2), electrically isolated, mark voltage 36 V, short-circuit proof, overcurrent monitoring and protection (max. 135 mA) 300...9600 (19 200, 38 400) bit/s Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible 2-wire (M+/M−) up to 1000 m; RS-232 (D+/D−/GND) up to 3 m Integration of M-Bus meters Up to 80 M-Bus unit loads (UL of 1.5 mA); up to 256 M-Bus devices (with external M-Bus level converter via RS-232) 600 M-Bus channels for BACnet I/O/V objects for up to 256 M-Bus devices; REQ_UD2, SND_NKE, SND_UD, primary/secondary addressing, readout (triggered, by offset or filter)
Ambient conditions
Interfaces, communication
RS-232 (M‑Bus)
Bus speed Connection
Line1) Use Participant
Functions
Construction
Fitting Dimensions W × H × D Weight 1)
On metal DIN rail 35 × 7.5/15 as per EN 60715 55.7 (3 HP) × 100 × 59 mm 118 g
M-Bus cable lengths depend on the cable type (J-Y(ST)Y 4 × 0.5 mm2 max. 1000 m, LiYY 2 × 1.5 mm2 max. 4000 m), number of bus segments and the baud rate; see engineering notes
Right of amendment reserved © 2024 Fr. Sauter AG
391
HVAC automation | HVAC automation
Standards, directives
Type of protection Environment class Software class2) EMC Directive 2014/30/EU3)
CE conformity according to
RoHS Directive 2011/65/EU
Connections and terminals: IP00 Front in DIN cut-out: IP30 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 EN IEC 63000
Overview of types Type
Features
EY6CM30F031
M-Bus communication module
Accessories Type
Description
0920360601
Placeholder module for modu6**CM
Manuals
¨
Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203 Additional information P100018041 MD 91.205
2) 3)
392
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
Fitting instructions SAUTER Declaration on materials and the environment
The product is not suitable for safety functions HBES/BACS: 3 metres max. between EY-PS and AS
Right of amendment reserved © 2024 Fr. Sauter AG
Security in the building network The IoT provides incredible opportunities for building automation thanks to its openness, availability and variety of solutions. On the other hand, it can pose a threat for exactly the same reasons. New devices must therefore be secure from the outset. Because of this, modulo 6 was developed according to the recommendations of IEC 62443-3-3. With modulo 6, the latest generation of building automation systems, SAUTER offers a security-oriented solution. The security concept is based on the international standard for cybersecurity in industrial automation, IEC 62443, which defines system security requirements and security levels. With BACnet Secure Connect (BACnet/SC), modulo 6 is now even more secure. The new BACnet data connection only supports encrypted communication and is based on the latest version of the encryption protocol, TLS 1.3. BACnet/SC is also ideally suited for enterprise IT due to the basic technologies used (TCP, WebSocket, TLS, IPv4, IPv6). Seamless integration into the existing infrastructure is made easy with BACnet/SC BACnet/IP routers. Proven security technologies provide encryption, authentication and access protection. This means the system is already well protected against cyber attacks on the automation level.
Right of amendment reserved © 2024 Fr. Sauter AG
393
HVAC automation | HVAC automation
EY6RT30: BACnet router and SC hub, B/IP <-> B/SC, modu630-RT Features • Part of the SAUTER modulo 6 system family • Suitable for use as BACnet router between BACnet networks • Suitable for use as BACnet Secure Connect Hub (B/SC-Hub) • BACnet profiles: B-RTR, B-SCHUB, B-BBMD • BACnet data links: BACnet/IP, BACnet/SC • BACnet/IP-BBMD or FD function
EY6RT30F001
• Four RJ45 connections for two separate IP networks • Three connections switched for daisy chain • Encryption of communication with TLS 1.3
Technical data Power supply
¨
Power supply Power consumption Dissipated power Peak inrush current1)
24 VDC ± 10% ≤3W ≤3W ≤ 20 A, ≤ 1 ms, on the 24 V side
Connection
Spring-type terminal, pluggable, 0.5...1.5 mm2 (rigid) 0.5...2.5 mm2(flexible) 8...10 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal
Parameters
Battery (buffer: RTC) Earth connector
Ambient conditions
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…90% rh, no condensation
BACnet profiles
BACnet router
B-RTR (BACnet router) B-SCHUB (BACnet SC hub) B-BBMD (BACnet Broadcast Manager) BACnet/IP, BACnet/SC Data Links
Processor RAM (memory) Flash Operating system
ARM Cortex A8, 32-bit, 1 GHz 512 MB (DDR3) 512 MB Embedded Linux
Communication
Via BACnet/IP (UDP) BACnet/SC (web sockets, TCP) TLS V.1.3 (BACnet/SC) BACnet/IP, BACnet/SC 1 × RJ45 connector 10/100 Mbit/s BACnet/IP, BACnet/SC 3 × RJ45 connector
Function
Architecture
Interfaces, communication
Ethernet network #1
Ethernet network #2
1)
394
Encryption Communication protocols Ethernet network 10/100 BASE-T(X) Communication protocols Ethernet network
Measured value with EY-PS021F021 power supply unit
Right of amendment reserved © 2024 Fr. Sauter AG
HVAC automation | HVAC automation 10/100 BASE-T(X) switched
10/100 Mbit/s
Fitting
On metal DIN rail 35 × 7.5/15 as per EN 60715. Rail housing as per DIN 43880 92.6 (5 HP) × 100.9 × 58.3 mm 260 g
Construction
Dimensions W × H × D Weight Standards, directives
Type of protection
CE/UKCA conformity2)
Protection class Environment class EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) EN 55024, EN 55032 Class B EN 55024, EN 55032 Class B EN 62368-1 EN 62368-1 EN IEC 63000 EN IEC 63000
¨
Overview of types Type
Features
EY6RT30F001
BACnet router and SC hub, BACnet/SC <-> BACnet/IP
Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203
2)
Language de de en en fr fr
Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I
Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
395
Room automation 5 High-performance, modular, communicative and ready for IoT. SAUTER ecos guarantees seamless integration into the building management system as well as the automation system of the primary plants while also providing maximum flexibility with the minimum use of energy. Integrated room automation from SAUTER controls not only the room climate, but also the lighting and sunshading. Individual daily programs and realtime monitoring ensure comfort for users. 396
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation Room automation EY-RC 504/505: Room automation station, ecos504/505
399
EY-CM 581: Wireless interface, EnOcean, ecosCom581
423
EY-RC 311: Room controller, ecos311
404
FMS 116, 196: Smart Sensor viaSens116/196
426
EY-RU 310...316: Room operating unit, ecoUnit310...316
408
EY-EM 510...512: Remote I/O module, ecoLink510...512
432
EY-RU 365: Touch room operating unit, ecoUnit365
410
EY-EM 514, 515: Remote I/O module, ecoLink514, 515
434
EY-RU 355: Room operating unit, ecoUnit355
413
EY-EM 522, 523: Remote I/O module, ecoLink522, 523
436
EY-SU 358: Push-button unit for room operating unit, ecoUnit358
416
EY-EM 527: Remote I/O module, ecoLink527
438
EY-RU 110: Room sensor, EnOcean, ecoUnit110
418
EY-PS 031: Power supply, DIN rail, 230 V / 24 VDC
441
EY-RU 146: Room operating unit, EnOcean, ecoUnit146
420
EY-SU 106: Push-button unit for EnOcean room operating unit, ecoUnit106
422
HVAC automation Overview of communication modules
443
EY-BU 292: novaNet-Ethernet interface, moduNet292
444
EYZ 291: Router, novaNet291
446
N
Right of amendment reserved © 2024 Fr. Sauter AG
397
SAUTER ecos room automation stations The areas of use for the SAUTER ecos room automation stations range from precise room control with heating and cooling to integrated room automation with demand-controlled ventilation, lighting and sunshading. The scalable solutions for controlling and regulating the rooms are individually adjusted to the required functional scope and the usage profile. You thus reduce your energy consumption, your costs and the CO2 emissions while providing maximum comfort and well-being. The ecos devices enable the area usage to be adjusted flexibly during operation by dividing the area on each floor into room segments.
Overview of room automation stations
Type designation Product name
EY-RC504F*** ecos504
Parameters Power supply Room segments Room operating units I/O extension modules
EY-RC505F0** ecos505
EY-RC311F001 ecos311
24 V=/~ 8 2×4 2×8
230 V~ 1 1 2
Inputs/outputs Universal inputs Digital inputs Analogue outputs Digital outputs Relay outputs (2 A / 10 A)
− − − − −
5 − 3 4 3/1
Interfaces, communication Interfaces Protocols BACnet profile
RS-485, Ethernet BACnet/IP, MQTT, Modbus RTU, M-Bus, SLC, KNX, DALI, SMI B-BC
RS-485 BACnet MS/TP, SLC B-ASC
Objects Data points (value objects) Control (Loop) Calendars (Calendar) Time programmes (Schedule) Historical data (Trend Log) Alarms (Notification Class)
600 32 16 32 256 16
50 6 3 4 − − Page 404
Further information
398
Page 399
Page 399
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation
EY-RC 504/505: Room automation station, ecos504/505 Features • Part of the SAUTER modulo 5 system family • Modular room automation station (AS) for up to eight rooms or eight flexible room segments • BACnet/IP communication (EN ISO 16484-5) as BACnet Building Controller (B-BC) • The ecoUnit 3 and ecoUnit 1 room operating units enable individual adjustment of the room climate
EY-RC 504
• Optimises energy consumption thanks to presence function, window contact monitoring, demand-controlled
ventilation, control of lighting and window blinds, and time-dependent setpoint specification • Function libraries for climate, lighting and sunshading • Expansion bus for remote ecoLink modules, ecoUnit room operating units and EnOcean wireless interface • KNX interface to connect KNX operating units, sensors and actuators • Integrated KNX tunnelling function (KNX/IP) for the commissioning of KNX with ETS • DALI interface with DALI bus power supply for the connection of DALI electronic ballasts (EB) and DALI
sensors • Web-based commissioning tool for DALI network
EY-RC 505
• SMI interface (SMI/SMI LoVo) for activating SMI motors for sunshading (window blinds, roller shutters) • Integrated tunnelling function for commissioning with SMI-easyMonitor • RS‑485 half duplex, electrically isolated interface for Modbus/RTU, Modbus/ASCII • Baud rate 600 to 115,200 bit/s with configurable RS-485 network resistors
N
• Modbus master with up to four simultaneous communication profiles • Integrated tunnelling function for commissioning and monitoring with serial Modbus master tools • Physical M-Bus interface and RS‑232 interface for external M-Bus level converters • Supports M-Bus baud rates of 300 to 38,400 bit/s • M-Bus master function with up to four simultaneous communication profiles • Integrated tunnelling function for commissioning and monitoring with M-Bus tools • Time programme and calendar function; data recording • Integrated (EY‑RC504F202 only) or licensable MQTT functionality (MQTT Broker / Client) • Engineering/programming using SAUTER CASE Suite (based on IEC 61131-3) • Integration into the building management system via BACnet/IP with Ethernet interface
Technical data Power supply
Power supply Max. peak inrush current Connection
24 VDC ±10% 24 VAC +25%/−15%, 48…63 Hz 23 A (10 milliseconds) Spring-type terminals 0.2...2.5 mm2 rigid/flexible Ampacity max. 5 A
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −25…70 °C 10…85% rh, no condensation
BACnet profile BACnet data point objects Control Active COV subscription BACnet client links Time programmes Calendar
B-BC (EN ISO 16484-5) 600 (incl. HW) 32 (Loop) 1500 200 (Peer-to-Peer) 32 (Schedule) 16 (Calendar)
Ambient conditions
Function
BACnet
Dynamic objects
Right of amendment reserved © 2024 Fr. Sauter AG
399
Room automation | Room automation Notification Historical data
Services Gateway
16 (Notification Class) 256 (Trend Log) up to 60,000 entries 32 (Log View), moduWeb (F101) only 16 (Command) 32 32 KNX, DALI, SMI, Modbus, M-Bus, SLC, SLC/EnOcean BACnet/IP as per ISO 16484-5, HTTP for moduWeb (F101 only), MQTT protocol V3.1.1/V5 as per ISO/IEC 20922 via TCP or TCP/TLS 1.2 (F202 only / licence) Number of topics / alias topics for max. number of BACnet objects (600) Number of topics, depending on CPU/memory resources (> 1000)
Chart Command object Number of BBMDs in BDT Number of FDs in FDT Field bus protocols IP protocols
MQTT
MQTT Client MQTT Broker
Architecture
N
Processor SDRAM (synchronous dynamic RAM) SRAM (static RAM) Flash Operating system Cycle time Application data
32-bit, 600 MHz (ARM) 128 MB 64 kB 128 MB Embedded Linux 100 milliseconds Via CASE Engine
Communication protocol
BACnet/IP, HTTP (F101 only), MQTT (F202 only or with licence), NTP client 2 × RJ-45 connector 10/100 BASE-TX switched 2 × RS-485, SLC ecoLink I/O modules; ecoUnit 1, ecoUnit 3 operating units; ASV 2 VAV actuators Max. 2 × 8 ecoLink modules Max. 2 × 4 ecoUnit 1, 3 or FCCP 2 Max. 2 × 12 ASV 2 5 V ±5% < 200 mA (sum of both RS-485), protected against short circuit Pluggable spring-type terminals 2 × 4-pin 0.2...1.5 mm2 rigid/flexible 4-wire, twisted, shielded Max. 100 m (30 m) with ecoUnit, up to 500 m, bus termination necessary KNX TP1 (ISO/IEC 14543-3) KNX bus max. 6 mA Via external KNX power supply KNX bus terminal x4 0.6...0.8 mm rigid lines KNX cable, 2-wire, twisted KNX actuators and sensors Up to 64 KNX devices, depending on the external KNX power supply
Interfaces, communication
Ethernet network
RS-485 A, RS-485 B
Connection Type Communication protocol Use
Participant
Power supply Connection
Line1) Line length2)
KNX
Communication protocol Power consumption Bus power supply Connection Line Use Participant
1) 2)
400
Example cable CAT-5, J-Y(ST)Y, RS-485 bus cable (e.g. Belden 9842) With the cable length and the conductor cross-section, the supply voltage (+5 V) for the ecoUnit 3 must not fall below the minimum required voltage due to the voltage drop.
