Skip to main content

SAUTER Catalogue 2024 Products and Systems

Page 1

D100523338

2024

Systems Components Services Facility Services

SAUTER – your local partner. www.sauter-controls.com

Right of amendments reserved © 2024 Fr. Sauter AG

Catalogue Product and Systems Information


Complete solutions from a single source New building, refurbishment or building operation – SAUTER is your reliable partner for sustainability, operational safety and comfort of real estate. With our intelligent solutions for building control, room automation and technical facility management, we safeguard your investment and support you in achieving your ESG goals. We create sustainable environments. Since 1910.

The SAUTER Group •

Global company headquartered in Basel, Switzerland

•

Technology leader in the field of building automation, system integration and building services

•

Focus: maximum energy efficiency and sustainability

•

Goal: investment and operational safety throughout the entire building life cycle

•

Member of the BACnet Interest Group (BIG-EU), BACnet International, EnOcean Alliance as well as the eu.bac, KNX and DALI Alliance (DiiA)

Right of amendment reserved © 2024 Fr. Sauter AG

1


2

Right of amendment reserved © 2024 Fr. Sauter AG


Contents Field devices 2-point controllers

9

Data capture

47

Single-room, heating and air-conditioning controllers

91

Valves, control valves, dampers, actuators

127

HVAC automation

355

Room automation

397

Management level

449

Engineering tools

459

Abbreviations used

461

Alphabetical list of contents

462

Right of amendment reserved © 2024 Fr. Sauter AG

3

Y X C V

Building management

Appendix

¨ N > _


Product highlights

Smart Sensor viaSens Smart buildings need comprehensive sensor technology. The Smart Sensor viaSens measures temperature, air humidity and air quality as well as brightness, presence and sound pressure level. It also has an animated LED light ring. Multiple sensors communicate wirelessly via a Bluetooth mesh network. Effective IoT integration is possible with the secure MQTT interface of the sensor gateway.

SAUTER Vision Center The web-based building management and integration platform for operating and visualising building operations is constantly being expanded. Highlights in 2024 include new alarm features, improved user administration, audit trail updates and intrinsic security mechanisms.

modulo 6 IP coupler for I/O modules The new modu612-LC unit enables I/O and communication modules of a modulo 6 automation station to be remotely connected via the IP network. Communication is encrypted via MQTT. The integrated web server provides a secure user interface for configuration during commissioning.

4

Right of amendment reserved © 2024 Fr. Sauter AG


AXT3/AXS3 actuators for unit valves The AXT3 actuators for unit valves and AXS3 continuous actuators for unit valves with stroke indicator ensure efficient room temperature control. The range includes two basic types for different operating voltages as well as NC (normally closed) and NO (normally open) versions. There are also versions with plug-in cables for flexible use. Numerous valve adapters allow fitting on all common unit valves. OEM solutions are possible.

Redesigned room transducers with app The comprehensive range of room transducers for optional detection of temperature, humidity, VOC or CO2 now have upgraded CO2 sensors and a new, timeless design. A smartphone app is now available for individually configuring the measuring ranges and output signals of the room transducers with active signals.

modulo 6 with BACnet/SC Firmware update 2.0 for modulo 6 provides multi-layered protection for installations of any size. It supports BACnet/SC and the RADIUS protocol and has even more secure network separation. moduWebUnity, the web application for visualisation, now supports operation via touch panels and the export of measurement data for further processing with ERP systems.

Right of amendment reserved © 2024 Fr. Sauter AG

5


6

Right of amendment reserved © 2024 Fr. Sauter AG


Mobile Apps From installation to service. Mobile apps supplement the SAUTER product portfolio. They help users execute tasks or provide services remotely. Here is a handy overview of the apps that are currently available.

Overview of mobile apps (alphabetical order)

Name

Main functions

ecoUnit

•

Controlling the ecoUnit Touch room operating unit (EY-RU365)

eValveco Assistant

•

Commissioning, configuration, service and operation Creating and managing projects

•

Mobile Room Control, the Mobile Building Services app

•

modulo 6

•

Commissioning, service and operation

Smart Actuator

• • •

Commissioning, service and operation Application selection and configuration Creating and managing projects

ValveDim

•

Access to the SAUTER valve and actuator portfolio Configuring valve and actuator combinations

•

iOS

Android

Operating room functions, information and notifications for tenants, owners and operators Booking meeting rooms, assets, parking spaces and workspaces

modulo 6

•

viaSens

•

Commissioning the sensor in the SAUTER meshNet • Sensor network configuration • Basic configuration of the sensor • Calibration of the sensor • Beacon transmission capacity display

Right of amendment reserved © 2024 Fr. Sauter AG

7


On/off controllers

Proven technology developed further. Two-point controllers from SAUTER are used to limit, regulate and monitor temperature, pressure and humidity, with no auxiliary energy required. They provide reliability, even in difficult conditions.

8

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers Thermostats Overview of fan-coil room-temperature controllers

10

TSHK 681, 682: Fan-coil room temperature controller

17

TSO, TSH: Room thermostat

11

Overview of universal thermostats

19

TSHK 621...643: Fan-coil room temperature controller

13

TUC: Universal thermostat

20

TSHK 670...672: Fan-coil room temperature controller

15

Thermowells

22

Frost monitors Overview of frost monitors

24

TFL 201: Frost protection monitor/limiter with capillary-tube sensor

25

TFL 611: Continuous frost monitor

27

Pressure switches Overview of pressure switches

29

DSL, DSH: Pressure limiters

34

DSA: Pressure switches

30

DFC 17B, 27B: Pressure switch

36

DSB, DSF: Pressure monitors and pressure switches

32

DSD: Differential pressure switch

38

Humidistats HSC 120: Room humidistat

41

HSC 101: Panel-mounted humidistat

42

HBC: Duct-mounted humidistat

43

Right of amendment reserved © 2024 Fr. Sauter AG

9

Y


Fan-coil room-temperature controllers SAUTER fan-coil controllers are used for demand-led activation of fan-coil units and ensure that they are operated with optimum use of energy. There are controllers for fan-coil units with a three-speed fan and for the continuous activation of EC motors. The controllers are suitable for 2- and 4-pipe installations and also for fan-coil units with an electric reheater.

Overview of fan-coil room-temperature controllers

Type designation Indicating and operating elements Mode switch for heating Mode switch for cooling Mode switch for fan Setpoint adjuster LCD Method of operation Load (A) External sensor 2-pipe installation 4-pipe installation C/O (changeover) Further information

10

TSO, TSH

TSHK 621…643

TSHK 670…672

TSHK 681…682

• • • • −

• • • • −

• • • • −

− − • • •

≤ 10 − − − − Page 11

≤6 − • • − Page 13

≤ 10 − − • − Page 15

≤6 • • • • Page 17

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Thermostats

TSO, TSH: Room thermostat Features • Variable room temperature as setpoint based on printed temperature scale

Y

• Variants of the standard devices are available, such as thermal feedback, night set-back mode, fan switches

and switches for heating/cooling • Setpoint adjuster with mechanical min. and max. limitation of the setting range

Technical data TSO67*F001

Power supply

Load1)

230 V~ 10(2,5) A, 24 V= max. 1 A, 24 V~ min. 0.2 A

Setting range Night-time reduction (N/R) Time constant in still air Time constant in moving air (0.2 m/s) Proportional band Shortest switching interval

5...30 °C Approx. 5 K 17 minutes 13 minutes Approx. 3 K Approx. 19 minutes (E = 0.5)

TSO67*F001

Parameters

Thermal feedback

TSH67*F002 E 1

Ambient conditions

Ambient temperature

0...50 °C 0,5

Weight Dimensions Housing Housing material Fitting Cable inlet Baseplate Screw terminals

0.11 kg 76 × 76 mm Pure white (RAL 9010) Fire-retardant thermoplastic Wall/recessed At rear Black thermoplastic with membrane sensor and contact system For electrical cables of up to 1.5 mm²

Standards, directives

Type of protection Protection class Energy class

CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP20 (EN 60529) II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC EN 60730-1, EN 60730-2-9 EN 60730-1

Xs xi

0 Xp

Xt/2 E=0,25

E=0,50

E=0,75

B01806_de

Construction

E= control factor

Overview of types

/

Supply voltage: 10% more voltage means proportional band approx. 4 K, switching period 15 minutes and actualvalue reduction approx. 0.5 K

/

H/C = heating or cooling, depending on connection; H//C = heating or cooling, selectable

Type

Operating mode switch

Output for

Power supply

TSO670F001

-

H/C

-

TSH670F002

-

H/C

230 VAC, ± 10%, 50...60 Hz

TSH676F002

-

H/C

230 VAC, ± 10%, 50...60 Hz

1)

For TSO672F001 for cooling 5(1.5) A

Right of amendment reserved © 2024 Fr. Sauter AG

11


2-point controllers | Thermostats

A A A

Y

TSO670F001, TSO672F001: Switching difference 1.3 K without thermal feedback2) TSH670F002, TSH676F002: Dynamic switching difference 0.5 K with thermal feedback3) TSH676F002: Additional feature N/R (normal/reduced) for external clock

Accessories Type

Description

0362225001

Intermediate plate, pure white, for wall mounting on recessed junction box

2)

3)

12

Devices without thermal feedback are pure 2-point controllers. The static switching difference is given, i.e. for very slow changes in temperature. For faster changes in temperature, the time constant must be taken into account. Devices with thermal feedback are pulsed by a built-in heating resistor. The control factor falls as the temperature increases, i.e. the controller has proportional behaviour. A small temperature variation of ±0.1...0.5 K occurs as a result of switching, depending on the time constant of the room.

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Thermostats

TSHK 621...643: Fan-coil room temperature controller, electromechanical Features

Y

• Variable room temperature as setpoint based on printed temperature scale • Changeover from heating to cooling via switch or type of connection • ON/OFF toggle switch for mains voltage, plus other slide switches for operating mode and fan, depending

on the type • More constant room temperature due to thermal feedback

TSHK6**F00*

• Suitable for wall mounting or fitting on recessed junction boxes • Setpoint adjuster with mechanical min. and max. limitation of the setting range • 2-point pulsed activation • Individual unitary temperature control in residential and business rooms for activating, for example, electric

heating systems, thermal actuators, or fans or cooling units in air-conditioning systems. Technical data Power supply

Power supply1)

230 V~, approx. ±10%, 50...60 Hz

Setting range Proportional band Hysteresis2) Shortest switching interval Time constant in still air Dead time in still air Time constant in moving air (0.2 m/s) Dead time in moving air (0.2 m/s)

5...30 °C 3K Approx. ±0.1...0.5 K Approx. 19 minutes (E = 0.5) 20 minutes 2 minutes 15 minutes 1 minute

Ambient temperature

0...55 °C

Load Fan load

6(3) A, 230 V~ 6(3) A, 230 V~

Weight Housing Housing material

0.18 kg Pure white (RAL 9010) Fire-retardant thermoplastic (fire classification UL94 HB) Black thermoplastic with bimetallic sensor and contact snap mechanism with permanent magnet At rear For electrical cables of up to 2.5 mm²

Parameters

Ambient conditions

Outputs

Construction

Baseplate

Cable inlet Screw terminals Standards and directives

Type of protection Protection class Energy class

1)

2)

IP30 (EN 60529) II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC

10% more voltage results in: Proportional band approx. 4 K, switching period 15 min, actual-value reduction approx. 0.5 K Devices with thermal feedback are pulsed by a built-in heating resistor. The control factor reduces as the temperature increases (i.e. the controller has proportional behaviour). A small temperature variation of ±0.1...0.5 K occurs as a result of pulsing, depending on the time constant of the room

Right of amendment reserved © 2024 Fr. Sauter AG

13


2-point controllers | Thermostats Overview of types

Y

Type

Operating mode

TSHK621F001

Heating/cooling; 2-pipe

TSHK642F001

Heating only / cooling only; 2-pipe

TSHK643F001

Heating/cooling; 4-pipe

Mains switch on/off Operating mode switch Fan speeds

TSHK621 • ir opü

TSHK642 • − opü

TSHK643 • ir opü

Accessories

14

Type

Description

0362239001

Pure white intermediate cover plate, suitable for various recessed junction boxes

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Thermostats

TSHK 670...672: Fan-coil room temperature controller, heating/cooling sequence Features

Y

• Variable room temperature as setpoint based on printed temperature scale • Gradual transition from heating to cooling through sequence characteristic • Variants with master switch plus slide switch for the fan • Suitable for wall mounting or fitting on recessed junction boxes

TSHK67*F001

• Electronics unit and switching relay • Setpoint adjuster with mechanical min. and max. limitation of the setting range • Quasi-continuous temperature control • 2-point pulsed activation • Individual unitary temperature control in residential and business rooms for activating, for example, electric

heating systems, thermal actuators, or fans or cooling units in air-conditioning systems. Technical data Power supply

Power supply

230 V~, approx. ±10%, 50...60 Hz

Setting range Proportional band Sequence dead zone Hysteresis1) Shortest switching interval Time constant in still air Dead time in still air Time constant in moving air (0.2 m/s) Dead time in moving air (0.2 m/s)

5...30 °C 2×3K 2 K ±0,7 Approx. ±0.1...0.5 K Approx. 19 minutes (E = 0.5) 20 minutes 2 minutes 15 minutes 1 minute

Ambient temperature

0...55 °C

Load Fan load

10(4) A, 230 V~ 6(3) A, 230 V~

Operating mode

Heating/cooling sequence; 4-pipe

Weight Housing Housing material Baseplate Cable inlet Screw terminals

0.18 kg Pure white (RAL 9010) Fire-retardant thermoplastic (fire classification UL94 HB) Black thermoplastic with NTC sensor At rear For cables of up to 2.5 mm²

Type of protection

IP30 (EN 60529)

Parameters

Ambient conditions

Outputs

Function

Construction

Standards and directives

1)

The device is pulsed electronically. When the temperature increases, the control factor is reduced to 0 on the “Heating” output and increased to E = 1 on the “Cooling” output. A small temperature variation of ±0.1...0.5 K occurs as a result of pulsing, depending on the time constant of the room

Right of amendment reserved © 2024 Fr. Sauter AG

15


2-point controllers | Thermostats Protection class Energy class

Y

II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC

Overview of types Type

Number of switches

TSHK670F001

0

TSHK672F001

2 TSHK670

TSHK672

Mains switch ON/OFF Fan speeds

— —

Indicators/display

—

• opü 1 LED

Accessories

16

Type

Description

0362239001

Pure white intermediate cover plate, suitable for various recessed junction boxes

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Thermostats

TSHK 681, 682: Fan-coil room temperature controller, with digital display Features

Y

• LCD of the room temperature or setpoint, with two buttons (±) for adjusting the setpoint • Output for heating or cooling depending on connection type, or change in direction of operation with

external switch • With main switch for mains power supply and slide switch for three fan speeds • Suitable for wall mounting or fitting on recessed junction boxes

TSHK68*F001

• Electronics unit and switching relay • Quasi-continuous temperature control • 2-point pulsed activation • Individual unitary temperature control in residential and business rooms for activating e.g. electric heating

systems, thermal actuators, or fans or cooling units in air-conditioning systems. Technical data Power supply

Power supply1)

230 V~, approx. ±10 V, 50...60 Hz

Setting range Proportional band Display of actual value Hysteresis2) Shortest switching interval Time constant in still air Dead time in still air Time constant in moving air (0.2 m/s) Dead time in moving air (0.2 m/s)

5...30 °C; resolution 0.5 °C 3K 0...40 °C; resolution 0.1 °C Approx. ±0.1...0.5 K Approx. 18 minutes (E = 0.5) 20 minutes 2 minutes 15 minutes 1 minutes

Ambient temperature

0...55 °C

Load Fan load

3(2) A, 230 V~ 6(3) A, 230 V~

Weight Housing Housing material

0.18 kg Pure white (RAL 9010) Fire-retardant thermoplastic (fire classification UL94 HB) Black thermoplastic with NTC sensor At rear For cables of up to 2.5 mm²

Parameters

Ambient conditions

Outputs

Construction

Baseplate Cable inlet Screw terminals Standards and directives

Type of protection Protection class Energy class

1)

2)

IP30 (EN 60529) II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC

10% more voltage results in: Proportional band approx. 4 K, switching period 15 min, actual-value reduction approx. 0.5 K The device is pulsed electronically. When the temperature increases, the control factor falls to zero at the “Heating” output and rises to E = 1 at the “Cooling” output. A small temperature variation of ±0.1...0.5 K occurs as a result of pulsing, depending on the time constant of the room

Right of amendment reserved © 2024 Fr. Sauter AG

17


2-point controllers | Thermostats Overview of types

Y

Type

Operating mode

TSHK681F001

Heating or cooling or heating/cooling; 2-pipe

TSHK682F001

Heating/cooling; 4-pipe TSHK681

Mains switch ON/OFF Operating mode switch Fan speeds Indicators/display

TSHK682 • —

i OFF r o

(•)

opü °C digital

opü °C digital

Accessories

18

Type

Description

0362238001

Cable temperature sensor, 4 m long, made of PVC, for external temperature measurement (max. 50 m)

0362239001

Pure white intermediate cover plate, suitable for various recessed junction boxes

Right of amendment reserved © 2024 Fr. Sauter AG


Universal thermostats Temperature control, temperature monitoring and temperature limitation: SAUTER universal thermostats are used for these three applications. They provide control, monitoring and limitation according to needs without auxiliary energy.

Overview of universal thermostats

Type designation

TUC

Application Clamp-on temperature Duct Pipe

• • •

Operating mode Temperature controller, monitor (TR, TW) Safety temperature limiter (STB) Temperature limiter (TB) Further information

Right of amendment reserved © 2024 Fr. Sauter AG

• • • Page 20

19


2-point controllers | Thermostats

TUC: Universal thermostat Features • Regulates and monitors the temperature of liquids in baths, containers, pipes, ducts and HVAC installations

Y

• Variants as temperature monitor (TW) and temperature limiter (TB) • Double thermostat as TW and TB • Thermostat with remote sensor • Clamp-on thermostat • Capillary tube thermostat with or without thermowell • The shift in the change-over point is minimised due to the temperature compensation

TUC*0*F00*

• Thermowell supplied (max. 12 bar)

The following features and certifications do not apply to the United Kingdom of Great Britain and Northern Ireland (UK): • Variants as safety temperature monitor (STW), or safety temperature limiter (STB) • Double thermostat as STW or STB

TW, STW

• As per PED 2014/68/EU classified as cat. IV (TUC207F003, TUC407F001, TUC407F002)

Use in safety applications is not permitted in the United Kingdom. Technical data Power supply

Max. load

Terminal 1-2

Min. load

Terminal 1-4 Terminal 1-2, 1-4

Parameters

Adjustment point At ta 22 °C Effect of temperature at instrument Approx. –0.1...–0.2 K/K head Time constant with thermowell (LW 7) < 45 s (water) < 60 s (oil) Time constant without thermowell < 120 s (air)

Xsd

Xs

T

TB, STB

230 VAC, 10(2.5) A (on the normallyclosed contact) 230 VAC 2(0.4) A 24 VAC/DC, 100 mA

1

B01571

4 2

Ambient conditions

Ambient temperature Storage and transport temperature Max. pipe temperature during fitting

0...70 °C −25...80 °C 120 °C

Connection terminals Cable cross-section

Plug-in connectors

Construction

TUC207F003

Housing material Weight

0.75...2.5 mm2 Ø 6.5 mm Two sections, lower section black, upper section yellow, including inspection window PA, ABS, PMMA 0.2 kg

Type of protection Protection class

IP54 (EN 60529) I (EN 60730)

Sensor cartridge Housing

TUC407F001 TUC407F002

Standards, directives

20

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Thermostats Overview of types Type

Setting range Type

Switching difference

Capillary Sensor cartube length tridge length (± 12 mm)

Thermowell

Max. sen- Approval sor temp.

TUC101F003

−10…50 °C TW

Approx. 4.2 K

1.6 m

80 mm

100 mm, brass

140 °C CE, UKCA

TUC102F001

5...30 °C

TW

Approx. 5.6 K

0.7 m

65 mm

100 mm, brass

200 °C CE, UKCA

TUC105F001

15...95 °C

TW

Approx. 5.6 K

0.7 m

65 mm

100 mm, brass

200 °C CE, UKCA

TUC106F001

40...120 °C TW

Approx. 5.6 K

0.7 m

65 mm

100 mm, brass

200 °C CE, UKCA

TUC107F001

50...130 °C TW

Approx. 5.6 K

0.7 m

65 mm

100 mm, brass

200 °C CE, UKCA

TUC108F001

80...160 °C TW

Approx. 5.6 K

0.7 m

65 mm

100 mm, 200 °C CE, stainless steel UKCA

TUC207F003

70...130 °C STW

Approx. 10 K

1.6 m

60 mm

100 mm, brass

160 °C CE

TUC303F001

15...60 °C

TB

≤ 20 K

0.7 m

70 mm

100 mm, brass

200 °C CE, UKCA

TUC307F001

50...130 °C TB

≤ 20 K

0.7 m

65 mm

100 mm, brass

200 °C CE, UKCA

TUC407F001

95...130 °C STB

≤ 20 K

0.7 m

76 mm

100 mm, brass

160 °C CE

TUC407F002

95...130 °C STB

≤ 20 K

0.7 m

76 mm

150 mm, brass

160 °C CE

A A

Y

Universal thermostats approved in the UK must not be used as STW or STB in safety applications. The TUC207F003, TUC407F001 and TUC407F002 devices comply with modules B (type test) and D (QA system, CE 0035) of Pressure Equipment Directive 2014/68/EU.

A

Only use the supplied thermowells or stainless steel thermowells (part nos.: 0393022*** or 0392022***) with the TÜV-certified devices.

A

TUC108F001 with adapter for temperature reduction, only mount with supplied thermowell.

Accessories Type

Description

0300360008

Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)

0300360009

Holder for sensor cartridge

0300360010

Retaining strap for fitting onto pipes with a diameter of 15…100 mm

0300360011

Mounting plate for double thermostats

0300360012

Sensor support spiral for fitting in ventilation duct

0300360013

Duct/wall mounting bracket

Right of amendment reserved © 2024 Fr. Sauter AG

21


2-point controllers | Thermostats

Thermowells Features • Fitted in pipes and containers for holding sensor cartridges, immersion stems, temperature sensors,

Y

temperature controllers or thermostats Made of brass (Ms) or stainless steel (V4A) • • Versions with cylindrical pipe thread (G½" male ISO 228/1, flat-sealing)

1)

or cone-shaped

(R½" ISO 7/1 sealing in thread) • With pressure spring (LW 15) • With retaining holder

Overview of types Type

LW

Length

Material

Thread

Nominal pressure

Test pressure Tmax

0391022050

7

50 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022100

7

100 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022200

7

200 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022300

7

300 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022450

7

450 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022600

7

600 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391011050

7

50 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011100

7

100 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011150

7

150 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011200

7

200 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011300

7

300 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011450

7

450 mm

Brass

R½"

10 bar

16 bar

160 °C

0393022100

15

100 mm

Stainless steel

G½"

40 bar

60 bar

450 °C

0393022200

15

200 mm

Stainless steel

G½"

40 bar

60 bar

450 °C

0393022450

15

450 mm

Stainless steel

G½"

40 bar

60 bar

450 °C

0393012100

15

100 mm

Brass

G½"

16 bar

25 bar

160 °C

0393012200

15

200 mm

Brass

G½"

16 bar

25 bar

160 °C

0392022100

7

100 mm

Stainless steel

G½"

25 bar

40 bar

450 °C

0392022200

7

100 mm

Stainless steel

G½"

25 bar

40 bar

450 °C

0392022300

7

300 mm

Stainless steel

G½"

25 bar

40 bar

450 °C

1)

22

G½" male ISO 228/1, flat-sealing: for welding bushings with flat seal (accessories)

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Thermostats

A A A

0392022100 and 0392022300 for TUC thermostats only With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). 0391... with pressure screw (retaining holder) up to max. 200 °C

Y

Accessories Type

Description

0300360008

Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)

0364263000

Welding sleeve of steel, with female thread G½", flat seal of copper

0300360017

Pressure spring for LW 15 (10 pieces)

•

LW 7, 50 mm LW 7, 100 mm LW 7, 150 mm LW 7, 200 mm

• • • •

LW 7, 300 mm LW 7, 450 mm LW 7, 600 mm LW 15, 100 mm LW 15, 200 mm LW 15, 450 mm 0392022100 0392022200 0392022300

A A A A

• • • • • − − −

• L > 50 mm • • • • L > 300 mm • − − − − − − −

− − − − − − − • • • • • •

0392022100 and 0392022300 for TUC thermostats only. With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). Only use the thermowells (LW 15) with at least 2 sensors or thermostats with a diameter of at least 6 mm 0391... with pressure screw (retaining holder) up to max. 200 °C.

Right of amendment reserved © 2024 Fr. Sauter AG

23


Frost monitors SAUTER frost monitors protect ventilation systems against icing. With their special construction and design, they are particularly suitable for compact installations and/or installations that are subject to vibrations.

Overview of frost monitors

Type designation Function Monitor Limiter Output signal Switched Continuous Auxiliary energy Further information

24

TFL 201

TFL 611

• •

• −

• − • Page 25

• • − Page 27

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Frost monitors

TFL 201: Frost protection monitor/limiter with capillary-tube sensor Features

Y

• Temperature monitoring in heating coils and air ducts • Variants as monitors or limiters • Copper capillary tube • Switching point can be set internally • Small switching difference • With capillary-tube holders made of plastic

TFL201F**2

Technical data Power supply

230 VAC, 10(2.5) A (on the normallyclosed contact) 230 VAC 2(0.4) A

Parameters

Setting range −10...15 °C Factory setting 5 °C Switching difference 1.5 K Tolerance of switching difference Max. ±1 K Max. sensor temperature 120 °C Time constant in moving air (0.3 m/s)1) Capillary tube length 1.5 m: 25 s Capillary tube length 3 m: 31 s Capillary tube length 6 m: 51 s

Time characteristic

TFL201F*02 T

Terminal 1-4

Xs

Terminal 1-2

Xsd

Max. load

2 4

Ambient conditions

Ambient temperature2) Max. capillary temperature Storage and transport temperature

−5...70 °C 120 °C −30...80 °C

Connection terminals Cable cross-section

Plug-in connectors

1

Construction

Housing material Weight

Ø 0.75...2.5 mm2 Two sections, lower section black, upper section yellow, including inspection window ABS, PMMA 0.2 kg

Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP65 (EN 60529) I (IEC 60730) EN 60730-1, EN 60730-2-9 EN 60730-1, EN 60730-2-9

Housing

TFL201F*22

Standards, directives

Overview of types Type

Function

Switching difference

Capillary tube

Capillary tube holder

TFL201F002

Monitor

1.5 K (±1 K)

3000 mm

3

TFL201F022

Limiter

1.5 K (±1 K)

3000 mm

3

TFL201F102

Monitor

1.5 K (±1 K)

1500 mm

3

TFL201F602

Monitor

1.5 K (±1 K)

6000 mm

6

TFL201F622

Limiter

1.5 K (±1 K)

6000 mm

6

1) 2)

The frost monitor always reacts to the coldest point (minimum length 7.5 cm (1.5 m), 15 cm (3 m) and 30 cm (6 m)) The head of the instrument must be fitted in a warmer location than the sensor; see fitting instructions

Right of amendment reserved © 2024 Fr. Sauter AG

25


2-point controllers | Frost monitors Accessories Type

Description

0300360014

Six holders for fitting the capillary tube

Y

26

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Frost monitors

TFL 611: Continuous frost monitor with capillary sensor Features • Records the lowest temperature that occurs for a length of at least 250 mm at any position along the

Y

capillary tube • Used on air side in ventilation and air conditioning units where protective measures must be taken against freezing Active capillary sensor for measuring the lowest temperatures in the range 0...15 °C • • Vapour-filled capillary tube and diaphragm system with inductive system of measurement • Setting range 1...10 °C

TFL611F*01

• Start-up function • LED and 7-segment display • Self-monitoring of sensor line

Technical data Power supply

Y10

Power supply Power consumption Frequency 1)

24 V~, 10/-20% < 6.6 VA 50...60 Hz

6K Q11

10 V

Q12 Q14

Q11

Parameters

Measuring range Setting range Adjustment point Accuracy for adjustment point Switching difference Temperature for capillary tube Time constant in still air Time constant in moving air Response length for capillary tube

0...15 °C 1...10 °C 5 °C ±1K Approx. 2 K < 110 °C Approx. 90 s < 40 s Min. 250 mm

Admissible cable length Valve control for terminal Y Current Sensor temperature for terminal B Valve control for terminal Y10 Current Min. switching capacity

300 m with 1.5 mm² 0...10 V < 0.1 mA 0...10 V ≙ 0...15 °C 0...10 V ±1 mA 12 V~/=, 100 mA

Max. switching capacity

250 V~, 6(2) A; 24 V=, 6 A

Humidity (non-condensing) Temperature Humidity (non-condensing) Temperature

< 85% rh -15...55 °C < 95% rh -25...65 °C

Terminals with spring technology

Max. 2 × 1.5 mm² Or 1 × 2.5 mm² Min. 0.25 mm² Cable gland M16 for cable diameter 5...10 mm I PA, silver grey (RAL 7001)

Q12 Q14 0V 2K

T [°C]

P (1...10 °C)

Inputs/outputs

Analogue input Analogue outputs

Potential-free relay outputs (Q terminals)

Ambient conditions

Operation Storage and transport

Construction

Cable inlet Protection class2) Housing 1) 2)

SELV/PELV: Safety Extra Low Voltage/Protected Extra Low Voltage No earth conductor necessary

Right of amendment reserved © 2024 Fr. Sauter AG

27


2-point controllers | Frost monitors Housing cover Cap Capillary tube

PC, transparent ABS, light grey (RAL 7035) Copper

Vibration resistance Type of protection Operation as per IEC 721-3-3 Storage and transport as per IEC 721-3-2 RoHS Directive 2011/65/EU EMC Directive 2014/30/EU

EN 60721-3-3 (class 3M2) IP42 (EN 60529) Class 3K5 Class 2K3

Standards and directives

Y

Low-Voltage Directive 2014/35/EU

EN IEC 63000 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN60730-2-9

Overview of types Type

Description

Weight

TFL611F201

Continuous frost monitor; 0...15 °C; capillary tube length= 2 m

340 g

TFL611F601

Continuous frost monitor; 0...15 °C; capillary tube length= 6 m

410 g

Accessories

28

Type

Description

0292146001

Set for duct fitting consisting of: 5 capillary-tube holders, 1 depth-adjustable flange

0300360014

Six holders for fitting the capillary tube

0374534001

Depth-adjustable flange

Right of amendment reserved © 2024 Fr. Sauter AG


Pressure switches SAUTER pressure switches can be used in any application for controlling and monitoring the pressure in liquids, gases and vapours. They detect changes in pressure in gaseous and/or liquid media and are used to switch pumps, valves or compressors.