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Functions DALI (per COM module)
Communication protocol Power consumption Bus power supply
Connection Line Use Participant
Functions
SMI (per COM module)
Communication protocol Bus power supply
Connection Line Use Participant Functions
RS-485 (COM module)
Communication protocol
Bus physics
Bus speed Connection
Line3) Use Participant Functions
M-Bus/RS-232 (COM module)
Communication protocol Bus physics
Bus speed Connection
3)
256 KNX group addresses for BACnet I/O objects (256 channels) DALI (IEC 62386-101/-103) DALI bus max. 2 mA (only when operating with external power supply) Typ. 16 V, max. 116 mA (can be switched off for external bus power supply) Spring-type terminals 0.2...2.5 mm2 rigid/flexible 2-wire, NYM…, up to 300 m DALI ballasts (IEC 62386-102) DALI sensors (see list) Up to 64 DALI ballasts and 64 DALI sensors (depending on type and bus power supply) 256 DALI functions for BACnet I/O objects (256 channels) with addressable 64 DALI short addresses and 16 group addresses SMI master (SMI standard V2.3.2) Typ. 17 V, max. 20 mA, for 16 motors typ. 12.8 mA (0.8 mA/motor), protected against short circuit (30 mA) Spring-type terminals 0.2...2.5 mm2 rigid/flexible 2-wire, NYM…, up to 350 m SMI actuators, SMI (230 V) or SMI LoVo (see list) Up to 16 SMI motors 128 SMI functions for BACnet I/O objects (128 channels) for up to 16 single and group addresses each Modbus/RTU and Modbus/ASCII Master as per V1.02 2-wire (2W) 1 unit load (UL); electrically isolated; integrated RS-485 network resistors (LT, PU, PD) configurable via software 600...115,200 bit/s Parity bit, stop bit, Rx/Tx bus timing Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible 3-/4-wire (D+/D−/COM reference), twisted, shielded, up to 1000 m Integration of Modbus slaves in an RS-485 segment (line) Up to 31 RS-485 unit loads (UL) 600 Modbus channels for BACnet I/O/V objects for up to 247 Modbus devices; FC01-06, 15, 16, 22; unicast and broadcast; access optimisation M-Bus master (EN 13757-3) M-Bus (EN 13757-2); electrically isolated, mark voltage 36 V, short-circuit proof, overcurrent monitoring and protection 300...9600 (19 200, 38 400) bit/s Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible
N
Example cable CAT-5, J-Y(ST)Y, RS-485 bus cable (e.g. Belden 9842)
Right of amendment reserved © 2024 Fr. Sauter AG
401
Room automation | Room automation 2-wire (M+/M-) up to 1000 m; RS-232 (RX/TX/C) up to 15 m Integration of M-Bus meters Up to 40 M-Bus unit loads (UL of 1.5 mA); up to 256 M-Bus devices (with external M-Bus level converter via RS-232) 400 M-Bus channels for BACnet I/O/V objects for up to 256 M-Bus devices; REQ_UD2, SND_NKE, SND_UD, primary/secondary addressing, readout (triggered, by offset or filter)
Line4) Use Participant
Functions
Construction
Fitting
DIN rail 35 × 7.5/15 EN 50022 Rail housing DIN 43880 EY-RC 504: 105 (6 HP) × 90 × 58 mm EY-RC 505: 210 (12 HP) × 90 × 58 mm
Dimensions W × H × D
Standards, directives
Type of protection
N
Energy class5)
Environment class Protection class EMC Directive 2014/30/EU
CE conformity according to
eu.bac certificate
Energy Performance of Buildings Directive 2010/31/EU eu.bac licence
Connections and terminals: IP00 Front in DIN cut-out: IP30 IP30 (EN 60529), with accessory terminal cover I to VIII = up to 5% as per EU 811/2013, 2010/30/EU, 2009/125/EC 3K3 (IEC 60721) I (EN 61140) EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 15500 No. 2166
Overview of types Type
COM2
COM3
Weight
Current consumption (max.)
Power consumption
EY-RC504F001
--
--
--
220 g
0.33 A
4 W / 8 VA
EY-RC504F202
--
--
–
220 g
0.33 A
4 W / 8 VA
EY-RC504F011
KNX
--
–
240 g
0.33 A
4 W / 8 VA
EY-RC504F021
DALI
--
--
245 g
0.43 A
6 W / 10 VA
EY-RC504F041
SMI
--
–
240 g
0.33 A
4 W / 8 VA
EY-RC504F0C1
RS-485
--
--
243 g
0.33 A
5 W / 9.5 VA
EY-RC504F0D1
M-Bus
--
--
253 g
0.48 A
6.9 W / 10 VA
EY-RC505F031
KNX
DALI
--
385 g
0.61 A
7 W / 10 VA
EY-RC505F051
SMI
DALI
--
410 g
0.61 A
7 W / 11 VA
EY-RC505F061
KNX
SMI
--
385 g
0.33 A
4 W / 8 VA
EY-RC505F071
KNX
SMI
DALI
420 g
0.61 A
7 W / 11 VA
EY-RC505F081
--
DALI
DALI
410 g
0.61 A
9 W / 14 VA
EY-RC505F091
SMI
SMI
DALI
430 g
0.61 A
8 W / 12 VA
EY-RC505F0A1
KNX
DALI
DALI
420 g
0.61 A
9 W / 14 VA
4)
5)
402
COM1
M-Bus cable lengths depend on the cable type (J-Y(ST)Y 4 × 0.5 mm2 up to 1000 m, LiYY 2 × 1.5 mm2 up to 4000 m), the number of bus segments and the baud rate; see engineering notes When the room automation station is being used as a temperature controller, most temperature controller classes can be fulfilled according to EU Directive 2010/30 / EU Regulation 811/2013. For information on the exact temperature class reached, please refer to the system integrator’s user program
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Type
COM1
COM2
COM3
Weight
Current consumption (max.)
Power consumption
EY-RC505F0B1
SMI
SMI
--
400 g
0.33 A
4 W / 8 VA
EY-RC505F0E1
RS-485
M-Bus
--
405 g
0.48 A
7.1 W / 10.6 VA
EY-RC505F0F1
RS-485
DALI
--
405 g
0.61 A
6 W / 10 VA
EY-RC505F0G1
RS-485
SMI
DALI
430 g
0.61 A
7 W / 10 VA
EY-RC505F0H1
KNX
RS-485
DALI
420 g
0.61 A
9 W / 14 VA
EY-RC505F0J1
RS-485
DALI
DALI
440 g
0.61 A
9 W / 14 VA
EY-RC505F0K1
KNX
RS-485
--
385 g
0.61 A
7 W / 10 VA
A A A A A A
EY-RC 504, 505: Room automation station, 8 rooms/segments, 2 × SLC/RS-485 COM1...3: Integrated communication interfaces F*0*: EY-RC504F001 (ecos504, standard), EY-RC504F202 (ecos504-IoT, BACnet MQTT gateway) DALI: DALI interface with bus power supply (116 mA) RS-485: RS-485 interface for Modbus/RTU and Modbus/ASCII SMI: SMI interface for SMI or SMI/LoVo
Accessories Type
Description
0940240001
ecos504/505 terminal covers (2 pcs)
0450573001
Transformer 230 VAC / 24 VAC, 42 VA; for DIN rail 35 mm, dimensions: 78 × 74 × 52 mm (W×H×D)
EY-CM581F081
ecosCom581 EnOcean wireless interface
EY-RU 1**
ecoUnit 1 room operating units with EnOcean wireless technology (via EY-CM581F081)
EY-RU 3**
ecoUnit 3 room operating units
EY-EM51*
Remote ecoLink I/O modules (24 V)
EY-EM52*
Remote ecoLink I/O modules (230 V)
YY-FX502F001
ecos-IoT: MQTT Client, licence for ecos504/505
YY-FX502F002
ecos-IoT: MQTT Client + Broker, licence for ecos504/505
YY-FX503F001
ecos504/505: RADIUS supplicant, licence
A
N
1 HP = one horizontal pitch with 17.5 mm
Right of amendment reserved © 2024 Fr. Sauter AG
403
Room automation | Room automation
EY-RC 311: Room controller, ecos311 Features • Part of the SAUTER modulo system family (BACnet MS/TP) • BACnet MS/TP communication (EN ISO 16484-5) • BACnet room controller (B-ASC) for fan coil unit, chilled beam, chilled ceiling, radiator heater, light, control
of window blinds, variable volume flow control (VAV) etc. EY-RC311F001
• Individual adjustment of the setpoints via ecoUnit 3 room operating units (EY-RU 3**) • Optimisation of energy consumption using presence function, monitoring of window contacts, demand-
controlled switching of fan speeds and time-dependent setpoint specification Freely configurable time programme (BACnet Schedule objects) • • Freely programmable with CASE Suite software (based on IEC 61131-3) • Expandable with ecoLink I/O modules for lighting and control of window blinds
Technical data Power supply
Power supply
N
Power consumption Dissipated power
230 V, 200 V min., 253 V max., 50...60 Hz Max. 14 VA 5 W / 8 VA
Operating temperature Storage and transport temperature Humidity
0...45 °C −20...70 °C 10...85% rh, no condensation
Type
0-I relays, normally-open contacts with shared power supply 230 VAC / 30 VDC 2 A resistive load, total max. 5 A 230 VAC; 10 A resistive load
Ambient conditions
Inputs / outputs
Relay outputs
Load
Switching frequency Semiconductor outputs (MOS-FET)
Type Load
Analogue outputs Universal inputs
Type Analogue Digital Potentiometer Resistance Ni1000/Pt1000
> 3 × 105 cycles (2 A) > 2 × 105 cycles (10 A) 0-I, 24 VAC/DC, switched to ground 0.5 A Max. peak current 1 A (< 20 ms) 0…10 V / 2 mA 0…10 V 0-I, max. 2 Hz 1…10 kΩ (for potentiometer) 100…2500 Ω -20...100 °C
Interfaces and communication
Interface Protocol Line Line length
1 × RS-485 electrically isolated, ½ load BACnet MS/TP 2-wire, twisted with reference, shielded 1000 m with bus termination
SAUTER Local Communication interfaces
Interface Protocol Cable Cable length
404
1 x RS-485 SLC 2×2-wire, twisted, shielded < 100 m with bus termination (with ROU) < 500 m with bus termination (without ROU)
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Room operating units I/O modules
Max. 1; EY-RU 31*/355/110/146 (via EY-CM581) Max. 2; EY-EM 51*, 52*
Dimensions W × H × D Weight Fitting
178 × 103 × 53 mm 674 g DIN rail; TH35×7.5/15 EN 50022
Type of protection
IP00 (EN 60529) IP20 (cover with front aperture) II (EN 60730-1) I to VIII = up to 5% as per EU 811/2013, 2010/30/EU, 2009/125/EC 3K3 (IEC 60721) EN 61000-6-1 EN 61000-6-3 EN 60730-1 EN 60730-2-9
Construction
Standards and directives
Protection class Energy class1)
CE conformity according to
Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
Overview of types Type
Description
EY-RC311F001
ecos311 - room controller B-ASC, MS/TP, 16IO, 230 V
Overview of I/O mix Universal inputs Relay outputs Digital outputs Analogue outputs
1)
N 5 3 (2 A) 1 (10 A) 4 3
When the automation station is being used as a temperature controller, most temperature controller classes can be fulfilled according to EU Directive 2010/30/EU, Regulation 811/2013. For information on the exact temperature class, please refer to the system integrator’s user program.
Right of amendment reserved © 2024 Fr. Sauter AG
405
SAUTER ecos room operating units SAUTER ecoUnit 3 and ecoUnit 1 room operating units combine technology with design. The buttons can be freely assigned with various functions. Due to the standard internal dimensions of 55 × 55 mm, these devices fit both SAUTER frames and common frames of third-party manufacturers of light switches.
Overview of room operating units
Type designation Product name Function
Use Interface Indicator/display Temperature sensor Button functions Fan speeds Setpoint correction Room occupancy Further information
406
EY-RU310F001 ecoUnit310 Temperature sensor
− • − − − − Page 408
EY-RU311F001 ecoUnit311 Temperature sensor, setpoint correction
EY-RU314F001 EY-RU316F001 ecoUnit314 ecoUnit316 Temperature sensor, setTemperature sensor, setpoint correction, occupan- point correction, occupancy, fan cy, fan, and control of lighting and window blinds ecos 5, ecos311 RS-485 − − − • • • − 2 4 − AUTO-0-1-2-3 Rotary knob − 3 modes Page 408 Page 408 Page 408
Right of amendment reserved © 2024 Fr. Sauter AG
Type designation Product name Housing colour Function
Use Interface Indicator/display Temperature sensor Button functions Fan speeds Setpoint correction Room occupancy Further information
Type designation Product name Function
Use Interface Indicator/display Temperature sensor Button functions Fan speeds Setpoint correction Room occupancy Further information
EY-RU365F0** EY-RU355F*** ecoUnit365 ecoUnit355 Traffic white/jet black Traffic white/jet black Temperature sensor, 12 setpoints Temperature sensor, setpoint corwith 4 functions (temperature, rection, occupancy, fan lights, blinds and fans) modulo 6, ecos 5 modulo 6, ecos 5, ecos 311 SLC/RS-485 TFT colour display LCD • • 32 on 6 pages with 6 tiles each 5 • AUTO-0-1-2-3 Digitally adjustable via buttons • 3 modes Page 410 Page 413
EY-RU110F201 ecoUnit110 Temperature sensor
EY-RU146F201 ecoUnit146 Temperature sensor, setpoint correction, occupancy, fan, and control of lighting and window blinds With ecosCom581 for: ecos 5, ecos311, modulo 6 EnOcean wireless − LCD • • − 6 − AUTO-0-1-2-3 − Digitally adjustable via buttons − 3 modes Page 418 Page 420
Right of amendment reserved © 2024 Fr. Sauter AG
EY-SU358F081 ecoUnit358 Traffic white/jet black Push-button unit
Connection to ecoUnit355 − − − 2, 4, 8 − − − Page 416
EY-SU106F100 ecoUnit106 Solar panel supply, control of lighting and window blinds Connection to ecoUnit1** − − − 6 − − − Page 422
407
Room automation | Room automation
EY-RU 310...316: Room operating unit, ecoUnit310...316 Features • Part of the SAUTER modulo 5 system family • Room operating unit for ecos504/505 • Can be extended with EY-SU 306 push-button unit • Operating unit to control and guarantee the highest possible room comfort • Temperature measurement and setpoint adjustment
EY-RU316F001
• Device insert with transparent front, fits into frame with 55 × 55 mm aperture • Frame can be ordered as an accessory • Room climate can be adapted individually • Operating mode can be set for room occupancy and actuation of a 3-speed fan • Control of window blinds, windows and lighting (ON/OFF/dim) • Multicolour LED indicators for visualisation of local energy consumption • Room operating unit with a wide range of functions, designs and colours
Technical data Power supply
N
EY-RU310F001
Power supply Current consumption
From automation station ≤ 25 mA ≤ 38 mA with 2 × EY-SU306
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C –25...70 °C 10...85% rh, no condensation
Measuring range Resolution Time constant Setpoint correction Room occupancy (presence) Fan speeds Position LED
0...40 °C 0.1 K Approx. 7 minutes Variable 3 modes, LED indicator 5 functions, LED indicator Switchable: green/red/OFF
Activation Interface Protocol Line Line length1) Connection terminals
ecos 5, modu521 RS-485 SLC 4-wire, twisted, shielded ≤ 100 m (30 m) with bus termination Pluggable; for wire of 0.12...0.5 mm² (Ø 0.4...0.8 mm)
Fitting Dimensions W × H × D Weight Housing Labelling insert
Recessed/surface-mounted (see accessories) 59.5 × 59.5 × 25 mm 0.1 kg Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C)
Type of protection
IP30 (EN 60529)
Ambient conditions
Parameters
Sensors
Functionality
Interfaces and communication
Connection to automation station
Construction
Standards and directives
1)
408
Max. 30 m for industrial applications as per EN 61000-6-2
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation
CE conformity according to
Protection class Environment class EMC Directive 2014/30/EU
III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3
Overview of types Type
Features
Buttons
EY-RU310F001
NTC sensor
−
EY-RU311F001
Operating unit, NTC sensor, dXs setpoint correc- − tion (rotary knob)
EY-RU314F001
Operating unit, NTC sensor, dXs setpoint correc- 2 tion (rotary knob), fan, occupancy
EY-RU316F001
Operating unit, NTC sensor, dXs setpoint correc- 4 tion (rotary knob), fan, occupancy, window blinds / light
Accessories Operating unit Type
Description
EY-SU306F001
Push-button unit, without frame
Fitting Type
Description
0940240***
For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055
0949360004
Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)
0949241301
Transparent cover for EY-RU and EY-SU, 10 pcs.
0949241302
RAL 9010 white cover for EY-CM581, EY-RU and EY-SU (10 pcs.)
Right of amendment reserved © 2024 Fr. Sauter AG
N
409
Room automation | Room automation
EY-RU 365: Touch room operating unit, ecoUnit365 Features • Part of the SAUTER modulo system family • High quality room operating unit with touch operation and tile display • 3.5" TFT colour display, 320x240 pixels • Scratch-resistant, capacitive touch interface • Navigation of up to 6 pages with up to 6 functions (tiles) each • Intuitive operation for predefined functions (temperature, lights, blinds, fans)
EY-RU365F00*
• Up to 32 values/channels can be defined as a reference for BACnet objects • Display of the energy efficiency function (“ECO 10”) • Mode and symbol displays, e.g. heating/cooling • Audio feedback when pressed • Supply voltage 24 VAC/DC • SLC/RS-485 communicative interface for ecos 5, modulo 6 • Can be located up to 500 m from the automation station • 6 digital inputs for connecting presence detector, door/window contacts, digital contact directly • Configuration with CASE Suite (CASE Engine “EY-RU365 module configuration”, RU_TOUCH module) • Optional: Bluetooth (BLE 4.0) for using the “ecoUnit” app on a smartphone
N EY-RU365F0A*
Technical data Power supply
Power supply
24 VAC/DC, ±20% – SELV 0 / 50/60 Hz or from EY-PS of station < 2.6 W
Rated power during continuous operation Ambient conditions
Operation Transport
Operating temperature Ambient humidity Ambient humidity Storage and transport temperature
0...45 °C 10...85% rh, no condensation < 85% rh, no condensation −25...70 °C
Values/channels
Up to 32 values/channels, parameterisable as setpoint, switching command or value display; 12 of which for complete setpoint inputs Various symbols: e.g. room mode – comfort/reduced/set-back; ECO mode – green-yellow-red; heating/cooling; windows; humidity; wind; alarm; block Up to 6 pages Up to 6 tiles per page Temperature, fan, light dimming, light switching, blind control (position/angle), value displays (feedback), switching function with various predefined symbols (lamp type, mode, scenes...) °C/°F changeover for temperature function; home button; navigation display; (title) labelling for pages, tiles and functions None, time, actual temperature or any value (channel) NTC 10kΩ 0...40 °C
Parameters
Symbol
Number of functions Tile function
Special functions
Screensaver display Temperature sensor
410
Type of sensor Measuring range
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Resolution Accuracy
Refresh interval Drift Position Number of inputs Type of inputs Polling voltage Polling current Internal resistance Input refresh interval Switching thresholds
Inputs
Audible feedback
Display with backlight
Touchpad
Switching hysteresis Type Application Screen diagonal Resolution Display refresh interval Type Number of colours Brightness Contrast ratio Perspective
Touchpad type Refresh rate
0.1 K ± 1 K at typ. 0.1 ms dependent on environment (e.g. air flow) 1s < 0.1 °C/year Bottom left 6 For potential-free switching contacts 24 VDC unregulated >3 mA (closed contact) > 4.7 kΩ 20 ms <10 V (voltage “rising”) >6 V (voltage “falling”) >1 V Piezoelectric signal Audio feedback when touch function is executed 3.5 inches (8.9 cm) 320 x 240 pixels 60 Hz TFT 262,000 500 cd/m² 300 From above: 15° From below: 35° From left/right: 45° Capacitive with gesture recognition 10 ms
N
Interfaces, communication
Connection terminals
SLC/RS-485, DI, power supply
Communication
Activation Interface Protocol Line
Line length Protection circuit Wireless
Bluetooth specification Module Number of app participants Supported OS Bluetooth app
2 x 6-pin screw terminals, pluggable, for solid or braided wires, max. 1.5 mm² (grid dimension 5 mm) From station (ecos 5, modulo 6) RS-485 with 115kbit/s (no integrated terminating resistor) SLC (SAUTER Local Communication) 2-wire twisted, shielded (D+, D-); MM terminal is reference for RS-485; shielded at controller ≤ 500 m with bus termination Protected against excess voltage and reversed polarity 4.0 Low Energy Class 2 Panasonic PAN1740 1 simultaneously 256 registered iOS 8.0 or higher Android 4.1 (Jelly Bean) or higher
Construction
Device dimensions
Fitting Dimensions W × H Surface depth T Recessed depth T (recessed junction box) Compatible recessed junction boxes
Right of amendment reserved © 2024 Fr. Sauter AG
Recessed mounting Glass front: 86 × 86 mm² Plastic housing: 85 × 85 mm² Max. 15 mm Min. 34 mm (incl. terminals) Swiss and European recessed junction boxes
411
Room automation | Room automation Housing
Colour
Weight
Weight
Glass front
Glass type Glass thickness Surface hardness
F00*: White (similar to RAL 9010) F0A*: Black (similar to RAL 9005) F0*1: 0.190 kg F0*2: 0.200 kg Float glass, chemically hardened sodalime glass 2.9 mm 6H
Standards, directives
CE/UKCA conformity1)
Software class Plastic fire classification Type of protection Protection class Environment class EMC-D 2014/30/EU (CE) EMC-2016 (UKCA)
N
Other applicable legal acts
LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) Chemicals WEEE
A (EN 60730) UL94V2 IP30 (EN 60529) III (EN 60730) 3K3 (IEC 60721) EN 50491-5-2, EN 50491-5-3 ETSI EN 301 489-1 v.1.9.2 EN 50491-5-2, EN 50491-5-3 ETSI EN 301 489-1 v.1.9.2 EN 62311 EN 62311 ETSI EN 300 328 v2.1.1 ETSI EN 300 328 v2.1.1 EN IEC 63000:2018 EN IEC 63000:2018 REACH Regulation (EC) 1907/2006 WEEE Directive 2012/19/EU
Overview of types Type
Title
EY-RU365F001
ecoUnit365, white, touch, NTC, 6DI
EY-RU365F002
ecoUnit365, white, touch, NTC, 6DI, Bluetooth
EY-RU365F0A1
ecoUnit365, black, touch, NTC, 6DI
EY-RU365F0A2
ecoUnit365, black, touch, NTC, 6DI, Bluetooth
1)
412
Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation
EY-RU 355: Room operating unit, ecoUnit355 Features • Part of the SAUTER modulo system family • Room operating unit for ecos311, ecos504/505, modu680/660-AS, ASV2 and A*M***SA • Local, intuitive operation for temperature, fan and occupancy • Large backlit (BL) display for status information on the room condition • Ergonomic buttons with mechanical, tactile feedback • Individual adjustment of the room climate via temperature detection and setpoint adjustment • Operating mode can be set for room occupancy and actuation of a 3-speed fan
EY-RU355F051
• ECO button for resetting to automatic mode • Multicolour LED indicator for visualisation of energy consumption or as position LED • Sturdy surface of front cover • Fits into standard frame with 55 × 55 mm aperture • Individually assignable buttons with different symbols, can be ordered as accessories • Expandable with EY-SU 358 switching unit for operating lights, window blinds etc. • Frame can be ordered as an accessory • Room operating unit with various functions, designs and colours
N
Technical data Power supply
Power supply
Current consumption
F***: 12...24 VDC, ± 20% (with BL) F0**/A**: 5 VDC, ± 20% (without BL) from ecos 5/ecos311/ASV2: 5 VDC from ecos311: 15 VDC from EY-PS, modu6**-AS, A*M-SA: 24 VDC ≤ 7 mA (at 24 VDC, with BL) ≤ 10 mA (at 15 VDC, with BL) ≤ 9 mA (at 5 VDC, without BL) ≤ 12 mA with 2 x EY-SU 358 (24 VDC)
EY-RU355FA51
Ambient conditions
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C −25...70 °C 10...85% rh, no condensation
Measuring range Resolution Time constant Measuring accuracy Setpoint correction Room occupancy (presence) Fan speeds Position/energy LED Symbols in LCD
0...40 °C 0.1 K 14 min. 0.5 K in 15...35 °C range Can be set and reset; LCD 3 modes; LCD 3 levels, off, automatic; LCD 1; green, red, orange, off; switchable Time/date, air quality, heating/cooling, ECO, different units, state symbols (window, dew point, locked), SAUTER logo (can be hidden)
Activation
ecos 5**, ecos311, modu6*0-AS, ASV215, A*M***SA RS-485
Parameters
Sensor
Functionality
Interfaces, communication
Connection to automation station, controller
Interface
Right of amendment reserved © 2024 Fr. Sauter AG
413
Room automation | Room automation Protocol Line Line length1) Connection terminals
SLC 4-wire, twisted, shielded ≤ 100 m with bus termination Pluggable, for wire of 0.12...0.5 mm² (Ø 0.4...0.8 mm)
Fitting
Recessed/surface-mounted (see accessories) 55 × 55 × 23 mm 0.05 kg F0xx/F1xx: traffic white FAxx/FBxx: jet black F0xx/F1xx: black FAxx/FBxx: white
Construction
Dimensions W × H × D Weight Housing Button printing
Standards, directives
CE/UKCA conformity2)
Type of protection Protection class Environment class EMC-D 2014/30/EU (CE)
IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN IEC 63000:2018
EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
N
EN IEC 63000:2018
Overview of types Type
Features
Buttons _ = dummy button, PRA = presence
EY-RU355Fx02
Operating device, LCD, NTC, 0T
No buttons supplied
EY-RU355Fx21
Operating device, LCD, NTC, 2T
+|−|_|_|_
EY-RU355Fx31
Operating device, LCD, NTC, 3T
+ | − | _ | _ | PRA
EY-RU355Fx32
Operating device, LCD, NTC, 3T
+ | − | _ | FAN | _
EY-RU355Fx41
Operating device, LCD, NTC, 4T
+ | − | _ | FAN | PRA
EY-RU355Fx42
Operating device, LCD, NTC, 4T
+ | − | ECO | _ | PRA
EY-RU355Fx51
Operating device, LCD, NTC, 5T
+ | − | ECO | FAN | PRA
EY-RU355Fx52
Operating device, LCD, NTC, 5T
+ | − | UP | DOWN | PRA
EY-RU355Fx53
Operating device, LCD, NTC, 5T
+ | − | UP | DOWN | LIGHT
EY-RU355Fx54
Operating device, LCD, NTC, 5T
+ | − | ECO | FAN | °C/°F
EY-RU355Fx55
Operating device, LCD, NTC, 5T
+ | - | UP | DOWN | FAN
A
All types: x = 0 ≙ traffic white, 5/12...24 VDC x = 1 ≙ traffic white, 12...24 VDC x = A ≙ jet black, 5/12...24 VDC x = B ≙ jet black, 12...24 VDC
Accessories Type
Description
Colour
EY-SU358F021
Push-button unit with 2 button functions
Traffic white
EY-SU358FA21
Push-button unit with 2 button functions
Jet black
EY-SU358F041
Push-button unit with 4 button functions
Traffic white
EY-SU358FA41
Push-button unit with 4 button functions
Jet black
EY-SU358F081
Push-button unit with 8 button functions
Traffic white
EY-SU358FA81
Push-button unit with 8 button functions
Jet black
1) 2)
414
SLC/RS-485 permits a line length of up to 500 m (decentralised supply) Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Fitting accessories, spare parts Type
Description
0940240***
For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055
0940240103
Frame, single, recessed, white (RAL9016), 10 pcs.
0940240104
Frame, single, recessed, black (RAL9005), 10 pcs.
0940240703
Mounting plate, single, for recessed fitting (10 pcs.)
0940240203
Frame, double, recessed, white (RAL9016), 10 pcs.
0940240204
Frame, double, recessed, black (RAL9005), 10 pcs.
0940240802
Mounting plate, double, for recessed fitting (10 pcs.)
0940240302
Frame, single, surface-mounted, white (RAL9016), 10 pcs.
0940240303
Frame, single, surface-mounted, black (RAL9005), 10 pcs.
0940240402
Frame, double, surface-mounted, white (RAL9016), 10 pcs.
0940240403
Frame, double, surface-mounted, black (RAL9005), 10 pcs.
094013****
Buttons as accessories/spares, 10 pcs. (see product data sheet 94.055)
0949360004
Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)
0940360005
Terminal RU-SU, push-in, @3P (V,C,DQ), 10 pcs. (accessory for EY-SU 358)
0940360007
Terminal RU-SU, screw, @3P (V,C,DQ), 10 pcs. (optional accessory for EY-SU 358)
0940360006
Terminal and cable RU-SU, @3P (V,C,DQ), 15 cm, 10 pcs. (optional accessory for EY-SU 358)
0940360012
Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)
N
Right of amendment reserved © 2024 Fr. Sauter AG
415
Room automation | Room automation
EY-SU 358: Push-button unit for room operating unit, ecoUnit358 Features • Part of the SAUTER modulo system family • Push-button unit to supplement the ecoUnit355 (EY-RU 355) • Various designs and colour versions in black and white • For controlling window blinds and lighting (on/off, dim) • 2, 4 or 8 button functions • Labelling insert for individual labelling • Fits into frame with 55 × 55 mm aperture
EY-SU358F081
• Frame can be ordered as an accessory
Technical data Power supply
N
Power supply Current consumption
From ecoUnit355 ≤ 2.5 mA (at 24 V= for ROU) ≤ 3 mA (at 15 V= for ROU) ≤ 8.5 mA (at 5 V= for ROU)
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C −25...70 °C 10...85% rh, no condensation
Functionality
Position LED
Connection
Line Length
Labelling
Labelling insert
2; green, red, orange, off; can be connected parallel to EY-RU 355 LED 3-wire (V, C, DQ) ≤ 30 m (can be installed remotely from ecoUnit355) 1 to 3, depending on type; Colour: silver (similar to Pantone 877 C)
Ambient conditions
EY-SU358FA81
Parameters
Construction
Fitting Dimensions W × H × D Weight Buttons
Recessed/surface-mounted (see list of accessories) 55 × 55 × 23 mm 0.04 kg F021: two (dual buttons, dummy buttons) F041: four (dual buttons) F081: eight (single buttons)
Standards, directives
CE conformity according to
416
Type of protection Protection class Environment class EMC Directive 2014/30/EU
IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Overview of types Type
Description
Colour
EY-SU358Fx21
Push-button unit, ecoUnit358, 2T
x=0, traffic white x=A, jet black
EY-SU358Fx41
Push-button unit, ecoUnit358, 4T
x=0, traffic white x=A, jet black
EY-SU358Fx81
Push-button unit, ecoUnit358, 8T
x=0, traffic white x=A, jet black
Accessories Type
Description
0940360005
Terminal RU-SU, push-in, @3P (V,C,DQ), 10 pcs. (accessory for EY-SU 358)
0940360007
Terminal RU-SU, screw, @3P (V,C,DQ), 10 pcs. (optional accessory for EY-SU 358)
0940360006
Terminal and cable RU-SU, @3P (V,C,DQ), 15 cm, 10 pcs. (optional accessory for EY-SU 358)
0940240***
For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055
0940240103
Frame, single, recessed, white (RAL9016), 10 pcs.