Overview of pressure switches

Type designation

DSA •

DSB •

DSF •

DSL −

DSH −

DFC 17B •

DFC 27B •

DSD −

−

−

−

−

•

•*)

•*)

−

For falling pressure

−

−

−

•

−

•*)

•*)

−

Differential pressure switch Pressure sensors Of brass Of stainless steel

−

−

−

−

−

−

−

•

• −

• −

− •

• −

− •

• −

− •

− •

Switching difference Fixed Variable

• −

− •

− •

• −

• −

− •

− •

• −

− − − − − Page 30

• • • • −

• • • • •

• • • • −

• • • • •

• • • − −

• • • − •

− − − − − Page 38

Pressure monitors Pressure limiters For rising pressure

Certification VdTÜV 100 EN 12952-11, EN 12953-9 Germanischer Lloyd (GL) Lloyds Register Can be used for aggressive media Further information

A

Page 32

Page 34

Page 36

*) Depending on approval

Right of amendment reserved © 2024 Fr. Sauter AG

29


2-point controllers | Pressure switches

DSA: Pressure switch Features • For regulating and monitoring pressure in liquids, gases and vapours

Y

• Especially suitable for applications in compact installations • Upper switching point can be adjusted • Fixed switching difference, no hysteresis setting is necessary • Sealable

DSA14*F002

• Pressure sensor made of brass for non-aggressive media

Technical data Power supply

Xsd

Xs

P

Maximum load with gold-plated contacts1) Minimum load with gold-plated contacts Maximum load with silver-plated contacts Minimum load with silver-plated contacts

400 mA, 24 V, 10 VA 4 mA, 5 V 10(4) A, 250 VAC, 50 W, 250 VDC 100 mA, 24 V

Parameters

1

B01574

3 2

Pressure connection

G½" A

Admissible sensor temperature Ambient temperature

70 °C −20...70 °C

Fitting Housing Housing material Device plug

Pipe and wall mounting Transparent cover Impact-proof thermoplastic Standard female connector for Ø 6...10 mm cable

Type of protection2) Protection class LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE)

IP65 (EN 60529) I (IEC 60730) EN 60730-1, EN 60730-2-6 EN 60730-1, EN 60730-2-6 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN ISO12100: Annex II B of the Reg. EN ISO12100: Annex II B of the Reg. (Partly Completed Machinery) EN IEC 63000

Ambient conditions

Construction

Standards, directives

CE/UKCA conformity3)

EMC-2016 (UKCA) Machinery-D 2006/42/EC (CE) SMSR-2008 (UKCA)

RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) PED 2014/68/EU (CE) PESR-2016 (UKCA)

1)

2) 3)

30

EN IEC 63000 Article 4.3 and Annex A of the Reg. Article 8.3 and Essential Safety Requirements of the Reg.

If the contacts are subjected to a load greater than specified, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts. Depending on the fitting position, see the fitting instructions. The devices are not suitable for outdoor applications. Use as a pressure limiter is not permitted. The use of an electrical interlock is not permitted.

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Pressure switches Overview of types Type

Setting range

Switching difference

Maximum pressure Admissible vacuum Weight loading

DSA140F002

0.5...2.5 bar

0.25 bar

12 bar

-0.7 bar

0.5 kg

DSA143F002

0.5...6 bar

0.3 bar

16 bar

-0.7 bar

0.5 kg

DSA146F002

1...10 bar

0.4 bar

20 bar

-1.0 bar

0.4 kg

A

Y

DSA: Pressure sensor made of brass for non-aggressive media; Xs = upper switching point

Accessories Type

Description

0035465000

Throttle screw for absorbing pressure surges, brass

0214120000

Throttle screw for absorbing pressure surges, stainless steel

0259239000

Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass

0292001000

Setpoint adjuster according to customer's wishes (setting accuracy: ±3% of the setting range, but a minimum of ±0.2 bar)

0292004000

Setpoint adjuster sealed (with accessory 0292001000 only)

0292018001

Damping screw for absorbing pressure surges in low viscosity media

0292150001

Fixing bracket for wall mounting

0296936000

Fixing brackets for rail: top-hat rail EN 60715, 35 × 7.5 mm and 35 × 15 mm

0300360007

Capillary throttle, stainless steel, length 1 m, G½"-G½"

0311572000

Screw fitting for copper tubes of Ø 6 mm, brass

0381141001

Profile sealing ring, copper, for G½"

A

0296936000: With accessory 0292150001 only

Right of amendment reserved © 2024 Fr. Sauter AG

31


2-point controllers | Pressure switches

DSB, DSF: Pressure monitors and pressure switches Features • For regulating and monitoring pressure in liquids, gases and vapours

Y

• Adjustable lower switching point • Adjustable switching difference • Sealable • Pressure sensor made of brass for non-aggressive media (DSB)

DSB1**F001

• Pressure sensor made of stainless steel for aggressive media (DSF) • SIL 2-certified as per IEC 61508

1)

• Approved for marine applications (GL- and LR-certified)

Technical data

Xs

Xsd

P

Power supply

1

B03377

3 2

Maximum load with gold-plated contacts2) Minimum load with gold-plated contacts Maximum load with silver-plated contacts Minimum load with silver-plated contacts

400 mA, 24 V, 10 VA

Pressure connection

G ½" A

Ambient temperature

−20…70 °C

Housing Housing material Device plug

Transparent cover Impact-proof thermoplastic Standard female connector for cable Ø 6…10 mm

Type of protection3) Protection class Test mark4)

IP65 (EN 60529) I (IEC 60730) TÜV DWFS (SDBFS) ID: 06024 Germanischer Lloyd (GL) Lloyds Register (LR) EN 60730-1, EN 60730-2-6 EN 60730-1, EN 60730-2-6 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN ISO12100:2018

4 mA, 5 V 10(4) A, 250 VAC, 50 W, 250 VDC 100 mA, 24 V

Parameters

Ambient conditions

Construction

Standards, directives

Ship-approved CE/UKCA conformity5)

LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) Machinery-D 2006/42/EC (CE)

1) 2)

3) 4)

5)

32

SIL 2 approval is not valid in the United Kingdom (UK). If the contacts are subjected to a load greater than specified, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts Depending on the fitting position, see the fitting instructions. The devices are not suitable for outdoor applications. For the EU: DWFS (SDBFS): As a safety pressure limiter when an external electrical locking facility is fitted downstream in the circuit. Certificates can be downloaded from www.certipedia.com. For the United Kingdom (UK): Use as a safety pressure limiter is not permitted. The use of an electrical interlock is not permitted. Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Pressure switches SMSR-2008 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) PED 2014/68/EU (CE)

EN ISO12100:2018 EN IEC 63000:2018 EN IEC 63000:2018 VdTÜV pressure information sheet 100, sheet 1, cat. IV EN 12952-11, EN 12953-9 Article 8.3 of the Reg. AD 2000 Rulebook IEC 61508 parts 1-2 and 4-7

PESR-2016 (UKCA)6) SIL conformity as per SIL 2

Standards7)

Y

Overview of types Type

Setting range

Switching differ- Maximum pres- Max. sensor ence sure temp.

Admissible vac- Weight uum loading

DSB138F001

0...1.6 bar

0.25...0.65 ba 12 bar r

70 °C

-0.7 bar

0.5 kg

DSB140F001

0...2.5 bar

0.25...0.75 ba 12 bar r

70 °C

-0.7 bar

0.5 kg

DSB143F001

0...6 bar

0.3...1.6 bar

16 bar

70 °C

-0.7 bar

0.5 kg

DSB146F001

0...10 bar

0.8...3.7 bar

30 bar

70 °C

-1 bar

0.4 kg

DSB152F001

6...16 bar

1...4 bar

30 bar

70 °C

-1 bar

0.4 kg

DSB158F001

0...25 bar

1...7.5 bar

60 bar

70 °C

-1 bar

0.4 kg

DSB170F001

5...40 bar

1.4...7.5 bar

60 bar

70 °C

-1 bar

0.4 kg

DSF125F001

–1...1.5 bar

0.25...0.75 ba 12 bar r

110 °C

-1 bar

0.5 kg

DSF127F001

–1...5 bar

0.3...1.5 bar

16 bar

110 °C

-1 bar

0.5 kg

DSF135F001

0...0.6 bar

0.12...0.60 ba 12 bar r

110 °C

-1 bar

0.5 kg

DSF138F001

0...1.6 bar

0.25...0.7 bar 12 bar

110 °C

-1 bar

0.5 kg

DSF140F001

0...2.5 bar

0.25...0.75 ba 12 bar r

110 °C

-1 bar

0.5 kg

DSF143F001

0...6 bar

0.3...1.5 bar

16 bar

110 °C

-1 bar

0.5 kg

DSF146F001

0...10 bar

0.8...3.0 bar

18 bar

110 °C

-1 bar

0.5 kg

DSF152F001

0...16 bar

1.2...3.8 bar

60 bar

110 °C

-1 bar

0.3 kg

DSF158F001

0...25 bar

1.5...8.0 bar

60 bar

110 °C

-1 bar

0.3 kg

DSF170F001

15...40 bar

1.7...8.2 bar

60 bar

110 °C

-1 bar

0.3 kg

A A A

DSB: Pressure sensor made of brass for non-aggressive media; XS = lower switching point. DSF: Pressure sensor made of stainless steel for aggressive media; XS = lower switching point. The switching difference must be within the setting range of the switching point. The minimum values of the switching difference are only possible in the lower setting range.

Accessories Type

Description

0259239000

Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass

0292001000

Setpoint adjuster according to customer's wishes (setting accuracy: ±3% of the setting range, but a minimum of ±0.2 bar)

0292002000

Switching difference according to customers' wishes (setting accuracy: ±5% of the setting range, but a minimum of ±0.05 bar, with accessory 0292001000 only)

0292004000

Setpoint adjuster sealed (with accessory 0292001000 only)

0292150001

Fixing bracket for wall mounting

0296936000

Fixing brackets for rail: top-hat rail EN 60715, 35 × 7.5 mm and 35 × 15 mm

0311572000

Screw fitting for copper tubes of Ø 6 mm, brass

0381141001

Profile sealing ring, copper, for G½"

A 6) 7)

0296936000: With accessory 0292150001 only

SIL 2 approval is not valid in the United Kingdom (UK). SIL 2 approval is not valid in the United Kingdom (UK).

Right of amendment reserved © 2024 Fr. Sauter AG

33


2-point controllers | Pressure switches

DSL, DSH: Specially designed pressure limiter Features • Switching point can be adjusted

Y

• Sealable • Pressure sensor made of brass for non-aggressive media (DSL) • Pressure sensor made of stainless steel for aggressive media (DSH) • Locking type: With falling pressure (DSL) or with rising pressure (DSH) • SIL 2 certified as per IEC 61508 • Approved for marine applications (GL and LR certified)

P

Technical data

Xs

Xsd

Power supply

B03377

3 2

1

DSL1**F001

Maximum load with gold-plated contacts1) Minimum load with gold-plated contacts Maximum load with silver-plated contacts Minimum load with silver-plated contacts

400 mA, 24 V, 10 VA

Pressure connection

G ½" A

Ambient temperature

−20…70 °C

Housing Housing material Device plug

Transparent cover Impact-proof thermoplastic Standard female connector for cable of Ø 6…10 mm

Type of protection2) Protection class Test mark3)

IP65 (EN 60529) I (IEC 60730) TÜV DSL: SDBF ID: 06022 DSH: SDB ID: 06023 PED: 2014/68/EU, cat. IV Germanischer Lloyd (GL) Lloyds Register (LR) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-6 VdTÜV pressure information sheet 100, cat. IV EN 12952-11, EN 12953-9 EN ISO 12100:2018

4 mA, 5 V 10(4) A, 250 VAC, 50 W, 250 VDC 100 mA, 24 V

Xsd

Xs

P

Parameters

Ambient conditions

1

B01574

3 2

Construction

DSH1**F001

Standards and directives

Ship-approved CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU PED 2014/68/EU

SIL conformity as per SIL 2

1)

2) 3)

34

Machinery Directive 2006/42/EC (according to Appendix II, 1B) Standards

IEC 61508 parts 1-2 and 4-7

If the contacts are subjected to a load greater than specified, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts Depending on the fitting position, see the fitting instructions. The devices are not suitable for outdoor applications. Certificates can be downloaded from www.certipedia.com. The certificates are not valid in the United Kingdom of Great Britain and Northern Ireland.

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Pressure switches Overview of types

/

Min. change for reset: Average values

Type

Setting range

Min. change for Maximum pres- Admissible sen- Admissible vac- Weight reset sure sor temperature uum loading

DSL140F001

0...2.5 bar

0.4 bar

12 bar

70 °C

-0.7 bar

DSL143F001

0...6 bar

0.5 bar

16 bar

70 °C

-0.7 bar

0.5 kg

DSL152F001

6...16 bar

1.2 bar

30 bar

70 °C

-1.0 bar

0.4 kg

DSH127F001

-1...5 bar

-0.4 bar

16 bar

110 °C

-1.0 bar

0.5 kg

DSH143F001

0.5...6 bar

-0.45 bar

16 bar

110 °C

-0.7 bar

0.5 kg

DSH146F001

1...10 bar

-0.8 bar

18 bar

110 °C

-1.0 bar

0.5 kg

DSH152F001

2...16 bar

-1.5 bar

60 bar

110 °C

-1.0 bar

0.3 kg

DSH158F001

5...25 bar

-1.8 bar

60 bar

110 °C

-1.0 bar

0.3 kg

DSH170F001

15...40 bar

-2.0 bar

60 bar

110 °C

-1.0 bar

0.3 kg

A A

Y

0.5 kg

DSL: Locks when the pressure falls (SDBF); pressure sensor made of brass for non-aggressive media. DSH: Locks when the pressure rises (SDB); pressure sensor made of stainless steel.

Accessories Type

Description

0259239000

Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass

0292001000

Setpoint adjuster according to customer's wishes (setting accuracy: ±3% of the setting range, but a minimum of ±0.2 bar)

0292004000

Setpoint adjuster sealed (with accessory 0292001000 only)

0292150001

Fixing bracket for wall mounting

0296936000

Fixing brackets for rail: top-hat rail EN 60715, 35 × 7.5 mm and 35 × 15 mm

0311572000

Screw fitting for copper tubes of Ø 6 mm, brass

0381141001

Profile sealing ring, copper, for G½"

A

0296936000: With accessory 0292150001 only

Right of amendment reserved © 2024 Fr. Sauter AG

35


2-point controllers | Pressure switches

DFC 17B, 27B: Heavy-duty pressure switch Features • For regulating and monitoring pressure in liquids, gases and vapours

Y

• Especially suitable for installations subject to vibrations • Contact rating 1 mA/6 V to 10 A/400 V • Gold-plated silver contacts, vibration-proof snap-action switch with single-pole change-over switch • Upper and lower switching points can be set independently of each other

DFC17B76F001

• Sealable • Splashproof • DFC17B**F001: Pressure sensor made of brass for non-aggressive media • DFC27B**F002: Pressure sensor made of stainless steel for aggressive media

Technical data

Xs2

Xsd

Xs1

P

Power supply

1

B03311

3 2

Maximum load with gold-plated contacts1) Minimum load with gold-plated contacts Maximum load with silver-plated contacts2) Minimum load with silver-plated contacts

200 mA, 50 V

Media temperature Ambient temperature

≤ 110 °C −40...70 °C

Housing Housing material Cable inlet Screw terminals Pressure connection

Transparent cover Light alloy PG 13.5 For electrical cables up to 2.5 mm² G½" A

Type of protection Protection class Test mark3)

IP44 (EN 60529) I (IEC 60730) TÜV DWFS (SDBF) ID: 06018 DWFS (SDB) ID: 06019 DB (SDBF) ID: 06017 Type 2 B (EN 60730) EN 60730-1, EN 60730-2-6 EN 60730-1, EN 60730-2-6 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN ISO12100:2018

1 mA, 6 V 10(2) A, 400 VAC (25 W), 250 VDC 100 mA, 24 V

Ambient conditions

Construction

Standards, directives

CE/UKCA conformity4)

Mode of operation LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) Machinery-D 2006/42/EC (CE)

1)

2)

3) 4)

36

If the contacts are subjected to a load greater than 200 mA, 50 V, the gold plating will be destroyed. They are then classed merely as silver contacts and lose the properties of gold-plated contacts Take the RC circuitry into account for inductive loads 230/400 V networks From 70 °C media temperature, the current must be reduced to 6 A Certificates can be downloaded from www.certipedia.com. The certificates are not valid in the United Kingdom (UK). Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Pressure switches SMSR-2008 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) PED 2014/68/EU (CE)

EN ISO12100:2018 EN IEC 63000:2018 EN IEC 63000:2018 VdTÜV pressure information sheet 100, sheet 1, cat. IV EN 12952-11, EN 12953-9 Article 8.3 of the Reg. AD 2000 Rulebook

PESR-2016 (UKCA)5)

Y

Overview of types Type

Setting range (bar)

Min. switching Maximum pres- Max. temp., difference (bar) sure (bar) sensor (°C)

Admissible vac- Weight (kg) uum loading (bar)

DFC17B54F001

0...2.5

0.14

16

70

-0.7

1.2

DFC17B58F001

0...6.0

0.18

16

70

-1.0

1.2

DFC17B59F001

–1...5.0

0.20

16

70

-1.0

1.2

DFC17B76F001

0...10

0.50

40

70

-1.0

1.1

DFC17B78F001

0...16

0.50

40

70

-1.0

1.1

DFC17B79F001

16...32

0.80

42

70

-1.0

1.1

DFC17B96F001

0...25

1.70

100

70

-1.0

1

DFC17B97F001

25...50

2.00

100

70

-1.0

1

DFC17B98F001

0...40

1.80

100

70

-1.0

1

DFC27B26F002

–1...2.5

0.30

21

110

-1.0

0.9

DFC27B43F002

0.5...6.0

0.30

21

110

-1.0

0.9

DFC27B46F002

1...10

0.30

21

110

-1.0

0.9

DFC27B52F002

2...16

0.30

21

110

-1.0

0.9

A

The switching difference must be within the setting range of the switching point. The minimum values of the switching difference are only possible in the lower setting range.

Accessories Type

Description

0259239000

Reduction nipple G½" on 7/16" 20-UNF-2A for copper tubes of Ø 6 mm, brass

0311572000

Screw fitting for copper tubes of Ø 6 mm, brass

0035465000

Throttle screw for absorbing pressure surges, brass

0214120000

Throttle screw for absorbing pressure surges, stainless steel

0300360007

Capillary throttle, stainless steel, length 1 m, G½"-G½"

0292018001

Damping screw for absorbing pressure surges in low viscosity media

0259189000

Holder for raised wall mounting

0292019001

Setpoint adjustment for each switching point according to customer's wishes (setting accuracy: ±3% of the setting range)

0292019002

Sealing of the adjustment screw for each switching point (only with accessory 0292019001)

0381141001

Profile sealing ring, copper, for G½"

5)

For the United Kingdom (UK): Use as a safety pressure limiter is not permitted. The use of an electrical interlock is not permitted.

Right of amendment reserved © 2024 Fr. Sauter AG

37


2-point controllers | Pressure switches

DSD: Differential pressure switch Features • For monitoring the differential pressure in liquids, gases and vapours

Y

• For use in, for example, filter technology and in process plants • Differential pressure setting ranges from 0.06 to 6 bar • Up to 80 °C media temperature • High repeatability • High overload protection • Can be used in all neutral media, such as heating water, neutral gases, oils etc.

DSD1**F002

• Long serviceable life • With fitting bracket

Technical data Parameters

Min. load

AC min: 0.1 A, 250 VAC, 25 VA DC min: 0.1 A, 30 VDC AC max: 3(1) A, 250 VAC, 250 VA DC max: 0.4 A, 30 VDC, 10 W 1.5%/10 K 3% of the setting range 12% of the setting range

Max. load Temperature dependence Accuracy Hysteresis Mechanical serviceable life

2 3

106 switchings 16 bar

Max. static operating pressure (positive and negative pressure) Ambient conditions

Ambient temperature Media temperature Ambient humidity

−10…70 °C 0...80 °C (non-freezing media) 45…75% rh

Power cable1) Diaphragms Connection thread Weight

3...0.5 mm2 Chromium-nickel steel 1.4310 G ⅛" (female thread) 0.2 kg

Type of protection Protection class Low-Voltage Directive 2014/35/EU

IP65 (EN 60529) II (EN 60730) EN 60730-1, EN 60730-2-6 Altitude up to 2000 m EN 55014-1 Click rate N < 0.2 Art. 4.4 Art. 4.3 and Art. 13, fluid group 2

Construction

Standards, directives

CE conformity according to

EMC Directive 2014/30/EU PED 2014/68/EU

Overview of types Type

Setting range (bar)

DSD134F102

0.06...0.6

DSD137F002

0.10...1.0

DSD140F002

0.25...2.5

DSD143F002

0.6...6.0

1)

38

1 m long, fixed wiring

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Pressure switches Accessories Type

Description

0300360005

Cutting ring fitting G⅛" to 6 mm pipe (2 pcs)

0300360006

Pneumatic fitting G⅛" to 6 mm hose (2 pcs)

0300360016

Throttle screws G⅛", G⅛" (2 pcs)

Right of amendment reserved © 2024 Fr. Sauter AG

Y

39


Humidistats Room-, panel- and duct-mounted humidistats are employed for monitoring and controlling devices that are used for humidity regulation (fans, driers and humidifiers).

Overview of humidistats

Type designation Application Room Panel Duct Further information

40

HSC 120

HSC 101

HBC

• − − Page 41

− • − Page 42

− − • Page 43

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Humidistats

HSC 120: Room humidistat Features • Monitoring and regulation of relative air humidity in rooms by controlling fans, drying units and air

Y

humidifiers • Variable relative humidity as setpoint based on printed scale in % rh • Measurement taken via a measuring element of stabilised synthetic textile tape. • Controller with fixed switching difference of Xsd

Technical data HSC120F001

Power supply

Max. load Min. load

5(3) A, 250 VAC 100 mA, 24 VAC/DC

Setting range Setting accuracy1) Humidity calibration at Switching difference Xsd Long-term stability Time constant in moving air (0.2 m/s) Temperature effect

30...90% rh ±5% rh 55% rh, 23 °C Typ. 8% rh Approx. -1.5% rh/a Approx. 5 minutes 0.5% rh/K

Ambient humidity Temperature Ambient humidity Temperature

30...90% rh non-condensing 0...50 °C 10...95% rh non-condensing -25...70 °C without condensation

Dimensions W × H × D Weight Housing Housing material Screw terminals

76 × 76 × 34 mm 0.09 kg Pure white (RAL 9010) Fire-retardant thermoplastic, UL94V-0 For electrical wires of up to 1.5 mm²

Parameters

Ambient conditions

Operation Storage and transport

HSC120F010

XSd

Xs

H%

Construction

3 2

CE conformity according to

Type of protection2) Protection class Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP 30 (EN 60730-1), operating status II (IEC 60730) 3K3 (IEC 60721-3-3) EN 60730 EN 60730-1, EN 60730-2-13

Overview of types Type

Features

HSC120F001

Setting via external setpoint adjuster

HSC120F010

Internal setpoint adjuster

1

B01572

Standards, directives

relative humidity at 23 °C

Accessories Type

Description

0362225001

Intermediate plate, pure white, for wall mounting on recessed junction box

1)

2)

The setting accuracy of the humidistat is valid for the calibration point ±5% rh at 55% rh and 23 °C following initial calibration at the factory. See diagram “Setting accuracy”. In general, humidity sensors (humidistats) are subject to increased ageing if they are used and/or stored in very contaminated air or aggressive gases. The humidistat may start to drift and its linearity may change under these conditions. If the humidistats are used in very contaminated air, the warranty does not cover a premature re-calibration or the replacement of the complete humidistat Operating status: device mounted and closed

Right of amendment reserved © 2024 Fr. Sauter AG

41


2-point controllers | Humidistats

HSC 101: Panel-mounted humidistat (packing unit: 50 pieces) Features

Y

• Monitoring and regulation of relative humidity by controlling fans, drying units and air humidifiers • Adjustment of change-over point via setpoint adjustment axis

HSC101F001

• Suitable for fitted applications with protection class II • Measurement via a measuring element of stabilised synthetic textile tape • Secured with bolting hole and fixing hole (blind hole) • Micro-switch with single-pole change-over contacts and fixed switching difference

Xs

H%

• Suitable for panel-mounted units only

XSd

Technical data Power supply

1

B01572

3 2

Max. load Min. load

5(3) A, 250 VAC 100 mA, 24 V

Setting range Setting accuracy1) Humidity calibration at Switching difference Xsd2) Long-term stability Time constant in moving air (0.2 m/s) Temperature effect

25...95% rh ±5% rh 55% rh, 23 °C Typ. 8% rh

Humidity (non-condensing) Temperature Humidity (non-condensing) Temperature

25...95% rh 0...70 °C 10...95% rh -20...70 °C

Weight Baseplate Electrical connection

0.03 kg Thermoplastic AMP terminals 2.8 mm

Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP00 (EN 60529) 0 (IEC 60730) EN 55014 Art. 4.2 EN 60730-1, EN 60730-2-13

Parameters

relative humidity at 23 °C

–1.5% rh/a Approx. 3 minutes 0.5% rh/K

Ambient conditions

Operation Storage and transport

Construction

Standards, directives3)

CE conformity according to

Overview of types Type

Features

HSC101F001

Panel-mounted humidistat

1)

2) 3)

42

The setting accuracy of the humidistat is valid for the calibration point ±5% rh at 55% rh and 23 °C following initial calibration at the factory. See diagram “Setting accuracy”. In general, humidity sensors (humidistats) are subject to increased ageing if they are used and/or stored in very contaminated air or aggressive gases. The humidistat may start to drift and its linearity may change under these conditions. If the humidistats are used in very contaminated air, the warranty does not cover a premature re-calibration or the replacement of the complete humidistat Can be substantially improved by recalibration during usage The fitting method must adhere to the relevant safety standards

Right of amendment reserved © 2024 Fr. Sauter AG


2-point controllers | Humidistats

HBC: Duct-mounted humidistat Features • Monitoring and regulation of relative humidity by controlling fans, drying units and air humidifiers

Y

• Temperature-compensated humidity sensor • Variable relative humidity as setpoint based on printed scale in % rh • Includes fixing bracket with seal for duct or wall mounting • For fitting in a ventilation duct or on a wall • With single-pole change-over contacts and fixed switching difference Xsd

HBC11*F001

• Immersion depth 130...156 mm; includes fixing bracket

Technical data Power supply

5(3) A, 250 VAC 100 mA, 24 V

Setting range Setting accuracy Humidity calibration at Temperature influence Long-term stability Time constant in moving air (0.2 m/s) Switching difference Xsd Max. air speed

15...95% rh ±5% rh 55% rh, 23 °C Compensated –1.5% rh/a Approx. 3 minutes Typically 8% rh (after humidity calibration) 10 m/s

Humidity (non-condensing) Temperature Humidity (non-condensing) Temperature

30...90% rh 0...70 °C 10...95% rh -20...70 °C

Housing material Housing cover Sensor tube

Glass-fibre-reinforced thermoplastic Thermoplastic, sealable Glass-fibre-reinforced thermoplastic, Ø 30 mm PG 11 For electrical cables of up to 1.5 mm²

HBC111F001

Storage and transport

Xs XSd 3 2

1

HBC111F001

Ambient conditions

Operation

H%

Parameters

B01572

Max. load Min. load

Construction

H% Xs XSh

XSd

Cable inlet Screw terminals

HBC112F001

Low-Voltage Directive 2014/35/EU

IP30 (EN 60529) II (IEC 60730) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-13

Overview of types

1

Type

Switching range Xsh

Number of switches

Weight

HBC111F001

–

1

0.33 kg

HBC112F001

6...25% rh

2

0.35 kg

A

6 5 3 2 B04333

Type of protection Protection class EMC Directive 2014/30/EU

XSd

Standards and directives

HBC112F001

HBC 112: For 3-point control or min./max. monitoring and internally adjustable switching range X sd

Right of amendment reserved © 2024 Fr. Sauter AG

43


2-point controllers | Humidistats Accessories

Y

44

Type

Description

0303538001

Set for increasing protection rating to IP55 (housing lid with transparent cap for setpoint knob, seal, 1 cable gland - PG 11, 1 plug - PG 11)

0370560011

Cable screw fitting PG 11, plastic, for cable of Ø 9...11 mm

Right of amendment reserved © 2024 Fr. Sauter AG


Right of amendment reserved © 2024 Fr. Sauter AG

45


Data capture

Accurate measured values are the basis for efficient control. The results from the data capture form the basis for control and monitoring. SAUTER provides quality sensors for all physical variables, such as temperature, humidity, pressure, flow and air quality, that are specifically geared towards building automation systems and the HVAC industry.

46

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture Temperature EGT 130, 330, 332, 335, 430: Room temperature sensor, surface-mounted

49

EGT 386, 388, 486, 686, 688: Room temperature sensors, recessed

51

EGT 301, 401, 601: Outdoor-temperature sensor

52

EGT 353...356, 456, 554, 654: Cable temperature sensors

54

EGT 346...348, 392, 446, 447, 646, 647: Duct temperature sensors

56

Thermowells

58

EGT 311, 411, 611: Clamp-on temperature sensors

60

EGS 100: Radiation temperature sensor

62

Air quality EGQ 220, 222: Room transducer, CO2, surface-mounted

64

EGQ 212: Duct transducer, CO2, temperature

68

EGQ 120: Room transducer, air quality, surface-mounted

66

EGQ 110: Duct transducer, air quality (VOC), temperature

70

EGQ 281: Room transducer, CO2, recessed

67

72

EGE 112: Duct transducer, enthalpy

76

EGH 120, 130: Room transducer

73

EGH 102: Dew point monitor and transducer

77

EGH 681: Room transducer, relative humidity and temperature, recessed

74

EGH 103: Dew point monitor

78

EGH 110...112: Duct transducer, relative humidity and temperature

75

Humidity Overview of humidity sensors

Flow and pressure Overview of flow and pressure sensors

79

EGP 100: Differential pressure transmitter

80

XAFP 100: Flow probe

82

SVU 100: Air-flow transducer

83

DSU, DSI: Pressure transmitters

84

DSDU, DSDI: Differential pressure transmitter

86

SGU 100: Sash sensor

88

Right of amendment reserved © 2024 Fr. Sauter AG

47

X


Temperature sensors SAUTER temperature sensors are used for heating and air-conditioning systems in residential, office and business spaces. They are used to measure room, duct, outside and pipe temperatures.

Overview of temperature sensors

Type designation Application Pipe/duct Cable Room (passive) Room (active) Clamp-on temperature Outdoor temperature Further information

Type designation Application Pipe/duct Cable Room (passive) Room (active) Clamp-on temperature Outdoor temperature Radiation temperature Further information

48

EGT 130

EGT 330...335, 430

EGT 386, 388, 486, 686, 688

EGT 301, 401

− − − • − − Page 49

− − • − − − Page 49

− − • − − − Page 51

− − − − − • Page 52

EGT 353...356, 456, 554

EGT 346...348, 392, 446, 447

EGT 311, 411

EGS 100

− • − − − − − Page 54

• − − − − − − Page 56

− − − − • − − Page 60

− − − − − − • Page 62

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Temperature

EGT 130, 330, 332, 335, 430: Room temperature sensor, surface-mounted Features • Passive or active measuring element for room temperature • Variants with setpoint adjuster, presence button and multicolour status LED • Suitable for direct wall mounting and recessed junction boxes

X

Technical data Ambient conditions

Ambient temperature Ambient humidity

−35…70 °C Max. 85% rh, non-condensing

Colour Housing material Cable inlet Connection terminals Weight

Traffic white (RAL9016) Polycarbonate (PC) UL94-V0 Through the back Spring-type terminals, max. 1.5 mm² 50 g

Type of protection EMC-D 2014/30/EU (CE)

IP20 (EN 60529) after fitting EGT130F032: EN 60730-1 (mode of operation 1, residential premises) See EMC Directive EN IEC 63000

EGT*30F***

Construction

Standards, directives

CE/UKCA conformity1)

EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

EN IEC 63000

EGT332F103

Resistance values Measuring element Ni500 Ni1000 Pt100 Pt1000

A

Standard DIN 43760 DIN 43760 DIN EN 60751 DIN EN 60751

Nominal value at 0 °C 500 Ω 1000 Ω 100 Ω 1000 Ω

Tolerance at 0 °C ±0.4 K ±0.4 K ±0.3 K ±0.3 K

The tolerances only apply to the measuring elements. The accuracy of the sensor depends on the measuring element used and the cable length

Active type EGT130F032

Measuring range Measuring accura- Output signal cy at 21 °C Typically ±1% of 0...10 V, min. load 0…50 °C impedance 5 kΩ Other ranges can measuring be parametrised range2)3)

Power supply

Power consumption

15…24 VDC Max. 0.3 W (±10%) / (24 VDC) 24 VAC (±10%) 0.5 VA (24 VAC)

EGT335F103

Overview of types Type

Description

Output signal

Measuring range

EGT330F053

Room temperature sensor

Passive, Ni500

−35…70 °C

−

EGT330F103

Room temperature sensor

Passive, Ni1000

−35…70 °C

−

EGT332F103

Room temperature sensor, setpoint ad- Passive, Ni1000 juster

−35…70 °C

Pot. 2.5 kΩ

1)

2) 3)

Setpoint adjuster

Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be prevented by the customer.