0940240104
Frame, single, recessed, black (RAL9005), 10 pcs.
0940240703
Mounting plate, single, for recessed fitting (10 pcs.)
0940240203
Frame, double, recessed, white (RAL9016), 10 pcs.
0940240204
Frame, double, recessed, black (RAL9005), 10 pcs.
0940240802
Mounting plate, double, for recessed fitting (10 pcs.)
0940240302
Frame, single, surface-mounted, white (RAL9016), 10 pcs.
0940240303
Frame, single, surface-mounted, black (RAL9005), 10 pcs.
0940240402
Frame, double, surface-mounted, white (RAL9016), 10 pcs.
0940240403
Frame, double, surface-mounted, black (RAL9005), 10 pcs.
0940001501
Blank foil for EY-SU 358, silver, (10 pcs.)
094013****
Buttons as accessories/spares, 10 pcs. (see product data sheet 94.055)
Right of amendment reserved © 2024 Fr. Sauter AG
N
417
Room automation | Room automation
EY-RU 110: Room sensor, EnOcean, ecoUnit110 Features • Part of the SAUTER modulo system family • Room sensor with integrated digital temperature sensor • Compatible with ecosCom581 and EnOcean interfaces from third-party manufacturers • Battery-free with integrated solar panel • Expandable with ecoUnit106 as additional solar panel supply • Device insert with transparent front, fits into frame with 55 x 55 mm aperture
EY-RU110F201
• Frame can be ordered as an accessory • Frames and foils in many colours and designs possible
Technical data Power supply
Power supply
3 V, from integrated solar panel (external battery operation optional) Min. 250 lux, min. 5 hours daily in 5 of 7 days 60 h of full operation, additional 7 days at least in low power mode
Illuminance Dark period1)
N
Parameters
Technology Frequency Range
Sensor (temperature)
Measuring range Resolution2) Time constant Measuring accuracy, temperature
EnOcean, STM 300 868 MHz band (868.3 MHz) Up to 30 m, depending on building structure (planning recommendation: 10 m) 0…40 °C 0.2 K (hysteresis) Approx. 7 min. Typ. 0.5 K in the 15…35 °C range
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C −25…70 °C 5…85% rh, no condensation
Connection4)
EnOcean Equipment Profile5)
No wiring necessary, teach-in (pairing) with ecosCom581 or ecoMod580 wireless interface via SLC/RS-485 EEP: A5-10-01 (unidirectional)
Weight Dimensions W × H × D Housing Labelling insert
0.05 kg 59.5 × 59.5 × 27.8 mm Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C)
Ambient conditions3)
Interfaces, communication
Construction
1) 2) 3)
4) 5)
418
Bridging time without lighting when the internal energy storage/battery is fully charged Measurement value hysteresis for spontaneous transmission (EnOcean telegram) The device may be active during transport. The device is equipped with a permanently installed lithium cell (energy storage/battery) See quick reference for ecosCom581/ecoMod580 EEP V2.6.8 or higher The ecoUnit110 room sensor currently only supports the temperature value of EEP A5-10-01 and no other EEP as a temperature sensor, such as A5-02-05 (temp. sensor 0...40 °C)
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Fitting
Recessed/surface-mounted (see accessories)
Type of protection Protection class Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RED Directive 2014/53/EU RoHS Directive 2011/65/EU
IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3 EN 60730-1 ETSI EN 300220‑2 (V3.1.1) EN IEC 63000
Standards, directives
CE conformity according to
Overview of types Type
Description
EY-RU110F201
Room sensor, EnOcean, temperature sensor, solar panel
A A
The device is supplied with a silver-coloured labelling insert. Spare inserts: 0940001510 (10 pcs.) Order frame and mounting plate separately (see accessories)
Accessories Type
Description
EY-SU106F100
Push-button unit with solar panel, 6 push-buttons, without frame
0940240***
For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055
0949241301
Transparent cover for EY-RU and EY-SU, 10 pcs.
0949360004
Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)
0940360012
Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)
0949570001
Battery pack, 10 pcs.
0940001510
Labelling insert, foil, silver, without button symbols, 10 pcs.
A
EY‑SU106F100: Can be used as an extended solar panel for the EY-RU110F201 room sensor, but not as a pushbutton unit.
A
0949570001: Suitable as energy supply in permanently darkened rooms.
Right of amendment reserved © 2024 Fr. Sauter AG
N
419
Room automation | Room automation
EY-RU 146: Room operating unit, EnOcean, ecoUnit146 Features • Part of the SAUTER modulo system family • Room operating unit with integrated digital temperature sensor • Bidirectional and compatible with ecosCom581 (EnOcean SMART ACK) • Compatible with EnOcean interfaces of third-party manufacturers • Battery-free with LCD, ecoUnit106 push-button unit can be added • Display with extensive status information on room conditions
EY-RU146F201
• Device insert with transparent front, fits into frame with 55 x 55 mm aperture • Room climate can be adapted individually • Selection of three operating modes for room occupancy • Control of a fan with three speed levels • Control of window blinds, windows and lights (on/off/dim) • Frame can be ordered as an accessory • Frames and foils in many colours and designs possible
Technical data
N
Power supply
Power supply
3 V, from integrated solar panel (external battery operation optional) Min. 250 lux, min. 5 hours daily in 5 of 7 days 50 h of full operation, 60 h all of most important functions, additional 7 days at least in low power mode
Illuminance Dark period1)
Parameters
Technology Frequency Range
Sensor (temperature)
Measuring range Resolution2) Time constant Measuring accuracy, temperature
EnOcean, STM 300 868 MHz band (868.3 MHz) Up to 30 m, depending on building structure (planning recommendation: 10 m) 0…40 °C 0.1 K (display), 0.2 K (hysteresis) Approx. 7 min. Typ. 0.5 K in the 15...35 °C range
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −25…70 °C 5…85% rh, no condensation
Setpoint correction Room occupancy (presence) Fan speeds
Adjustable and resettable 3 modes, LCD 5 functions, LCD
Ambient conditions3)
Function
1) 2) 3)
420
Bridging time without lighting when the internal energy storage/battery is fully charged 0.2 K (hysteresis): Measurement value hysteresis for spontaneous transmission (EnOcean telegram) The device may be active during transport. The device is equipped with a permanently installed lithium cell (energy storage/battery)
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Interfaces, communication
Connection4)
EnOcean Equipment Profile5)
No wiring necessary, teach-in (pairing) with ecosCom581 or ecoMod580 wireless interface via SLC/RS-485 EEP: D2-00-01 (bidirectional, SMART ACK) EEP: A5-10-01 (unidirectional) EEP: F6-03-01 (buttons 3, 4, [7…12 with ecoUnit106])
Construction
Weight Dimensions W × H × D Housing Labelling insert Fitting
0.055 kg 59.5 × 59.5 × 27.8 mm Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C) Recessed/surface-mounted (see accessories)
Type of protection Protection class Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RED Directive 2014/53/EU RoHS Directive 2011/65/EU
IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3 EN 60730-1 ETSI EN 300220‑2 (V3.1.1) EN IEC 63000
Standards, directives
CE conformity according to
N
Overview of types Type
Description
EY-RU146F201
Room operating unit, EnOcean, LCD, temperature sensor, solar panel, 6 buttons: dXs setpoint correction (+/-), fan, presence, 2 free buttons (window blind/light)
A A
The device is supplied with a silver-coloured labelling insert. Spare inserts: 0940001533 (10 pcs.) Order frame and mounting plate separately (see accessories)
Accessories Type
Description
EY-SU106F100
Push-button unit with solar panel, 6 push-buttons, without frame
0940240***
For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055
0949241301
Transparent cover for EY-RU and EY-SU, 10 pcs.
0949360004
Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)
0940360012
Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)
0949570001
Battery pack, 10 pcs.
0940001511
Labelling insert, foil, silver, (symbols: +, −), 10 pcs.
0940001521
Labelling insert, foil, silver, (symbols: +, −, presence), 10 pcs.
0940001522
Labelling insert, foil, silver, (symbols: +, −, fan), 10 pcs.
0940001523
Labelling insert, foil, silver, (symbols: +, −, presence, fan), 10 pcs.
0940001531
Labelling insert, foil, silver, (symbols: +, −, presence, two lights), 10 pcs.
0940001532
Labelling insert, foil, silver, (symbols: +, −, fan, two lights), 10 pcs.
0940001533
Labelling insert, foil, silver, (symbols: +, −, presence, fan, two lights), 10 pcs.
4) 5)
See quick reference for ecosCom581/ecoMod580 EnOcean Equipment Profile (EEP) V2.6.8 or higher
Right of amendment reserved © 2024 Fr. Sauter AG
421
Room automation | Room automation
EY-SU 106: Push-button unit for EnOcean room operating unit, ecoUnit106 Features • Part of the SAUTER modulo system family • Integrated solar cell for additional solar panel supply of ecoUnit 1 EnOcean devices • Push-button unit to supplement the ecoUnit14* room operating unit • Control of window blinds and lighting (on/off, dim) • Up to six button functions • Device insert with transparent front, fits into frame with 55 x 55 mm aperture
EY-SU106F100
• Frame can be ordered as an accessory • Frames and foils in many colours and designs possible
Technical data Power supply
Power supply1)
Not required
Line Length2)
4-wire ≤1m
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −25…70 °C 10…85% rh, no condensation
Fitting Dimensions W × H × D Weight
Recessed/surface-mounted (see accessories) 59.5 × 59.5 × 27.8 mm 0.047 kg
Type of protection Protection class Environment class EMC Directive 2014/30/EU RoHS Directive 2011/65/EU
IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3 EN IEC 63000
Parameters
Connection
N
Ambient conditions
Construction
Standards and directives
CE conformity according to
Overview of types Type
Features
EY-SU106F100
Push-button unit with up to 6 button functions, integrated solar cell
Accessories Type
0940240***
For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055
0949241301
Transparent cover for EY-RU and EY-SU, 10 pcs.
0949360004
Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)
0940360012
Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)
0940001541
Labelling insert, foil, silver, (symbols: two lights, two window blinds), 10 pcs.
0940001542
Labelling insert, foil, silver, (symbols: two lights), 10 pcs.
0940001543
Labelling insert, foil, silver, (symbols: two window blinds), 10 pcs.
1) 2)
422
Description
The power supply is provided by the connected device (ecoUnit14* or ecoUnit110) See connection diagram
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation
EY-CM 581: Wireless interface, EnOcean, ecosCom581 Features • Part of the SAUTER modulo system family • Bidirectional wireless communication according to EnOcean (ISO/IEC 14543-3-10) • Internal, optimised wireless antenna (no BNC antenna necessary) • Integration of EnOcean devices: SAUTER ecoUnit110 room sensor and ecoUnit146 room operating unit
and other EnOcean devices from third-party manufacturers Wide-range supply voltage for compatibility with ecos 5 and ecos311 room controllers and modulo 6 • automation stations • RS-485 interface for remote, optimum positioning of the wireless interface in the room • Firmware update via SLC/RS-485
EY-CM581F081
• Device insert with transparent front, fits into frame with 55 x 55 mm aperture • Frame and white cover front can be ordered as accessories • Frames and foils in many colours and designs possible
Technical data Power supply
Power supply
Current consumption
5…24 V DC ±20% ecos 5:+5 V, ecos311:+15 V/+5 V, modulo 6:+24 V 5 V: typ. 36 mA, 68 mA peak 15 V: typ. 14 mA, 24 mA peak 24 V: typ. 10 mA, 17 mA peak
N
Ambient conditions
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C −25…70 °C 5…85% rh, no condensation
Wireless technology Frequency Protocol Range
EnOcean, TCM 300 868 MHz band (868.3 MHz) EnOcean EEP (see EEP list) Up to 30 m, depending on building structure (planning recommendation: 10 m) RS-485, 115.2 kbit/s SLC (SAUTER Local Communication) ecos 5, ecos311, modulo 6 4-wire twisted (shielding, RS-485:line end resistance recommended) ≤ 100 m
Interfaces and communication
Connection to automation station
Interface Protocol Activation Line
Line length Construction
Weight Dimensions W × H × D Housing Labelling insert Fitting
0.07 kg 59.5 × 59.5 × 27.8 mm Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C) Recessed/surface-mounted (see accessories)
Type of protection Protection class Environment class
IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721)
Standards and directives
Right of amendment reserved © 2024 Fr. Sauter AG
423
Room automation | Room automation CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RED Directive 2014/53/EU RoHS Directive 2011/65/EU
EN 61000-6-1, EN 61000-6-3 EN 60730-1 ETSI EN 300220‑2 (V3.1.1) EN IEC 63000
Overview of types Type
Description
EY-CM581F081
COM module EnOcean, SLC/RS-485, 5...24 V DC, 868 MHz
Accessories Type
Description
0940240***
For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055
0949241301
Transparent cover for EY-RU and EY-SU, 10 pcs.
0949241302
RAL 9010 white cover for EY-CM581, EY-RU and EY-SU (10 pcs.)
0949360004
Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)
0940360012
Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)
N
424
Right of amendment reserved © 2024 Fr. Sauter AG
SAUTER smart sensors Smart
multi-sensors
in
a
mesh
network
for
precise
detection
of
presence/motion, brightness, temperature, humidity, air quality (VOC) and noise levels in rooms or room zones for optimum indoor air and indoor environment quality.
Overview of smart sensors
Type designation Housing colour Sensors Temperature sensor (digital / FIR) Humidity sensor (digital) VOC sensor (air quality, digital) PIR sensor (presence and motion detector) Light sensor Noise level sensor (SL) Display and operation LED ring Push-button, capacitive Interfaces, communication Interfaces Ethernet protocols Bluetooth Mesh profile/model
FMS116F121 Traffic white
FMS116F121A Jet black
FMS196F121 Traffic white
FMS196F121A Jet black
•/• • • • • •
•/• • • • • •
•/• • • • • •
•/• • • • • •
•
•
12 LEDs, RGB colours •
•
Bluetooth Mesh, Bluetooth Beacon, NFC, UART −
Further information
Right of amendment reserved © 2024 Fr. Sauter AG
− Sensor server
Ethernet, Bluetooth Mesh, Bluetooth Beacon, NFC, UART MQTT client, MQTT TCP/TLS Sensor server and client Page 426
425
Room automation | Room automation
FMS 116, 196: Smart Sensor viaSens116/196 Features • Measurement of indoor air quality (IAQ ), such as temperature, humidity and air quality (VOC ) 1)
2)
• Measurement of indoor environment quality (IEQ ), such as motion/presence, brightness and sound 3)
pressure level • Sensor values can be linked together for more precise information on the state of the room (sensor fusion) • For ceiling mounting (recessed/surface-mounted) • Minimal sensor wiring thanks to Bluetooth® 4) mesh network
FMS1*6F121
• Controllable coloured LED ring for displaying the room status to room users • Parameterisable animation profiles for LED ring, e.g. room reserved/available, room air quality good/bad,
room ready for cleaning, etc.) • Bluetooth Beacon function for locating the room user with a smartphone and optimised use of
SAUTER Mobile Building Services (Mobile Room Control app) • Simple integration into the SAUTER automation system with viaSens196 • For up to 16 sensors for an ecos504/505 room controller • Complete commissioning with CASE Suite and Bluetooth smartphone app • Meshing of up to 15 viaSens116 sensors via Bluetooth mesh technology to the viaSens196 sensor
gateway • IoT ready thanks to encrypted MQTT communication in the viaSens196 as an MQTT client
N
FMS1*6F121A
Technical data Power supply
Power supply Current consumption Power consumption
12...34 VDC, typ. 24 VDC Max. 80 mA at 24 VDC Typ. 2 W
Method of measurement Measuring range Resolution Time constant Method of measurement Measuring range Resolution Measuring accuracy6) Emissivity Field of view (FOV) Method of measurement Measuring range Resolution Measuring accuracy Time constant Method of measurement Measuring range Resolution Time constant
CMOS technology (SHT40) 0…40 °C 0.1 K Approx. 8 s (dew 63%) Far infrared (MLX) 15…40 °C 0.1 K ±1 K 0...100%, parameterisable 50° CMOS technology (SHT40) 0...100%, typ. 20...80% rh 1% ±2% in 10…90% range at 25 °C. Approx. 8 s (dew 63%) CMOS technology (SGP40) 1…500 VOC index 1 VOC index < 10 s (dew 63%)
Parameters5)
Temperature (TDIG)
Temperature (TFIR)
Relative humidity (HUM)
Volatile compound gases (VOC)
1) 2) 3) 4) 5) 6)
426
IAQ: indoor air quality VOC: volatile organic compounds IEQ: indoor environment quality The Bluetooth® word mark and logos are registered trademarks of Bluetooth SIG, Inc. For explanations, see the “Abbreviations (sensor types and functions)” list Thermal objects can affect the measuring accuracy
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Motion, presence (PIR)
Brightness (LUX)
Sound pressure level (SPL)
Technology
Method of measurement Detection range7)
Field of view (FOV) Fresnel lens Method of measurement Measuring range Resolution Field of view (FOV) Measuring range Frequency spectrum Filter type Sensitivity Processor
Four-element IR detector (PYQ) Ø 9 m and approx. 8 × 8 m area at 2.5 m fitting height, 360° tangential and radial 120° 34 zones Digital light sensor (APDS) 0…16 000 lux 1 lux 140° 0...120 dB(A) 60…20 000 Hz A weighting −26 dB on the measuring range, ±1 dB tolerance Dual-Core ARM Cortex, 32-bit, 240 MHz
Ambient conditions
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −25…70 °C 10…80% rh, no condensation
Indicator/display8)
LED ring with 12 LEDs, RGB colours (red, green, blue; 24 bit) Configurable animation profiles with 16 predefined colours Identification, service menu, restart, factory reset (front)
Display and operation
Push-button, capacitive
N
Interfaces, communication
Bluetooth mesh
Network Radio frequency Range9) Bluetooth mesh profile
Localisation Ethernet (FMS 196)
Ethernet network 10/100 BASE-T(X) Communication protocol NFC (near field communication) Slide switch10) Serial port WiFi (802.11 a/b/g/n)
Bluetooth mesh node (2.4 GHz), up to 8 TTL hops 2.4 GHz (5 dBm) Up to 10 m FMS 116: Bluetooth mesh relay node, sensor-node (sensor server model, V1.0) FMS 196: Bluetooth mesh, sensor gateway (sensor server + client model, V1.0) Bluetooth beacon (iBeacon), indoor position determination 1 × RJ-45 connector 10/100 Mbit/s MQTT client V3.1.1/V5, MQTT(S), TLS V1.2, WS(S) (ISO/IEC 20922) Product data and configuration parameters (De)activation of sound pressure level (rear) UART for firmware update (point to point), 3.3 V TTL WLAN client deactivated, can be temporarily activated for firmware update with app
7)
As per IEC 63180:2020 Example application: Presence: LED ring off/blue, room climate / air quality: LED ring green/red 9) Depending on building and room structure; planning recommendation: max. 10 m between two Bluetooth mesh nodes 10) Switching only takes effect when the power is off 8)
Right of amendment reserved © 2024 Fr. Sauter AG
427
Room automation | Room automation Construction
Surface Ø × D: 103 × 30 mm Recessed Ø × D: min. 50 × 35 mm Thermoplastic (PC, PC-ABS) Recessed, surface and hollow ceiling mounting 2.5…3.5 m (ceiling)
Dimensions11) Housing material Fitting12) Fitting height Standards, directives
CE/UKCA conformity13)
Type of protection Protection class Environment class Plastic fire classification EMC-D 2014/30/EU (CE)
IP20 (EN 60730) III 3K3 (IEC 60721) UL94 EN 301489 (EMC for radio equipment) EN 60730-1 (residential premises) See EMC Directive EN 60730-1, EN 62311 EN 60730-1, EN 62311 ETSI EN 300 328 (V2.2.2), 2.4 GHz band ETSI EN 300 328 (V2.2.2), 2.4 GHz band EN IEC 63000
EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)
N
EN IEC 63000
Overview of types Type
Description
Weight
Housing
FMS116F121
Smart sensor, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL
0.2 kg
Traffic white (ws)
FMS116F121A
Smart sensor, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL
0.2 kg
Jet black (sw)
FMS196F121
Smart sensor, MQTT/ETH, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL
0.3 kg
Traffic white (ws)
FMS196F121A
Smart sensor, MQTT/ETH, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL
0.3 kg
Jet black (sw)
A
FMS196F121(A) has the same sensor characteristics as FMS116F121(A). The additional Ethernet interface is used as a sensor gateway for the Bluetooth mesh network and for integrating the sensor network in the automation system with MQTT via TCP/TCP+TLS (MQTT/MQTTS) or via web socket (WS/WSS)
A
Housing: matt, traffic white similar to RAL 9016, jet black similar to RAL 9005
Abbreviations (sensor types and functions) FOV HUM LUX MQTT/ETH PIR SPL TDIG TFIR VOC
Field of view Measurement of relative humidity with digital measuring element Measurement of illuminance Ethernet interface for MQTT Motion and presence detection with passive infrared sensor Measurement of sound pressure level Temperature measurement with digital measuring element Temperature measurement with far infrared temperature element Measurement of volatile organic compounds
11)
For dimensions of accessories, see fitting instructions Recessed mounting with box at least 45 mm deep for FMS 116 and at least 61 mm deep for FMS 196 (Ethernet cable bending radius). Mounting in hollow ceiling with spring clamps, at ceiling thickness 2…20 mm hole diameter 68 mm; at 20…25 mm hole diameter 75 mm. Surface mounting with box 28 mm deep for FMS 116 and 53 mm deep for FMS 196 13) Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues 12)
428
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Accessories Type
Delivery quantity
Description
0940241101
1 pcs.
Mounting plate, recessed, white
0940241101A
1 pcs.
Mounting plate, recessed, black
0940241110
Set of 10
Mounting plate, recessed, white
0940241110A
Set of 10
Mounting plate, recessed, black
0940241201
1 pcs.
Mounting plate, surface, 53 mm, white
0940241201A
1 pcs.
Mounting plate, surface, 53 mm, black
0940241210
Set of 10
Mounting plate, surface, 53 mm, white
0940241210A
Set of 10
Mounting plate, surface, 53 mm, black
0940241301
1 pcs.
Mounting plate, surface, 28 mm, white
0940241301A
1 pcs.
Mounting plate, surface, 28 mm, black
0940241310
Set of 10
Mounting plate, surface, 28 mm, white
0940241310A
Set of 10
Mounting plate, surface, 28 mm, black
0940241420
2 sets of 10
Mounting spring, false ceiling
0940241510
Set of 10
PIR orifice plate, 180° angle (half), white
0940241510A
Set of 10
PIR orifice plate, 180° angle (half), black
0949360014
Set of 10
Terminal, 2-pin, push-in, @2×2P (green)
A
The sensors are supplied without mounting accessories. Accessory 0949360014 for power supply connection is supplied
N
Right of amendment reserved © 2024 Fr. Sauter AG
429
SAUTER ecos remote I/O modules The SAUTER ecoLink modules are remote modules for flexibly expanding the I/O mix of the ecos504/505 and modulo 6 automation stations. The modules are used to capture digital and analogue signals from sensors and HVAC installations. They control valve actuators, dampers, fans, dimmable lamps or sunshade actuators. The remote fitting reduces the wiring needed for the sensors and actuators.
Overview of remote I/O modules
Type designation Product name Power supply Inputs/outputs Universal inputs 0-10 V / digital inputs Ni1000/Pt1000 inputs DIM-10 V outputs Normally-open relay contacts Changeover relay contacts Triac Analogue outputs Further information
430
EY-EM510F001 ecoLink510 24 VAC
EY-EM511F001 ecoLink511 24 VAC
EY-EM512F001 ecoLink512 24 VAC
− 4 2 − 3 − 3 3 Page 432
− 4 2 − − − 3 3 Page 432
− 4 − − − − 2 3 Page 432
Right of amendment reserved © 2024 Fr. Sauter AG
Type designation Product name Power supply Inputs/outputs Universal inputs 0-10 V/digital inputs Ni1000/Pt1000 inputs DIM-10 V outputs Normally-open relay contacts Changeover relay contacts Triac 24 VDC MOS-FET 24 VAC/DC Analogue outputs Further information
Type designation Product name Power supply Inputs/outputs Universal inputs 0-10 V/digital inputs Ni1000/Pt1000 inputs Digital/meter inputs DIM-10 V outputs Normally-open relay contacts Changeover relay contacts Triac Analogue outputs Further information
EY-EM514F001 ecoLink514 24 VAC/DC
EY-EM515F001 ecoLink515 24 VAC/DC
4 − − − 4 − − 6 4 Page 434
4 − − − − − − 6 4 Page 434
EY-EM522F001 ecoLink522 230 VAC
EY-EM523F001 ecoLink523 230 VAC
EY-EM527F001 ecoLink527 230 VAC
4 − − − 4 4 − − 4 Page 436
4 − − − 4 − − − 4 Page 436
4 − − 4 − 4 − − − Page 438
Right of amendment reserved © 2024 Fr. Sauter AG
431
Room automation | Room automation
EY-EM 510...512: Remote I/O module, ecoLink510...512 Features • Part of the SAUTER modulo 5 system family • Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC
engineering • Remote I/O module for ecos504/505 • Communicative connection of actuators to automation stations
EY-EM510F001
• Can be located up to 500 m from automation stations
Technical data Power supply
Power supply Current consumption
Dissipated power
24 VAC, ±20%, 50...60 Hz ≤ 0.2 A, without load current from Triac and relay outputs ≤ 6.6 VA Triac outputs not under load, ≤ 48 VA Triac outputs with rated load ≤ 5 W (typically approx. 0.5 W)
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C –25...70 °C 10...85% rh, no condensation
Analogue/digital inputs Ni1000/Pt1000-Eingänge Relay outputs
Type Type Type Load1)
0...10 V/O-I -20...100 °C 0-I, normally-open contacts 230 VAC, 5 A (total max. 10 A)
Switching frequency Triac outputs Analogue outputs
Type Type
> 3 × 105 cycles 0-I, 24 V~/0.5 A 0...10 V, 2 mA
Activation Interface Protocol Line Line length2)
From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination
Dimensions W × H × D Weight
105 × 95 × 60 mm 0.22 kg
Type of protection3) Protection class
IP00 (EN 60529) II (EN 60730-1) for EY-EM 510, III (EN 60730-1) for EY-EM 511, EY-EM 512 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1
Power consumption
Ambient conditions
N Inputs/outputs
Interfaces and communication
Construction
Standards and directives
CE conformity according to
Environment class EMC Directive 2014/30/EU4) Low-Voltage Directive 2014/35/EU
1) 2) 3) 4)
432
See the section “Digital outputs (relays)” See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted EN 61000-6-2: In order to meet the European Standard, the power cables for the inputs and outputs must not exceed 30 metres in length
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Overview of types Type
Description
EY-EM510F001
Remote I/O module, 24 V~, 3 relays, 3 Triacs
EY-EM511F001
Remote I/O module, 24 V~, 3 Triacs
EY-EM512F001
Remote I/O module, 24 V~, 2 Triacs
Overview of I/O mix Relay Triac 0...10 V Out Ni1000/Pt1000 0...10 V In, Digital In
EY-EM 510 3 3 3 2 4
EY-EM 511 0 3 3 2 4
EY-EM 512 0 2 2 0 4
Accessories Type
Description
0949360003
Plug-in connector for ecoLink RS-485, 10 pcs.
0900240020
Terminal cover
0450573001
Transformer 230 VAC / 24 VAC, 42 VA; for DIN rail 35 mm, dimensions: 78 × 74 × 52 mm (W×H×D)
N
Right of amendment reserved © 2024 Fr. Sauter AG
433
Room automation | Room automation
EY-EM 514, 515: Remote I/O module, ecoLink514, 515 Features • Part of the SAUTER modulo 5 system family • Remote I/O module for ecos504/505 • Communicative, digital connection of actuators and sensors to automation stations • Activation of actuators for heated/chilled ceilings, recirculated air and fan coil units, and window blinds
EY-EM514F001
• Inputs for presence detectors, temperature sensors, analogue sensors and window contacts • Can be located up to 500 m from automation stations
Technical data Power supply
Power supply
Dissipated power
24 VAC, ±20%, 50...60 Hz 24 VDC, ±10% Max. 150 mA Without load current of DO (relay, FET) Plus up to 0.5 A / FET Max. 2 W (typically 1.2 W)
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C –25...70 °C 10...85% rh, no condensation
Type Load
0-I relay, normally-open contacts 24...250 V 5 A resistive load Total max. 10 A
Switching frequency
Current consumption
EY-EM515F001 Ambient conditions
N Inputs/outputs
Relay outputs
Semiconductor outputs (FET)
Type
Analogue outputs Universal inputs
Type Analogue Digital Resistance Potentiometer Ni1000/Pt1000
> 3 × 105 cycles 0-I, 24 VAC/DC, 0.5 A, connected to ground max. peak current 1 A at 20 ms 0...10 V/2 mA 0...10 V / 0...1 V 0-I 100...2500 Ω 1...10 kΩ -20...100 °C
Activation Interface Protocol Line Line length1)
From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination
Dimensions W × H × D
105 × 95 × 60 mm
Type of protection2) Protection class
IP00 (EN 60529) II (EN 60730-1) for EY-EM 514 III (EN 60730-1) for EY-EM 515 3K3 (IEC 60721)
Interfaces, communication
Connection to automation station
Construction
Standards, directives
Environment class
1) 2)
434
See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1 (EY-EM 514 only)
Overview of types Type
Description
Weight
EY-EM514F001
Remote I/O module, 24 V~/=, 4 relays, 6 DO FET, 4 AO, 4 UI
270 g
EY-EM515F001
Remote I/O module, 24 V~/=, 6 DO FET, 4 AO, 4 UI
220 g
Overview of I/O mix Normally-open relay contacts Semiconductor FET switch (connected to ground) Analogue outputs Universal inputs
EY-EM 514 4 6 4 4
EY-EM 515 – 6 4 4
Accessories Type
Description
0949360003
Plug-in connector for ecoLink RS-485, 10 pcs.