Right of amendment reserved © 2024 Fr. Sauter AG

49


Data capture | Temperature

X

Type

Description

Measuring range

Setpoint adjuster

EGT335F103

Room temperature sensor, setpoint ad- Passive, Ni1000 juster, presence button, status LED (RGB)

Output signal

−35…70 °C

Pot. 2.5 kΩ

EGT430F013

Room temperature sensor

Passive, Pt100

−35…70 °C

−

EGT430F103

Room temperature sensor

Passive, Pt1000

−35…70 °C

−

EGT130F032

Room temperature transducer

Active, 0…10 V

0…50 °C

−

Accessories

50

Type

Description

0300230010

USB Bluetooth® dongle

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Temperature

EGT 386, 388, 486, 686, 688: Room temperature sensor, recessed Features • Passive room temperature measurement • For temperature measurement in dry rooms (e.g. in residential properties, offices and business premises) • Including frame

X

Technical data Parameters

Measuring range Time constant in still air

Time characteristic

-35...70 °C 30 minutes

EGT386F101 EGT486F101

Ambient conditions

Storage and transport temperature Ambient temperature

–35...70 °C -35...70 °C

Housing Housing material Frame design

Pure white Thermoplastic Gira E2

Type of protection RoHS Directive 2011/65/EU

IP20 (EN 60529) EN IEC 63000

EGT686F101

Construction

Standards, directives

CE conformity according to

Resistance values / characteristics

/

The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.

Measuring element Ni1000 Pt1000 NTC 10k

Standard DIN 43760 DIN EN 60751 -

Nominal value at 0 °C 1000 Ω 1000 Ω 10 kΩ at 25 °C

Tolerance at 0 °C ±0.4 K ±0.3 K ±0.3 K

EGT388F101 EGT388F102 EGT688F101

Overview of types Type

Measuring element

Adjuster

Weight

EGT386F101

Ni1000

–

53 g

EGT388F101

Ni1000

10 kΩ

83 g

EGT388F102

Ni1000

100 Ω

83 g

EGT486F101

Pt1000

–

83 g

EGT686F101

NTC 10k

–

53 g

EGT688F101

NTC 10k

10 kΩ

83 g

Right of amendment reserved © 2024 Fr. Sauter AG

51


Data capture | Temperature

EGT 301, 401, 601: Outdoor-temperature sensor Features • Passive or active measuring element • Extra protection against dust and humidity (IP65) • Cable inlet on back or via cable gland

X

EGT*01F102

• For weather-dependent heating and ventilation systems

Technical data Parameters

Time characteristic

Recommended measurement current Time constant in still air

< 1 mA EGT*01F102: 12 minutes EGT301F031: 7 minutes

Ambient temperature

EGT*01F102: −35…90 °C EGT301F031: −35…70 °C −35…70 °C 85% rh

Ambient conditions

Storage and transport

Storage and transport temperature Humidity (non-condensing)

EGT301F031 Construction

Sensor sleeve

EGT301F031: stainless steel 1.4571 Ø 6 × 25 mm White Polyamide Screw terminals 0.35...1.5 mm2, for number of poles, see connection diagram EGT*01F102: M16 for cable min. Ø 5 mm, max. Ø 8 mm EGT301F031: M20 for cable min. Ø 5 mm, max. Ø 8 mm

Housing Housing material Connection terminals

Cable inlet

Standards, directives

Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU

CE conformity according to

IP65 (EN 60529) EN IEC 63000 EGT301F031: EN 60730-1 (mode of operation 1, residential premises)

Resistance values / characteristics

/

The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.

Measuring element Ni1000 Ni1000 TK5000 Pt1000

52

Standards DIN 43760 – DIN EN 60751

Nominal value at 0 °C 1000 Ω 1000 Ω 1000 Ω

Tolerance at 0 °C ±0.4 K ±0.4 K ±0.3 K

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Temperature Active type EGT301F031

Measuring range

Measuring accura- Output signal cy at 21 °C 5 temperature ranges Typically ±1% of 0...10 V, min. (−50...160 °C), adjustable on measuring range1)2) load impedevice (see connection diadance 1 kΩ gram)

Power supply 15…24 VDC (±10%) / 24 VAC (±10%)

Power consumption Max. 0.42 W / 0.84 VA

Overview of types Type

Description

Output signal

Measuring range

Weight

EGT301F102

Outdoor temperature sensor

Passive, Ni1000

−35…90 °C

80 g

EGT401F102

Outdoor temperature sensor

Passive, Pt1000

−35…90 °C

80 g

EGT601F102

Outdoor temperature sensor

Passive, Ni1000 TK5000

−35…90 °C

80 g

EGT301F031

Outdoor temperature transmit- Active, 0…10 V ter

1) 2)

X

−50...160 °C 120 g (5 ranges)

With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be avoided by the customer.

Right of amendment reserved © 2024 Fr. Sauter AG

53


Data capture | Temperature

EGT 353...356, 456, 554, 654: Cable temperature sensor Features • Passive measuring element • Particularly suitable for direct connection in installations with short distances between the controllers and the

sensors • Sensor with a wide range of applications and high type of protection (IP67) and fast time characteristic

X

• Used in air, used in liquid media with thermowells, or as a clamp-on temperature sensor with an accessory • Large temperature measuring range

EGT*5*F***

Technical data Parameters

Recommended measurement current Time constant with thermowell (LW 7) in still water Time constant in still air Time constant in moving air (3 m/s)

Time characteristic in water Time characteristic in air

Typ. < 1 mA 9 seconds (t63) 155 seconds (t63) 35 seconds (t63)

Construction

Sensor sleeve Material

Ø 6 × L (mm) - see table, up to 16 bar Sensor sleeve: Stainless steel 1.4571 Cable: see table Ø 5 mm with wire ferrules

Power cable Cable cross-section Active length

2 x 0.25 mm2 10 mm

Type of protection RoHS Directive 2011/65/EU

IP67 (EN 60529) EN IEC 63000

Standards and directives

CE conformity according to Resistance values / characteristics

/

The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.

Measuring element Ni1000 Ni1000 TK5000 Pt100 Pt1000 NTC 10k NTC 22k

Standards DIN 43760

Nominal value 1000 Ω at 0 °C 1000 Ω at 0 °C 100 Ω at 0 °C 1000 Ω at 0 °C 10 kΩ at 25 °C 22 kΩ at 25 °C

DIN EN 60751 DIN EN 60751 -

Tolerance at 0 °C ±0.4 K ±0.4 K ±0.3 K ±0.3 K ±0.3 K ±0.3 K

Overview of types Type

54

Measuring element

Sleeve length LH

Total length Lg

Material

Measuring range

Weight

EGT353F101

NTC 10k

50 mm

1.5 m

PVC

-35...100 °C

40 g

EGT353F103

NTC 10k

50 mm

3m

PVC

-35...100 °C

85 g

EGT353F110

NTC 10k

50 mm

10 m

PVC

-35...100 °C

280 g

EGT353F120

NTC 10k

50 mm

20 m

PVC

-35...100 °C

550 g

EGT554F103

NTC 22k

50 mm

3m

PVC

-35...100 °C

85 g

EGT354F102

Ni1000

50 mm

1m

PVC

-35...100 °C

30 g

EGT354F104

Ni1000

50 mm

3m

PVC

-35...100 °C

85 g

EGT354F111

Ni1000

50 mm

10 m

PVC

-35...100 °C

280 g

EGT354F121

Ni1000

50 mm

20 m

PVC

-35...100 °C

550 g

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Temperature Type

Measuring element

Sleeve length LH

Total length Lg

Material

Measuring range

Weight

EGT654F102

Ni1000 TK5000

50 mm

1m

PVC

-35…100 °C

30 g

EGT355F902

Ni1000

100 mm

2m

Silicone

-50...180 °C

60 g

EGT355F903

Ni1000

150 mm

2m

Silicone

-50...180 °C

60 g

EGT356F102

Ni1000

50 mm

1m

Silicone

-50...180 °C

30 g

EGT356F104

Ni1000

50 mm

3m

Silicone

-50...180 °C

90 g

EGT356F111

Ni1000

50 mm

10 m

Silicone

-50...180 °C

300 g

EGT356F304

Ni200

50 mm

3m

Silicone

-50...180 °C

90 g

EGT456F012

Pt100

50 mm

1m

Silicone

-50...180 °C

30 g

EGT456F102

Pt1000

50 mm

1m

Silicone

-50...180 °C

30 g

X

Accessories Type

Description

0300360000

Compression fitting G¼"; stainless steel, up to 16 bar

0300360003

Mounting flange; plastic

0300360004

Heat-conducting paste incl. gun with 2 g content

0300360008

Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)

0300360012

Sensor support spiral for fitting in ventilation duct

0313214001

Fixing kit for cable temperature sensor (holder, heat-conducting paste, retaining strap)

A

039*******: Thermowells (LW 7 and LW 15) made of brass or stainless steel (see product data sheet)

Right of amendment reserved © 2024 Fr. Sauter AG

55


Data capture | Temperature

EGT 346...348, 392, 446, 447, 646, 647: Duct temperature sensor Features • Passive or active measuring element • For use in pipes and vessels by means of optional thermowells (LW 7). For use in standard HVAC

applications up to 160 °C and aggressive ambient conditions up to 260 °C (EGT392F102)

X

Technical data Parameters

Time characteristic

EGT*4*

Recommended measurement current Typ. < 1 mA Time constant in moving air (3 m/s) 35 s (t63) Time constant in still air 155 s (t63) Time constant in still water 9 s (t63) Time constant in still water, with thermo- 17 s (t63) well made of brass Time constant in still water, with thermo- 20 s (t63) well made of stainless steel

Ambient conditions

Ambient temperature

Storage and transport

Storage and transport temperature Humidity (non-condensing)

EGT*4* passive: −35...90 °C EGT*4* active: −35...70 °C EGT392F102: −25...90 °C −35...70 °C 85% rh

Construction

Housing Housing material

EGT*4*: Black/yellow EGT*4*: Polyamide EGT392F102: Form J made of die-cast aluminium EGT*4*: 45° screw terminals 0.35...1.5 mm2 For number of poles, see connection diagram M16 for cable min. Ø 5 mm, max. Ø 8 mm Ø 6×L (mm) made of stainless steel 1.4571, up to 16 bar, see table 10 mm

Connection terminals EGT392F102

Cable inlet Immersion stem

Active length Standards, directives

CE conformity according to

Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU

IP65 (EN 60529) EN IEC 63000 EGT34*F031: EN 60730-1 (mode of operation 1, residential premises)

Resistance values / characteristics

/

The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.

Measuring element Ni1000 Ni1000 TK5000 Ni200 Pt1000 Pt100

56

Standard DIN 43760 – DIN 43760 DIN EN 60751 DIN EN 60751

Nominal value at 0 °C 1000 Ω 1000 Ω 200 Ω 1000 Ω 100 Ω

Tolerance at 0 °C ±0.4 K ±0.4 K ±0.4 K ±0.3 K ±0.3 K

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Temperature Measuring accura- Output signal cy at 21 °C1)2)

Active types

Measuring range

EGT346F031 EGT347F031 EGT348F031

5 temperature ranges Typically ±1% of (−50...160 °C), adjustable on measuring range device (see connection diagram)

0...10 V, min. load 5 kΩ

Power supply

Power consumption

15…24 V= Typical (±10%) / 0.35 W / 24 V~ (±10%) 0.82 VA

Overview of types Type

Description

Output signal Measuring range

Immersion length (L)

Weight

EGT346F022

Duct temperature sensor

Passive, Ni200

−50… 160 °C

100 mm

85 g

EGT346F102

Duct temperature sensor

Passive, Ni1000

−50… 160 °C

100 mm

85 g

EGT347F022

Duct temperature sensor

Passive, Ni200

−50… 160 °C

200 mm

95 g

EGT347F102

Duct temperature sensor

Passive, Ni1000

−50… 160 °C

200 mm

95 g

EGT348F102

Duct temperature sensor

Passive, Ni1000

−50… 160 °C

450 mm

120 g

EGT392F102

Duct temperature sensor

Passive, Ni1000

−50… 260 °C

100 mm

105 g

EGT446F012

Duct temperature sensor

Passive, Pt100

−50… 160 °C

100 mm

85 g

EGT446F102

Duct temperature sensor

Passive, Pt1000

−50… 160 °C

100 mm

85 g

EGT447F012

Duct temperature sensor

Passive, Pt100

−50… 160 °C

200 mm

95 g

EGT447F102

Duct temperature sensor

Passive, Pt1000

−50… 160 °C

200 mm

95 g

EGT646F102

Duct temperature sensor

Passive, Ni1000 TK5000

−35… 160 °C

100 mm

85 g

EGT647F102

Duct temperature sensor

Passive, Ni1000 TK5000

−35… 160 °C

200 mm

85 g

EGT346F031

Duct temperature transmit- Active, ter 0…10 V

−50...160 ° 100 mm C (5 ranges)

90 g

EGT347F031

Duct temperature transmit- Active, ter 0…10 V

−50...160 ° 200 mm C (5 ranges)

100 g

EGT348F031

Duct temperature transmit- Active, ter 0…10 V

−50...160 ° 450 mm C (5 ranges)

120 g

X

Accessories Type

Description

0300360000

Compression fitting G¼"; stainless steel, up to 16 bar

0300360003

Mounting flange; plastic

0300360004

Heat-conducting paste incl. gun with 2 g content

A

1) 2)

039*******: Thermowells (LW 7 and LW 15) made of brass or stainless steel (see product data sheet)

With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be avoided by the customer.

Right of amendment reserved © 2024 Fr. Sauter AG

57


Data capture | Temperature

Thermowells Features • Fitted in pipes and containers for holding sensor cartridges, immersion stems, temperature sensors,

temperature controllers or thermostats Made of brass (Ms) or stainless steel (V4A) • • Versions with cylindrical pipe thread (G½" male ISO 228/1, flat-sealing)

X

1)

or cone-shaped

(R½" ISO 7/1 sealing in thread) • With pressure spring (LW 15) • With retaining holder

Overview of types Type

LW

Length

Material

Thread

Nominal pressure

Test pressure Tmax

0391022050

7

50 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022100

7

100 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022200

7

200 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022300

7

300 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022450

7

450 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391022600

7

600 mm

Stainless steel

G½"

40 bar

60 bar

325 °C

0391011050

7

50 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011100

7

100 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011150

7

150 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011200

7

200 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011300

7

300 mm

Brass

R½"

10 bar

16 bar

160 °C

0391011450

7

450 mm

Brass

R½"

10 bar

16 bar

160 °C

0393022100

15

100 mm

Stainless steel

G½"

40 bar

60 bar

450 °C

0393022200

15

200 mm

Stainless steel

G½"

40 bar

60 bar

450 °C

0393022450

15

450 mm

Stainless steel

G½"

40 bar

60 bar

450 °C

0393012100

15

100 mm

Brass

G½"

16 bar

25 bar

160 °C

0393012200

15

200 mm

Brass

G½"

16 bar

25 bar

160 °C

0392022100

7

100 mm

Stainless steel

G½"

25 bar

40 bar

450 °C

0392022200

7

100 mm

Stainless steel

G½"

25 bar

40 bar

450 °C

0392022300

7

300 mm

Stainless steel

G½"

25 bar

40 bar

450 °C

1)

58

G½" male ISO 228/1, flat-sealing: for welding bushings with flat seal (accessories)

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Temperature

A A A

0392022100 and 0392022300 for TUC thermostats only With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). 0391... with pressure screw (retaining holder) up to max. 200 °C

Accessories Type

Description

0300360008

Retaining holder for cable temperature sensor or capillary tube with 0392022*** (LW 7) or LW 15 (10 pcs)

0364263000

Welding sleeve of steel, with female thread G½", flat seal of copper

0300360017

Pressure spring for LW 15 (10 pieces)

•

LW 7, 50 mm LW 7, 100 mm LW 7, 150 mm LW 7, 200 mm

• • • •

LW 7, 300 mm LW 7, 450 mm LW 7, 600 mm LW 15, 100 mm LW 15, 200 mm LW 15, 450 mm 0392022100 0392022200 0392022300

A A A A

• • • • • − − −

• L > 50 mm • • • • L > 300 mm • − − − − − − −

X

− − − − − − − • • • • • •

0392022100 and 0392022300 for TUC thermostats only. With the TUC407F001 and TUC207F003, only use the supplied thermowells or stainless-steel thermowells (part nos.: 0393022*** or 0392022***). Only use the thermowells (LW 15) with at least 2 sensors or thermostats with a diameter of at least 6 mm 0391... with pressure screw (retaining holder) up to max. 200 °C.

Right of amendment reserved © 2024 Fr. Sauter AG

59


Data capture | Temperature

EGT 311, 411, 611: Clamp-on temperature sensor Features • Passive or active measuring element • Extra protection against dust and humidity (IP65) • Temperature measurement on pipes • Including retaining strap for pipes of Ø 10...50 mm

X

• Heat-conducting paste (silicone-free) is included in the scope of delivery

EGT*11F***

Technical data Parameters

Time characteristic with heatconducting paste

Recommended measurement current Time constant

Typ. < 1 mA 16 s

Storage and transport temperature Humidity (non-condensing)

−35…70 °C 85% rh

Housing Housing material Connection terminals

Yellow/black Polyamide

Ambient conditions

Construction

Screw terminals 0.35...1.5 mm2, for number of poles, see connection diagram M16 for cable min. Ø 5 mm, max. Ø 8 mm

Cable inlet

Standards, directives

Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU

CE conformity according to

IP65 (EN 60529) EN IEC 63000 EGT311F031: EN 60730-1 (mode of operation 1, residential premises)

Resistance values / characteristics

/

The tolerance listed below applies only to the corresponding measuring element. The accuracy of the sensor depends on the cable length and the measuring element used.

Measuring element Ni1000 Ni1000 TK5000 Ni200 Pt1000 Active type EGT311F031

1) 2)

60

Standards DIN 43760 – DIN 43760 DIN EN 60751 Measuring range

Nominal value at 0 °C 1000 Ω 1000 Ω 200 Ω 1000 Ω

Measuring accura- Output signal cy at 21 °C 5 temperature ranges Typically ±1% of 0...10 V, min. (−50...160 °C), adjustable on measuring range1)2) load impedevice (see connection diadance 5 kΩ gram)

Tolerance at 0 °C ±0.4 K ±0.4 K ±0.4 K ±0.3 K Power supply

Power consumption 15…24 V= Max. (±10%) / 0.42 W / 24 V~ (±10%) 0.84 VA

With offset adjustment ±3 K The transducers must be operated at a constant operating voltage (±0.2 V). Current/voltage peaks when switching the supply voltage on/off must be avoided by the customer.

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Temperature Overview of types Type

Description

Output signal

Measuring range

Weight

EGT311F022

Clamp-on temperature sensor

Passive, Ni200

−35…90 °C

80 g

EGT311F102

Clamp-on temperature sensor

Passive, Ni1000 −35…90 °C

80 g

EGT411F102

Clamp-on temperature sensor

Passive, Pt1000

−35…90 °C

80 g

EGT611F102

Clamp-on temperature sensor

Passive, Ni1000 −35…90 °C TK5000

80 g

EGT311F031

Clamp-on temperature trans- Active, 0…10 V mitter

−50...160 °C (5 ranges)

X

120 g

Accessories Type

Description

0300360002

Retaining strap 900 mm and heat-conducting paste

0300360004

Heat-conducting paste incl. gun with 2 g content

Right of amendment reserved © 2024 Fr. Sauter AG

61


Data capture | Temperature

EGS 100: Radiation temperature sensor Features • Mean value measuring of radiation temperature and room temperature • Ni or NTC characteristic • Passive measuring element • Measuring range: -35…70 °C

X

• Measuring element: Thin-film sensor

EGS100F70*

Technical data Parameters

Time characteristic

Measuring range Time constant in still air

-35...70 °C 15 min

Weight Dimensions Housing Housing material Connection terminals

0.1 kg 84.5 × 84.5 mm Pure white, similar to RAL 9010 Thermoplastic with black hemisphere 2 × 1.5 mm²

Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU

IP30 (EN 60529) EN IEC 63000 EN 60730-1 (mode of operation 1, residential premises)

Construction

Standards and directives

CE conformity

Overview of types

62

Type

Resistance values

Tolerance

Measuring elements

EGS100F705

1 kΩ (at 0 °C)

±0.4 K (at 0 °C)

2 × Ni500 as per DIN 43760 in series

EGS100F706

10 kΩ (at 25 °C)

±1% (at 25 °C)

2 × NTC 5 kΩ in series

EGS100F707

22 kΩ (at 25 °C)

±1% (at 25 °C)

2 × NTC 11 kΩ in series

Right of amendment reserved © 2024 Fr. Sauter AG


Air quality sensors Air quality is of the utmost importance for the performance and well-being of people in closed rooms. With CO2 and VOC sensors from SAUTER, it is possible to measure air quality exactly, so that ventilation systems can be controlled in accordance with demand. As a result, not only is the indoor air quality improved, but energy consumption is also reduced by improving the operational efficiency of ventilation systems.

Overview of air quality sensors

EGQ 220, 222

EGQ 120

EGQ 281

Application Room, surface-mounted Room, recessed Duct

Type designation

• − −

• − −

− • −

Variables CO2

•

−

•

− • − − Page 64

• − − − Page 66

− − − − Page 67

VOC Temperature Humidity Pressure Further information

EGQ 212

EGQ 110

Application Room, surface-mounted Room, recessed Duct

Type designation

− − •

− − •

Variables CO2

•

−

− • − − − Page 68

• − − − − Page 70

VOC Temperature Humidity Pressure Volume flow Further information

Right of amendment reserved © 2024 Fr. Sauter AG

63


Data capture | Air quality

EGQ 220, 222: Room transducer, CO2, surface-mounted Features • Measurement of CO2 concentration for demand-controlled ventilation of rooms such as meeting and

conference rooms, offices and classrooms • Available with and without temperature sensor • CO2 measurement with NDIR

Dual-beam technology, therefore stable in the long term and largely resistant to external influences • Very fast response to changes in the CO2 concentration in rooms

X EGQ220F032

1)

• Developed according to EN 13779, EN 15251, VDI 6038 and VDI 6040 directives

Technical data Power supply

Power supply Power consumption EGQ222F032

Start-up current

15…35 VDC / 19…29 VAC SELV Typ. 0.4 W at 24 VDC Typ. 0.8 VA at 24 VAC Max. 1.6 A

Parameters

Time characteristic

Readiness for operation

Temperature dependence Gradual drift2) Measuring range Average measuring accuracy

< 2 minutes operational, < 15 minutes response time 2 minutes 0…2000 ppm (ex works) ±75 ppm >750 ppm: ±10% (typ. at 21 °C) Typ. 0.135% of the measured value per mm Hg Typ. 2 ppm per °C (0…50 °C) < 5% FS or < 10% per year −35…70 °C ±0.5 K (typ. at 21 °C)

CO2

In room (0.1 m/s) Measuring range Average measuring accuracy

Ambient temperature Ambient humidity

−35…70 °C Max. 85% rh, non-condensing

Output signal

0…10 V CO2/temperature

Colour Housing material Cable inlet Connection terminals

Traffic white (RAL9016) Polycarbonate (PC) UL94-V0 Through the rear wall

Pressure dependence

Temperature (EGQ 222)

Ambient conditions

Inputs/outputs

Construction

Weight

Spring-type terminal, max. 1.5 mm2 90 g

Standards, directives

CE/UKCA conformity3)

Type of protection EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

1) 2) 3)

64

IP20 (EN 60529) after fitting EN 60730-1 (mode of operation 1, residential premises) See EMC-D EN IEC 63000 EN IEC 63000

NDIR: Non-dispersive infrared sensor Air flow velocity: 0.15 m/s. Air flow direction: Laminar upwards Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Air quality Overview of types Type

Description

EGQ220F032

Room transducer, CO2

Output signal

Active, 1 × 0…10 V, load ≥ 10 kΩ

EGQ222F032

Room transducer, CO2, temp.

Active, 2 × 0…10 V, load ≥ 10 kΩ

Accessories Type

Description

0300230010

USB Bluetooth® dongle

Right of amendment reserved © 2024 Fr. Sauter AG

X

65


Data capture | Air quality

EGQ 120: Room transducer, air quality, surface-mounted Features • Measures the relative VOC mixed gas concentration (organic components in the room air), such as

tobacco smoke, kitchen vapours • Demand-based ventilation control in buildings such as restaurants and offices • Active VOC semi-conductor sensor for measuring mixed gas concentration

X

• Suitable for direct wall mounting and recessed junction boxes

EGQ120F032

Technical data Power supply

Power supply Power consumption Start-up current

15…35 VDC / 19…29 VAC SELV Typ. 0.4 W at 24 VDC Typ. 0.8 VA at 24 VAC Max. 1.6 A

Parameters

Type of sensor

VOC (heated metal oxide semiconductor)

Ambient temperature Ambient humidity

−35…70 °C Max. 85% rh, no condensation

Output signal

Active, 0…10 V, min. load 10 kΩ

Colour Housing material Cable inlet Connection terminals

Traffic white (RAL9016) Polycarbonate (PC UL94-V0) Through the rear wall

Ambient conditions

Inputs/outputs

Construction

Weight

Spring-type terminal, max. 1.5 mm2 65 g

Standards, directives

CE/UKCA conformity1)

Type of protection EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

IP20 (EN 60529) after fitting EN 60730-1 (mode of operation 1, residential premises) See EMC-D EN IEC 63000 EN IEC 63000

Overview of types Type

Description

EGQ120F032

Room transducer, active, air quality

Accessories Type

Description

0300230010

USB Bluetooth® dongle

1)

66

Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Air quality

EGQ 281: Room transducer, CO2, recessed Features • CO2 sensor for continuous measurement of the CO2 concentration for the demand-controlled ventilation of

rooms (e.g. meeting rooms, conference rooms, offices, classrooms, etc.) • CO2 measurement with NDIR dual-beam technology , therefore stable in the long term and resistant to 1)

external influences

X

• Any ageing or contaminating effects are continuously compensated in real time • Very fast response to changes in the CO2 concentration in rooms • Temperature-compensated calibration for the standard air pressure of 1013 mbar

EGQ281F031

• Calibrated ex works and ready to use immediately • Low energy requirement of the ventilation system during the warming up time of the sensor • Including frame

Technical data Power supply

Power supply (SELV) Power consumption

15...24 V= (±10%) / 24 V~ (±10%) < 1.6 W (typ. 0.3 W) < 3.9 VA (typ. 0.7 VA)

Analogue output Load current

0...10 V Max. 10 mA

Measuring range Measuring accuracy Time constant Measuring cycle Long-term stability

0...2000 ppm < ±50 ppm 2% of the measured value (25 °C and 1013 mbar) < 195 s (t90) 15 s Typ. 20 ppm/year

Ambient temperature

−20...70 °C

Housing Housing material

Pure white Lower section: PA6 Front plate: PC Gira E2 90 g

Output signal

Parameters

Ambient conditions

Construction

Frame design Weight Standards, directives

CE conformity according to

Type of protection EMC Directive 2014/30/EU RoHS Directive 2011/65/EU

IP30 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000

Overview of types Type

Description

EGQ281F031

Room transducer, CO2; 0...10 V, recessed

1)

NDIR: Non-dispersive infrared sensor

Right of amendment reserved © 2024 Fr. Sauter AG

67


Data capture | Air quality

EGQ 212: Duct transducer, CO2 and temperature Features • Duct sensor for measuring carbon dioxide (CO2) content for demand-based ventilation of indoor spaces • CO2 measurement with NDIR

1)

Dual-beam technology, therefore stable in the long term and largely

resistant to external influences • Measurement of temperature in ventilation ducts

X

• Two analogue 0...10 V outputs are available: one for CO2 measurement and one for temperature

measurement. This allows direct connection to an automation station • Automatic drift compensation • Mounting accessories and flange included

Technical data EGQ212F032

Power supply

Power supply (SELV) Power consumption Peak inrush current

15…35 V= / 19…29 V~ Max. 2.3 W (24 V=) / 4.3 VA (24 V~) 1.2 A < 3 ms

Output signal

2 × 0…10 V, load min.: 10 kΩ

Flow speed In moving air (3 m/s) Measuring range Measuring accuracy

Measuring range Measuring accuracy

Min. 0.3 m/s, max. 12 m/s 5 minutes 0…2000 ppm ±50 ppm drift over the serviceable life +3% of the measured value (typical at 21 C, 50% rh) 0…50 °C ±0.5 K (typical at 21 °C)

Ambient temperature Ambient humidity

0...50 °C Max. 85% rh non-condensing

Connection terminals Cable cross-section Cable inlet

Plug-in female connectors, removable Max. 2.5 mm² Removable insert, M20 for cable, min. Ø 4.5 mm, max. Ø 9 mm Yellow/black Housing: PC, sensor tube: PA6 Stainless steel, wire mesh 19.5 mm 180 mm 150 g

Outputs

Parameters

Time characteristic CO2

Temperature

Ambient conditions

Construction

Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards, directives

CE conformity according to

Type of protection EMC Directive 2014/30/EU RoHS Directive 2011/65/EU

1)

68

Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000

NDIR: Non-dispersive infrared sensor

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Air quality Overview of types Type

Features

EGQ212F032

Duct transducer, CO2 and temperature; 2 × 0...10 V

Accessories Type

Description

0300360003

Mounting flange; plastic

X

Right of amendment reserved © 2024 Fr. Sauter AG

69


Data capture | Air quality

EGQ 110: Duct transducer, air quality (VOC), temperature Features • Duct air quality sensor for detection of volatile organic compounds (VOC) for demand-controlled ventilation

of indoor spaces. VOC sources include flue gases, solvents as well as various cleaning agents and building materials • Measurement of temperature in ventilation ducts

X

• Two analogue 0...10 V outputs are available: one for VOC measurement and one for temperature

measurement. This allows direct connection to an automation station • Automatic calibration via an integrated algorithm • Mounting accessories and flange included

Technical data EGQ110F032

Power supply

Power supply (SELV) Power consumption Peak inrush current

15…35 V= / 19…29 V~ Max. 2.3 W (24 V=) / 4.3 VA (24 V~) 1.2 A < 3 ms

Output signal

2 × 0…10 V, load min.: 10 kΩ

Flow speed In moving air (3 m/s) Measuring range Serviceable life Sensor Measuring range Measuring accuracy

Min. 0.3 m/s, max. 12 m/s 5 minutes 0...100% Typically 10 years Heated tin dioxide semiconductor 0…50 °C ±0.5 K (typical at 21 °C)

Ambient temperature Ambient humidity

0...50 °C Max. 85% rh non-condensing

Connection terminals Cable cross-section Cable inlet

Plug-in female connectors, removable Max. 2.5 mm² Removable insert, M20 for cable, min. Ø 4.5 mm, max. Ø 9 mm Yellow/black Housing: PC, sensor tube: PA6 Stainless steel, wire mesh 19.5 mm 180 mm 150 g

Outputs

Parameters

Time characteristic VOC

Temperature

Ambient conditions

Construction

Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards, directives

CE conformity according to

Type of protection EMC Directive 2014/30/EU

Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000

RoHS Directive 2011/65/EU

Overview of types

70

Type

Features

EGQ110F032

Duct transducer; VOC and temperature; 2 × 0...10 V

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Air quality Accessories Type

Description

0300360003

Mounting flange; plastic

X

Right of amendment reserved © 2024 Fr. Sauter AG

71


Humidity sensors SAUTER humidity sensors are used for the energy-efficient control and monitoring of ventilation systems. Sensors are available for measuring the relative humidity and enthalpy of the air. They can be used in residential or business premises and can also be fitted in air ducts.

Overview of humidity sensors

Type designation Application Room, surface-mounted Room, recessed Duct Clamp-on sensor Measurement Temperature Relative humidity Enthalpy Dew point Further information

72

EGH 120, 130

EGH 681

EGH 110…112

EGE 112

EGH 102

• − − −

− • − −

− − • −

− − • −

− − − •

• • − − Page 73

• • − − Page 74

• • − − Page 75

• − • − Page 76

− − − • Page 77

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Humidity

EGH 120, 130: Room transducer, relative humidity and temperature, surface-mounted Features • Measurement of humidity via a fast, capacitive sensor • Active measuring element • Suitable for direct wall mounting and recessed junction boxes

X

• Converts the measured values into a continuous analogue signal (0...10 V / 4...20 mA)

Technical data EGH120F042

Parameters

Relative humidity

Measuring range Measuring accuracy

Temperature

Measuring range Measuring accuracy

0...100% rh, no condensation ±2 % between 10…90 % rh (typ. at 21 °C) 0…50 °C ±0.5 °C (typ. at 25 °C)

Ambient temperature Ambient humidity

−35…70 °C Max. 85% rh, non-condensing

Colour Housing material Cable inlet Connection terminals

Traffic white (RAL9016) Polycarbonate (PC) UL94-V0 Through the rear wall

EGH130F032

Ambient conditions

Construction

Weight

Spring-type terminals, max. 1.5 mm2 80 g

Standards, directives

CE/UKCA conformity1)

Type of protection EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

IP20 (EN 60529) after fitting EN 60730-1 (mode of operation 1, residential premises) See EMC Directive EN IEC 63000 EN IEC 63000

Overview of types Type

Description

Output signal

Power supply

Power consumption

EGH120F042

Room transducer, rh, temp.

Active, 2 × 4…20 mA Max. load 500 Ω

15…24 VDC, ±10%

Max. 1 W

EGH130F032

Room transducer, rh, temp.

Active, 2 × 0…10 V Min. load 20 kΩ

15…24 VDC, ±10% 24 VAC, ±10%

Max. 0.3 W (24 VDC) 0.5 VA (24 VAC)

Accessories Type

Description

0300230010

USB Bluetooth® dongle

1)

Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

73


Data capture | Humidity

EGH 681: Room transducer, relative humidity and temperature, recessed Features • Measures the relative humidity and temperature in rooms • Regulation of the room climate in combination with room automation systems • Fast response time and high precision

X

• Including frame

EGH681F031

Technical data Power supply

Power supply Power consumption

15...24 V= (±10%) or 24 V~ (±10%) Typ. 0.3 W / 0.5 VA

Output signal

0...10 V, load resistance at least 10 kΩ

Measuring range, temperature Measuring range, humidity

0...50 °C 0...100% rh

Ambient temperature

−20...70 °C

Housing Housing material

Pure white Lower section: ABS Front plate: PC Gira E2 80 g

Output signal

Parameters

Ambient conditions

Construction

Frame design Weight Standards, directives

CE conformity according to

Type of protection RoHS Directive 2011/65/EU EMC Directive 2014/30/EU

IP30 (EN 60529) EN IEC 63000 EN 60730-1 (mode of operation 1, residential premises)

Overview of types

74

Type

Description

EGH681F031

Room transducer, relative humidity and temperature, recessed

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Humidity

EGH 110...112: Duct transducer, relative humidity and temperature Features • Measures the relative humidity and temperature in air ducts • Measurement by means of fast capacitive measuring element • Active and passive measuring element

X

• Immersion depth 140 mm • Mounting flange supplied

Technical data Power supply

EGH11*F0*1

Power supply Peak inrush current

15...24 V= (±10%) or 24 V~ (±10%) 1.5 A, 4 ms

Measuring range, humidity Measuring accuracy, humidity Repeat accuracy Gradual drift Measuring range, temperature Measuring accuracy, temperature Repeat accuracy Gradual drift In moving air (3 m/s) Readiness for operation

Hysteresis

0...100% rh, no condensation Typ. ±2% (10...90% rh) Typ. ±0.1% rh Typ. < 0.5% rh/year -20...80 °C ±0.5 °C (typ. at 25 °C) Typ. ±0.1 °C Typ. < 0.04 °C/year 2 minutes (t63) 10 seconds (operational), 5 minutes (max. precision) Min: 0 m/s Max: 10 m/s ±1%

Ambient temperature

-20...70 C

Connection terminals

Screw terminals, max. 1.5 mm2 M20 for cable with min. Ø 5 mm, max. Ø 10 mm Yellow/black PA6 Stainless steel, wire mesh 19.5 mm 140 mm 120 g

Parameters

Humidity

Temperature

Time characteristic

Flow speed

Ambient conditions

Construction

Cable inlet Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards and directives

CE conformity according to

Type of protection EMC Directive 2014/30/EU RoHS Directive 2011/65/EU

Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000

Overview of types Type

Power consumption

Output signal

EGH110F041

Max. 1 W (24 V=)

2 × 4...20 mA (max. load 500 Ω)

EGH111F031

Max. 0.4 W (24 V=) | 0.8 VA (24 V~)

2 × 0...10 V (min. load 10 kΩ) + Ni1000

EGH112F031

Max. 0.4 W (24 V=) | 0.8 VA (24 V~)

2 × 0...10 V (min. load 10 kΩ)

Right of amendment reserved © 2024 Fr. Sauter AG

75


Data capture | Humidity

EGE 112: Duct transducer, enthalpy Features • Measures the enthalpy and temperature in air ducts • Measurement by means of fast capacitive measuring element • Active measuring element • Unaffected by flow speeds and normal contamination

X

• Mounting flange supplied

Technical data Power supply

EGE112F031

Power supply Power consumption

15...24 V= (±10%) or 24 V~ (±10%) Max. 0.4 W (24 V=) | 0.8 VA (24 V~)

Output signal

2 x 0...10 V (min. load 10 kΩ)

Flow speed Time constant in moving air (3 m/s) Measuring range Measuring accuracy Measuring range Measuring accuracy

Min. 3 m/s Max. 10 m/s 3 minutes 0...100 kJ/kg 3.5 kJ/kg (typ. at 21 °C) −20...80 °C ±0.5 °C (typ. at 25 °C)

Ambient temperature

−20...70 °C

Connection terminals

Screw terminal, max. 1.5 mm2 M20 for cable Ø min. 5.8 mm, max. 10 mm Yellow/black PA6 Stainless steel, wire mesh 19.5 mm 140 mm 120 g

h

Outputs

Parameters

Time characteristic Enthalpy Temperature

Ambient conditions

Construction

Cable inlet Housing Housing material Filter unit material Sensor tube diameter Sensor tube length Weight Standards, directives

CE conformity according to

Type of protection EMC Directive 2014/30/EU

Instrument head: IP65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN IEC 63000

RoHS Directive 2011/65/EU

Overview of types

76

Type

Description

EGE112F031

Duct transducer, enthalpy and temperature, 2 x 0...10 V

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Humidity

EGH 102: Dew point monitor and transducer Features • Protects against dew formation on chilled ceilings • Controls a regulating unit via a holding relay that interrupts the cooling water flow or increases the cooling

water temperature • Best solution for monitoring chilled-ceiling systems

X

• Measurement taken by a spring-mounted dew point sensor • Active measuring element • Variant with external sensor (EGH102F101)

EGH102F*01

• Holding relay with changeover contacts • Includes retaining strap for pipes of Ø 10...100 mm and heat-conducting paste

Technical data

24 V~/=, ±20% Max. 1 VA

Measuring range Changeover contact1) Response time in still air Exposure to dew Switching difference Switching point

70...85% rh 1 A, 24 V~/= 80 to 99% rh, 99 to 80% rh, max. 3 minutes Max. 30 min Fixed, approx. 5% rh 95 ±4% rh

Ambient temperature

5...60 °C

Output signal

Approx. 70...85% rh, 0...10 V, load > 10 kΩ

Screw terminals Housing Housing material Weight Cable inlet

For electrical cables of up to 1.5 mm² Pure white (RAL 9010) Fire-retardant thermoplastic 0.1 kg For Pg 11

Type of protection Mode of operation

IP40 (EN 60529) Type 1 C (EN 60730)

XSd

Power supply Power consumption

95 %rh

Power supply

Parameters

6

5

4

Ambient conditions

Inputs/outputs

Construction

Standards and directives

Overview of types Type

Clamp-on sensor

EGH102F001

Integrated in housing

EGH102F101

Cable 1 m long, sensor integrated in the cable end

1)

When activating relays, gates etc. with cos φ < 0.3, it is recommended to use RC circuitry in parallel to the coil. This reduces contact pitting and prevents high-frequency interference

Right of amendment reserved © 2024 Fr. Sauter AG

77


Data capture | Humidity

EGH 103: Dew point monitor Features • Protects against dew formation on chilled ceilings, etc. • Controls a regulating unit via a holding relay that interrupts the cooling water flow or increases the cooling

water temperature. • Measurement is performed by a dew point sensor

X

• Potential-free output contact for 24 V and 230 V • Holding relay with changeover contacts • LED indicator for power supply and dew formation

EGH103F001

• Plug-in connectors for electrical cables up to 1.5 mm2 • Cable inlet M20 • Fitted onto pipes using the provided cable tie for pipes Ø 10...40 mm

Technical data Power supply

Power supply Power consumption

230 V~ ±10% Max. 3.5 VA

Changeover contact1) Switching point Switching difference

5 A, 230 V~ 95 ±4% rh Fixed, approx. 5% rh

Ambient temperature

−20…60 °C (non-condensing)

Housing Weight

Pure white, PA6 0.19 kg

Type of protection EMC Directive 2014/30/EU

IP 65 (EN 60529) EN 60730-1 (mode of operation 1, residential premises) EN 61000-6-1, EN 61000-6-3

Parameters

Ambient conditions

Construction

Standards and directives

CE conformity according to

Low-Voltage Directive 2014/35/EU

Overview of types Type

Description

EGH103F001

Dew point monitor 230 V~

Accessories Type

Description

0300360004

Heat-conducting paste incl. gun with 2 g content

1)

78

When activating relays, gates, etc. with cos φ < 0.3, it is recommended to use RC circuitry in parallel to the coil. This reduces contact pitting and prevents high-frequency interference

Right of amendment reserved © 2024 Fr. Sauter AG


Flow and pressure sensors SAUTER flow and pressure sensors enable the accurate measurement of air pressures and flow speeds in rooms and ventilation ducts. This includes the measurement of duct pressures for precise control and monitoring of ventilation systems. Additionally, SAUTER flow and pressure sensors can also be used to measure room pressures in laboratories and clean rooms and for flow monitoring in fume cupboards.

Overview of flow and pressure sensors

Type designation Variable Application Duct Laboratories & clean rooms Fume cupboards Pressure monitoring in liquids, gases and vapours Travel measurement Further information

EGP 100 ∆p

XAFP 100 ∆p

SVU 100 m/s

DSU, DSI ∆p

DSDU, DSDI ∆p

SGU 100 mm

• • • −

• • • −

− − • −

− − − •

− − − •

− − • −

− Page 80

− Page 82

− Page 83

− Page 84

− Page 86

• Page 88

Right of amendment reserved © 2024 Fr. Sauter AG

79


Data capture | Flow and pressure

EGP 100: Differential pressure transducer Features • Exact measurement of positive, negative and differential pressures in gases • Optimised for applications such as filter monitoring, room or duct pressure monitoring, level monitoring in

fluids, actuating frequency converters for fan control and recording volume flow, especially for room air balancing in laboratories • Can be ideally combined with XAFP 100 flow probe for precise measurement of volume flow

X

• Static pressure sensor • Can be fitted in any position • Can be used for dusty air or air polluted with chemicals (not ATEX approved)

EGP100F*12

• Manufacturer’s test certificate ex works • The measuring range can be adapted optimally to the needs of the application • Variable zero point and filter time constant to suppress pressure surges in the system • Display shows the actual value and the signal progression (depending on type) • Status LED for immediate indication of operating status (depending on type) • Measuring range can be reduced to one third (depending on type) • Fitted to either wall or DIN rail (EN 60715) • Cover that does not require special tools to open

Technical data Power supply

Power consumption F**2 Power consumption F**1

Power supply 24 V~ 24 V= 24 V~ 24 V=

24 V~/=, ±20% 3.0 VA 1.3 W 1.4 VA 0.4 W

Admissible positive pressure Influence of position1) Non-linearity Zero point stability Reproducibility Pneumatic connection2) Parts in contact with media

±20 kPa < 0.1% FS (full span) 1% FS pressure-linear < 0.3% FS 0.2% FS 6.2 mm PC/ABS blend

Media temperature Admissible operating pressure pstat3) Ambient temperature Ambient humidity

0…70 °C ±7 kPa

Output signal4)

F*01: 0...10 V, load > 10 kΩ F*02/F*12: 0(2)...10 V, load < 500 Ω F*01: 0.05...2 s F*02, F*12: 0.15...5.2 s

Parameters

Output signal (sqr) 10 V-

Ambient conditions

0(2) 0

Differential pressure Dp Measuring range

Gain Dp = 1

Inputs/outputs

Gain Dp = 3

Filter time constant

1)

2)

3) 4)

80

0…60 °C 5...95% rh, no condensation

The sensor is calibrated at the factory for vertical fitting. The influence of position must be taken into account if the unit is not fitted in the vertical position Max. length of measuring wire (di = 6.2 mm): Lmax = 15 m for time constant < 0.5 s, Lmax = 60 m for time constant > 0.5 s The zero point should be recalibrated if the admissible operating pressure is exceeded With a load of < 500 Ω, a change-over to 0...20 mA or 4...20 mA occurs automatically. Output protected against short circuits and excess voltage up to 24 V~

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Flow and pressure

Construction

Pressure connection Housing Cable gland Screw terminals

Internal Ø 6 mm PC/ABS M16 For electrical cables of up to 1.5 mm²

Type of protection Protection class EMC Directive 2014/30/EU

IP65 (EN 60529) III (EN 60730-1) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4

Standards, directives

X

Overview of types

/

Output signal: Analogue output limited to 10.6 V. Measured values with an overrun of 6% of the measuring range can therefore be transferred

/

Variable characteristic/LED: Manual adjustment of measuring range with gain potentiometer. Signal curve: linear/rootextracted. Output signal: 0...10 V / 2...10 V via DIP switches or with CASE Sensors software

Type

Measuring range

Display

Variable characteristic/LED

Weight (kg)

EGP100F101

±75 Pa, ±0.75 mbar

−

−

0.17

EGP100F102

±75 Pa, ±0.75 mbar

−

•

0.18

EGP100F112

±75 Pa, ±0.75 mbar

•

•

0.19

EGP100F201

±150, 1.5 mbar

−

−

0.17 0.18

EGP100F202

±150, 1.5 mbar

−

•

EGP100F212

±150, 1.5 mbar

•

•

0.19

EGP100F301

0...150 Pa, 0...1.5 mbar

−

−

0.17

EGP100F302

0...150 Pa, 0...1.5 mbar

−

•

0.18

EGP100F312

0...150 Pa, 0...1.5 mbar

•

•

0.19

EGP100F401

0...300 Pa, 0...3.0 mbar

−

−

0.17

EGP100F402

0...300 Pa, 0...3.0 mbar

−

•

0.18

EGP100F412

0...300 Pa, 0...3.0 mbar

•

•

0.19

EGP100F601

0...1000 Pa, 0...10.0 mbar

−

−

0.17

EGP100F602

0...1000 Pa, 0...10.0 mbar

−

•

0.18

EGP100F612

0...1000 Pa, 0...10.0 mbar

•

•

0.19

Accessories Type

Description

0010240300

Connection set, 6 mm, complete

XAFP100F001

Flow probe to measure the air volume in ventilation ducts

CERTIFICAT001

Manufacturer’s test certificate type M

CERTIFICAT999

Test for further device (from 2 pcs.)

0300360001

USB-RS-485 converter

Right of amendment reserved © 2024 Fr. Sauter AG

81


Data capture | Flow and pressure

XAFP 100: Flow probe for ventilation ducts Features • Flow probe for precise and inexpensive recording of differential pressure signals in ventilation and air

X XAFP100F001

conditioning systems • Efficient regulation of applications for demand-controlled ventilation in offices, laboratories, fume cupboards and clean rooms, by combining an air damper and an electronic/pneumatic volume flow controller In combination with a square root differential pressure sensor, air volume flows can be reliably recorded • and monitored • Optimised flow profile for accurate measurement of differential pressure signals • Can be used in atmospheres containing aggressive substances • Length (396 mm) can be shortened on site if necessary

Technical data Parameters

Measurement tolerance Range (mm)

< 3% DN 80…400

Operating temperature Ambient humidity

0...50 °C < 85% rh, no condensation

Function

Flow probe

Dimensions Bore Flow probe Seal Connecting tube

65 × 40 × 396 mm (W × H × L) Ø 30...32 mm PA 6 PE, physiologically safe PU

Electrical Flammability

UL 7468 UL 94, IEC 60695-2-12, IEC 60695-2-13

Admissible ambient conditions

Function

Construction

Material

Standards and directives

Flow probe

Overview of types

82

Type

Features

XAFP100F001

Flow probe for ventilation ducts

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Flow and pressure

SVU 100: Air-flow transducer Features • Precise and long-term stable recording of air inflow speeds in fume cupboards with a time constant of <100

ms Particularly suitable for fume cupboards with horizontal and vertical front sashes • • Air volume control according to needs for fume cupboards with horizontal and vertical front sashes

X

• Precise and long-term stable recording of air inflow speeds in fume cupboards • Reliable detection of reversal of flow direction • Integrated filter unit that protects against contamination of the sensor

SVU100F005

• Dynamic pressure sensor based on thin-film technology • Fitted to the fume cupboard simply and quickly

Technical data Power supply

Power supply Power consumption

24 V~, -15%/+20%, 50...60 Hz 1 VA

Measuring range Measuring span1) Differential pressure Time constant Air throughput rate

0...1 Pa 0...1.3 m/s Approx. 0...1 Pa < 0.1 s

Ambient temperature Ambient humidity

5...55 °C < 90% rh

Output signal2) Linearity

0...10 V 2% (based on the output signal)

Type of protection EMC Directive 2014/30/EU

IP40 (EN 60529) with terminal cover EN 61000-6-1, EN 61000-6-3

Parameters

3 cm3/min (at 1 m/s)

Ambient conditions

Inputs/outputs

Standards and directives

CE conformity according to

Overview of types Type

Feature

SVU100F005

Linear to v [m/s]

A

1) 2)

Specified flow speed is based on ρ = 1.2 kg/m3

Recommended measuring span 0.2...1.3 m/s (output 2...10 V) Output signal: Output protected against short circuits and excess voltage up to 24 V~

Right of amendment reserved © 2024 Fr. Sauter AG

83


Data capture | Flow and pressure

DSU, DSI: Pressure transmitter Features • For measuring pressure in liquids, gases and vapours • Sturdy device with ceramic diaphragm • High precision • High positive pressure protection

X

• High vibration resistance • Low hysteresis • Standard signal 2...10 V or 4...20 mA

DS*2**F002

• Pressure sensor made of stainless steel for aggressive media • With standard plug as per DIN EN 175301-803-A

Technical data Power supply

Power supply Electrical connection

See type list DSI: Two-wire DSU: Three-wire

Temperature dependence

Zero point 0.07% FS/K Measuring range 0.05% FS/K DSU: Ub ≥ 15 V ≥ 5 kΩ Ub ≥ 20 V ≥ 2 kΩ DSI: (Ub-6 V)/0.02 A

Parameters

Admissible load

Ambient conditions

Ambient temperature Media temperature

0...60 °C 0...85 °C

Hysteresis Linearity

< 0.5% FS < 1% FS

Housing material Device plug

Chromium-nickel steel 1.4305 Plug connection 4-pin, standard plug DIN EN 175 01-803-A, cable gland M16

Cable cross-section

Max. 1.5 mm2 G ½" 0.2 kg

Inputs/outputs

Construction

Pressure connection Weight Standards and directives

CE conformity according to

Type of protection Protection class EMC Directive 2014/30/EU

PED 2014/68/EU

84

IP65 (EN 60529) III (EN 61140) EN 61000-6-1 / EN 61000-6-2 EN 61000-6-3 / EN 61000-6-4 EN 60730 Subject to Art. 3.3 of PED without safety function

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Flow and pressure Overview of types Type

Measuring range (bar)

Output signal

Power supply

Maximum pressure Power consumption

DSU203F002

0...2.5 bar

0...10 V

24 V=/~

8 bar

24 V=/~, 0.5 W (VA)

DSU206F002

0...6 bar

0...10 V

24 V=/~

20 bar

24 V=/~, 0.5 W (VA)

DSU210F002

0...10 bar

0...10 V

24 V=/~

32 bar

24 V=/~, 0.5 W (VA)

DSU216F002

0...16 bar

0...10 V

24 V=/~

50 bar

24 V=/~, 0.5 W (VA)

DSU225F002

0...25 bar

0...10 V

24 V=/~

80 bar

24 V=/~, 0.5 W (VA)

DSI203F002

0...2.5 bar

4...20 mA

24 V=

8 bar

24 V=, 0.7 W

DSI206F002

0...6 bar

4...20 mA

24 V=

30 bar

24 V=, 0.7 W

DSI210F002

0...10 bar

4...20 mA

24 V=

32 bar

24 V=, 0.7 W

DSI216F002

0...16 bar

4...20 mA

24 V=

50 bar

24 V=, 0.7 W

DSI225F002

0...25 bar

4...20 mA

24 V=

80 bar

24 V=, 0.7 W

X

Accessories Type

Description

0300360007

Capillary throttle, stainless steel, length 1 m, G½"-G½"

0300360015

Wall holder for DSU/DSI

Right of amendment reserved © 2024 Fr. Sauter AG

85


Data capture | Flow and pressure

DSDU, DSDI: Differential pressure transmitter Features • For measuring pressure differences in liquids, gases and vapours • Pressure measuring in non-aggressive fluids or gaseous media • Sturdy device with ceramic diaphragm • For use in filter technology, heating systems etc.

X

• Differential pressure measuring range from 0...6 bar • Analogue signal 0...10 V or 4...20 mA • 24 V~/= supply voltage

DSD*10*F021

• With fitting bracket • Standard plug as per DIN EN 175301-803-A

Technical data Power supply

Power supply Electrical connection Power consumption

24 V=/~, ±20%, (50...60 Hz) Three-wire < 1.5 W (VA)

Output signal

0...10 V Load: > 2 kΩ 4...20 mA Load: ≤ 700 Ω (V=), ≤ 400 Ω (V~) ≤ 1%

Parameters

Accuracy1) Ambient conditions

Ambient temperature Media temperature

-20...80°C 0...80°C (non-freezing media) 45...75% rh 64 bar (both sides)

Ambient humidity Burst pressure Construction

Housing material Diaphragms Connection thread Device plug

Weight

Brass Ceramic G ⅛" (female thread) Plug connection 4-pin, standard plug DIN EN 175 01-803-A, cable gland M16 0.62 kg

Type of protection EMC Directive 2014/30/EU PED 2014/68/EU

IP65 (EN 60529) EN 61326-1, EN 61326-2-3 Fluid group II, article 4.3

Standards and directives

CE conformity according to

Overview of types Type

Measuring range ∆p

Output signal

Max. pressure (connection +)

Max. pressure (connection -)

DSDI101F021

0...1 bar

4...20 mA

10 bar

5 bar

DSDI103F021

0...2.5 bar

4...20 mA

21 bar

15 bar

DSDI106F021

0...6 bar

4...20 mA

21 bar

15 bar

DSDU101F021

0...1 bar

0...10 V

10 bar

5 bar

DSDU103F021

0...2.5 bar

0...10 V

21 bar

15 bar

DSDU106F021

0...6 bar

0...10 V

21 bar

15 bar

1)

86

Including non-linearity and hysteresis in compensated temperature range 10...70°C

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Flow and pressure Accessories Type

Description

0300360005

Cutting ring fitting G⅛" to 6 mm pipe (2 pcs)

0300360006

Pneumatic fitting G⅛" to 6 mm hose (2 pcs)

0300360016

Throttle screws G⅛", G⅛" (2 pcs)

X

Right of amendment reserved © 2024 Fr. Sauter AG

87


Data capture | Flow and pressure

SGU 100: Sash sensor Features • Infinitely-variable measurement of the position of the vertical front sash on laboratory fume cupboards • Accurate detection of sash position, with no wear and tear • Fast control of the air volume; no oscillation • Easy fitting, preferably on the counterweight of the front sash

X

• Teach-in function for adjusting the travel of the front sash

SGU100F01

• Easy to program using the SAUTER CASE Sensors software • Integrated excess-travel alarm • Power cable 2.5 m long, 7 × 0.32 mm2, fixed to housing • Fitted with halogen-free cable as standard • Remote access and remote maintenance: Commissioning and service via bus or external push-button • 3-colour LED status indicator • Acoustic status and alarm elements (can be deactivated)

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power consumption 24 V~1)

±20%, 50...60 Hz ±20% Typically: 2 VA, 0.75 W, inactive buzzer, max.: 4 VA, 1.5 W, active buzzer Typically: 0.6 W, inactive buzzer, max.: 1.1 W, active buzzer

Power consumption 24 V=2)

Parameters

Linearity error

Max. 1.5% based on working range, e.g.: 2...10 V = 8 V < 100 ms 0...5, 22 s, variable using SAUTER CASE Sensors

Hardware response time3) Filter time constant

Ambient conditions

Operating temperature Storage and transport temperature Humidity

0...55 °C –20...70 °C 85% rh, no condensation

Digital input

Iout_source max.: 1 mA, Vout max.: 18 V at Rload = ∞ Isink max.: 2 mA, open collector output, 100 mV at Isink 2 mA, Vin max.: 24 V=, 20% at Isink = 0 mA 0/2...10 V, 1 mA max., Vout max.: 11.5 V, can be parametrised, Default 2...10 V 2.5% (unlinearity, hysteresis, offset, amplified; based on working range) < 0.04 %/K

Inputs/outputs

Alarm output

Voltage output4)

Typical overall error Temperature effect

1) 2) 3) 4)

88

Default is buzzer active Inactive/active buzzer: Default is buzzer active The set filter time constant must be added Protected against short circuits and excess voltage to 24~

Right of amendment reserved © 2024 Fr. Sauter AG


Data capture | Flow and pressure Construction

Weight Length of cable without bus termination5)

0.68 kg Up to 200 m, Ø 0.5 mm

Type of protection Protection class Software EMC Directive 2014/30/EU

IP10 (EN 60529, IP20 (EN 60529) III (EN 60730) A (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4

Standards and directives

X

Overview of types Type

Working range

Resolution of working stroke

SGU100F010

200…800 mm for bench-mounted fume cupboards (max. spring travel 1000 mm)

< 1 mm

SGU100F011

400…1600 mm for walk-in fume cupboards (max. spring travel 2000 mm)

< 2 mm

Accessories Type

Description

0300360001

USB-RS-485 converter

5)

Cable length of bus termination on both sides 120 Ω: 200...500 m, Ø 0.5 mm

Right of amendment reserved © 2024 Fr. Sauter AG

89


Single-room, heating and airconditioning controllers

For all building situations: stand-alone or networked. SAUTER stand-alone controllers are tailored to applications such as heating, air-conditioning, ventilation or room control. They can be installed quickly. The intuitive operating concept ensures maximum comfort and guarantees, at the same time, the greatest possible energy efficiency in day-to-day operations. This allows all requirements for smooth functionality and economical operation to be combined. 90

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers Single-room control Overview of room temperature controllers

92

NRFC 413, 422…424: Modbus fan coil thermostat

93

TRA 410, 421: Room thermostat for heating and heating/cooling with display

97

TRT 317, 327: Electronic room thermostat for heating and heating/cooling

99

FXV 3***: Electrical distributor

101

FXV 33** EasySwitch: Electric distributor for control signals

103

equitherm heating control Overview of heating controllers

105

EQJW 146: Heating and district heating controller, equitherm

108

EQJW 126: Heating controller, equitherm

106

EQJW 246: Heating and district heating controller, equitherm

111

flexotron controllers for ventilation and air-conditioning Overview of controllers for ventilation and air-conditioning

114

RDT 405, 410: Electronic controller for heating, cooling and ventilation, flexotron400

115

VAV compact controllers ASV205BF132*, ASV215BF132*: VAV compact controller

118

ASV2*5BF152*: VAV controller for laboratory and pharmaceutical applications

121

FCCP: Fume cupboard indicator and monitor

124

Right of amendment reserved © 2024 Fr. Sauter AG

91

C


Room temperature controllers The SAUTER single-room controller combines the highest standards of operability with a modern design. The device can be used in various applications in hotel, business or residential premises. These include individual temperature control for single rooms, apartments and zones in 2- and 4-pipe systems. The electronic room controller is powerful, economical and easy to operate.

Overview of room temperature controllers

Type designation

NRFC 4

Application Air-conditioning controller Fan-coil controller For 2-pipe installation For 4-pipe installation For 2/3-way zone valve For 6-way ball valve

• • • • − −

Outputs Continuous Quasi-continuous, 2-point 3-point Relay

• • − •

Control PI

•

Operation and indicator Display Presence button

• −

Communication Protocols Further information

92

Modbus RTU Page 93

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | Single-room control

NRFC 413, 422…424: Modbus fan coil thermostat Features • Single-room controller for heating and cooling by means of air conditioning units in commercial and

residential buildings For 2- or 4-pipe fan coil units, two-stage heating systems or water-bearing heat pumps • • Can be integrated into building management systems via Modbus/RTU • Large configurable display with backlight • Integrated ON/OFF timer • Deactivatable button operation for public installations • Valve control via 2-point or 0...10 V output

C

NRFC413MF111

• Supports 3-speed fans or fans with EC motor • Summertime/wintertime change-over in 2-pipe applications • Automatic deactivation of internal temperature sensor when using a cable temperature sensor • Installation via mounting plate without opening the controller • Universal design and low installation height of 14 mm for inconspicuous fitting

Technical data Power supply

Power supply Power consumption

100…240 V~, 50/60 Hz 5 VA

Ambient temperature Ambient humidity Storage and transport temperature

0…40 °C 10…90% rh, no condensation -10…60 °C

Temperature sensor Digital input

NTC 10k closed < 0.3 V= open > 0.7 V= 0…10 V 0…10 V (100 kΩ) 2.2 A (IR); 3.6 A (IX) cos φ 0.98 each at 240 V~

Ambient conditions

Inputs/outputs

Inputs

Analogue input Analogue output U Relay output

Outputs

Interfaces, communication

RS-485

Communication protocol Connection

Indicator/display Buttons

Modbus/RTU Screw terminal, 3-pole 0.14...1.5 mm² rigid A (D+) / B (D-) 4800, 9600 bit/s (adjustable) 164 01, 03, 04, 06, 16 CRC-16 u16 10 bit, 1 start, 8 data, 1 stop, no parity LCD display with backlight (adjustable) 6

Weight Dimensions W × H × D Housing Housing material Fitting

0.3 kg 88 × 88 × 46.2 mm Upper and lower part white Polycarbonate On round or square recessed box

Bus speed Address range Function codes CRC check Data type Data format

Construction

Right of amendment reserved © 2024 Fr. Sauter AG

93


Single-room, heating and air-conditioning controllers | Single-room control

Standards, directives

CE conformity according to

Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RoHS Directive 2011/65/EU

IP20 (EN 60529) II as per IEC 60730 EN 60730-1, EN 60730-2-9 residential premises Type1.C EN 60730-1, EN 60730-2-9 EN IEC 63000

Inputs/outputs Type NRFC413MF111 NRFC422MF111 NRFC423MF111 NRFC424MF112

C

AI 1 × NTC, 1 × 0...10 V 1 × NTC 1 × NTC 1 × NTC

DI 1 1 1 1

AO 1 0 2 2

DO 3 × relay (single-pole normally-open contact) 5 × relay (single-pole normally-open contact) 3 × relay (single-pole normally-open contact) 3 × relay (single-pole normally-open contact)

Overview of types

94

Type

Description

Fan

NRFC413MF111

2-pipe, continuous, with positional feedback signal

3 speeds 3 speeds

NRFC422MF111

2-pipe or 4-pipe, 2-point

NRFC423MF111

2-pipe or 4-pipe, continuous

3 speeds

NRFC424MF112

2-pipe or 4-pipe, 2-point or 2-pipe, continuous

EC motor with cut-off function

Right of amendment reserved © 2024 Fr. Sauter AG


Surface temperature regulation The systems and solutions from SAUTER set standards for convenient control of surface heating and cooling systems. The products stand for technologically advanced, precise and easy to operate installations. The systems provide modern solutions for single- and multi-family buildings, hotels and public buildings, where the focus is on optimal comfort, easy operation and energy efficiency.