0900240020
Terminal cover
0450573001
Transformer 230 VAC / 24 VAC, 42 VA; for DIN rail 35 mm, dimensions: 78 × 74 × 52 mm (W×H×D)
Right of amendment reserved © 2024 Fr. Sauter AG
N
435
Room automation | Room automation
EY-EM 522, 523: Remote I/O module, ecoLink522, 523 Features • Part of the SAUTER modulo 5 system family • Remote I/O module for ecos504/505 • Switching and dimming of up to four lamps • Can be located up to 500 m from the automation station
EY-EM522F001
Technical data Power supply
Power supply Current consumption Dissipated power
230 VAC ±10%, 50...60 Hz Max. 20 mA (typically 14 mA) Without load current of relays Max. 2.5 W (typically 1.5 W)
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C –25...70 °C 10...85% rh, no condensation
Type
0-I relay, NO contacts 230 VAC with voltage applied 230 VAC / 5 A resistive load Total max. 10 A
Ambient conditions
EY-EM523F001 Inputs/outputs
N
Relay outputs
Load Switching frequency DIM-10V outputs
Type
Analogue outputs Universal inputs
Type Analogue Digital Resistance Potentiometer Ni1000/Pt1000
> 3 × 105 cycles 1...10 V passive output for electronic ballasts as per EN 60929 Electrically isolated 0...10 V / 2 mA 0...10 V / 0...1 V O-I 100…2500 Ω 1...10 kΩ -20...100 °C
Activation Interface Protocol Line Line length1)
From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination
Dimensions W × H × D Weight
105 × 95 × 60 mm 0.32 kg
Type of protection2) Protection class Environment class EMC Directive 2014/30/EU3)
IP00 (EN 60529) II (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1
Interfaces and communication
Connection to automation station
Construction
Standards and directives
CE conformity according to
Low-Voltage Directive 2014/35/EU 1) 2) 3)
436
See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted EN 61000-6-2: In order to meet the European Standard, the power cables for the inputs and outputs must not exceed 30 m in length
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation Overview of types Type
Description
EY-EM522F001
Remote I/O module, 230 V~, 4 normally-open relay contacts, 4 DIM outputs
EY-EM523F001
Remote I/O module, 230 V~, 4 DIM outputs
Overview of I/O mix Normally-open relay contacts (with voltage applied) DIM-10V Analogue outputs Universal inputs
EY-EM 522 4 4 4 4
EY-EM 523 4 4 4
Accessories Type
Description
0949360003
Plug-in connector for ecoLink RS-485, 10 pcs.
0900240020
Terminal cover
N
Right of amendment reserved © 2024 Fr. Sauter AG
437
Room automation | Room automation
EY-EM 527: Remote I/O module, ecoLink527 Features • Part of the SAUTER modulo 5 system family • Remote I/O module for ecos504/505 • Communicative, digital connection of actuators and sensors to automation stations • Controlling ventilation dampers, motorised windows and blinds
EY-EM527F001
• Inputs for positional feedback, presence detectors, window contacts • Universal inputs for temperature measurement, 0-10 V signals, potentiometer • Meter inputs for recording energy pulses up to 10 Hz • Can be located up to 500 m from automation stations
Technical data Power supply
Power supply Current consumption Dissipated power
230 VAC ±10%, 50...60 Hz Max. 15 mA Without load current of relays Max. 2.5 W (typically 1.5 W)
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C –25...70 °C 10...85% rh, no condensation
Type Load
0-I relay, normally-open contacts 24...250 VAC 5 A resistive load Total max. 10 A
Switching frequency Analogue Digital Resistance Potentiometer Ni1000/Pt1000 Digital Meter
> 3 × 105 cycles 0...10 V / 0...1 V 0-I 100...2500 Ω 1...10 kΩ -20...100 °C 0-I 10 Hz (pulse duration 50 ms)
Activation Interface Protocol Line Line length1)
From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination
Dimensions W × H × D Weight
105 × 95 × 60 mm 0.35 kg
Type of protection2) Protection class Environment class
IP00 (EN 60529) II (EN 60730-1) 3K3 (IEC 60721)
Ambient conditions
N
Inputs/outputs
Relay outputs
Universal inputs
Digital inputs
Interfaces and communication
Connection to automation station
Construction
Standards and directives
1) 2)
438
See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation CE conformity according to
EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU
EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1
Overview of types Type
Description
EY-EM527F001
Remote I/O module, 230 V~, 4 normally-open relay contacts, 4 universal and 4 digital inputs
Overview of I/O mix Normally-open relay contacts Universal inputs Digital inputs / meter inputs (10 Hz)
EY-EM 527 4 4 4
Accessories Type
Description
0949360003
Plug-in connector for ecoLink RS-485, 10 pcs.
0900240020
Terminal cover
N
Right of amendment reserved © 2024 Fr. Sauter AG
439
SAUTER modulo power supply units Efficient switched-mode power supply units for supplying power to automation stations, I/O modules and field devices in building automation. Optimal for use with the SAUTER ecos and modulo 6 system families. • Variable input voltage • Output protected against short circuit • Flat DIN-rail housing for small distribution box
Overview of power supply units
Type designation Nominal rating Nominal current Efficiency Dimensions W × H × D Weight Further information
440
EY-PS031F011 30 W 1.25 A Typ. 86.5% 36 × 94 × 68 mm 0.13 kg Page 441
EY-PS031F021 60 W 2.5 A Typ. 91.7% 52.5 × 95 × 68 mm 0.21 kg Page 441
EY-PS031F041 100 W 4.16 A Typ. 92.1% 72 × 93 × 68 mm 0.24 kg Page 441
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | Room automation
EY-PS 031: Power supply, DIN rail, 230 V / 24 VDC Features • Optimum power supply for the SAUTER modulo and ecos system families and the SAUTER field devices • Modern, efficient switching power supply with quasi-resonant flyback converter principle • High efficiency and minimum idle power (standby) • Variable input voltage • Controlled output voltage with tolerance of ± 3% with mains voltage fluctuations of ± 10% • Output short-circuit proof with HICCUP mode, without overshoot when switching on
EY-PS031F011
• Compact DIN rail housing ideal for DIN rail mounting in standard small distribution boxes or cabinets • High reliability
Technical data Power supply
Input voltage (SELV)
110…240 VAC, 45…65 Hz
Operating temperature Storage and transport temperature Ambient humidity
−10…50 °C −40…85 °C 0…95% rh, no condensation
Output voltage Setting range Overload behaviour1) LED indicator
24 VDC ± 3% 24…28 VDC HICCUP mode Green (device ready for operation)
Connection terminals
Screw terminals 0.5...2.5 mm2 rigid/flexible DIN rail as per EN 60715 Type TH 35 × 7.5/15 DIN rail housing DIN 43880
Ambient conditions
EY-PS031F021
N
Output
Construction
Fitting
EY-PS031F041
Standards, directives
CE conformity according to
Type of protection Protection class EMC Directive 2014/30/EU
Low-Voltage Directive 2014/35/EU RoHS-D 2011/65/EU & 2015/863/EU (CE)
1)
IP20 (EN 60529) II (EN 60730-1) EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 61000-6-3, EN 55032 Class B, EN 55035 EN 62368-1, EN 60335 EN IEC 63000
HICCUP: Halt or inhibit on overcurrent and overvoltage protection
Right of amendment reserved © 2024 Fr. Sauter AG
441
Room automation | Room automation Overview of types Type
Nominal rating Nominal cur- Efficiency rent
Dimensions W × H × D
Weight
EY-PS031F011
30 W
36 (2 HP) × 94 × 68 mm
130 g
EY-PS031F021 EY-PS031F041
A
86.5%
60 W
2.5 A
91.7%
52.5 (3 HP) × 95 × 68 mm
210 g
100 W
4.16 A
92.1%
72 (4 HP) × 93 × 68 mm
240 g
1 HP = one horizontal pitch with 17.5 mm
Type EY-PS031F011 EY-PS031F021 EY-PS031F041
A
1.25 A
Manufacturer/supplier's original type designation: Comatec® PSH series PSH02P03024AGEB PSH03C06024AGEB PSH04P10024AGEB
The original data sheets from Comatec Hi-Tech S.r.l., www.comatec-hitech.com, are legally binding
N
442
Right of amendment reserved © 2024 Fr. Sauter AG
SAUTER communication modules The devices of the SAUTER moduNet series enable the novaNet bus system to be integrated into parent IT networks. A direct Ethernet interface and an RS-232 serial port are provided for this purpose.
Overview of communication modules
Type designation Product name Property Fitting Further information
EY-BU292F001 moduNet292 Connection of novaNet to Ethernet/IP Cabinet model Page 444
Right of amendment reserved © 2024 Fr. Sauter AG
EYZ291F001 novaNet291 Router Cabinet model Page 446
443
Room automation | HVAC automation
EY-BU 292: novaNet-Ethernet interface, moduNet292 Features • Part of the SAUTER EY-modulo 2 system family • Bus access device for novaNet system bus with Ethernet interface • To integrate novaNet stations (EY3600, EY-modulo 2) into IP networks based on Ethernet (LAN/WAN) • For SAUTER CASE Suite applications • To download programmes onto the stations
EY-BU292F001
• For SAUTER novaPro visualisations • For remote monitoring via the internet • TCP/IP communication • Communication with two-wire novaNet system bus • RJ-45 plug for Ethernet 10 Base-T (10 Mbit/s) • Fixed IP addressing • RS-232 interface for parameterisation and updating • Five LEDs for Error, novaNet Send, Power, Activity, Link
Technical data
N
Power supply
Power supply Power consumption
230 V~, +10%, –15% 115 V~, +10%, –15% (50...60 Hz) 6 VA, < 7 W
Operating temperature Storage and transport temperature Ambient humidity
0...45 °C (32...113 °F) –25...70 °C (–13...158 °F) 10...85% rh, no condensation
Ethernet
TCP/IP address Subnet mask TCP port (App 1) TCP port (App 2)
1 × RJ-45 socket 10 Mbit/s (10 Base-T) 1 × DB-9 (male) as per DTE (57k6, 8n1) 192.168.10.20 255.255.255.0 51806 (nova292-Server) 51807 (nova291-Emulation)
Fitting
DIN rail mounting
Type of protection Protection class Software class EMC Directive 2014/30/EU
IP00 (EN 60529); IP20 (EN 60529) I (EN 60730-1) EN 60730-1 Appendix H EN 61000-6-1, EN61000-6-2, EN 61000-6-4 EN 60950-1
Ambient conditions
Interfaces, communication
RS-232 serial port Standard settings
Construction
Standards, directives
CE conformity according to
Low-Voltage Directive 2014/35/EU
Overview of types
444
Type
Description
Dimensions W × H × D novaNet
Weight
EY-BU292F001
panel-fitted model
193 × 131 × 41 mm
650 g
1 × a/b terminal
Right of amendment reserved © 2024 Fr. Sauter AG
Room automation | HVAC automation Accessories Software Type
Description
GZS100F599
CASE Tools CD, latest version (CASE TPC, CASE HWC, CASE Sun, novaNet292 SW etc.)
Connecting cables Type
Description
0367862001
novaNet RJ-11 to RJ-11: 1.5 m
0367862002
novaNet RJ-11 to RJ-11: 2.9 m
0367862003
novaNet RJ-11 to RJ-11: 6.0 m
0367842002
Ethernet RJ-45 to RJ-45: 1.5 m
0367842003
Ethernet RJ-45 to RJ-45: 2.9 m
0367842004
Ethernet RJ-45 to RJ-45: 6.0 m
0386507001
Ethernet crossover RJ-45 to RJ-45: 3.0 m
General Type
Description
0374509001
Connector, 3-pin, packaged
0010240105
Cable housing for 0374509 001, cable cord grip
0374677001
Installation kit for 2-DIN rail mounting
N
Right of amendment reserved © 2024 Fr. Sauter AG
445
Room automation | HVAC automation
EYZ 291: Router, novaNet291 Features • Part of the EY-modulo 2 and EY3600 system family • Bus access device for novaNet system bus with RS-232 interface • For configuring EY-modulo 2 and EY3600 stations with SAUTER CASE applications • For management-level software and all SAUTER novaPro visualisations and novaNet OPC servers • Direct communication from novaNet stations to PC with a serial connection
EYZ291F001
• Remote access with router function via RS-232 modem • Remote monitoring in routel mode via RS-232 modem (i.e. automatic uploading of events) • Communication using two-wire novaNet system bus • Communication with RS-232-compatible pairs of devices (dial-up modem, ISDN adapter, electronic surge
protector, OWG converter, wireless modem etc.) • 1 MB buffer for separating the time characteristics of novaNet and RS-232 interface Technical data Power supply
N
Power supply Max. current consumption
230 V~, 50/60 Hz 10 VA
Operating temperature Storage and transport temperature Humidity
0...45 °C (32...113 °F) –25...70 °C (–13...158 °F) 10…90% rh, no condensation
COM port (DTE) novaNet DIP switch
DB9 plug 1 × a/b terminal, 1 × RJ-11 socket 4 (baud rate, router/routel function)
Weight
0.99 kg (2.2 lb)
Ambient conditions
Interfaces and communication
Construction
Standards and directives
CE conformity according to
Type of protection EMC Directive 2014/30/EU
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Overview of types Type
Description
EYZ291F001
novaNet router
Accessories
446
Type
Description
0367862001
Connecting cable to novaNet291 or moduNet292 automation station 1.5 m (4.9 ft)
0367862002
Connecting cable to novaNet291 or moduNet292 automation station 2.9 m (9.5 ft)
0367862003
Connecting cable to novaNet291 or moduNet292 automation station 6.0 m (19.7 ft)
Right of amendment reserved © 2024 Fr. Sauter AG
Right of amendment reserved © 2024 Fr. Sauter AG
447
Management level
Building and energy management at any time, from anywhere. SAUTER Vision Center ensures optimum system monitoring and continuous operation. Energy management and maintenance modules offer additional benefits for facility management to ensure energy-efficient operation. SAUTER Mobile Building Services (MBS) is a SAUTER Cloud solution which is used in numerous applications for buildings and premises. Room conditions can be controlled in combination with the Mobile Room Control (MRC) app. SAUTER Digital Services allow secure remote access to plants, continuous analysis of buildings and access to key data. 448
Right of amendment reserved © 2024 Fr. Sauter AG
Management level Software YZP 480...495: SAUTER Vision Center
450
YCS 200...210: Mobile Building Services (MBS)
452
YCS 320…325: Vision Services
454
YCS 451...453: Digital Services – Remote Management
455
YCS451F001: Remote Management connector
456
>
Right of amendment reserved © 2024 Fr. Sauter AG
449
Management level | Software
YZP 480...495: SAUTER Vision Center Central building management and visualisation of decentralised installations SAUTER Vision Center (SVC) is a web-based building management and integration platform in the HTML5 standard for running and visualising the building operation. SVC is suitable for both single buildings and entire real estate parks or distributed premises. Typical areas of use are office complexes, business parks, college and industrial campuses, airports, railway stations, hospitals or internationally distributed branch networks. The modular concept allows the software to be extended precisely to meet the customer requirements of every installation. Therefore, SVC gathers all of the data for the entire building and energy management and makes it available to the user from anywhere at all times. In the energy monitoring, meters and other information can be mapped, thus making daily, weekly, monthly and yearly consumption from the plants, buildings and properties automatically available. Specific energy widgets, KPIs and energy labels and other dashboard widgets are used to display the energy values and consumption. Since version 7, a powerful building analytics and energy management module (AEM) has been integrated in SVC, which already contained all the energy monitoring functions. In addition, with chart types such as scatter and carpet plots, but also SANKEY and histogram displays with calculations of the Gaussian distribution, analytic tools are available to carry out energy inspections, to optimise systems in transition phases such as spring and autumn, for example, and thus to meet energy and CO2 reduction requirements, as demanded for companies in the context of certifications in accordance with ISO 50001. The additional online analytics integrated in the AEM enables immediate information in dashboards as KPIs (traffic lights, circular or linear gauge etc.) or alarm messages in the event of abnormal plant operation. In this way, deviations from operating patterns and setpoints, as well as oscillations, are detected automatically and in real time. The maintenance module for SVC is used for optimum planning and efficient performance of servicing and facility management tasks. Here, support is also provided by plant asset management, the definition of maintenance intervals and the automatic triggering of maintenance cycles based on building management information. With energy monitoring, energy management and the building analytics and maintenance modules, SVC provides comprehensive information and tools to ensure continuous and constantly optimised and thus efficient and sustainable plant and building operation.