Overview of surface temperature regulation

Type designation

TRA 410, 421

TRT 317, 327

Application Controller Electrical distributor Operating device

• − •

• − •

Circuits/zones Channels Time programme/set-back mode

− •

− •

Power supply 24 V / 230 V Battery mode

• −

• −

Operation and indicator Display Sensor buttons Rotary knob Status LED

• − • −

− − • −

− • − • − Page 97

− • − • − Page 99

Communication and functions Communication via wireless connection Communication via wire connection Network connection/LAN Heating/cooling Access via app Further information

Right of amendment reserved © 2024 Fr. Sauter AG

95


Type designation

FXV 3***

FXV 33**

Application Controller Electrical distributor Operating device

− • −

− • −

Circuits/zones Channels Time programme/set-back mode

6/10 •

8 •

Power supply 24 V / 230 V Battery mode

•/• −

−/• −

− − − •

− − − •

− • − • − Page 101

− • − • − Page 103

Operation and indicator Display Sensor buttons Rotary knob Status LED Communication and functions Communication via wireless connection Communication via wire connection Network connection/LAN Heating/cooling Access via app Further information

96

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | Single-room control

TRA 410, 421: Electronic room thermostat for heating and heating/cooling with display Features • Electronic room thermostat for 24 V or 230 V for heating or heating/cooling with display • Easy to read LCD with backlight on TRA 421 • Silent-switching Triac output (24 V types) • Easy to wire up • NTC sensor

C

• Time programme and pilot clock output integrated in TRA 421 • Optimised time programme for comfort control and energy saving • Input for lowering the room temperature (TRA 410)

TRA4**F21*

• Input for heating/cooling changeover (TRA 421) • Input for external temperature sensor • Cooling lock function on versions for heating/cooling • Integrated “NC” and “NO” changeover • Modern design with ergonomic setpoint adjuster • Restriction of temperature setting range • Automatic frost protection facility at 5 °C and valve protection facility

Technical data Power supply

Power supply Power consumption Fuse

See type list < 0.3 W in idle state In housing: 230 V= T1AH 24 V= T1A

Number of actuators

Setting range Switching difference Set-back Measuring element

AXT: 230 V, max. 5 pcs. parallel 24 V, max. 4 pcs. parallel 5...30 °C ±0.2 K 2 K or adjustable NTC 22k

Ambient temperature Ambient humidity

0...50 °C 5...80% rh, no condensation

Housing

Cover: White (RAL 9016) Lower section: Signal white (RAL 9003) Thermoplastic PC + ABS Wall, recessed junction box

Parameters

Ambient conditions

Construction

Housing material Fitting Inputs/outputs

Switching element Switch rating ECO input

Right of amendment reserved © 2024 Fr. Sauter AG

230 V, relay 24 V, Triac 230 V, 1 A 24 V, 1 A 230 V, voltage detection 230 V 24 V, voltage detection 24 V

97


Single-room, heating and air-conditioning controllers | Single-room control Heating/cooling

Input: 230 V, voltage detection 230 V 24 V, voltage detection 24 V Output: 230 V, 100 mA 24 V, 100 mA

Pilot timer

Connection terminals / cable

Connection terminals

C

Power cable

Screw terminals 0.22 mm2 to 1.5 mm2 Solid: NYM-J/NYM-O (max. 5 × 1.5 mm²) Flexible: H03V2V2H2-F / H05V2V2H2-F

Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP20 (EN 60529) III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-3 EN 60730-1, EN 60730-2-9

Standards, directives

CE conformity according to

Overview of types Type

Description

Power supply

Weight

TRA410F210

Heating, lowering, frost protection function

230 V~, ±10%, 50 Hz

130 g

TRA410F212

Heating, lowering, frost protection function

24 V~, ±20%, 50 Hz

130 g

TRA421F210

Heating/cooling, lowering, frost protection and valve protection function, cooling lock

230 V~, ±10%, 50 Hz

140 g

TRA421F212

Heating/cooling, lowering, frost protection and valve protection function, cooling lock

24 V~, ±10%, 50 Hz

140 g

Accessories Type

98

Description

AXT3**

Thermal actuators for unit valves (see product data sheet)

EGT554F103

Cable temperature sensor, NTC 22k, −35...100 °C, IP67, length 3 m

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | Single-room control

TRT 317, 327: Electronic room thermostat for heating and heating/cooling Features • Electronic room thermostat for 24 V or 230 V for heating or heating/cooling • Silent-switching Triac output on 24 V types • Easy to wire up • NTC sensor • With input for lowering the room temperature

C

• With input for heating/cooling changeover (TRT 327) • With cooling lock function on versions for heating/cooling • Modern design with ergonomic setpoint adjuster

TRT3**F21*

• With restriction of temperature setting range • Electrical connection in baseplate with screw terminals • With automatic frost protection facility at 8 °C and valve protection function

Technical data Power supply

Power supply Power consumption Fuse

24 V~ / 230 V~ < 0.3 W in idle state In housing: 230 V= T2AH 24 V= T1A

Number of actuators

Setting range Switching difference Set-back Measuring element

AXT: 230 V, max. 6 pcs. parallel 24 V, max. 4 pcs. parallel 10...28 °C ±0.5 K 2K NTC

Ambient temperature Ambient humidity

0...50 °C 5...80% rh, no condensation

Housing

Cover: White (RAL 9016) Lower section: Signal white (RAL 9003) Thermoplastic PC + ABS Wall, recessed junction box

Parameters

Ambient conditions

Construction

Housing material Fitting Inputs/outputs

Switching element Switch rating ECO input Heating/cooling

230 V, relay 24 V, Triac 230 V, 1.8 A 230 V, voltage detection 230 V 24 V, voltage detection 24 V 230 V, voltage detection 230 V 24 V, voltage detection 24 V

Connection terminals / cable

Connection terminals Switching difference Cord grip

Right of amendment reserved © 2024 Fr. Sauter AG

Screw terminals 0.22mm2 to 1.5mm2 ±0.5 K External

99


Single-room, heating and air-conditioning controllers | Single-room control

Standards, directives

CE conformity according to

Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP20 (EN 60529) III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-3 EN 60730-1, EN 60730-2-9

Overview of types

C

Type

Description

Voltage

TRT317F210

Heating, lowering, frost protection function

230 V~, ± 10 %, 50 Hz 90 g

Weight

TRT317F212

Heating, lowering, frost protection function

24 V~, ± 20 %, 50 Hz

TRT327F210

Heating/cooling, lowering, frost protection and valve protection function, cooling lock

230 V~, ± 10 %, 50 Hz 135 g

TRT327F212

Heating/cooling, lowering, frost protection and valve protection function, cooling lock

24 V~, ± 10 %, 50 Hz

90 g

135 g

Accessories

100

Type

Description

AXT3**

Thermal actuators for unit valves (see product data sheet)

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | Single-room control

FXV 3***: Electric distributor for positioning signals Features • For easy wiring of up to 6 or 10 zones in a surface heating system • For transferring switching signals from the unitary controllers for heating or heating/cooling • Individual forwarding of time commands or night set-back to the appropriate actuators; max. 2 timer

FXV3210F002

channels • With pump and boiler control • Pump logic with adjustable follow-on time for actuating the circulation pump • Integrated valve protection function

C

• Input for temperature limiter or dew point monitor • LED status indicator • Pump control direction switching for NC/NO actuators • For connecting up to 18 actuators • Cable guidance, standard-compliant cord grip and screwless terminal connections • Easy, intuitive wiring and installation

Technical data Power supply

Power supply 230 VAC Power supply 24 VAC Distributor fuse 24 V Distributor fuse 230 V

±10%, 50...60 Hz ±20%, 50...60 Hz T2A T4AH

Circuits/zones Timer channels/set-back

6 or 10 2

Ambient temperature Storage temperature Ambient humidity

0...50 °C –20…70 °C < 80% rh

Outputs

Number of actuators

Inputs

Pump connection Boiler connection Set-back Heating/cooling TB or dew point

6 channels: Max. 15 pcs. 10 channels: Max. 18 pcs. Max. 6 (2) A Max. 6 (2) A Potential-free contact input Potential-free contact input Potential-free NC contact

Parameters

Ambient conditions

Inputs/outputs

Construction

Housing material Cover Fitting

Flame-retardant ABS plastic, black RAL9005 Transparent grey plastic Mounted unit, DIN rail

Connection terminals / cable

Connection terminals

Power cable

Cable clamping device

Right of amendment reserved © 2024 Fr. Sauter AG

Terminals with spring technology for 0.2 to 1.5 mm² vertical cable entry Solid: NYM-J/NYM-O (max. 5 × 1.5 mm²) Flexible: H03V2V2H2-F / H05V2V2H2-F Integrated in housing

101


Single-room, heating and air-conditioning controllers | Single-room control Standards, directives

Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

CE conformity

IP20 (EN 60529) II (EN 60730) EN 60730-1 Type 1C EN 60730-1 & -2-9 Type 1C

Overview of types

C

Type

Nominal voltage

Channels

Weight

FXV3006F001

24 V~ / 230 V~ Heating, with decrease

Features

6

482 g

FXV3110F001

230 V~

Heating/cooling, with decrease and pump control

10

515 g

FXV3110F002

24 V~

Heating/cooling, with decrease and pump control

10

515 g

FXV3210F001

230 V~

Heating/cooling, with decrease, pump logic, boiler control and LED indicator

10

550 g

FXV3210F002

24 V~

Heating/cooling, with decrease, pump logic, boiler control and LED indicator

10

534 g

Accessories

102

Type

Description

0450573001

Transformer 230 / 24 V, 42 VA

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | Single-room control

FXV 33** EasySwitch: Electric distributor for control signals Features • For the control of a maximum of twelve thermal actuators for unit valves and the connection of up to eight

room thermostats • Flexible assignment of the actuators to the room thermostats via rotary switch

FXV3308F011

• Distribution of the power supply, the positioning signals and a shared time programme for room operating

units • Easy-to-change channel assignment without rewiring • Pump logic module for activating a circulation pump

C

• Input for timer for individual forwarding of time commands to the heating zones • LED status indicators for power supply, pump logic module and active heating channels • Integrated cable guides and terminal connection without tools • Fitting on DIN rail or wall mounting

Technical data Power supply

Power supply Distributor fuse 230 V

230 V~, ±10%, 50...60 Hz T4AH (5 × 20 mm)

Control loops/heating zones1) Timer channel/set-back

Max. 8 inputs Yes

Ambient temperature Storage temperature Ambient humidity

0...50 °C −20...70 °C 10...85% rh

Outputs

Number of actuators

Inputs

Pump connection Set-back

Max. 12 thermal actuators for unit valves (for heating circuits) Max. 2 (1) A Contact input

Parameters

Ambient conditions

Inputs/outputs

Construction

Housing material

Cover material Fitting Dimensions W × H × D

PC-ABS plastic, black (similar to RAL9005) Fire-retardant as per UL94V-0 PC plastic, grey transparent Fire-retardant as per UL94V-0 Mounted unit, DIN rail, 35 mm or optionally screw-on mounting 350 × 100 × 52 mm

Connection terminals / cable

Connection terminals Cable cross-section Power cable

Cable clamping device

1)

Spring-loaded plug-in connectors 0.5...1.5 mm² Solid: NYM-J/NYM-O (max. 5 × 1.5 mm²) Flexible: H05V2V2H2-F Cable fastening points integrated without tools into housing

TRA or TRT room thermostats: TRA: max. five AXT per heating zone TRT: max. six AXT per heating zone

Right of amendment reserved © 2024 Fr. Sauter AG

103


Single-room, heating and air-conditioning controllers | Single-room control Standards, directives

Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

CE conformity

IP20 (EN 60730) II (EN 60730) EN 60730-1, residential premises EN 60730-1 & -2-9 Type 1C

Overview of types Type

Nominal voltage

Features

Channels

Weight

FXV3308F011

230 V~

Heating/cooling, with decrease, pump logic and LED indicator

8

580 g

C

104

Right of amendment reserved © 2024 Fr. Sauter AG


Heating controller SAUTER heating controllers of the equitherm series are easy to operate, while ensuring that your installation meets the highest standards of energy-optimised operation. Using communication accessories, the devices can be networked together in larger plants or integrated into a building automation system. The applications for these heating controllers include weather-dependent boiler and/or supply temperature control and domestic hot water preparation, as well as heating control in local or district heating networks.

Overview of heating controllers

EQJW 126

EQJW146F001

EQJW146F002

EQJW246F002

Application Solar Boiler control Supply temperature control Heating of drinking water Local/district heating

Type designation

− − • − •

• • • • •

• • • • •

• • • • •

Operation Symbol display Graphics display

• −

• −

− •

− •

Function Control loops Switching programmes

1 •

•

•

3 •

Inputs/outputs Inputs/outputs (0...10 V) Digital inputs Analogue inputs (Ni1000/ Pt1000) Relay (pump/actuator)

− − 3 3

Communication Interfaces Protocols

Logbook Further information

2

1 2 8 7

1/1 17 17 11

RJ45 Modbus RTU, device bus (TAP)

− Page 106

Right of amendment reserved © 2024 Fr. Sauter AG

− Page 108

• Page 108

Modbus RTU, Device bus (TAP), M-Bus • Page 111

105


Single-room, heating and air-conditioning controllers | equitherm heating control

EQJW 126: Heating controller with digital user interface, equitherm Features • PI supply temperature control by heating curve or 4-point characteristic • Convenient to use with modern operating concept (turn and press) and large LCD • Convenient weekly and annual switching programmes with optimisation of switching times

EQJW126F001

C

• Automatic summertime/wintertime changeover • Min./max. limitation of supply temperature and max. limitation of return temperature • Frost-protection facility and pump and valve anti-jamming function • Function heating (floor-drying function) • Room temperature switching using room temperature sensor • Ni/Pt1000 inputs for the outside, supply, return flow and room temperature • Relay outputs with varistor suppression for activating control units and pump • Manual mode • Electrical connection in baseplate • Interface for various accessories such as modem, gateway, data logging module etc.

Technical data Power supply

Power supply Power consumption

230 V~, ±15%, 50...60 Hz Approx. 1.5 VA

Amplification KP Integral action time Frost-protection temperature Normal temperature Reduced temperature Supply temperature Outdoor temperature Cycle time Running time of valve

0.1...50 1...999 seconds 3 °C 0...40 °C 0...40 °C −5...150 °C −50...50 °C Running time of the valve ÷ 15 30...300 seconds

Ambient temperature Ambient humidity Storage and transport temperature

0...40 °C 5...95% rh, no condensation −10...60 °C

Number of inputs Number of outputs Pump relay1) Actuator relay (3-point or 2-point)2)

3 analogue, Ni1000/Pt1000 3 relays 1 × 2 A, 250 V~, cos φ > 0,5 2 × 2 A, 250 V~, cos φ > 0,5

Backup power supply

Min. 24 hours, typically 48 hours

Accuracy Number of switching commands Min. switching interval Number of switching commands Min. switching interval

< 10 minutes/year 42/week 15 minutes 20 1 day

Parameters

Control parameters

Temperature ranges

Ambient conditions

Inputs/outputs

Function

Digital timer for weekly/annual switching programme Weekly switching programme Annual switching programme

1) 2)

106

Start-up current max. 16 A (1 second) Extra low voltage not admissible

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | equitherm heating control

Interfaces and communication

Interface Protocol

RJ45 Modbus, device bus (TAP)

Weight Dimensions Housing Housing material Fitting Screw terminals

0.5 kg 144 × 98 × 54 mm Light-grey Fire-retardant thermoplastic Wall, switch panel, DIN rail For electrical cables of up to 2.5 mm²

Type of protection (when fitted in panels) Protection class Software class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP40 (EN 60529)

Construction

C

Standards and directives

CE conformity according to

II (IEC 60730-1) A (IEC 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-3 EN 60730-1

Overview of types Type

Features

EQJW126F001

Heating controller with digital user interface

Accessories Type

Description

AVF***

Motorised valve actuator (see product data sheet)

AVM***

Motorised valve actuator (see product data sheet)

AXM***

Motorised valve actuator (see product data sheet)

EGT***

External temperature sensor Ni1000 (see product data sheet)

0440210001

Communication module for connecting EQJW 126/146 controllers to RS-232 (PC)

0440210002

Communication module for connecting EQJW 126/146 controllers to modem

0440210003

Communication module for connecting EQJW 126/146 controllers to RS-485 bus

0440210004

Communication module for connecting EQJW 126/146 controllers to RS-485 bus (master)

0440210005

ModBus-TCP gateway

0440210011

ModBus-GPRS gateway

0440210006

ModBus-MBus gateway

0440210007

Converter/repeater for RS-232 or RS-485 interfaces

0440210008

RS-485 overvoltage protection

0440210010

Parameter storage module for transferring controller parameters

0440210012

Cable converter, 2 conductors, RS-485

Right of amendment reserved © 2024 Fr. Sauter AG

107


Single-room, heating and air-conditioning controllers | equitherm heating control

EQJW 146: Heating and district heating controller, equitherm Features • Weather-dependent supply temperature control by heating curve or 4-point characteristic and drinking

water heating • 29 system models, for example for district heating, single-stage boilers, drinking water heating with solar

energy or buffer tank EQJW146F002

C

• Convenient to use with modern operating concept (turn and press) and large LCD • Convenient weekly and annual switching programmes with optimisation of switching times • Automatic summertime/wintertime changeover • Min./max. limitation of supply temperature and max. limitation of return temperature • Frost-protection facility and anti-jamming function for valve and pump • Floor-drying function • Function for protecting against legionellae • Room temperature switching using room-temperature sensors • Ni/PT1000 inputs for the outside, supply, drinking water, return flow and room temperature • Relay outputs with varistor suppression for activating control units and pumps • Manual mode • Logbook • Configurable input/output 0...10 V • External demand processing, binary or analogue (0..10 V) • Interface for various accessories such as modem, gateway, data logging module etc.

Technical data Power supply

Power supply Power consumption

230 V~, ±15%, 50...60 Hz Approx. 1.5 VA

Parameters

Control characteristic Control parameters

Temperature ranges

Supply temperature PI control Drinking water temperature 2-point Amplification KP 0.1...50 Integral action time 1...999 seconds Switching difference for drinking water 1...30 K Normal temperature 0...40 °C Reduced temperature 0...40 °C Supply temperature 0...140 °C Return temperature 0...140 °C Outdoor temperature −50...50 °C Drinking water temperature 20...90 °C Frost-protection temperature −15...3°C Running time of valve 30...300 seconds Cycle time Running time of the valve ÷ 15

Ambient conditions

Ambient temperature Ambient humidity Storage and transport temperature

0...40 °C 5...95% rh, no condensation −10...60 °C

Number of outputs Pump relay1)

7 relays 3 × 2 A, 250 V~, cos φ > 0,5

Inputs/outputs

1)

108

Start-up current max. 16 A (1 second)

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | equitherm heating control Actuator relay2) Continuous input/output3) Number of inputs Analogue inputs

4 × 2 A, 250 V~, cos φ > 0,5 1 × 0...10 V 2 digital, 8 analogue 8 Ni1000/Pt1000

Backup power supply Accuracy Number of programmes Number of switching commands Min. switching interval Number of programmes Number of switching commands Min. switching interval

Min. 24 hours, typically 48 hours < 10 minutes/year 3 42 each 15 minutes 1 (for heating circuits) 20 each 1 day

Interface Protocol

RJ45 Modbus, device bus (TAP)

Weight Dimensions Housing Housing material Fitting Screw terminals

0.5 kg 144 × 98 x 54 mm Light-grey Fire-retardant thermoplastic Wall, switch panel, DIN rail For electrical cables of up to 2.5 mm²

Type of protection

IP40 (EN 60529) (when fitted in panels) II (IEC 60730-1) A (IEC 60730-1, Appendix H) EN 61000-6‑1, EN 61000‑6‑3 EN 60730-1

Function

Timer Weekly switching programme

Annual switching programme

C

Interfaces, communication

Communication

Construction

Standards, directives

CE conformity according to

Protection class Software class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

Overview of types Type

Features

EQJW146F001

Heating and district heating controller with symbol display

EQJW146F002

Heating and district heating controller with graphic display

Accessories Type

Description

AVF***

Motorised valve actuator (see product data sheet)

AVM***

Motorised valve actuator (see product data sheet)

AXM***

Motorised valve actuator (see product data sheet)

EGT***

External temperature sensor Ni1000 (see product data sheet)

0440210001

Communication module for connecting EQJW 126/146 controllers to RS-232 (PC)

0440210002

Communication module for connecting EQJW 126/146 controllers to modem

0440210003

Communication module for connecting EQJW 126/146 controllers to RS-485 bus

0440210004

Communication module for connecting EQJW 126/146 controllers to RS-485 bus (master)

0440210005

ModBus-TCP gateway

0440210011

ModBus-GPRS gateway

0440210006

ModBus-MBus gateway

0440210007

Converter/repeater for RS-232 or RS-485 interfaces

0440210008

RS-485 overvoltage protection

2) 3)

Extra low voltage not admissible As input for requirement or outside temperature signal. As output for continuous control or requirement request, load > 5 kΩ

Right of amendment reserved © 2024 Fr. Sauter AG

109


Single-room, heating and air-conditioning controllers | equitherm heating control Type

Description

0440210010

Parameter storage module for transferring controller parameters

0440210012

Cable converter for 2-conductor RS-485 interface

C

110

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | equitherm heating control

EQJW 246: Heating and district heating controller, equitherm Features • Max. three control loops in the following combinations: • Control of a primary heat exchanger or boiler, two regulated and one unregulated heating circuit, and

control of the drinking water heating in the secondary circuit • Weather-dependent buffer tank control with solid fuel boiler and solar circuit control, as well as max. two

mixed-heating circuits • Control of two weather-dependent heating circuits and one drinking water heating with three valves in

the primary circuit

EQJW246F002

C

EQJW246F003

• Control of three weather-dependent heating circuits • EQJW246F003: Applications with up to six control loops via expansion modules • Different system models, e.g. for district heating, single-stage boilers, buffer tanks, drinking water heating

with solar energy • Weather-dependent supply temperature control based on heating characteristic or 4-point characteristic • To regulate more circuits, multiple controllers can be connected to each other via a device bus • Convenient operation with state-of-the-art operating concept (turn and press) and large graphical display • Convenient weekly and annual switching programmes with optimisation of switching times • Automatic summertime/wintertime change-over • Min./max. limitation of supply temperature and max. limitation of return temperature • Frost-protection facility and anti-jamming function for valve and pump • Floor-drying function • Function for protecting against legionellae • Room temperature switching using room-temperature sensors • Ni/Pt1000 inputs for the outside, supply, drinking water, return flow and room temperature • Relay outputs with varistor suppression for activating control units and pumps • Manual mode • Logbook • 0...10 V inputs for external requirement or outdoor temperature signal • 0...10 V outputs for external requirement, analogue/PWM outputs, speed-controlled pump etc. • Binary interfaces for fault signals or external requirement processing • Interfaces for various accessories such as modem, gateway, data storage module etc.

Technical data Power supply

Power supply Power consumption

230 VAC, ±15%, 50...60 Hz Max. 10 VA

Parameters

Control characteristic Control parameters

Temperature ranges

Supply temperature PI control Drinking water temperature 2-point Amplification KP 0.1…50 Integral action time 1...999 sec. Switching difference for drinking water 1…30 K Normal temperature 0…40 °C Reduced temperature 0…40 °C Supply temperature 0…140 °C Return temperature 0…140 °C Outdoor temperature −50…50 °C Drinking water temperature 20…90 °C Frost-protection temperature −15…3°C

Right of amendment reserved © 2024 Fr. Sauter AG

111


Single-room, heating and air-conditioning controllers | equitherm heating control Running time of valve Cycle time

15...240 sec. Running time of the valve ÷ 15

Ambient temperature Ambient humidity Storage and transport temperature

0…40 °C 5…95% rh, no condensation −10…60 °C

Pump relay2) Actuator relay3)

Inputs

5 × 2 A, 250 VAC F002: 6 × 2 A, 250 VAC F003: 4 × 2 A, 250 VAC, 2 × 0,12 A, 250 VAC (Triac) F002: 2 × 0…10 V F003: 4 × 0…10 V F002: 17 configurable Ni/Pt1000, binary, 1 × 0…10 V F003: 14 configurable Ni/Pt1000, binary, 3 × 0…10 V F002 and F003: 1 × pulse 3…800 lmp/h of h from heat meter for power limitation in HK1

Backup power supply Accuracy Number of programmes Number of switching commands Min. switching interval Number of programmes Number of switching commands Min. switching interval

Min. 24 h; typically 48 h < 10 minutes/year 3 42 each 15 minutes 1 (for heating circuits) 20 each 1 day

M-Bus

Ethernet

For max. 3 M-Bus units, protocol as per EN 1434-3 F002: 1 × RS-485 for device bus or Modbus/RTU F003: 2 × RS-485 for device bus and Modbus/RTU Modbus TCP/IP

Weight Dimensions Housing Housing material Fitting Screw terminals

0.5 kg 144 × 98 × 54 mm Light-grey Fire-retardant thermoplastic Wall, switch panel, DIN rail For electrical cables up to 2.5 mm²

Type of protection Protection class Software class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

IP40 (EN 60529) (panel mounting) II (IEC 60730-1) A (IEC 60730-1, Appendix H) EN 61000-6‑1, EN 61000‑6‑3 EN 60730-1

Ambient conditions

Inputs/outputs1)

C

Continuous output4)

Function

Timer Weekly switching programme

Annual switching programme

Interfaces, communication

RS-4855)

Construction

Standards, directives

CE conformity according to

1) 2) 3) 4)

5)

112

See also “Type overview” Start-up current max. 16 A (1 second) Extra low voltage not admissible 0...10 V output, e.g. for continuous control, outside temperature, external requirement or for speed control of pumps, load > 5 kΩ. 0/10 V: PWM signal for pump speed control Device bus: 2-wire bus, inverse, with reverse polarity protection, max. 32 users. Modbus/RTU: Modbus protocol data format 8N1, RJ45

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | equitherm heating control Overview of types Type

Features

Outputs

Inputs

EQJW246F002

Heating and district heating controller with graphic display, 1 × RS-485

11 relays, 2 × 0…10 V.

17 × Ni1000/Pt1000 and binary 1 × 0…10 V 1 × pulse

EQJW246F003

Heating and district heating controller with graphic display, 2 × RS-485, expandable for up to 6 control loops with accessories

12 relays, 4 × 0…10 V.

14 × Ni1000/Pt1000 and binary 3 × 0…10 V 1 × pulse

Accessories Type

Description

AVF***

Motorised valve actuator (see product data sheet)

AVM***

Motorised valve actuator (see product data sheet)

AXM***

Motorised valve actuator (see product data sheet)

EGT***

External temperature sensor Ni1000 (see product data sheet)

0440210001

Communication module for connecting EQJW 126/146 controllers to RS-232 (PC)

0440210002

Communication module for connecting EQJW 126/146 controllers to modem

0440210003

Communication module for connecting EQJW 126/146 controllers to RS-485 bus

0440210004

Communication module for connecting EQJW 126/146 controllers to RS-485 bus (master)

0440210005

ModBus-TCP gateway

0440210006

ModBus-MBus gateway

0440210011

ModBus-GPRS gateway

0440210007

Converter/repeater for RS-232 or RS-485 interfaces

0440210008

RS-485 overvoltage protection

0440210010

Parameter storage module for transferring controller parameters

0440210012

Cable converter for 2-conductor RS-485 interface

0440210014

I/O extension module for EQJW246F003

Right of amendment reserved © 2024 Fr. Sauter AG

C

113


Controllers for ventilation and air-conditioning SAUTER controllers for ventilation and air-conditioning cover all the possible applications for demand-based control of ventilation and air-conditioning systems. The large number of integrated standard applications meets the requirements for the modularity and the energy-efficient operation of your installations. A wide range of additional functions enable the establishment of complex control systems and the integration into a building automation system.

Overview of controllers for ventilation and air-conditioning

flexotron400 Type designation

RDT405F201

RDT410F*01

Control loops Cascade P-controller PI-controller PID-controller

− • • −

• • • •

Function Time programme

−

•

3 2 − − −

5 5 − − −

• − −

• • −

Communication Number of inputs Number of outputs Modbus BACnet Serial interface for parameters and configuration Application Supply temperature control Supply air cascade control Air-conditioning control Further information

114

Page 115

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | flexotron controllers for ventilation and air-conditioning

RDT 405, 410: Electronic controller for simple applications, flexotron400 Features • Five different control models for each device, for temperature, pressure, CO2, supply air cascade, heating • Easy to operate with large, illuminated LCD and rotary knob • Fast commissioning due to simple operating concept • Weekly programme (depending on variant) • External setpoint

RDT4**F*01

Power supply

Power supply

RDT 405 RDT 410

Power consumption Power consumption Start-up current

24 V~, ±15%, 50...60 Hz (RDT4**F201 230 V~, +10%/-15% 50…60 Hz (RDT4**F301) 4 VA, 2 W 7.5 VA, 5 W 16 A (2 ms) 24V~ devices 23 A (2 ms) 230 V~ devices

C

Y10188

PI

Technical data

RDT405F201 PI

RDT410F*01

Parameters

Control characteristics P-band Xp Integral action time

P/PI 0...99 K 0...990 s

Measuring range, temperature Measuring range, temperature Input for external setpoint Humidity Humidity CO2

-20...60, 20…100, 60…140°C 5…80, -30…50°C 0…40°C 0...100% rh 0...100% rh 10...9900 ppm for 100% signal

Ambient temperature Ambient humidity Storage and transport temperature

0...50 °C 5...95% rh, no condensation –20...70 °C

Universal inputs Digital inputs Analogue inputs

Digital outputs

Ni1000 (DIN 43760) Potential-free contacts Ni1000 (DIN 43760) for temperature, setpoint 0...10 V, 2 mA, protected against short circuit RDT410F201: Triac 2 × 24 V~, 0.3 A 1 × 230 V~, 5 A RDT410F301: Triac 2 × 24 V~, 0.16 A 1 × 230 V~, 5 A

Dimensions W × H × D Screw terminals Fitting Housing material

123 × 99 × 64 mm For electrical cables of up to 1.5 mm² Top-hat rail, wall, panel PC+ABS

Setting and measuring ranges

RDT 405 RDT 410

Ambient conditions

Inputs/outputs

Analogue outputs

Construction

Right of amendment reserved © 2024 Fr. Sauter AG

115


Single-room, heating and air-conditioning controllers | flexotron controllers for ventilation and air-conditioning

Standards and directives

IP20 (EN 60529) II (RDT410F301 only) EN 61000-6-1, EN61000-6-3

Type of protection1) Protection class EMC Directive 2014/30/EU

CE conformity according to

Overview of types

C

Type

Analogue inputs

Digital inputs

Universal inputs

Analogue outputs

Digital out- Input for ex- Week time- Weight puts ternal set- switch point

RDT405F201

1

1

1

2

0

1

−

0.2 kg

RDT410F201

2

2

1

2

3

1

•

0.3 kg

RDT410F301

2

2

1

2

3

1

•

0.45 kg

A

Week time-switch: only RDT410F*01 (number of switching commands: 8)

Accessories Type

Description

XYE460F001

flexotron400 demo case

0460240001

flexotron400/800 pluggable terminal strips

0460240010

Cabinet fitting kit for flexotron400

EGT388F102

External setpoint adjuster, room operating unit with potentiometer and temperature sensor, recessed

EGT333F102

External setpoint adjuster, room operating unit with potentiometer and temperature sensor, surfacemounted

1)

116

When installed

Right of amendment reserved © 2024 Fr. Sauter AG


VAV compact controller for laboratory and pharmaceutical applications SAUTER VAV controllers enable the air volume to be regulated in accordance with demand in order to optimise energy consumption in ventilation systems. They are used in laboratories, clean rooms, hospital wards and operating theatres. In combination with additional sensors and monitoring facilities, they ensure that fume cupboards are regulated in accordance with the relevant standards.