>
Thanks to SVC’s simple and intuitive operation, starting, planning and changing predefined building automation procedures is easy with the scenario manager. This allows users with PC skills to set rooms, for example, to Comfort or ECO mode at precise times, and to plan and log them via calendar views. For the integration of different equipment systems, SVC supports the manufacturer-independent BACnet standard, as well as connection to OPC UA servers, for integrating different protocols in the building automation. Thus, SVC is the first building and energy management system (BEMS) certified with a crossplatform profile B-XAWS 1.18. SVC supports device profiles B-AWS, B-ALWS, B-ACCWS and thus profile B-XAWS. As of SVC 7.1, the BACnet/SC protocol is also supported. It enables the encryption of the data traffic based on certificates. Ideally, this ensures a secure connection from local sites via BACnet/SC routers to Vision Services (SVC in the cloud) with full BACnet functionality. In addition to the OPC UA client, operation as an OPC UA server is also implemented. Furthermore, an IoT client is integrated that supports the connection of room controllers and automation stations via MQTT. TLS encryption ensures secure communication from decentralised automation stations, e.g. to connect SAUTER ecos or modulo 6 stations via the internet with an SVC located in the cloud. Direct connection of moduWeb Vision via web services and SAUTER novaNet plants via OPC is available for comprehensive support of the integration options. This makes it possible to connect existing systems when converting to the new generation of building management software without having to replace the existing automation level. SVC sends alarms directly via e-mail or SMS to mobile phones according to the responsibilities assigned. With its many user-defined settings and customisable dashboards, SVC guarantees maximum user convenience. SVC can be deployed in virtual IT environments and uses Microsoft SQL databases. These modern architectures and infrastructures enable topics such as high availability, redundancy via cluster systems and
450
Right of amendment reserved © 2024 Fr. Sauter AG
Management level | Software corresponding load assignments (load balancing) to be implemented and used.1) For optimum integration of the user structures of a company, it is possible to connect SVC to an existing LDAP server that additionally supports the latest communication types (LDAP signing & channel binding). Overview of types
/
SVC licences and options
Type
Description
YZP480F000
Provision of all codes in a single ticket
YZP480F098
Latest SVC version on a USB stick
YZP480F200
Basic licence for 500 addresses with maintenance
YZP481F200
Additional 100 objects with maintenance
YZP481F210
Additional 1000 objects with maintenance
YZP481F220
Additional 10000 objects with maintenance
YZP481F230
Additional 25000 objects with maintenance
YZP482F101
Termination of the software maintenance
YZP482F210
Resumption of the software maintenance
YZP483F300
novaNet connection (YZP487F201 is a prerequisite)
YZP484F200
Licence key for VM
YZP484F310
Migration Manager for SVC from nP32 and nPO
YZP484F400
Vision Center Studio
YZP485F201
Energy monitoring with maintenance
YZP485F203
Analytics and energy management with maintenance
YZP485F210
Maintenance module with software maintenance
YZP485F220
Scenario manager with software maintenance
YZP485F230
Touch panel server with 5 clients
YZP485F231
Additional 5 touch panel clients
YZP485F240
Reports and designer
YZP486F205
Upgrade from energy monitoring to analytics and energy management
YZP487F201
OPC UA client for SVC with maintenance
YZP487F203
OPC UA server with maintenance
YZP487F205
SVC MQTT client with maintenance (price per MQTT broker connection)
0900360001
Hardlock (dongle) for VM
1)
>
Scalable via MS SQL Express up to SQL Enterprise depending on the specified properties, virtual IT environments and high-availability VMware & SQL Enterprise.
Right of amendment reserved © 2024 Fr. Sauter AG
451
Management level | Software
YCS 200...210: Mobile Building Services (MBS) Features • Connects the local building management, including the integral room automation, with the room operation
via smartphone or tablet Control of lighting, temperature, window blinds and ventilation (depending on the building equipment) • • Direct access to information such as caretaker services, cafeteria schedule and other information • Direct notification from the MRC app of caretaker services and other services such as comfort notifications,
repair and cleaning requests, meeting room beverage orders, hotel and boarding house service requests • Reservations for meeting rooms, mobile workstations, parking spaces or equipment items (assets) • E-mail invitations including reservations directly from the MRC app • Guest invitations: Sending temporary access codes for the agreed meeting period • Integrated Indoor Navigation for employees and guests via MRC app • Access and rights management via unique access codes for each device based on user profiles and
dedicated room assignments • Room identification and user access via iBeacon badges for smartphones and tablets (iOS and Android) • Perfect for use in office buildings with meeting rooms and mobile workstations, hotels with business
facilities, suites and rooms, as well as upscale apartment buildings • High level of security and up-to-date functionality thanks to Microsoft Azure technology • MRC app available free of charge in the Google Play Store and the Apple App Store
Overview of types
>
452
Type
Description
YCS200F300
MRC app subscription per apartment (1-5 access codes per apartment), price per apartment per year, annual subscription based on monthly use of the master access code per apartment, invoice date 1 year after project activation by basic subscription, automatically renewed
YCS200F320
MRC app subscription (without indoor localisation), price per device (badge) per room, annual subscription based on monthly use of access codes (badges), invoice date 1 year after project activation by basic subscription, automatically renewed
YCS210F300
MRC app subscription (with indoor localisation via iBeacon), price per device (badge) including access profile for rooms, annual subscription based on monthly use of access codes (badges), invoice date 1 year after project activation by basic subscription, automatically renewed
YCS200F200
MBS Cloud Basic subscription for up to 50 rooms/apartments, annual subscription with automatic renewal
YCS200F210
MBS Cloud Basic subscription for up to 150 rooms/apartments, annual subscription with automatic renewal
YCS200F220
MBS Cloud Basic subscription for up to 300 rooms/apartments, annual subscription with automatic renewal
YCS200F230
MBS Cloud Basic subscription for up to 500 rooms/apartments, annual subscription with automatic renewal
YCS200F240
MBS Cloud Basic subscription for up to 1000 rooms/apartments, annual subscription with automatic renewal
YCS210F200
MBS Cloud Basic subscription for office with indoor localisation for up to 50 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes
YCS210F210
MBS Cloud Basic subscription for office with indoor localisation for up to 150 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes
YCS210F220
MBS Cloud Basic subscription for office with indoor localisation for up to 300 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes
YCS210F230
MBS Cloud Basic subscription for office with indoor localisation for up to 500 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes
YCS210F240
MBS Cloud Basic subscription for office with indoor localisation for up to 1000 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes
YCS210F250
MBS Cloud Basic subscription for office with indoor localisation for over 1000 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes
YCS211F200
MBS Cloud Booking option, subscription per MS Exchange Online
YCS220F200
MBS Cloud Indoor Navigation option, subscription for up to 100 iBeacons
YCS220F210
MBS Cloud Indoor Navigation option subscription for up to 200 iBeacons
Right of amendment reserved © 2024 Fr. Sauter AG
Management level | Software Type
Description
YCS220F220
MBS Cloud Indoor Navigation option subscription for up to 300 iBeacons
YCS220F230
MBS Cloud Indoor Navigation option subscription for up to 500 iBeacons
YCS220F240
MBS Cloud Indoor Navigation option subscription for up to 1000 iBeacons
YCS221F000
RTLS engineering support for Indoor Navigation per day excl. expenses for on-site work
>
Right of amendment reserved © 2024 Fr. Sauter AG
453
Management level | Software
YCS 320…325: Vision Services Vision Services: Powerful, efficient energy and building management from the cloud SAUTER Vision Services are comprehensive, powerful modules from the SAUTER Cloud for energy monitoring, building management and energy management and analytics. The centralised approach of cloud operation means that the latest functions and extensions are always available for all building and energy management applications, without the need for time-consuming installations and migrations. Additionally, it saves the investment costs in hardware and software and shifts these investments and their support to the cloud. IoT clients are used to securely transfer local energy and automation data by means of the MQTT protocol with TLS encryption. Features • Vision Services Energy Monitoring with dashboards, diagrams, energy navigation, meter overview with
correction and offset functions for meter replacement, alarms, reports and data import and export management • Vision Services Building with dashboards, diagrams, alarms, object lists, scenario manager, reports and export function • Vision Services Energy Management & Analytics with additional diagrams for energy and plant analysis such as SANKEY, carpet & scatter plots. Histogram plots with Gaussian distribution function and analytics functions for automatic detection of operating pattern deviations, setpoint deviations and oscillations. All Vision Services Energy Monitoring functions are included. All Vision Services can be booked individually or in combination. For example, Vision Services Energy can be used to operate dedicated monitoring in the cloud that runs independently of the local building management. However, complete building and energy management with analytics from the cloud can also be booked as a subscription.
>
Overview of types
454
Type
Description
YCS320F200
Vision Services Building, subscription incl. 1 admin & 1 standard user, 1 MQTT client
YCS321F200
Vision Services Energy Monitoring, subscription incl. 1 admin & 1 standard user, 1 MQTT client
YCS321F210
Vision Services Energy Management & Analytics, subscription incl. 1 admin & 1 standard user, 1 MQTT client
YCS324F200
Object package 50 from 0...500
YCS324F201
Object package 100 from 500...1000
YCS324F202
Object package 100 from 1000
YCS324F220
Additional standard user
YCS325F010
Cloud Connection Service (project & user set-up) incl.1 MQTT connection
YCS325F020
Additional MQTT connection per device
YCS325F400
Cancellation of project subscription; no option of single item cancellation
Right of amendment reserved © 2024 Fr. Sauter AG
Management level | Software
YCS 451...453: Digital Services – Remote Management Features • Secure access to decentralised systems and applications • Two-factor authentication via e-mail or SMS • Fully transparent and secure network connection via browser and Windows client • Remote access: • To applications such as SAUTER Vision Center or moduWeb Unity (via http/https) • To PCs and servers and their applications (via RDP/VNC) • Via VPN tunnel (Layer 2):
The local PC appears in the remote network structure (use of all engineering and network tools from the local PC in the remote system) • Rights administration with user and group management for the assignment of rights for individual systems and buildings, right up to distributed properties Overview of types Type
Description
YCS451F010
G100 Remote Management connector with 2 Ethernet ports, incl. pre-installed OS and VPN licence
YCS451F002
3G/4G option for YCS451F001 (Huawei e3372 modem)
YCS452F200
Remote Management basic connector subscription incl. 5 secured connections
YCS452F210
Remote Management connector subscription, additional 5-pack of secured connections
YCS452F220
Remote Management connector subscription, 5-pack of time-limited, unauthenticated links
YCS453F200
End user subscription, access to all predefined connections via dashboard and Windows client
YCS453F203
End user + 1 VPN channel subscription, access to all pre-defined connections via dashboard and Windows client, incl. VPN tunnel (layer 2 and 3)
YCS453F210
Engineering user subscription with full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client
YCS453F220
Admin user subscription, full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client, incl. user & group management
A
The term of the connector subscription (YCS452F2**) is 12 months with automatic renewal. YCS452F200 must be ordered together with the universal gateway.
A
The user subscriptions (YCS453F2**) of the SAUTER Cloud for Remote Management are monthly subscriptions with automatic monthly renewal.
Right of amendment reserved © 2024 Fr. Sauter AG
>
455
Management level | Software
YCS451F001: Remote Management connector Features • VPN gateway for SAUTER Digital Services – Remote Management • Integrated web server for configuration and monitoring • MicroSD, USB, watchdog, LED indicator • Painted aluminium DIN rail housing as per DIN 43880
Technical data Power supply
Power supply
12...24 V=, 2 A
Connection Battery (buffer: RTC)
Screw terminals, plug-in terminal block CR2032, backup for up to 7 days
Operating temperature Storage and transport temperature Ambient humidity
0…45 °C −20…70 °C 10…80% rh, no condensation
Web server VPN/access point DHCP, DNS services
Yes (Node.js, V 7.8.x) Yes (Open SSL, L2TP) Yes, IPv4 and IPv6
Processor RAM (memory) Memory
H3 Quad-Core Cortex-A7 1 GB (Low Power DDR2) microSDHC, 64 GB included, includes OS and software USB up to 64 GB Embedded Linux (on SD card)
Parameters
Ambient conditions
Function
>
Architecture
Operating system Interfaces, communication
Ethernet/LAN
Ethernet network
Wireless
Transmission rate WLAN
1 × RJ45 connector, 10/100 BASET(X) 10/100 Mbit/s 3 × USB type C (for accessory YCS451F002)
Construction
Fitting
On metal DIN rail 35 × 7.5/15 as per EN 60715 71 (4 HP) × 102 × 62 mm 300 g
Dimensions W × H × D Weight
Overview of types Type
Description
YCS451F001
SAUTER Remote Management connector – universal gateway, incl. pre-installed OS and VPN licence
A
The device can only be ordered together with a connector subscription, see accessories.
Accessories
456
Type
Description
YCS451F002
3G/4G option for YCS451F001 (Huawei e3372 modem)
YCS452F200
Remote Management basic connector subscription incl. 5 secured connections
Right of amendment reserved © 2024 Fr. Sauter AG
Management level | Software Type
Description
YCS452F210
Remote Management connector subscription, additional 5-pack of secured connections
YCS452F220
Remote Management connector subscription, 5-pack of time-limited, unauthenticated links
YCS453F200
End user subscription, access to all predefined connections via dashboard and Windows client
YCS453F210
Engineering user subscription with full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client
YCS453F220
Admin user subscription, full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client, incl. user & group management
A
The term of the connector subscription (YCS452F2**) is 12 months with automatic renewal. YCS452F200 must be ordered together with the universal gateway.