Overview of VAV compact controllers

Type designation Technical data Adm. dimensions of damper shaft (mm) Running time (s) Power supply (V) Communication/protocol Further information

ASV205BF132*, ASV215BF132*

ASV215BF152*

Ø 8...16 30...105 60...105 24 RS-485 SLC / BACnet MS/TP Page 118

Ø 8...16 3...15

Right of amendment reserved © 2024 Fr. Sauter AG

24 RS-485 SLC / BACnet MS/TP Page 121

117


Single-room, heating and air-conditioning controllers | VAV compact controllers

ASV205BF132E, ASV215BF132E: VAV compact controller Features • Supply and return air control for individual rooms such as offices, conference rooms and hotel rooms, in

conjunction with a VAV box or a damper and flow probe Pressure control in supply and return air ducts for low-noise, energy-efficient air distribution • • Static measurement of differential pressure with MEMS sensor • Can be used for measuring in areas with dirty or contaminated return air • Low energy consumption and long serviceable life thanks to low-wear stepping motor • Electromechanical, torque-based switch-off for safe operation

C

• Extremely simple installation due to self-centring shaft adapter

ASV205BF132E

• Disengageable gear unit for manual adjustment and positioning of damper • Integrated second control loop for the following applications : 1)

• Duct pressure and zone control • Room climate regulation • 2 x RS-485 bus interface on RJ12 and connection terminal • Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol +

• Communication within network via BACnet MS/TP

+

• Input and output signals for integrating: • Setpoints and actual values • Power outputs for reheaters and recoolers • EY-RU 3** digital room operating units • Analogue output • Easy programming of the following applications using the SAUTER CASE VAV software : 2)

• Volume flow control • Room pressure control • Duct pressure control • Adjustable end values of the differential pressure measuring range

3)

• 100...300 Pa • Efficient control algorithm for fast control loops • Priority control via switching contacts • Zero point can be calibrated

Technical data Power supply

Power supply4) Power consumption at nominal voltage Rated power 50/60 Hz (~/=) during continuous operation5) Power consumption when idle6)

1)

2)

3) 4)

5) 6)

118

24 V~, +/-20%, 50...60 Hz 24 V=, -10%/+20% 4.7 VA/2.5 W 1.5 VA/0.7 W

Application support depending on hardware and software version in CASE VAV manual D100316836 (German), D100316957 (English), D100316878 (French) Application support depending on hardware and software version in CASE VAV manual D100316836 (German), D100316957 (English), D100316878 (French) Available measuring ranges depending on hardware/type 24 V=: Analogue inputs that are not connected are rated 0 V. The nominal torque is achieved within the specified tolerances. Power specified without operating units FCCP 200, EY-RU 3* Holding torque ASV205*: 4 Nm ASV215*: 8 Nm

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | VAV compact controllers Parameters

Integrated damper actuator

∆p sensor

90° Angle of rotation7) Admissible dimensions of damper shaft Ø 8...16 mm, □ 6.5...12.7 mm Admissible damper shaft (hardness) Max. 300 HV Surge-voltage resistance 500 V (EN 60730) Operating noise < 35 dB (A) 0...500 Pa Measuring range ∆p (gain = 1)8) Linearity error 2% (at 25 °C) Time constant 0.2 s < 1 Pa Influence of position9) Reproducibility 0.2% FS Zero point stability 0.2% for 1 year Admissible positive pressure ±12.5 kPa Admissible operating pressure pstat10) ±7 kPa Low-pressure connections11)

Ø i = 3.5...6 mm

Operating temperature Storage and transport temperature Air humidity

0...55 °C –20...55 °C < 85% rh, no condensation

Analogue inputs Analogue outputs Digital inputs12)

0...10 V (Ri = 100 kΩ) 0...10 V, load > 10 kΩ Closed 1 V=, 1 mA, open > 2 V= 0.3 A at 24 V ~/= 0 to 50 °C Ni1000 (DIN 43760), NTC10k (10k3A1), Pt1000 (EN 60751) 0.3 °C (Ni1000/Pt1000), 0.1 °C (NTC) +/- 0.6 °C 0.3 A at 24 V ~/= Period duration 1 s....15 minutes 0...100%

C

Ambient conditions

Inputs/outputs

Digital output Resistive input

Resolution Measuring difference PWM

Interfaces and communication

RS-485 not electrically isolated Communication protocols Access method Topology Number of participants13) Bus termination

115 kBaud SAUTER Local Communication (SLC), BACnet MS/TP, ¼ load Master/slave Line 31 (32) with SLC 120 Ω (both ends)

Weight Fitting

0.8 kg Self-centring spindle adapter

Type of protection

IP00, IP30 (EN 60529) (with protection set) III (EN 60730)

Construction

Standards and directives

Protection class

7)

Maximum rotation angle 102° (without end stop) Available measuring ranges depending on hardware/type 9) Zero adjustment recommended during commissioning 10) Short-term overload; zero adjustment of sensor is recommended 11) Recommended hardness of tubing < 40 Sha (e.g. silicone) 12) Digital inputs for external potential-free contacts (gold-plated recommended) 13) One participant is always also the parametering tool, hence the maximum number of 31 connectible devices 8)

Right of amendment reserved © 2024 Fr. Sauter AG

119


Single-room, heating and air-conditioning controllers | VAV compact controllers Conformity

Machine directive 2006/42/EC, appendix II 1.B EN 61000-6-1, EN 61000-6-3, EN 61000-6-4, EN 61000-6-2

EMC Directive 2014/30/EU

Overview of types Type

Measuring range ∆p

Running time for 90°

Rotational torque

Holding torque

ASV205BF132E

0...300 Pa

30, 45, 60, 75, 90, 105 s

5 Nm

4 Nm

ASV215BF132E

0...300 Pa

60, 75, 90, 105 s

10 Nm

8 Nm

A A

C

For a running time of 105 s and an ambient temperature of ≥ 55 °C, the specified torque is reduced by 0.5 Nm. Current-free holding torque by means of interlocking in gear unit.

Accessories

120

Type

Description

0372301001

Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.

XAFP100F001

Flow probe to measure the air volume in ventilation ducts

0300360001

USB-RS-485 converter

0297867001

Reference pressure container

0430360100

IP30 protection set

0430360200

Replacement LP connector

0372129001

Torsion protection

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | VAV compact controllers

ASV215BF152*: VAV compact controller for laboratory and pharmaceutical applications Features • Controlling the return air in fume cupboards and controlling the supply and return air in laboratories, clean

rooms, hospital wards and operating theatres using a VAV box or a damper and flow probe • Static measurement of differential pressure based on the capacitive method of measurement • Zero point can be calibrated using software • Adjustable end values of the differential pressure measuring range

1)

• 50...150 Pa

C

• 100...300 Pa • Can be used for measuring in areas with dirty or contaminated return air • Brushless DC motor guarantees minimum energy consumption and a long service life

ASV215BF152D

• Electromechanical, torque-based switch-off for safe operation • Extremely simple installation due to self-centring shaft adapter • Disengageable gear unit for manual adjustment and positioning of damper • Easy programming of the following applications using SAUTER CASE Components:

2)

• Volume flow control • Room pressure control

+

+

• Duct pressure control • Flow control for fume cupboards • Efficient control algorithm for fast control loops • Integrated second control loop for:

3)

• Room-pressure control: can be ideally combined with EGP 100 with symmetrical measuring range • Fume-cupboard control ideally combined with SVU 100, SGU 100 and FCCP 200 • 2 x RS-485 bus interface on RJ12 and connection terminal • Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol • Communication within network via BACnet MS/TP

4)

• Integration of EY-RU 3** digital room operating units • FCCP 200 display and alarm unit for fume-cupboard control or room monitoring • Input and output signals for integrating: • Setpoints and actual values • Analogue output • Priority control via switching contacts

Technical data Power supply

Rotational torque Power supply5) Power consumption at nominal voltage Rated power 50/60 Hz (~/=) after 3 s running time during continuous operation Power consumption when idle6)

1) 2) 3) 4) 5)

6)

10 Nm 24 V~, ±20%, 50...60 Hz 24 V=, -10%/+20% Approx. 19 VA/10 W (10 Nm) Approx. 20 VA/11 W with FCCP 200 Approx. 6 VA/2 W

Available measuring ranges depending on hardware/type Application support depending on hardware and software version in CASE VAV manual Application support depending on hardware and software version in CASE VAV manual Support of BACnet MS/TP interface 24 V=: Analogue inputs that are not connected are rated 0 V. The nominal torque is achieved within the specified tolerances. Holding torque approx. 5 Nm

Right of amendment reserved © 2024 Fr. Sauter AG

121


Single-room, heating and air-conditioning controllers | VAV compact controllers Parameters

Integrated damper actuator

∆p sensor

C

Rotational torque 10 Nm 2 Nm Holding torque7) 90° Angle of rotation8) 3...15 s Running time for 90°9) Admissible dimensions of damper shaft Ø 8...16 mm, □ 6.5...12.7 mm Admissible damper shaft (hardness) Max. 300 HV Surge-voltage resistance 500 V (EN 60730) Operating noise < 49 dB (A) at 3 s Measuring range ∆p (gain = 1) 0...150/300 Pa Pressure range, types D/E10) Linearity error 2% FS Time constant 0.1 s Typically ±1 Pa Influence of position11) Reproducibility 0.2% FS Zero point stability 0.2% FS (at 20 °C) Admissible positive pressure ±10 kPa Admissible operating pressure pstat12) ±3 kPa Low-pressure connections13)

Ø i = 3.5...6 mm

Operating temperature Storage and transport temperature Air humidity

0...55 °C –20...55 °C < 85% rh, no condensation

Analogue inputs14) Digital inputs15)

0...10 V (Ri = 100 kΩ) Closed 1 V=, 1 mA, open > 2 V= 0...10 V, load > 10 kΩ max. cable length 30 m max. adm. external voltage ±24 V 0.3 A at 24 V ~/=

Ambient conditions

Inputs/outputs

Analogue outputs16)

Digital output Interfaces and communication

RS-485 not electrically isolated Communication protocols17) Access method Topology Number of participants18) Bus termination

115 kBaud SAUTER Local Communication (SLC), BACnet MS/TP, ¼ load Master/slave Line 31 (32) with SLC 120 Ω (both ends)

Weight Fitting

0.8 kg Self-centring spindle adapter

Type of protection

IP00, IP30 (EN 60529) (with protection set) III (EN 60730)

Construction

Standards and directives

Protection class 7)

Current-free holding torque by means of interlocking in gear unit Maximum rotation angle 102° (without end stop) 9) Running time can be set via software 10) Available measuring ranges depending on hardware/type 11) Zero adjustment recommended during commissioning 12) Short-term overload; zero adjustment of sensor is recommended 13) Recommended hardness of tubing < 40 Sha (e.g. silicone) 14) Depending on the application, can be parameterised as an analogue input or output using SAUTER CASE Components 15) Digital inputs for external potential-free contacts (gold-plated recommended) 16) Depending on the application, can be parameterised as an analogue input or output using SAUTER CASE Components 17) Available protocols switched using software 18) One participant is always also the parametering tool, hence the maximum number of 31 connectible devices 8)

122

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | VAV compact controllers Conformity EMC Directive 2014/30/EU

Machine directive 2006/42/EC, appendix II 1.B EN 61000-6-1, EN 61000-6-3, EN 61000-6-4, EN 61000-6-2

Overview of types Type

Measuring range ∆p

ASV215BF152D 0...150 Pa ASV215BF152E

0...300 Pa

C

Accessories Type

Description

0372301001

Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.

XAFP100F001

Flow probe to measure the air volume in ventilation ducts

0300360001

USB-RS-485 converter

0297867001

Reference pressure container

0430360100

IP30 protection set

0430360200

Replacement LP connector

0372129001

Torsion protection

Right of amendment reserved © 2024 Fr. Sauter AG

123


Single-room, heating and air-conditioning controllers | VAV compact controllers

FCCP 200: Fume cupboard indicator and monitor Features • Measured value display and indication of operating statuses for a range of ambient conditions such as

pressure, temperature, relative humidity etc. in combination with an EY-RC 504/505 room automation station or an ASV 2*5 VAV compact controller Monitoring fume cupboards as per EN 14175-2 to check that they are functioning correctly and that the • ventilation is operated to provide maximum safety for the laboratory staff • Indication when the front sash is open > 500 mm • Switching the fume cupboard lighting on and off

C

• Up to two function indicators for double-sided fume cupboards • Indication of day/night change-over

FCCP200F010

International Design

• Audible alarm can be delayed or muted via configuration • Demand-controlled regulation of fume cupboards as per EN 14175-6 in combination with the

ASV 2*5 VAV compact controller

Award

• Function indicator with visual and audible notification as per EN 14175-2 • Storage of all defined parameters with protection from power failure • Interface for easy configuration of the connected VAV ASV 2*5 • Five freely configurable push-buttons

1)

• Chemical-resistant glass surface • Units that can be displayed: m/s, fps, l/s, m3/h, cfm, Pa, °C, °F, %rh, ppm

Technical data Power supply

Power supply Power consumption

5 V, ±10% 0.4 VA

Sound pressure level Frequency Alarm duration2) Start-up delay Brightness Field of view Measuring range of temperature sensor3)

80 dB (A) 4 kHz 60 s Adjustable from 0 to 3200 s EN 842, punctiform > 120° −5…50 °C

Operating temperature Storage temperature Humidity without condensation

5…45 °C −20…80 °C < 5…85% rh

Dimensions W × H × D

169 × 36 × 12 mm

Protection class Protection class (when installed) EMC Directive 2014/30/EU

III (EN 60730) IP41 installed vertically EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4

Parameters

Audible alarm

Optical alarm Temperature sensor

Admissible ambient conditions

Construction

Standards and directives

1) 2) 3)

124

In combination with the EY-RC 504/505 room automation station and CASE Engine. Can be set using software. After it is installed, the temperature sensor must be calibrated using CASE Engine software during the commissioning.

Right of amendment reserved © 2024 Fr. Sauter AG


Single-room, heating and air-conditioning controllers | VAV compact controllers Overview of types Type

Features

FCCP200F010

Fume cupboard monitor and indicator

Accessories Type

Description

0300360001

USB-RS-485 converter

0430600100

USB-C RJ12 cable FCCP 200

C

Right of amendment reserved © 2024 Fr. Sauter AG

125


Valves, control valves, dampers, actuators

A high degree of flexibility for optimum results. SAUTER valves and actuators each come in a few basic versions that cover all needs for reliable and long-lasting control elements. The valve and the actuator are perfectly matched to each another as a basis for optimum control quality. The new Smart Actuator allows autonomous control of heating, ventilation and air conditioning. Cloud-based applications and an app simplify commissioning as well as optimisation during operation. 126

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators Smart actuators AKM 115SA: Smart Actuator for ball valve

131

SAIO 100: I/O module for smart actuators

140

AVM 115SA: Smart Actuator for 2- and 3-way valves

134

Power and connecting cables for Smart Actuators

142

ASM 115SA: Smart Actuator for ventilation dampers

137

Unit valves and actuators for unit valves Overview of unit valves

145

AXT 301, 311: Thermal actuator for unit valves

163

VUL: 2-way valves, PN 16

146 149

AXS 315S: Continuous thermal actuator for unit valves with stroke indicator

166

BUL: 3-way unit valve, PN 16 VUT: 2-way valve, PN 16

154

AXF 217S: Motorised actuator for unit valves with positioner

169

BUT: 3-way unit valve

156

AXM 217: Motorised actuator for unit valves

171

AXM 217S: Motorised actuator for unit valves with positioner

172

BXL: 3-way unit valve, PN 16

159

Overview of actuators for unit valves

161

Regulating valves and valve actuators VUN: 2-way valve with male thread, PN 16

177

BUS: 3-way flanged valve, PN 40

225

BUN: 3-way valve, PN 16

180

Overview of valve actuators

228

V6R: 2-way valve, PN 16

183

AVM 105, 115: Valve actuator

230

B6R: 3-way valve, PN 16

186

AVM 105S, 115S: Valve actuator (SUT)

232

VUD: 2-way flanged valve, PN 6

189

AVM 215: Valve actuator

234

VQD: 2-way flanged valve, PN 6

192

AVM 215S: Valve actuator with SAUTER Universal Technology (SUT)

236

BUD: 3-way flanged valve, PN 6

194

AVM 321, 322: Valve actuator

238

BQD: 3-way flanged valve, PN 6

197

AVM 321S, 322S: SUT valve actuator

241

VUE: 2-way flanged valve, PN 16/10

199

AVM 322-R: Retrofit actuator

244

VQE: 2-way flanged valve, PN 16

203

AVM 322S-R: Retrofit actuator

246

BUE: 3-way flanged valve, PN 16/10

205

AVM 234S: SUT valve actuator

249

BQE: 3-way flanged valve, PN 16

209

AVF 124: Valve actuator

252

VUG: 2-way flanged valve, PN 25/16

212

AVF 125S: SUT valve actuator

254

BUG: 3-way flanged valve, PN 25/16

216

AVF 234S: SUT valve actuator

256

VUP: Pressure-relieved 2-way flanged valve, PN 25

220

AVN 224S: SUT valve actuator

259

VUS: 2-way flanged valve, PN 40

222

Multi-function valves Overview of dynamic regulating valves

262

VDL 010...050: 2-way regulating valve, PN 25, Valveco compact

269

UVC 106: Dynamic flow control system with 6-way ball valve, eValveco

264

VDL 050…100: 2-way regulating valve, PN 16, Valveco flange

274

UVC102MF065…100: Dynamic flow control system with 2-way valve and energy monitoring, eValveco

266

292

Ball valves and ball valve actuators Overview of ball valves

276

VKAI: 2-way cut-off ball valve, PN 40

VKR: 2-way regulating ball valve, PN 40

278

VKAI: 2-way cut-off ball valve, PN 40

294

VKRA: 2-way regulating ball valve, PN 40

282

BKLI: 3-way changeover ball valve (L) with female thread, PN 40

297

BKR: 3-way regulating ball valve, PN 40

286

BKTI: 3-way changeover ball valve with female thread, PN 40

300

BKRA: 3-way regulating ball valve, PN 40

289

BKTA: 3-way changeover ball valve with male thread, PN 40

303

Right of amendment reserved © 2024 Fr. Sauter AG

127

V


Overview of 6-way ball valves

306

AKM 105S, 115S: Rotary actuator

313

B2KL: 6-way ball valve with male thread, PN 16

307

AKM 115S F152: High-speed rotary actuator

315

Overview of actuators for ball valves

309

AKF 112, 113: Rotary actuator

317

AKM 105, 115: Rotary actuator

311

AKF 113S: Rotary actuator

318

Overview of control valves and butterfly valves

319

MH32F, MH42F: Control valve, PN 6

322

M3R, M4R: Control valve, PN 10

320

DEF: Tight-sealing butterfly valve, PN 16

324

Control valves and rotary and damper actuators

Damper and rotary actuators

V

Overview of damper and rotary actuators

327

ADM 322: Rotary actuator

329

ADM 322S: Rotary actuator with positioner

331

ASM 105, 115: Damper actuator

334

ASM 105S, 115S F132: Damper actuator, SUT

336

ASM 105S, 115S F152: High-speed damper actuator, SUT

338

ASM 124: Damper actuator

340

ASM 134: Damper actuator

342

ASM 124S, 134S: Damper actuator, SUT

344

ASF 112, 113: Damper actuator

346

ASF 113S: Damper actuator

348

ASF 122, 123: Damper actuator

350

ASF 123S: Damper actuator

352

128

Right of amendment reserved © 2024 Fr. Sauter AG


Valve specification – calculating made easy SAUTER valve slide rule [1] Use SAUTER´s practical valve slide rule to specify the valve nominal diameter depending on the flow rate for liquids and saturated steam. You can order the slide rule at your sales partner or sales consultant.

SAUTER VALVEDIM software [2] A tried and tested tool for convenient valve and actuator specification, SAUTER provides installers and project engineers with its SAUTER VALVEDIM PC software. The tool comprises three function levels: 1. Valve and actuator specification • using recommended values for a rough specification of the required versions and variables; • based on the existing or stipulated installation values for the definitive specification of the required versions and variables. 2. Selection of the valve and the suitable actuator based on characteristics. 3. Direct transfer of the results to the project documentation. VALVEDIM is available from your SAUTER subsidiary or as a download at https://www.sauter-controls.com/produkt/case-suite/

1,5

30

2

4

1,5 1,6

2

40 50

70

30

40 50

5

3 4 5 6 7 8 9 10

100 70 50 30 20 1 0,7 0,5 0,3 0,2 1

0,4 0,5 0,63

20 20

3

70

100 100

10 7 5 3 2 0,1 0,05 0,03 0,02

2,5 3

4

5

150 200

5 7 10 15 20

30

1,5

300 400 500 2 40 50

3 70

700

4 5 100

1000

6 7 8 9 10 6,3

40 50 63 70 80 100

1,0

1,6

2,5

4

6,3

10

16

22

25

28

40

63

100

160

220

250

320

340

15

15

15

15

15

20

25

32

40

40

50

50

65

80

100 125 AVM

125

150

150

4 6 10 6

4 6 VUN 10 6

4 6 10 6 4 6 10 6

4 6 10 6 4 6 10 6 4 6 6 6

AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 10 321(S) 10 AVF 6 124/125S 6 AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 10 321(S) 10 AVF 6 124/125S 6 AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 6 321(S) 6 AVF 6 124/125S 6 AVM 322(S) AVM 234S AVF 234S AVM 4 105(S) 4 AVM 6 115(S) 6 AVM 10 321(S) 10 AVF 6 124/125S 6 AVM 322(S) AVM 234S AVF 234S AVM 16 322(S) 16 AVM 16 234S 16 AVF 16 234S16 AVM ? 322(S) ? AVM 40 234S 40 AVF 40 234S40

4 5 10 5 4 5 10 6 4 6 6 6

4 4 10 4 3 4 10 5 2,8 6 6 6

3 3,5 10 3,5 2 3,7 10 4 2,1 5,2 6 5,2

1,9 3 6 3 1,2 2,7 230 V AC 6 24 V AC 3,7

BUN

VUD BUD VQD BQD 4* 4* 6* VUE* 6* 10* BUE 10* PN16 6* 6* EN-JL 1040 VQE

4 6 10 6

4 6 10 6

BQE 16* 16* 16* 16* VUG* PN25 16* 16* 16* 16* EN-JS 102 16* 16* 16* BUG 16* ? ? ? ? VUS* PN40 40* 40* 40* 40* 1.0619 40* 40* 40* BUS 40*

16 16 16 ? 40* 40*

16 16 16 40 40

24 V DC 1,2 3,3 2-Pt 6 3-Pt 3,3 0...10 V 4...20mA

4 6 10 6

16 16 16 ? 40 40

2,8 6 10 6

2,1 second 1,4 5,2 3,3 9 5,7 Newton 5,2 3,3

SF132

SF132

F112

F110

F122

2)

1000

5

160 200

300 400 250 320 340

F

2)

124

125

1)

234

1)

1)

A 96 48

40/80 40/80 40/80 48 120 120 120 60 60 60 60 80/160 80/160 80/160 32 240 240 80 120 120 120 120 120/240 120/240 120/240 1000

2,5 3 3

1,5 3 3

2 2

1,5 1,5

7,1 5,6 ? 6,1 4,7

4,7 3,4 ? 3,9 3

3 2,2 ? 1,5 1,5

? 1 1

www.sauter-controls.com

234

322 F120

F122

321

2,5 1,5 3 3 2 3 2 35 3 0,9 60 120 120 60 96 300,9 120 120 120 48 2 2 120 3,4 3,4 250 500 2 2

15,2 9,4 6,1 4 16 1) Module 16 230V-24V:160372332 001 11 16 2) Module 16 230V-24V 13,5 8,5 ? ? ? ? ? ? 37,8 28,7 16,4 10,5 29,6 22,5 12,8 8,2

5000 3 700

AVF

SF132

F120

F122

115 SF132

F120

F100

PN16 CC752S-GM

3000

F

15 20 25 30 16 22 28

15

1 1 2,4 1052,4 4 4 2,4 2,4 0,8 0,8 1,8 1,8 4 4 2,7 2,7 0,9 0,9 2 2 4 4 2 2

2000

7 106 1,5 2 150 200 300 400 500

1 0,01

SF132

)15DN 15

15 15 4

F230

0,15 0,2 0,3 0,16 0,25

[m3/h]0,40 0,63 ( kvs 0,25 0,16

PN6 EN-JL 1040

10 10

5000 7000 10 1,5 2

F130

[m3/h] 0,1

7 7

1

SF132

[bar]

kvs

5 5

2 1,5 1 0,7 0,5 2000 1000 500 300 200 20 10 7 5 3 2

& pv [kPa] / kv

4 3000 0,7

SF132

[kg/dm3]

SF132

%p

SF132

4

! t [K] " Q [kW] 1 0,7 1,5 2 3 § Q [kcal/h] 400 500 700 1000 1500 2000 0,1 0,2 0,3 0,4 0,5 $ V 0,15 [kcal/h]

0,5

2500

500

2000

A

1 1 2 1,6 ?

? 0,7 0,7

1,5 1,2 ?

[1]

[3]

[2]

SAUTER CASE ValveDim mobile app With the new CASE ValveDim mobile app, finding the right parts and the ideal valve/actuator combinations is impressively convenient and very efficient: Intuitive operation makes it easier to search for individual products and combine them. Selected valve/actuator combinations can be stored in projects. Personal

[3]

lists with valve/actuator combinations can be exported from the app as a project table in PDF format so that they can be shared with contacts. What’s more, CASE ValveDim can also be used offline.

Right of amendment reserved © 2024 Fr. Sauter AG

129


Valve specification – manual calculation Here you will find all the necessary information for the manual valve specification. Variables, constants and formulas

[1]

Variable Description

Value

V̇

Volume flow

Q̇ to

Supplied heat per unit of time (heat flow)

Unit

Q̇ from Supplied heat per unit of time (heat flow) Temperature difference Specific thermal capacity of water Density of water

Supposition:

Pressure difference across the valve Calculated flow rate for the valve Actual flow rate for the valve at nominal stroke, selected according to table or chart

Calculation formula for kv

[2]

kv = V̇·

1 bar Δpv

Diagram

[3]

[4]

Calculations The following are given:

1000

Q̇ to = 70 kW ≈ 250 000 kJ/h Δt = 20 K

Δpv = 45 mbar = 4.5 kPa (corresponds to 450 mm water column) To be found:

100

V̇, kv Approximate calculation of V̇ Assumption: Q̇ to = Q̇ from

10

Q̇ to = Q̇ from = V̇ · cw · Δt · ρw Q̇ to

V̇  =

3

V̇  =

1

cw · Δt · ρw

70

1.164 · 10 · 20 · 1 000 –3

·

kW·(kg·K)·m3

kWh·K·kg·h

≈ 3 m3/h

Calculation of Kv kv = 3 m3/h ·

0.1

1 bar 0.045 bar

≈ 14.1 m3/h

Determination of flow rate Determination of kv from the diagram kvs = 16 m3/h

0.01 10

100 35.2

1000

10 000

100 000

45

Example plotted: Given are the volume flow (3 m³/h) and a desired Δpv of 45 mbar, which results in a Kv value of 14.1 m³/h. The Kvs values entered are deliverable values. Selected: A valve with kvs = 16 m³/h, which results in a pressure difference Δpv of 35.2 mbar.

130

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Smart actuators

AKM 115SA: Smart Actuator for ball valve Features • Smart Actuator as an intelligent IoT solution for autonomous control of heating and air-conditioning

applications in smart buildings • Ready-made HVAC standard applications enable efficient installation and commissioning of small systems • Applications are selected from the library via smartphone app and installed on the Smart Actuator • BACnet, Bluetooth LE and WLAN interface for flexible system integration • Commissioning, parameterisation and remote access to the system are conveniently carried out via a

AKM115SAF232

smartphone app As an IoT device, the cloud connection for remote access takes place via MQTT using TLS encryption • • Extensive diagnostic data from the actuator enables predictive maintenance of installations • Enables creation of Smart Actuator networks with distributed intelligence

V

• Optionally, the Smart Actuator can be used flexibly in BA networks due to free programmability via

CASE Suite • Real-time clock for calendar functions and time programmes • Two universal I/Os for connecting external sensors and actuators • Direct connection of a room operating unit • Flexibly expandable with up to two Smart Actuator SAIO 100 I/O modules for comprehensive control

tasks • Pre-assembled cables, with colour- and mechanically-coded connectors, allow fast and error-free wiring • Fitting without tools using a bayonet ring made of glass-fibre reinforced plastic • BLDC motor technology enables extensive diagnostic functions • Intelligent angle of rotation adaptation and detection incl. feedback signal • Electronic, torque-dependent cut-off

Smart Actuator app

• Gear unit can be disengaged for manual adjustment • For operating the 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI and BKTA, as

well as 6-way ball valve B2KL Technical data Power supply

Power supply

24 VAC, −10%/+20%, 50…60 Hz 24 VDC, −10%/+20%

Surge-voltage resistance Rotational torque Holding torque1) Angle of rotation Response time Running time for 90° Characteristic Operating noise (unloaded)

500 V (EN 60730) 8 Nm 8 Nm 90° 200 ms 35/60/120 sec. Linear, (inverse) equal percentage, (inverse) quadratic, free characteristic < 30 dB (A)

Media temperature2) Ambient temperature Ambient humidity Storage and transport temperature

Max. 100 °C −10…55 °C 5…85% rh, no condensation −20…70 °C

Parameters

Ambient conditions

1) 2)

Holding torque energised and de-energised At media temperatures < 5 °C or > 100 °C, appropriate accessory must be used

Right of amendment reserved © 2024 Fr. Sauter AG

131


Valves, control valves, dampers, actuators | Smart actuators Inputs/outputs

Type of inputs

Number of universal I/O Analogue input U Analogue input I

Ni1000 Pt1000 Resistance Analogue output U

2 0…10 V (Ri = 100 kΩ, ±0.05 V) 4…20 mA (with ext. resistor 500 Ω or accessory 053060311**) Closed: ≤ 1 VDC, 1 mA Open: ≥ 4 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 200…3000 Ω 0…10 V (±0.1 V)

BACnet data point objects BACnet client links Control Active COV subscription Time programmes Calendar

Max. 100 (from firmware 1.1.0b58) 16 6 loops 64 4 (Schedule) 3 (Calendar)

Processor RAM (memory) Flash

ARM Cortex-M7 (528 MHz) 1024 kB 2 × 16 MB external, for data and system 128-bit AES Via CASE Engine or mobile app Zephyr 100 ms For commissioning and maintenance Via MQTT to IoT hub For time programmes and calendars

Digital input3)

Type of output Function

V

Dynamic objects

Architecture

Flash encryption Application data Operating system Cycle time Mobile app Cloud Real-time clock Interfaces, communication

RS-485 A connection4)

RS-485 B connection5)

Bluetooth

WLAN Indicator/display

Communication protocol Connection Termination/Pull-Up/Pull-Down Communication protocol Use Connection Termination Version Range Radiation Standard LED indicator

BACnet MS/TP, ¼ load 2 × 3-pin connector, coded, daisy chain Internal, switchable via software SLC master 2 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, switchable via software BLE 4.2 < 10 m 4 mW IEEE 802.11 b/g 2 status LEDs (green/red and blue)

Construction

Fitting position

Housing material

Connections at the bottom or side, not at the top 168 × 137 × 74 mm 0.7 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS

Type of protection Protection class

IP54 (EN 60529) III (IEC 60730-1)

Dimensions W × H × D Weight Housing

Standards, directives

3) 4) 5)

132

Switching thresholds: 2.28 V (0 to 1) and 2.69 V (1 to 0) or 2.19 kΩ (0 to 1) and 2.69 kΩ (1 to 0) Not electrically isolated Not electrically isolated

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Smart actuators

CE/UKCA conformity6)

Environment class RED 2014/53/EU (CE)

3K3 (IEC 60721) EN 60730-1:2011 EN 60730-2-14:1997 + A1:2001, A11:2005; A2:2008 EN 62479:2010 EN 301 489-1 V1.9.2 EN 61000-6-2:2005; AC:2005 EN 61000-6-3:2007 + A1:2011; AC 2012 EN 300 328 V2.2.2 See RED EN IEC 63000

RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

EN IEC 63000

Overview of types Type

Features

AKM115SAF232 Smart Actuator for ball valve, RS-485

A

V

Power consumption

Max. 5 W / 10 VA (without peripherals)

Power consumption: Without connected peripheral devices (room operating units, sensors, actuators or I/O modules)

Accessories Type

Description

SAIO100F020

I/O module, 5 × UI/AO, 3 × relay

0510420001

Adaptor required when temperature of the medium > 100 °C

0510240011

Adaptor required when temperature of the medium < 5 °C

05393601000

Dummy plug spare part set IP54

EY-PS031F011

Power supply unit, 110…240 VAC / 24 VDC, 1.25 A, 30 W, DIN rail mounting

EY-PS031F021

Power supply unit, 110…240 VAC / 24 VDC, 2.5 A, 60 W, DIN rail mounting

EY-PS031F041

Power supply unit, 110…240 VAC / 24 VDC, 4 A, 100 W, DIN rail mounting

A

6)

Order the device cables separately; see the section entitled “Accessories − power and connecting cables”

Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

133


Valves, control valves, dampers, actuators | Smart actuators

AVM 115SA: Smart Actuator for 2- and 3-way valves Features • Smart Actuator as an intelligent IoT solution for autonomous control of heating and air-conditioning

applications in smart buildings Ready-made HVAC standard applications enable efficient installation and commissioning of small systems • • Applications are selected from the library via smartphone app and installed on the Smart Actuator

AVM115SAF232

• BACnet, Bluetooth LE and WLAN interface for flexible system integration • Commissioning, parameterisation and remote access to the system are conveniently carried out via a

smartphone app As an IoT device, the cloud connection for remote access takes place via MQTT using TLS encryption • • Extensive diagnostic data from the actuator enables predictive maintenance of installations • Enables creation of Smart Actuator networks with distributed intelligence

V

• Optionally, the Smart Actuator can be used flexibly in BA networks due to free programmability via

CASE Suite • Real-time clock for calendar functions and time programmes • Two universal I/Os for connecting external sensors and actuators • Direct connection of a room operating unit • Flexibly expandable with up to two Smart Actuator SAIO 100 I/O modules for comprehensive control

tasks • Pre-assembled cables, with colour- and mechanically-coded connectors, allow fast and error-free wiring • Toolless assembly by means of automatic valve stem connection and brass cap nut • BLDC motor technology enables extensive diagnostic functions

Smart Actuator app

• Intelligent stroke adaptation and detection incl. feedback signal • Electronic, torque-dependent cut-off • Gear unit can be disengaged for manual adjustment • For activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series

Technical data Power supply

Power supply

24 VAC, −10%/+20%, 50…60 Hz 24 VDC, −10%/+20%

Surge-voltage resistance Actuating power Actuator stroke Response time Running time Characteristic Operating noise (unloaded)

500 V (EN 60730) 500 N 0...10 mm 200 ms 35/60/120 sec. Linear, (inverse) equal percentage, (inverse) quadratic, free characteristic < 30 dB (A)

Media temperature1) Ambient temperature Ambient humidity Storage and transport temperature

Max. 100 °C −10…55 °C 5…85% rh, no condensation −20…70 °C

Number of universal I/O

2

Parameters

Ambient conditions

Inputs/outputs

1)

134

At media temperature > 100 °C, appropriate accessory must be used

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Smart actuators Type of inputs

Analogue input U Analogue input I

Ni1000 Pt1000 Resistance Analogue output U

0…10 V (Ri = 100 kΩ, ±0.05 V) 4…20 mA (with ext. resistor 500 Ω or accessory 053060311**) Closed: ≤ 1 VDC, 1 mA Open: ≥ 4 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 200…3000 Ω 0…10 V (±0.1 V)

BACnet data point objects BACnet client links Control Active COV subscription Time programmes Calendar

Max. 100 (from firmware 1.1.0b58) 16 6 loops 64 4 (Schedule) 3 (Calendar)

Processor RAM (memory) Flash

ARM Cortex-M7 (528 MHz) 1024 kB 2 × 16 MB external, for data and system 128-bit AES Via CASE Engine or mobile app Zephyr 100 ms For commissioning and maintenance Via MQTT to IoT hub For time programmes and calendars

Digital input2)

Type of output Function

Dynamic objects

V

Architecture

Flash encryption Application data Operating system Cycle time Mobile app Cloud Real-time clock Interfaces, communication

RS-485 A connection3)

RS-485 B connection4)

Bluetooth

WLAN Indicator/display

Communication protocol Connection Termination/Pull-Up/Pull-Down Communication protocol Use Connection Termination Version Range Radiation Standard LED indicator

BACnet MS/TP, ¼ load 2 × 3-pin connector, coded, daisy chain Internal, switchable via software SLC master 2 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, switchable via software BLE 4.2 < 10 m 4 mW IEEE 802.11 b/g 2 status LEDs (green/red, blue)

Construction

Fitting position

Housing material

Connections at the bottom or side, not at the top 168 × 119 × 74 mm 0.7 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS

Type of protection Protection class Environment class

IP54 (EN 60529) III (IEC 60730-1) 3K3 (IEC 60721)

Dimensions W × H × D Weight Housing

Standards, directives

2) 3) 4)

Switching thresholds: 2.28 V (0 to 1) and 2.69 V (1 to 0) or 2.19 kΩ (0 to 1) and 2.69 kΩ (1 to 0) Not electrically isolated Not electrically isolated

Right of amendment reserved © 2024 Fr. Sauter AG

135


Valves, control valves, dampers, actuators | Smart actuators CE/UKCA conformity5)

RED 2014/53/EU (CE)

RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

EN 60730-1:2011 EN 60730-2-14:1997 + A1:2001, A11:2005; A2:2008 EN 62479:2010 EN 301 489-1 V1.9.2 EN 61000-6-2:2005; AC:2005 EN 61000-6-3:2007 + A1:2011; AC 2012 EN 300 328 V2.2.2 See RED EN IEC 63000 EN IEC 63000

Overview of types Type

V

Features

Power consumption

AVM115SAF232 Smart Actuator for globe valves, RS-485, BACnet Max. 5 W / 10 VA (without peripherals) MS/TP

A

Power consumption: Without connected peripheral devices (room operating units, sensors, actuators or I/O modules)

Accessories Type

Description

SAIO100F020

I/O module, 5 × UI/AO, 3 × relay

0372249001

Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50

0372273001

Adapter for Siemens valve VVG/VXG 44, 48

05393601000

Dummy plug spare part set IP54

EY-PS031F011

Power supply unit, 110…240 VAC / 24 VDC, 1.25 A, 30 W, DIN rail mounting

EY-PS031F021

Power supply unit, 110…240 VAC / 24 VDC, 2.5 A, 60 W, DIN rail mounting

EY-PS031F041

Power supply unit, 110…240 VAC / 24 VDC, 4 A, 100 W, DIN rail mounting

A

5)

136

Order the device cables separately; see the section entitled “Accessories − power and connecting cables”

Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Smart actuators

ASM 115SA: Smart Actuator for ventilation dampers Features • Smart Actuator as an intelligent IoT solution for autonomous control of heating and air-conditioning

applications in smart buildings Ready-made HVAC standard applications enable efficient installation and commissioning of small systems • • Applications are selected from the library via smartphone app and installed on the Smart Actuator

ASM115SAF232

• BACnet, Bluetooth LE and WLAN interface for flexible system integration • Commissioning, parameterisation and remote access to the system are conveniently carried out via a

smartphone app • As an IoT device, the cloud connection for remote access takes place via MQTT using TLS encryption • Extensive diagnostic data from the actuator enables predictive maintenance of installations • Enables creation of Smart Actuator networks with distributed intelligence

V

• Optionally, the Smart Actuator can be used flexibly in BA networks due to free programmability via

CASE Suite • Real-time clock for calendar functions and time programmes • Two universal I/Os for connecting external sensors and actuators • Direct connection of a room operating unit • Flexibly expandable with up to two Smart Actuator SAIO 100 I/O modules for comprehensive control

tasks • Pre-assembled cables, with colour- and mechanically-coded connectors, allow fast and error-free wiring • Easy fitting using self-centring spindle adapters

Smart Actuator app

• BLDC motor technology enables extensive diagnostic functions • Intelligent angle of rotation adaptation and detection incl. feedback signal • Electronic, torque-dependent cut-off • Gear unit can be disengaged for manual adjustment

Technical data Power supply

Power supply

24 VAC, −10%/+20%, 50…60 Hz 24 VDC, −10%/+20%

Surge-voltage resistance Rotational torque Holding torque1) Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Response time Running time for 90° Characteristic Operating noise (unloaded)

500 V (EN 60730) 10 Nm 10 Nm Max. 95° Ø 8...16 mm, □ 6.5...12.5 mm Max. 300 HV 200 ms 35/60/120 sec. Linear, (inverse) equal percentage, (inverse) quadratic, free characteristic < 30 dB (A)

Ambient temperature Ambient humidity Storage and transport temperature

−10…55 °C 5…85% rh, no condensation −20…70 °C

Number of universal I/O

2

Parameters

Ambient conditions

Inputs/outputs

1)

Holding torque energised and de-energised

Right of amendment reserved © 2024 Fr. Sauter AG

137


Valves, control valves, dampers, actuators | Smart actuators Type of inputs

Analogue input U Analogue input I

Ni1000 Pt1000 Resistance Analogue output U

0…10 V (Ri = 100 kΩ, ±0.05 V) 4...20 mA (with ext. resistor 500 Ω or accessory 053060311**) Closed: ≤ 1 VDC, 1 mA Open: ≥ 4 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 200…3000 Ω 0…10 V (±0.1 V)

BACnet data point objects BACnet client links Control Active COV subscription Time programmes Calendar

Max. 100 (from firmware 1.1.0b58) 16 6 loops 64 4 (Schedule) 3 (Calendar)

Processor RAM (memory) Flash

ARM Cortex-M7 (528 MHz) 1024 kB 2 × 16 MB external, for data and system 128-bit AES Via CASE Engine or mobile app Zephyr 100 ms For commissioning and maintenance Via MQTT to IoT hub For time programmes and calendars

Digital input2)

Type of output Function

Dynamic objects

V

Architecture

Flash encryption Application data Operating system Cycle time Mobile app Cloud Real-time clock Interfaces, communication

RS-485 A connection3)

RS-485 B connection4)

Bluetooth

WLAN Indicator/display

Communication protocol Connection Termination/Pull-Up/Pull-Down Communication protocol Use Connection Termination Version Range Radiation Standard LED indicator

BACnet MS/TP, ¼ load 2 × 3-pin connector, coded, daisy chain Internal, switchable via software SLC master 2 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, switchable via software BLE 4.2 < 10 m 4 mW IEEE 802.11 b/g 2 status LEDs (green/red, blue)

Construction

Fitting position

Housing material

Connections at the bottom or side, not at the top 168 × 62 × 74 mm 0.7 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS

Type of protection Protection class Environment class

IP54 (EN 60529) III (IEC 60730-1) 3K3 (IEC 60721)

Dimensions W × H × D Weight Housing

Standards, directives

2) 3) 4)

138

Switching thresholds: 2.28 V (0 to 1) and 2.69 V (1 to 0) or 2.19 kΩ (0 to 1) and 2.69 kΩ (1 to 0) Not electrically isolated Not electrically isolated

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Smart actuators CE/UKCA conformity5)

RED 2014/53/EU (CE)

RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

EN 60730-1:2011 EN 60730-2-14:1997 + A1:2001, A11:2005; A2:2008 EN 62479:2010 EN 301 489-1 V1.9.2 EN 61000-6-2:2005; AC:2005 EN 61000-6-3:2007 + A1:2011; AC 2012 EN 300 328 V2.2.2 See RED EN IEC 63000 EN IEC 63000

Overview of types Type

Features

ASM115SAF232 Smart Actuator for dampers, RS-485, BACnet MS/TP

A

Power consumption

V

Max. 5 W / 10 VA (without peripherals)

Power consumption: Without connected peripheral devices (room operating units, sensors, actuators or I/O modules)

Accessories Type

Description

SAIO100F020

I/O module, 5 × UI/AO, 3 × relay

0361977002

Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115

0372300001

Torsion protection, long (230 mm)

05393601000

Dummy plug spare part set IP54

0372301001

Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.

0372320001

Hexagon key as visualisation for position indicator

EY-PS031F011

Power supply unit, 110…240 VAC / 24 VDC, 1.25 A, 30 W, DIN rail mounting

EY-PS031F021

Power supply unit, 110…240 VAC / 24 VDC, 2.5 A, 60 W, DIN rail mounting

EY-PS031F041

Power supply unit, 110…240 VAC / 24 VDC, 4 A, 100 W, DIN rail mounting

A

5)

Order the device cables separately; see the section entitled “Accessories − power and connecting cables”

Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

139


Valves, control valves, dampers, actuators | Smart actuators

SAIO 100: I/O module for smart actuators Features • Extends the inputs and outputs of the smart actuator for extensive control tasks • Connection of sensors or actuators via five integrated universal inputs and outputs

SAIO100F010

• Three changeover relays for fan or pump control • Connection to the smart actuator via plug-in I/O module cable (SLC) • Direct connection of a room operating unit • Housing according to IP54 enables use without cabinet • Separate 24 V power supply for sensors and actuators with total power requirement up to 1 A

Technical data

V

Power supply

Power supply

24 VAC/DC (via smart actuator) 24 VAC/DC for terminals T4...T7 (via separate power supply) 1.2 VA at 24 VDC (without sensors and actuators)

Power consumption

Ambient conditions

Ambient temperature Ambient humidity Storage and transport temperature

−10…55 °C 5...95% rh, no condensation −20…70 °C

Number of universal I/O Number of relays Rating

Ni1000 Pt1000 Resistance Analogue output U

5 (+1 from smart actuator) 3 10 A (resistive) 5 A (inductive) Change-over 0…10 V (Ri = 100 kΩ, ±0.05 V) 4...20 mA (with ext. resistor 500 Ω) Closed: 1 VDC, 1 mA Open: > 2 VDC −20…100 °C (DIN 43760) −20…100 °C (IEC 751) 100…2500 Ω (±25 Ω) 0…10 V (±0.4 V)

Communication protocol Use Connection Termination LED indicator

SLC slave 1 × I/O module, 1 × ecoUnit 5-pin connector, coded Internal, DIP switch 1 status LED (green, red)

Fitting

Housing material

On DIN rail 35 × 7.5/15 (EN 60715) or on supplied rail 200 × 107 × 55 mm 0.5 kg Lower section black, upper section yellow Flame retardant plastic, PC/ABS

Type of protection Protection class Environment class

IP54 (EN 60529) III (IEC 60730-1) 3K3 (IEC 60721)

Inputs/outputs

Type of inputs

Type of output

Type Analogue input U Analogue input I Digital input

Interfaces, communication

RS-485 connection

Indicator/display Construction

Dimensions W × H × D Weight Housing

Standards, directives

140

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Smart actuators CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

EN 61000-6-1, EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14

Overview of types Type

Features

SAIO100F020

I/O module for smart actuator, 6 pcs. UI/AO, 3 Max. 1.7 W / 3.6 VA (without peripherals) pcs. relay

Power consumption

Accessories Type

Description

05393601000

Dummy plug spare part set IP54

A

For power cables or connecting cables (053060*****), see order code in PDS 53.950

V

Right of amendment reserved © 2024 Fr. Sauter AG

141


Valves, control valves, dampers, actuators | Smart actuators

Power and connecting cables for Smart Actuators Features • For connection to the power supply, to cable temperature sensors, and for connecting the actuators • Pre-assembled cables in various lengths from 0.5 to 30 metres • Robust XLPE sheathed cables

1)

With mechanically and colour-coded connectors

• Silicone- and halogen-free • Can also be laid under plaster, in and on masonry and non-reinforced concrete

2)

Technical data Parameters

V

Bending radius

Min. 10 × outer diameter for fixed installation

Ambient temperature

Max. +70 °C

Material

Silicone- and halogen-free according to EN 60754-1/2 Flame retardant according to EN 60332-1-2 Conductor stranded bare copper wires, open ends ultrasonically welded Black (plug and sheath)

Ambient conditions

Construction

Type Colour Standards, directives

CE/UKCA conformity according to

RoHS Directive 2011/65/EU & 2015/863/EU Restriction of Hazardous Substances Regulations 2012 (RoHS UKCA)

Overview of types Type

Cable type

Cable length

Connector type

05306020000

24 V power supply, open cable end

0.5 m

2-pin

05306020001

24 V power supply, open cable end

1.0 m

2-pin

05306020005

24 V power supply, open cable end

5.0 m

2-pin

05306020010

24 V power supply, open cable end

10.0 m

2-pin

05306020020

24 V power supply, open cable end

20.0 m

2-pin

05306020030

24 V power supply, open cable end

30.0 m

2-pin

05306020201

24 V power supply, Y-connector

1.0 m

2-pin

05306031001

I/O signals, open cable end, 3-core

1.0 m

3-pin

05306031005

I/O signals, open cable end, 3-core

5.0 m

3-pin

05306031010

I/O signals, open cable end, 3-core

10.0 m

3-pin

05306031020

I/O signals, open cable end, 3-core

20.0 m

3-pin

05306031030

I/O signals, open cable end, 3-core

30.0 m

3-pin

05306031105

I/O signals (I), open cable end, 3-core

5.0 m

3-pin

05306032001

I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 1.0 m ready to plug in

3-pin

05306032005

I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 5.0 m ready to plug in

3-pin

05306032010

I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 10.0 m ready to plug in

3-pin

1) 2)

142

XLPE: Cross-linked polyethylene National regulations must be observed

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Smart actuators Type

Cable type

05306032020

I/O signals, cable temperature sensor Ni1000 (−35...100 °C) 20.0 m ready to plug in

3-pin

05306032101

I/O signals, cable temperature sensor Pt1000 (−50...180 °C) 1.0 m ready to plug in

3-pin

05306032105

I/O signals, cable temperature sensor Pt1000 (−50...180 °C) 5.0 m ready to plug in

3-pin

05306034000

RS-485, daisy chain, open cable end, 3-core

0.5 m

3-pin

05306034001

RS-485, daisy chain, open cable end, 3-core

1.0 m

3-pin

05306034005

RS-485, daisy chain, open cable end, 3-core

5.0 m

3-pin

05306034010

RS-485, daisy chain, open cable end, 3-core

10.0 m

3-pin

05306034020

RS-485, daisy chain, open cable end, 3-core

20.0 m

3-pin

05306034030

RS-485, daisy chain, open cable end, 3-core

30.0 m

3-pin

05306034100

RS-485, daisy chain, connection of two actuators, ready to plug in

0.5 m

3-pin

05306034101

RS-485, daisy chain, connection of two actuators, ready to plug in

1.0 m

3-pin

05306034105

RS-485, daisy chain, connection of two actuators, ready to plug in

5.0 m

3-pin

05306034110

RS-485, daisy chain, connection of two actuators, ready to plug in

10.0 m

3-pin

05306034120

RS-485, daisy chain, connection of two actuators, ready to plug in

20.0 m

3-pin

05306034130

RS-485, daisy chain, connection of two actuators, ready to plug in

30.0 m

3-pin

05306051000

I/O signals, open cable end, 3-core

0.5 m

5-pin

05306051001

I/O signals, open cable end, 3-core

1.0 m

5-pin

05306051005

I/O signals, open cable end, 3-core

5.0 m

5-pin

05306051010

I/O signals, open cable end, 3-core

10.0 m

5-pin

05306051020

I/O signals, open cable end, 3-core

20.0 m

5-pin

05306051030

I/O signals, open cable end, 3-core

30.0 m

5-pin

05306053000

I/O signals, connection of actuator with I/O module SAIO100, 0.5 m ready to plug in

5-pin

05306053001

I/O signals, connection of actuator with I/O module SAIO100, 1.0 m ready to plug in

5-pin

05306053005

I/O signals, connection of actuator with I/O module SAIO100, 5.0 m ready to plug in

5-pin

05306053010

I/O signals, connection of actuator with I/O module SAIO100, 10.0 m ready to plug in

5-pin

05306053020

I/O signals, connection of actuator with I/O module SAIO100, 20.0 m ready to plug in

5-pin

05306053030

I/O signals, connection of actuator with I/O module SAIO100, 30.0 m ready to plug in

5-pin

05306053500

SLC connection, open cable end, 5-core

0.5 m

5-pin

05306053501

SLC connection, open cable end, 5-core

1.0 m

5-pin

05306053505

SLC connection, open cable end, 5-core

5.0 m

5-pin

05306053510

SLC connection, open cable end, 5-core

10.0 m

5-pin

05306053520

SLC connection, open cable end, 5-core

20.0 m

5-pin

05306053530

SLC connection, open cable end, 5-core

30.0 m

5-pin

A

Cable length

Connector type

V

Other models and lengths on request. For order numbers, see order code below

Example Order no. 05306020000

Designation Power cable, 2-pin, 24 V power supply, open cable end, 2-core, 0.5 m

Right of amendment reserved © 2024 Fr. Sauter AG

143


Valves, control valves, dampers, actuators | Smart actuators Order code (1) Product type 053060…

A

(2) Model …200…

(3) Cable length …00

Not all theoretically possible combinations can be ordered

(1) Product type Order no. 053060…

Type Power and connecting cables for Smart Actuator

(2) Model

V

Order no. …200… …201… …202… …310… …510… …311…

Plug 2-pin 2-pin 2-pin 3-pin 5-pin 3-pin

…320…

3-pin

…321…

3-pin

…340… …341… …530…

3-pin 3-pin 5-pin

…535…

5-pin

Function and connection 24 V power supply, open cable end 24 V power supply, daisy chain 24 V power supply, Y-connector I/O signals, 3-core open cable end I/O signals for current measurement with integrated 500 Ω resistor, 3-core open cable end I/O signals, cable temperature sensor Ni1000 (−35...100 °C), ready to plug in I/O signals, cable temperature sensor Pt1000 (−50...180 °C), ready to plug in RS-485, daisy chain, 3-core open cable end RS-485, daisy chain, connection of two actuators, ready to plug in I/O signals, connection of actuator with I/O module SAIO100, ready to plug in SLC connection, 5-core open cable end

(3) Cable length Order no.

3)

144

Length (m) …00 0.5 …01 1.0 …05 5.0 …10 10.0 …20 20.0 …30 30.0

Conductor cross-section (mm²)3) 0.5 / 0.75 0.5 / 0.75 0.5 / 0.75 0.75 0.75 0.75

Conductor cross-section depends on cable type and cable length

Right of amendment reserved © 2024 Fr. Sauter AG


Unit valves In combination with thermal actuators, unit valves are used to control radiators, air reheaters and recoolers as well as fan coil units.

Overview of unit valves

Type designation

VUL

BUL

VUT

BUT

BXL

Application Single-room control Chilled ceiling, underfloor heating Radiator Underfloor device

• • • •

• • • •

• • • •

• • • •

• • • •

• − 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 146

− • 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 149

• − 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 154

− • 10...20 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 156

− • 25...40 PN 16 AXM 217(S) AXT 301 AXS 315S AXF 217S Page 159

Version 2-way 3-way Nominal diameter (DN) Nominal pressure Combination options with actuator Further information

Right of amendment reserved © 2024 Fr. Sauter AG

145


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

VUL: 2-way valve, PN 16 Features • Control of heating zones, air secondary treatment units and fan coil units in combination with unit valve

actuators AXM 217(S), AXT 301 or AXS 315S • Flat-sealing standard version or version with clamping-ring screw fitting for pipe Ø 15 mm with DN 10 • Valve with male thread as per DIN EN ISO 228-1, class B • Stuffing box can be replaced under system pressure

VUL010F310

• Control passage A–AB is closed when the spindle is moved in • Closing procedure against the pressure • Valve body made of nickel-plated cast brass for DN 10 and gunmetal for DN 15 and DN 20 • Plug with EPDM soft seal

V

• Stainless-steel spindle • Stuffing box with double O-ring seal

Technical data Parameters

Nominal pressure Operating pressure Operating temperature Valve characteristic Valve stroke1) Leakage rate

PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Equal-percentage 4 mm 0.002% of Kvs value

Operating temperature at valve

Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)

Ambient conditions

Standards, directives

ValveDim app

Overview of types Type

Nominal diame- Kvs value ter

Connection

Weight

VUL010F340

DN 10

VUL010F330

DN 10

0.16 m³/h

G½" B

0.19 kg

0.4 m³/h

G½" B

VUL010F320

0.18 kg

DN 10

0.63 m³/h

G½" B

0.18 kg

VUL010F310

DN 10

1 m³/h

G½" B

0.18 kg

VUL010F300

DN 10

1.6 m³/h

G½" B

0.18 kg

VUL015F310

DN 15

2.5 m³/h

G¾" B

0.28 kg

VUL015F300

DN 15

3.5 m³/h

G¾" B

0.28 kg

VUL020F300

DN 20

4.5 m³/h

G1" B

0.33 kg

VUL010F630

DN 10

0.4 m³/h

Clamping ring vers. Ø15 mm

0.18 kg

VUL010F620

DN 10

0.63 m³/h

Clamping ring vers. Ø15 mm

0.18 kg

VUL010F610

DN 10

1 m³/h

Clamping ring vers. Ø15 mm

0.18 kg

VUL010F600

DN 10

1.6 m³/h

Clamping ring vers. Ø15 mm

0.18 kg

1)

146

The valve stroke is limited by the actuator

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Accessories Type

Description

0378133010

1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜

0378133015

1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½

0378133020

1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾

0378134010

1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½

0378134015

1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾

0378134020

1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1

0378135010

1 clamping-ring screw fitting for pipe Ø 15 mm, DN 10

0378145015

1 clamping-ring screw fitting for pipe Ø 15 mm, DN 15, flat-sealing, G¾

0378145020

1 clamping-ring screw fitting for pipe Ø 22 mm, DN 20, flat-sealing, G1

0378128001

Stuffing box for VUL valves, can be replaced under pressure

Combination of VUL with electric actuators

/ /

V

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences with motorised actuators Actuator

AXM217F200

AXM217F202

Page

171

171

AXM217SF402 AXM217SF404 173

Voltage

230 VAC

24 VAC/DC

24 VAC/DC

Control signal

2-/3-point

2-/3-point

0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA

Running time

13 s/mm

13 s/mm

8 s/mm

Closes against the pressure VUL010F340 VUL010F330 VUL010F320 VUL010F630 VUL010F620

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

4.0

4.0

4.0

VUL010F310 VUL010F300 VUL010F610 VUL010F600

3.8

3.8

3.8

VUL015F310 VUL015F300 VUL020F300

1.1

1.1

1.1

Cannot be used to close with the pressure

Right of amendment reserved © 2024 Fr. Sauter AG

147


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Pressure differences with thermal actuators Actuator

AXT301F102 AXT301F112 164

AXT301F210

AXT301F212

Page

AXT301F100 AXT301F110 164

164

164

164

164

Voltage

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

Control signal

2-point

2-point

2-point

2-point

2-point

2-point

Running time

48 s/mm

48 s/mm

48 s/mm

48 s/mm

52 s/mm

52 s/mm

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

VUL010F340 VUL010F330 VUL010F320 VUL010F630 VUL010F620

4.0

6.0

4.0

6.0

VUL010F310 VUL010F300 VUL010F610 VUL010F600

4.0

4.0

4.0

VUL015F310 VUL015F300 VUL020F300

1.1

1.1

1.1

Closes against the pressure

V

AXT301HF110

AXT301HF112

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

4.0

4.0

4.0

6.0

4.0

6.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

1.1

1.1

1.1

1.1

1.1

1.1

1.1

Cannot be used to close with the pressure

Pressure differences with thermal, continuous actuators Actuator Page

AXS315SF102 167

AXS315SF202 167

Voltage

24 VAC/DC

24 VAC/DC

Control signal

0…10 V

0…10 V

Running time

30 s/mm

30 s/mm

Closes against the pressure

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

VUL010F340 VUL010F330 VUL010F320 VUL010F630 VUL010F620

4.0

6.0

4.0

VUL010F310 VUL010F300 VUL010F610 VUL010F600

4.0

4.0

4.0

VUL015F310 VUL015F300 VUL020F300

1.1

1.1

1.1

Cannot be used to close with the pressure

148

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

BUL: 3-way unit valve, PN 16 Features • Ideally suited for unit valve actuators AXM 217(S), AXT 301 and AXS 315S • Flat-sealing standard version or version with clamping-ring screw fitting for pipe Ø 15 mm with DN 10 • Valve with male thread as per DIN EN ISO 228-1, class B • Special model for fan coil units with cast-on by-pass T-piece • Control passage A–AB is closed when the spindle is moved in • Can be used as a control valve and, thanks to its tight-sealing third passage, as a distribution valve • Nickel-plated valve body made of cast brass

BUL015F310

• Plug with EPDM soft seal for control passage and mixing passage • Stainless-steel spindle

V

• Stuffing box with double O-ring seal

Technical data Parameters

Nominal pressure Operating pressure Operating temperature Control passage valve characteristic Mixing passage valve characteristic Valve stroke Leakage rate of control passage A-AB Leakage rate of mixing passage B-AB

PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Equal-percentage Linear 3.7 mm 0.0001% of Kvs value Approx. 0.1% of Kvs value

Operating temperature at valve

Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)

BUL010F410

Ambient conditions

Standards, directives

Control valve

Overview of types

/ /

The BUL 3-way valve must not be used as a 2-way valve Kvs value: The Kvs value of the mixing passage (B-AB) is reduced by approx. 30%