A
The user subscriptions (YCS453F2**) of the SAUTER Cloud for Remote Management are monthly subscriptions with automatic monthly renewal.
Related documents Document number D100471121 D100471122 D100471123
Type Datenblatt Data sheet Données techniques
Language de en fr
Title Remote Management Remote Management Remote Management
>
Right of amendment reserved © 2024 Fr. Sauter AG
457
Engineering tools
Project engineering made easy. SAUTER CASE Suite is used to carry out the technical project processing for both building management systems and conventional control systems. Energy-efficient strategies and methods are already incorporated in the extensive and proven library. CASE Suite is also highly flexible when it comes to adapting solutions to special circumstances, so that even very unusual customer installations can be efficiently operated in terms of energy. 458
Right of amendment reserved © 2024 Fr. Sauter AG
Engineering tools Engineering GZS 100, 150: CASE Suite
460
_
Right of amendment reserved © 2024 Fr. Sauter AG
459
Engineering tools | Engineering
GZS 100, 150: CASE Suite Features • Supports the whole process of a project, from the planning stage to the engineering, commissioning and
servicing phases • ‘Nerve centre’ for the project data and software programs GZS 100, 150
• Seamless integration of the solution libraries • Safeguards the workflow between the specialist sub-programs (CASE Builder, CASE Engine, CASE Vision) • Planning and documentation of the system technology • Commercial and technical project processing • Creates the regulation, control and optimisation functions • Puts the automation stations into service • Based on the Microsoft Windows operating system • Multi-lingual program (German, English and French) • Licence is required for full use of the program
Technical data System requirements
Hardware
Processor Clock rate RAM memory
Intel I7 (recommended) 2.4 GHz or higher Min. 8 GB RAM – recommended 16 GB RAM Min. 20 GB free memory space USB (operating the VM licence dongle, program installation from USB stick), network Windows 10 Pro (x64) or higher, web browser, MS IIS (Internet Information Services) installed MS Office 2010 (32-bit) or higher Graphics program [CorelDRAW Graphics Suite]
Storage capacity Connections
_
Operating system
Software1)
Additional software2)
Overview of types
/
All licences delivered without CASE Suite application software
Type
Description
Running time
GZS150F010
CASE Suite Enterprise licence with maintenance [annual fees]
Unlimited
GZS150F011
CASE Suite Enterprise licence, excluding maintenance
Unlimited
GZS150F020
CASE Suite Enterprise time licence
365 days from activation
GZS150F021
CASE Suite Partner time licence
365 days from activation
GZS150F022
CASE Suite Designer time licence
365 days from activation
GZS100F699
CASE Suite, current software version on data carrier
–
Accessories Type
Description
0900360001
Hardlock VM
1) 2)
460
Compatible versions on request. To be able to use all the functions of CASE Suite Enterprise, we recommend installing the following software.
Right of amendment reserved © 2024 Fr. Sauter AG
Abbreviations used The following abbreviations are used in the technical data under “Standards, directives”:
ATEX-D ATEX-2016 CAN/CSA CE PED EAC EESR-2016 EMC-D EMC-2016 Machinery-D LVD PESR-2016 RED RER-2017 RoHS-D RoHS-2012 SMSR-2008 TÜV UKCA UL WEEE-D WEEE-2013
Explosive Atmospheres Directive 2014/34/EU Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres Regulations 2016 (UK) Standards and norms of the Canadian CSA Group Manufacturer's Declaration of Conformity for the European Union (EU) Pressure Equipment Directive 2014/68/EU Eurasian Conformity (Customs Union of Russia, Belarus, Kazakhstan, Armenia and Kyrgyzstan) Electrical Equipment (Safety) Regulations 2016 (UK) Electromagnetic Compatibility Directive 2014/30/EU Electromagnetic Compatibility Regulations 2016 (UK) Machinery Directive 2006/42/EC Low Voltage Directive 2014/35/EU Pressure Equipment (Safety) Regulations 2016 (UK) Radio Equipment Directive 2014/53/EU Radio Equipment Regulations 2017 (UK) Restriction of Hazardous Substances in Electrical and Electronic Equipment Directives 2011/65/EU & 2015/863/EU Restriction of Hazardous Substances (RoHS) Regulations 2012 (UK) Supply of Machinery (Safety) Regulations 2008 (UK) Technical Inspection Association (technical safety inspection with certificate) Manufacturer’s Declaration of Conformity for the United Kingdom of Great Britain and Northern Ireland (UK) Underwriters Laboratories (organisation for testing products, components, materials) Waste Electrical and Electronic Equipment Directive 2012/19/EU Waste Electrical and Electronic Equipment Regulations 2013 (UK)
Right of amendment reserved © 2024 Fr. Sauter AG
1 461
Alphabetical list of contents Type
Description
Page
Thermowells
22
Thermowells
58
Power and connecting cables for Smart Actuator
142
ADM 322
Rotary actuator
329
ADM 322S
Rotary actuator
331
AKF 112, 113
Rotary actuator
317
AKF 113S
Rotary actuator
318
AKM 105, 115
Rotary actuator
311
AKM 115S F132
Rotary actuator
313
AKM 115S F152
High-speed rotary actuator
315
AKM 115SA
Smart Actuator for ball valve
131
ASF 112, 113
Damper actuator
346
ASF 113S
Damper actuator
348
ASF 122, 123
Damper actuator
350
ASF 123S
Damper actuator
352
ASM 105, 115
Damper actuator
334
ASM 105S, 115S F132
Damper actuator, SUT
336
Type
Description
Page
AXT 301, 311
Thermal actuator for unit valves with stroke indicator
163
B2KL
6-way ball valve with male thread, PN 16
307
B6R
3-way valve (el.), PN 16
186
BKLI
3-way changeover ball valve with female thread, PN 40
297
BKR
3-way regulating ball valve, PN 40
286
BKRA
3-way regulating ball valve with male thread, PN 40
289
BKTA
3-way changeover ball valve, PN 40
303
BKTI
3-way changeover ball valve, PN 40
300
BQD
3-way flanged valve, PN 6 (el.)
197
BQE
3-way flanged valve, PN 16 (el.)
209
BUD
3-way flanged valve, PN 6 (el.)
194
BUE
3-way flanged valve, PN 16/10 (el.)
205
BUG
3-way flanged valve, PN 25/16 (el.)
216
BUL
3-way unit valve, PN 16
149
BUN
3-way valve, PN 16
180
BUS
3-way flanged valve, PN 40 (el.)
225
BUT
3-way unit valve, PN 16 (el.)
156
ASM 105S, 115S F152
High-speed damper actuator, SUT
338
BXL
3-way unit valve, PN 16
159
ASM 115SA
Smart Actuator for ventilation dampers
137
DEF
Tight-sealing butterfly valve
324
ASM 124
Damper actuator
340
DFC 17B, 27B
Pressure switches
36
ASM 124S, 134S
Damper actuator, SUT
344
DSA
Pressure switches
30
ASM 134
Damper actuator
342
DSB, DSF
Pressure monitors and pressure switches
32
ASV 215BF152*
VAV compact controller for laboratory and pharmaceutical applications
121
DSD
Differential pressure switch
38
DSDU, DSDI
Differential pressure transmitter
86
ASV205BF132E, ASV215BF132E
VAV compact controller
118
DSL, DSH
Pressure limiters
34
AVF 124
Valve actuator
252
DSU, DSI:
Pressure transmitters
84
AVF 125S
SUT valve actuator
254
EGE 112
Duct transducer, enthalpy
76
AVF 234S
SUT valve actuator
256
EGH 103
Dew point monitor
78
AVM 105S, 115S
SUT valve actuator
232
EGH 102
Dew point monitor and transducer
77
AVM 215
Valve actuator
234
EGH 110...112
Duct transducer, relative humidity and temperature
75
AVM 322-R
Retrofit actuator
244
AVM 322S-R
Retrofit actuator
246
EGH 120, 130
Room transducer, relative humidity and temperature, surface-mounted
73
AVM 105, 115
Valve actuator
230
AVM 115SA
Smart Actuator for 2- and 3-way valves
134
EGH 681
Room transducer, relative humidity and temperature, recessed
74
AVM 215S
SUT valve actuator
236
EGP 100
Differential pressure transmitter
80
EGQ 110
Duct transducer, air quality (VOC), temperature
70
EGQ 120
Room transducer, air quality, surface-mounted
66
EGQ 212
Duct transducer, CO2 and temperature
68
EGQ 220, 222
Room transducer, CO2, surface-mounted
64
EGQ 281
Room transducer, CO2, recessed
67
EGS 100
Radiation temperature sensor
62
Cable temperature sensors
54
Room temperature sensor, surface-mounted
49
AVM 234S
SUT valve actuator
249
AVM 321, 322
Valve actuator
238
AVM 321S, 322S
SUT valve actuator
241
AVN 224S
SUT valve actuator
259
AXF 217S
Motorised actuator for unit valves with positioner
169
AXM 217
Motorised actuator for unit valves
171
AXM 217S
Motorised actuator for unit valves with positioner
172
EGT 353...356, 456, 554, 654
AXS 315S
Continuous thermal actuator for unit valves with stroke indicator
166
EGT 130, 330, 332, 335, 430
EGT 301, 401, 601 Outdoor temperature sensor
462
52
Right of amendment reserved © 2024 Fr. Sauter AG
Type
Description
Page
Type
Description
Page
EY-SU 358
Push-button unit for room operating unit, ecoUnit358
416
EYZ 291
Router, novaNet291
446
FCCP 200
Fume cupboard indicator and monitor
124
FMS 116, 196
Smart Sensor viaSens116/196
426
EGT 311, 411, 611 Clamp-on temperature sensors
60
EGT 346...348, 392, 446, 447, 646, 647
Duct temperature sensor
56
EGT 386, 388, 486, 686, 688
Room temperature sensors, recessed
51
Heating controller with digital user interface, equitherm
FXV 3***
Electrical distributor
101
EQJW 126
106
Electric distributor for control signals
103
EQJW 146
Heating and district heating controller, equitherm
FXV 33** EasySwitch
108
GZS 100, 150
CASE Suite
460
EQJW 246
Heating and district heating controller, equitherm
111
HBC
Duct-mounted humidistat
43
HSC 101
Panel-mounted humidistat
42
EY6AS60
modular BACnet automation station, modu660-AS
361
EY6AS80
modular BACnet automation station and web server, modu680-AS
EY6CM20
HSC 120
Room humidistat
41
M3R, M4R
Control valve
320
357
MH32F, MH42F
Control valve
322
Modbus/RTU (RS‑485) communication module, modu620‑CM
389
NRFC 413, 422… 424
Modbus fan coil thermostat
93
EY6CM30
M-Bus communication module, modu630‑CM
391
RDT 405, 410
115
EY6IO30
16 x DI/CI inputs I/O module, modu630-IO
373
Electronic controller for simple applications, flexotron400
8 x UI (DI/CI/AI) and 8 x DI/CI I/O module, modu631-IO
SAIO 100
I/O module for smart actuators
140
EY6IO31
375
SGU 100
Sash sensor
88
EY6IO50
6 x relay (2A) outputs I/O module, modu650-IO
377
SVU 100
Air-flow transducer
83
TFL 201
Frost monitor/limiter with capillary sensor
25
EY6IO70
8 x DI/CI/DO (OC) and 8 x DI/CI I/O module
379
TFL 611
Continuous frost monitor
27
EY6IO71
8 x AO and 8 x DI/CI I/O module, modu671-IO
381
TRA 410, 421
Electronic room thermostat for heating and heating/cooling with display
97
EY6IO72
4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module, modu672-IO
383
TRT 317, 327
Electronic room thermostat for heating and heating/cooling
99
Module for separated I/O module supply, modu601-LC
TSHK 621...643
Fan-coil room temperature controller
13
EY6LC01
366
TSHK 670...672
Fan-coil room temperature controller
15
Coupling kit for I/O modules in cabinet, modu602-LC
TSHK 681, 682
Fan-coil room temperature controller
17
EY6LC02
368
TSO, TSH
Room thermostats
11
EY6LC12
IP coupler for I/O modules with web server, modu612‑LC
370
TUC
Universal thermostat
20
Operating and indicating unit for I/O modules, modu600-LO
UVC 106
264
EY6LO00
386
Dynamic flow control system with 6-way ball valve, eValveco
BACnet router and SC hub, B/IP <-> B/SC, modu630-RT
394
UVC102MF065… 100
Dynamic flow control system with 2-way valve and energy monitoring, eValveco
266
EY6RT30
V6R
2-way valve (el.), PN 16
183
EY-BU 292
novaNet-Ethernet interface, moduNet292
444
EY-CM 581
Wireless interface, EnOcean, ecosCom581
423
VDL 010…050
2-way regulating valve, PN 25, Valveco compact
269
EY-EM 510...512
Remote I/O module, ecoLink510...512
432
VDL 050...100
274
EY-EM 522, 523
Remote I/O module, ecoLink522, 523
436
2-way regulating valve, PN 16, Valveco flange
EY-EM 527
Remote I/O module, ecoLink527
438
VKAA
294
EY-EM 514, 515
Remote I/O module, ecoLink514, 515
434
2-way cut-off ball valve with female thread, PN 40
EY-PS 031
Power supply, DIN rail, 230 V / 24 VDC
441
VKAI
2-way cut-off ball valve with female thread, PN 40
292
EY-RC 311
Room controller, ecos311
404
VKR
2-way regulating ball valve, PN 40
278
EY-RC 504/505
Room automation station, ecos504/505
399
EY-RU 310...316
Room operating unit, ecoUnit310...316
408
VKRA
2-way regulating ball valve with male thread, PN 40
282
EY-RU 110
Room sensor, ecoUnit110
418
VQD
2-way flanged valve, PN 6 (el.)
192
EY-RU 146
Room operating unit, EnOcean, ecoUnit146
420
VQE
2-way flanged valve, PN 16 (el.)
203
2-way flanged valve (el.)
189
EY-RU 355
Room operating unit, ecoUnit355
413
VUD
EY-RU 365
Touch room operating unit
410
VUE
2-way flanged valve, PN 16/10 (el.)
199
VUG
2-way flanged valve, PN 25/16 (el.)
212
VUL
2-way valves, PN 16
146
VUN
2-way valve with male thread, PN 16
177
EY-SU 106
Push-button unit for EnOcean room operating unit, ecoUnit106
Right of amendment reserved © 2024 Fr. Sauter AG
422
463
Type
Description
Page
VUP
Pressure-relieved 2-way flanged valve, PN 25 (el.)
220
VUS
2-way flanged valve, PN 40 (el.)
222
VUT
2-way valve, PN 16
154
XAFP 100
Flow probe
82
YCS 200…210
Mobile Building Services (MBS)
452
YCS 320...325
Vision Services
454
YCS 451...453
Digital Services – Remote Management
455
YCS451F001
Remote Management connector
456
YZP 480…495
SAUTER Vision Center
450
464
Right of amendment reserved © 2024 Fr. Sauter AG
D100523338
2024
Systems Components Services Facility Services
SAUTER – your local partner. www.sauter-controls.com
Right of amendments reserved © 2024 Fr. Sauter AG
Catalogue Product and Systems Information