Type

Nominal diame- Kvs value ter

Connection

Weight

BUL010F330

DN 10

0.4 m³/h

G½" B

0.30 kg

BUL010F320

DN 10

0.63 m³/h

G½" B

0.30 kg

BUL010F310

DN 10

1 m³/h

G½" B

0.30 kg

BUL010F300

DN 10

1.6 m³/h

G½" B

0.30 kg

BUL015F310

DN 15

2.5 m³/h

G¾" B

0.33 kg

BUL015F300

DN 15

4 m³/h

G¾" B

0.33 kg

BUL020F300

DN 20

5 m³/h

G1" B

0.36 kg

BUL010F430

DN 10

0.4 m³/h

G½" B

0.38 kg

BUL010F420

DN 10

0.63 m³/h

G½" B

0.38 kg

BUL010F410

DN 10

1 m³/h

G½" B

0.38 kg

BUL010F400

DN 10

1.6 m³/h

G½" B

0.38 kg

BUL015F410

DN 15

2.5 m³/h

G¾" B

0.42 kg

BUL015F400

DN 15

4 m³/h

G¾" B

0.42 kg

Right of amendment reserved © 2024 Fr. Sauter AG

Distribution valve

149


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Type

Nominal diame- Kvs value ter

Connection

Weight

BUL020F400

DN 20

5 m³/h

G1" B

0.50 kg

BUL010F630

DN 10

0.4 m³/h

Clamping ring vers. Ø 15 mm

0.38 kg

BUL010F620

DN 10

0.63 m³/h

Clamping ring vers. Ø 15 mm

0.38 kg

BUL010F610

DN 10

1 m³/h

Clamping ring vers. Ø 15 mm

0.38 kg

BUL010F600

DN 10

1.6 m³/h

Clamping ring

0.38 kg

A

BUL0**F4**: Version with by-pass T-piece

Accessories

V

Type

Description

0378133010

1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜

0378133015

1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½

0378133020

1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾

0378134010

1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½

0378134015

1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾

0378134020

1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1

0378135010

1 clamping-ring screw fitting for pipe Ø 15 mm, DN 10

0378145015

1 clamping-ring screw fitting for pipe Ø 15 mm, DN 15, flat-sealing, G¾

0378145020

1 clamping-ring screw fitting for pipe Ø 22 mm, DN 20, flat-sealing, G1

0378126001

Stuffing box for BUL valves

0378126002

Stuffing box for BUL valves as of manufacturing date 1501

Combination of BUL with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences with motorised actuators

150

Actuator

AXM217F200

AXM217F202

Page

171

171

AXM217SF402 AXM217SF404 173

Voltage

230 VAC

24 VAC/DC

24 VAC/DC

Control signal

2-/3-point

2-/3-point

0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA

Running time

48 s

48 s

48 s

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600

1.7

1.7

1.7

BUL015F310 BUL015F410

1.4

1.4

1.4

BUL015F300 BUL015F400

1.2

1.2

1.2

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Actuator

AXM217F200

AXM217F202

Page

171

171

AXM217SF402 AXM217SF404 173

BUL020F300 BUL020F400

1.0

1.0

1.0

As distribution valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600

1.9

1.9

1.9

BUL015F310 BUL015F300 BUL020F300 BUL015F410 BUL015F400 BUL020F400

1.2

V 1.2

1.2

Pressure differences with thermal actuators Actuator

AXT301F102 AXT301F112 164

AXT301F210

AXT301F212

Page

AXT301F100 AXT301F110 164

AXT301HF110

AXT301HF112

164

164

164

164

Voltage

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

Control signal

2-point

2-point

2-point

2-point

2-point

2-point

Running time

48 s/mm

48 s/mm

48 s/mm

48 s/mm

52 s/mm

52 s/mm

As control valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600

1.7

1.8

1.7

1.8

BUL015F310 BUL015F410

1.4

1.5

1.4

BUL015F300 BUL015F400

1.2

1.3

BUL020F300 BUL020F400

1.0

1.1

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

1.7

1.7

1.7

1.8

1.7

1.8

1.5

1.4

1.4

1.4

1.5

1.4

1.5

1.2

1.3

1.2

1.2

1.2

1.3

1.2

1.3

1.0

1.1

1.0

1.0

1.0

1.1

1.0

1.1

Right of amendment reserved © 2024 Fr. Sauter AG

151


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Actuator Page

V

AXT301F100 AXT301F110 164

As distribution valve

∆pmax [bar]

BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600

AXT301F102 AXT301F112 164

AXT301F210

AXT301F212

AXT301HF110

AXT301HF112

164

164

164

164

∆ps [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

1.9

4.0

1.9

4.0

1.9

1.9

1.9

4.0

1.9

4.0

BUL015F310 BUL015F410

1.6

2.1

1.6

2.1

1.6

1.6

1.6

2.1

1.6

2.1

BUL015F300 BUL015F400

1.4

2.1

1.4

2.1

1.4

1.4

1.4

2.1

1.4

2.1

BUL020F300 BUL020F400

1.2

2.0

1.2

2.0

1.2

1.2

1.2

2.0

1.2

2.0

Pressure differences with thermal, continuous actuators

152

Actuator Page

AXS315SF102 167

AXS315SF202 167

Voltage

24 VAC/DC

24 VAC/DC

Control signal

0…10 V

0…10 V

Running time

30 s/mm

30 s/mm

As control valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600

1.7

1.8

1.7

BUL015F310 BUL015F410

1.4

1.5

1.4

BUL015F300 BUL015F400

1.2

1.3

1.2

BUL020F300 BUL020F400

1.0

1.1

1.0

As distribution valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

BUL010F330 BUL010F320 BUL010F310 BUL010F300 BUL010F430 BUL010F420 BUL010F410 BUL010F400 BUL010F630 BUL010F620 BUL010F610 BUL010F600

1.9

4.0

1.9

BUL015F310 BUL015F410

1.6

2.1

1.6

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Actuator Page

AXS315SF102 167

AXS315SF202 167

BUL015F300 BUL015F400

1.4

2.1

1.4

BUL020F300 BUL020F400

1.1

1.2

1.2

V

Right of amendment reserved © 2024 Fr. Sauter AG

153


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

VUT: 2-way valve, PN 16 Features • Regulation of fan coil units, air secondary-treatment units, heating zones and two-pipe systems with heat

exchanger in combination with AXM 217(S), AXT 301 or AXS 315S unit valve actuators Standard version flatsealing • • Adjustable Kvs value • When the spindle is pushed in, the valve is closed • Closing procedure against the pressure

VUT015F200

• Valve with male thread as per DIN EN ISO 228-1, class B • Valve body made of cast brass • Stainless-steel spindle

V

• Plug with EPDM soft seal • Stuffing box with O-ring seal • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Operating pressure Operating temperature Valve characteristic Leakage rate

PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Almost linear ≤ 0.0001% of Kvs value

Operating temperature at valve

Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 EN 60534, page 3 Fluid group II, No CE label (article 4.3)

Kvs range

Valve stroke (mm)

Connection

Weight (kg)

Ambient conditions

ValveDim app

Standards, directives

Overview of types Type

Nominal diameter (DN)

VUT010F200

10

0.2…1.6 m³/h

3

G½ B

0.18

VUT010F210

10

0.2…1.0 m³/h

3

G½ B

0.18

VUT010F220

10

0.2…0.63 m³/h

3

G½ B

0.18

VUT015F200

15

1.0…3.5 m³/h

4

G¾ B

0.28

VUT015F210

15

0.3…2.5 m³/h

3

G¾ B

0.28

VUT020F200

20

4.5 m³/h

4

G1 B

0.33

Accessories Type

154

Description

0378133010

1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜

0378133015

1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½

0378133020

1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾

0378134010

1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½

0378134015

1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾

0378134020

1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Combination of VUT with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences with motorised actuators Actuator

AXM217F200

AXM217F202

Page

171

171

AXM217SF402 AXM217SF404 173

Voltage

230 VAC

24 VAC/DC

24 VAC/DC

Control signal

2-/3-point

2-/3-point

0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA

Laufzeit

13 s/mm

13 s/mm

8 s/mm

Closes against the pressure VUT010F200 VUT010F210 VUT010F220

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

2.5

2.5

2.5

VUT015F200 VUT015F210

1.8

1.8

1.8

VUT020F200

1.0

1.0

1.0

V

Cannot be used to close with the pressure

Pressure differences with thermal actuators Actuator

AXT301F102 AXT301F112 164

AXT301F210

AXT301F212

Page

AXT301F100 AXT301F110 164

164

164

164

164

Voltage

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

Control signal

2-point

2-point

2-point

2-point

2-point

2-point

Laufzeit

48 s/mm

48 s/mm

48 s/mm

48 s/mm

52 s/mm

52 s/mm

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

VUT010F200 VUT010F210 VUT010F220

2.3

2.3

2.3

2.3

VUT015F200 VUT015F210

1.6

1.6

1.6

VUT020F200

0.9

0.9

0.9

Closes against the pressure

AXT301HF110

AXT301HF112

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

2.3

2.3

2.3

2.3

2.3

2.3

1.6

1.6

1.6

1.6

1.6

1.6

1.6

0.9

0.9

0.9

0.9

0.9

0.9

0.9

Cannot be used to close with the pressure

Pressure differences with thermal, continuous actuators Actuator Page

AXS315SF102 167

AXS315SF202 167

Voltage

24 VAC/DC

24 VAC/DC

Control signal

0…10 V

0…10 V

Laufzeit

30 s/mm

30 s/mm

Closes against the pressure

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

VUT010F200 VUT010F210 VUT010F220

2.5

2.5

2.5

VUT015F200 VUT015F210

1.8

1.8

1.8

VUT020F200

1.0

1.0

1.0

Cannot be used to close with the pressure

Right of amendment reserved © 2024 Fr. Sauter AG

155


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

BUT: 3-way unit valve, PN 16 (el.) Features • Regulation of fan coil units, air secondary-treatment units, heating zones and two-pipe systems with heat

exchanger in combination with AXM 217(S), AXT 301 or AXS 315S unit valve actuators Standard version flatsealing • • Special model for fan coil units with cast-on by-pass T-piece • Control passage closed when spindle is pushed in • Used as a control valve • Valve with male thread as per DIN EN ISO 228-1, class B

BUT015F210

• Valve body in cast brass • Stainless-steel spindle

V

• Plug with soft seal made of EPDM for control passage and mixing passage • Stuffing box with O-ring seal • Water quality as per VDI 2035

Technical data Parameters

BUT015F400

Nominal pressure Operating pressure Operating temperature Control passage valve characteristic Mixing passage valve characteristic Leakage rate of control passage A-AB Leakage rate of mixing passage B-AB

PN 16 Max. 16 bar (up to 120 °C) 2…120 °C Almost linear Linear (not reduced) 0.0001% of Kvs Approx. 0.1% of Kvs

Operating temperature at valve

Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)

Ambient conditions

Standards, directives

Overview of types

/

The BUT control valve must not be used as a through valve or diverting valve; mixing passage is not reduced.

Type

ValveDim app

156

Nominal diameter (DN)

Valve stroke (mm)

Kvs value

Connection

Weight (kg)

BUT010F200

10

3

1 m³/h

G½ B

0.3

BUT010F400

10

3

1.6 m³/h

G½ B

0.38

BUT010F410

10

3

1 m³/h

G½ B

0.38

BUT010F420

10

3

0.63 m³/h

G½ B

0.38

BUT015F210

15

3

2.5 m³/h

G¾ B

0.33

BUT015F410

15

3

2.5 m³/h

G¾ B

0.42

BUT015F400

15

4

3.5 m³/h

G¾ B

0.42

BUT020F200

20

4

4.5 m³/h

G1 B

0.36

BUT020F400

20

4

4.5 m³/h

G1 B

0.5

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

A

BUT0**F4**: Version with by-pass T-piece

Accessories Type

Description

0378133010

1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜

0378133015

1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½

0378133020

1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾

0378134010

1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½

0378134015

1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾

0378134020

1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1

0378145015

1 clamping-ring screw fitting for pipe Ø 15 mm, DN 15, flat-sealing, G¾

0378145020

1 clamping-ring screw fitting for pipe Ø 22 mm, DN 20, flat-sealing, G1

V

Combination of BUT with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.

/

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve. Data for a static pressure of 6 bar.

/

Definition for close/off pressure: Max. admissible differential pressure when closing the valve. Calculation, see below.

Pressure differences with motorised actuators Actuator

AXM217F200

AXM217F202

Page

171

171

AXM217SF402 AXM217SF404 173

Voltage

230 VAC

24 VAC/DC

24 VAC/DC

Control signal

2-/3-point

2-/3-point

0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA

Laufzeit

13 s/mm

13 s/mm

8 s/mm

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BUT010F200 BUT010F400 BUT010F410 BUT010F420

1.7

1.7

1.7

BUT015F210 BUT015F410

1.4

1.4

1.4

BUT015F400

1.2

1.2

1.2

BUT020F200 BUT020F400

1.0

1.0

1.0

Cannot be used as distribution valve

Right of amendment reserved © 2024 Fr. Sauter AG

157


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

A

Close/off pressure = ∆pmax + 0.1 bar

Pressure differences with thermal actuators Actuator

V

AXT301F102 AXT301F112 164

AXT301F210

AXT301F212

Page

AXT301F100 AXT301F110 164

AXT301HF110

AXT301HF112

164

164

164

164

Voltage

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

Control signal

2-point

2-point

2-point

2-point

2-point

2-point

Laufzeit

33 s/mm

33 s/mm

33 s/mm

33 s/mm

40 s/mm

40 s/mm

As control valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

BUT010F200 BUT010F400 BUT010F410 BUT010F420

1.5

1.8

1.5

1.8

1.5

1.5

1.5

1.8

1.5

1.8

BUT015F210 BUT015F410

1.2

1.5

1.2

1.5

1.2

1.2

1.2

1.5

1.2

1.5

BUT015F400

1.0

1.3

1.0

1.3

1.0

1.0

1.0

1.3

1.0

1.3

BUT020F200 BUT020F400

0.9

1.1

0.9

1.1

0.9

0.9

0.9

1.1

0.9

1.1

Cannot be used as distribution valve

A

Close/off pressure = ∆pmax + 0.3 bar

Pressure differences with thermal, continuous actuators Actuator Page

AXS315SF102 167

AXS315SF202 167

Voltage

24 VAC/DC

24 VAC/DC

Control signal

0…10 V

0…10 V

Laufzeit

30 s/mm

30 s/mm

As control valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

BUT010F200 BUT010F400 BUT010F410 BUT010F420

1.7

1.8

1.7

BUT015F210 BUT015F410

1.4

1.5

1.4

BUT015F400

1.2

1.3

1.2

BUT020F200 BUT020F400

1.0

1.1

1.0

Cannot be used as distribution valve

A

158

Close/off pressure = ∆pmax + 0.1 bar

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

BXL: 3-way unit valve, PN 16 Features • Ideally suited as control valve for unit valve actuators AXM 217(S), AXT 301 and AXS 315S • Valve with male thread as per DIN EN ISO 228-1, class A • Control passage A–AB open when the spindle is moved in • Used as a control valve • Valve body made of gunmetal • Plug with EPDM soft seal

BXL025F200

• Stainless-steel spindle • Stuffing box with double O-ring seal • Version with cap nut and flat seal

V

Technical data Parameters

Nominal pressure Operating pressure Operating temperature Control passage valve characteristic Mixing passage valve characteristic Valve stroke Control passage leakage rate Mixing passage leakage rate

PN 16 Max. 16 bar at 130 °C 2…130 °C Linear Complementary, reduced 2.9 mm Approx. 0.05% of Kvs value Approx. 0.2% of Kvs value

Operating temperature at valve

Max. 100 °C in combination with AXM 217(S), AXT 301 or AXS 315S

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 VDI/VDE 2173 Fluid group II, No CE label (article 4.3)

Ambient conditions

Standards, directives

ValveDim app

Overview of types

/

The BXL 3-way valve must not be used as a 2-way valve

Type

Nominal diameter

Kvs value

Weight

BXL025F200

DN 25

6.5 m³/h

1200 g

BXL040F200

DN 40

9.5 m³/h

2350 g

Accessories Type

Description

0361824025

3 threaded sleeves, R 1", flat-sealing

0361824040

3 threaded sleeves, R 5/4", flat-sealing

0361825028

3 solder nipple, Ø 28; flat-sealing, DN 25

0361825035

3 solder nipple, Ø 35; flat-sealing, DN 40

0361825042

3 solder nipple, Ø 42; flat-sealing, DN 40

Right of amendment reserved © 2024 Fr. Sauter AG

159


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Combination of BXL with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve. Data for a static pressure of 6 bar.

Pressure differences with motorised actuators

V

Actuator

AXM217F200

AXM217F202

Page

171

171

AXM217SF402 AXM217SF404 173

Voltage

230 VAC

24 VAC/DC

24 VAC/DC

Control signal

2-/3-point

2-/3-point

0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA

Running time

13 s/mm

13 s/mm

8 s/mm

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BXL025F200

0.5

0.5

0.5

BXL040F200

0.2

0.2

0.2

Cannot be used as distribution valve

Pressure differences with thermal actuators Actuator

AXT301F102 AXT301F112 164

AXT301HF110

AXT301HF112

Page

AXT301F100 AXT301F110 164

164

164

Voltage

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

Control signal

2-point

2-point

2-point

2-point

Running time

48 s/mm

48 s/mm

52 s/mm

52 s/mm

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BXL025F200

0.5

0.5

0.5

0.5

BXL040F200

0.2

0.2

0.2

0.2

Cannot be used as distribution valve

Pressure differences with thermal, continuous actuators Actuator Page

AXS315SF102 AXS315SF202 167

Voltage

24 VAC/DC

Control signal

0…10 V

Running time

30 s/mm

As control valve

∆pmax [bar]

BXL025F200

0.5

BXL040F200

0.2

Cannot be used as distribution valve

160

Right of amendment reserved © 2024 Fr. Sauter AG


Actuators for unit valves SAUTER actuators for unit valves provide reliable and accurate control. Pulsepause activation (with pulse widths of a few seconds) or continuous activation guarantees accurate control characteristic.

Overview of actuators for unit valves

AXS315SF102

AXS315SF202

AXT301F***

AXT301HF11*

AXT311F11*

Technical data Max. nominal stroke (mm) Max. closing force (N) Direction of closure Running time Power supply (V)

Type designation

6.5 125 NC 30 s/mm 24

6.5 125 NO 30 s/mm 24

5 100 NC/NO 4.0 min. 24/230

4 100 NC 3.5 min. 24/230

6.5 125 NC 4.5 min. 24/230

Method of operation Stroke indicator Thermal Motor

• • −

• • −

• • −

• • −

• • −

• − −

• − − VUL, BUL, VDL, VXL, VUT, BUT, BXL

• − −

Page 163

Page 163

Page 163

Control 2-point 3-point Positioner (0...10 V) Combination options with valve Further information

− − − − • • VUL, BUL, VDL, VXL, VUT, BUT, BXL Page 166

Right of amendment reserved © 2024 Fr. Sauter AG

Page 166

161


Type designation

AXF 217S

AXM 217

AXM 217S

Technical data Max. nominal stroke (mm) Max. pushing force (N) Direction of closure Running time Power supply (V)

6 160 − 8 s/mm 24

6.3 120 − 13 s/mm 24/230

5.5 120 − 8 s/mm 24

Method of operation Stroke indicator Status indicator Thermal Motor Reset function

− • − • •

− − − • −

− • − • −

− − • VUL, BUL, VDL, VXL, VUT, BUT, BXL

• • − VUL, BUL, VDL, VXL, VUT, BUT, BXL

− − • VUL, BUL, VDL, VXL, VUT, BUT, BXL

Page 169

Page 171

Page 172

Control 2-point 3-point Positioner Combination options with valve Further information

162

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

AXT 301, 311: Thermal actuator for unit valves with stroke indicator Features • Actuation of unit valves and valves in surface heating and cooling systems as well as fan coils • Low-force fitting on the valve using adapter ring • NC “normally closed” and NO “normally open” versions • NC version with first-open function • Adaptation to valve using plastic adapter M30 × 1.5 or M28 × 1.5

AXT301F***

• Max. closing force 125 N • With 230 V or 24 V thermal expansion element • Large visible and tactile position indicator

V

• Low-noise and maintenance-free • Contemporary design • High functional quality and service life • Version with integrated auxiliary contact • Standard version with 1-metre cable permanently connected • Version with 2 m or 5 m plug-in cable • Can be mounted in any position, even suspended under the valve

AXT301HF11*

Technical data Power supply

AXT301HF110/112

Power supply 230 VAC Power supply 24 VAC/DC Power consumption during operation1) Start-up current 230 VAC Start-up current 24 VAC/DC Power for auxiliary contacts 230 V Power for auxiliary contacts 24 V Changeover point of auxiliary contact

±10% 50…60 Hz +20%…−10% Approx. 1 W < 550 mA after max. 100 ms < 300 mA after max. 2 min. 5(1) A, 50/60 Hz 3(1) A, 50/60 Hz For approx. 2 mm stroke

Ambient temperature Storage and transport temperature Operating temperature at valve Air humidity

0…60 °C −25…60 °C Max. 100 °C < 85% rh, no condensation

Housing

Weight

White (RAL 9003), surface structured according to VDI 3400 Ref. 27 Polyamide PVC hose line (H03V2V2-F), Ø 0.75 mm², fixed mounting, light grey (RAL 7035) 0.1 kg (with 1 m power cable)

Type of protection Protection class 230 V Protection class 24 V

IP54 II (EN 60730-1) III (EN 60730-1)

AXT311F11*

Ambient conditions

Construction

Housing material Power cable2)

Standards, directives

1) 2)

ValveDim app

Power consumption after expansion element has reached steady temperature state AXT301F100 and F102 without pre-assembled cable

Right of amendment reserved © 2024 Fr. Sauter AG

163


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves CE/UKCA conformity3)

LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE)

EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN IEC 63000

EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

EN IEC 63000

Overview of types

V

Type

Voltage

Stroke

AXT301F110

230 VAC

5.0 mm

100 N

4.0 min

NC

1m

–

AXT301F112

24 VAC/DC 5.0 mm

100 N

4.0 min

NC

1m

–

AXT301F210

230 VAC

5.0 mm

100 N

4.0 min

NO

1m

–

AXT301F212

24 VAC/DC 5.0 mm

100 N

4.0 min

NO

1m

–

AXT301F100

230 VAC

5.0 mm

100 N

4.0 min

NC

Without cable –

AXT301F102

24 VAC/DC 5.0 mm

100 N

4.0 min

NC

Without cable –

AXT301HF110

230 VAC

4.0 mm

100 N

3.5 min

NC

1m

Auxiliary contacts

AXT301HF112

24 VAC/DC 4.0 mm

100 N

3.5 min

NC

1m

Auxiliary contacts

AXT311F110

230 VAC

6.5 mm

125 N

4.5 min

NC

1m

–

AXT311F112

24 VAC/DC 6.5 mm

125 N

4.5 min

NC

1m

–

A A A

Closing force Running time

NC/NO

Cable length

Function

AXT301F100/102: Connection cable available as optional accessory AXT301F*1*: Including adapter ring 0550389K008 M30 × 1.5 for closing dimension 10.5 mm, pack of one AXT311F11*: Including adapter ring 0550389K008 M30 × 1.5 for closing dimension 8.5 mm in combination with Frese or Siemens PICV valves

Accessories

/

Type

Delivery quantity Description

0550389K001

Set of 5

VA 10 adapter, plastic, light grey, M30 × 1.5 Suitable for: Dumser, Beulco (from 2005), Purmo, Strawa, Oventrop (also Cocon, Cocon 4, Hycocon,), Oventrop stainless steel distributor, Vescal (Metaplast), Cronatherm, eht Siegmund, Gampper, KaMo (H) before Sept. 2005, Aquatherm (brass distributor), Valvex brass distributor, Viega stainless steel distributor (Fonterra & pro Radiant), Thermotech, KaMo INOX distributor, Bianchi valves (series 401T & 403T) and brass distributor (series 332T), Unipipe (ECO distributor), CronaTech, Fränkische, Zehnder, ATS stainless steel distributor, Frese Optima (2.5 mm), Hesag/Herb (Profi-Line distributor), Luxor (CD distributor), TECE stainless steel (Strawa), Watts brass distributor (HKV-T), Tiemme valves, Watts (Vogel & Noot, Cosmo Objektline), Acome (Strawa), Multibeton HKV (Oventrop)

0550389K101

Set of 100

Adapter like 0550389K001

0550389K002

Set of 5

VA 16 adapter, plastic, red, M28 × 1.5 Suitable for: Polytherm (H), Buderus, Thermoval, KAN-Therm (brass distributor)

8.25 mm

0550389K102

Set of 100

Adapter like 0550389K002

8.25 mm

0550389K003

Set of 5

VA 17 adapter, plastic, dusty grey, M28 × 1.5 Suitable for: MMA (EDVH 25, FVXR 15, VXR 20), ICMA (BAS), industry technology Italy (DB VZ2)

11.5 mm

0550389K103

Set of 100

Adapter like 0550389K003

11.5 mm

3)

164

Valve adapters: The names of the manufacturers are provided for information purposes. Manufacturers may change the closing dimensions without prior notice. Closing dimension

11 mm

11 mm

Explanation of abbreviations in the “Additional technical information” section of this product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Type

Delivery quantity Description

0550389K004

Set of 5

VA 26 adapter, plastic, dusty grey, M30 × 1.5 Suitable for: Giacomini

Closing dimension

0550389K104

Set of 100

Adapter like 0550389K004

4 mm

0550389K005

Set of 5

VA 50 adapter, plastic, dark grey, M30 × 1.5 Suitable for: Honeywell & Braukmann, Broen (type: Ballorex Dynamic), Böhnisch/SBK (before 1998), Cazzaniga, Reich, MNG (before 1998), Frese, Schütz, Seppelfricke, Cufix, KaMo (from Sept. 2005), FAR (from 2007), Pantherm, Unicor, emcal (stainless steel from March 2013), Comap HKV module, black (H)

10 mm

0550389K105

Set of 100

Adapter like 0550389K005

0550389K006

Set of 5

VA 64 adapter, plastic, pure white Suitable for: Pettinaroli

17.8 mm

0550389K106

Set of 100

Adapter like 0550389K006

17.8 mm

0550389K007

Set of 5

VA 78 adapter, plastic, pure white Suitable for: Danfoss RA, Oventrop type: V3D, GD & GDF, Jaga

28.8 mm

0550389K107

Set of 100

Adapter like 0550389K007

28.8 mm

0550389K008

Set of 5

VA 80 adapter, plastic, pure white, M30 × 1.5 Suitable for: Heimeier, Herb, Onda, IVAR, Thermoval, Schlösser (from 1993), Kermi, Cazzaniga, Oventrop, Multiblock (from 1997), Frank (from 2003), Athe-Therm (brass up to Feb. 2005), Athe-Therm (stainless steel), BHS distributor, Jupiter, Böhnisch/SBK (from 1998), Simplex, RBM, Emmeti, Cosmo, Watts, Roth, Delphis-Therm, GC distributor, Cuprotherm, Caleffi distributor series 670 (plastic), Wieland, Caleffi, SKV distributor, Aquatechnik Italy (Multirapid, before 2007, from 2009), Brugman, TKM, Bianchi, Jaga, Gomacal, Nereus angle valve DN 10, Strasshofer, Taco (Vogel & Noot, Cosmo stainless steel and CMV module distributor), Caleffi (with thread ring on manufacturer side), Watts, Vogel & Noot (Cosmo brass distributor), RDZ (brass distributor), VIR (series 9520), Herz regulating valve and distributor

10.5 mm

0550389K108

Set of 100

Adapter like 0550389K008

10.5 mm

0550389K009

Set of 5

VA 90 adapter, plastic, crimson, M30 × 1.5 Suitable for: Chemidro, TECE (plastic distributor), KWH Pipe, Prandelli (brass HKV), Athe-Therm (brass from Feb. 2005), Roth DE (H) (type: Universal HK2), Uponor stainless steel distributor, Reliance stainless steel, SAS brass distributor, Luxor, Tiemme brass distributor (series: ‘Floor’), Honeywell VSMF, Afriso pro Calida EF1 (plastic)

11.5 mm

0550389K109

Set of 100

Adapter like 0550389K009

11.5 mm

0550389K010

Set of 5

VA 41 adapter, plastic, dark green, M30 × 1.5 Suitable for: Danfoss AB-QM (DN 10–DN 20) (4 mm actuator), Danfoss AB-QM (DN 25–DN 32) (5 mm actuator), RDZ (plastic distributor), Vescal (Cazzaniga), Frese Optima Compact and EVA (from 2016) + 5 mm actuator

9.5 mm

0550389K110

Set of 100

Adapter like 0550389K010

0550600202

1x 2 metres

PVC flat cable H03V2V2H2-F, 2-core, 0.75 mm²

–

0550600212

1x 2 metres

Thermoplastic cable H03Z1Z1-F, 2-core, 0.75 mm², halogen-free

–

0550600502

1x 5 metres

PVC flat cable H03V2V2H2-F, 2-core, 0.75 mm²

–

0550600512

1x 5 metres

Thermoplastic cable H03Z1Z1-F, 2-core, 0.75 mm², halogen-free

–

4 mm

10 mm

9,5 mm

A

The cables for the AXT301F100 and AXT301F102 actuators must be ordered separately and can be fitted as required on site. It is not possible to install the cables at the factory

A

Special covers to prevent theft or vandalism, for example, are available on request

Right of amendment reserved © 2024 Fr. Sauter AG

V

165


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

AXS 315S: Continuous thermal actuator for unit valves with stroke indicator Features • Actuation of unit valves and valves in surface heating and cooling systems as well as fan coils • First-open function for low-force fitting on the valve using adapter ring • NC “normally closed” and NO “normally open” versions • NC version with first-open function • Adaptation to valve using plastic adapter M30 × 1.5 or M28 × 1.5 • Max. closing force 125 N • With 24 V thermal expansion element

AXS315SF*02

V

• Large visible and tactile position indicator • Low-noise and maintenance-free • Contemporary design • High functional quality and serviceable life • Version with 1m, 2m or 5m plug-in cable • PVC or halogen-free cable, with or without position feedback signal, available as an accessory • Can be mounted in any position, even suspended under the valve

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power consumption during operation1) Start-up current

−10%, +20%, 50…60 Hz −20%…+20% 1.2 W < 320 mA after max. 2 minutes

Parameters

6.5 mm Stroke2) Closing force 125 N +5% 30 s/mm Running time3) Control signal 0…10 V Control signal input resistance 100 kΩ Position feedback signal 0…10 V (0.1 V resolution) Position feedback signal output impe- 10 kΩ dance Position feedback signal output current 0.1 mA (1 mA if shorted) Output load impedance 100 kΩ…1000 kΩ

ValveDim app

Ambient conditions

Ambient temperature Storage and transport temperature Operating temperature at valve Air humidity

0…50 °C −25…60 °C Max. 100 °C < 85% rh, no condensation

Housing

White (RAL 9003), surface structured according to VDI 3400 Ref. 27 Polyamide Ø 0.22 mm², 3- or 4-core, signal white (RAL 9003) 0.15 kg (without power cable)

Construction

Housing material Power cable4) Weight 1) 2) 3) 4)

166

Power consumption after expansion element has reached steady temperature state Stroke, incl. 0.5 mm overstroke range; see “Initialisation” Running time, see “Runtime behaviour” Order the power cable separately

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

Standards, directives

CE/UKCA conformity5)

Type of protection LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

IP54 EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN 60730-1/-2/-14 (mode of operation 1, residential premises) EN IEC 63000 EN IEC 63000

Overview of types Type

Features

AXS315SF102

Actuator for unit valves with first-open function, normally closed (NC)

AXS315SF202

Actuator for unit valves, normally open (NO)

A A A

V

Order the power cable 0550600*** separately, see accessories Includes adapter ring 0550389K010 suitable for SAUTER VUL, VDL, VUT, BUT and BXL valves Adapter ring 0550389K008 suitable for SAUTER BUL valve must be ordered separately

Accessories

/

The names of the manufacturers in the following list are provided for information purposes. Manufacturers may change the closing dimensions without prior notice.

Type

Delivery quantity Description

0550389K001

Set of 5

VA 10 adapter, plastic, light grey, M30 × 1.5 Suitable for: Dumser, Beulco (from 2005), Purmo, Strawa, Oventrop (also Cocon, Cocon 4, Hycocon,), Oventrop stainless steel distributor, Vescal (Metaplast), Cronatherm, eht Siegmund, Gampper, KaMo (H) before Sept. 2005, Aquatherm (brass distributor), Valvex brass distributor, Viega stainless steel distributor (Fonterra & pro Radiant), Thermotech, KaMo INOX distributor, Bianchi valves (series 401T & 403T) and brass distributor (series 332T), Unipipe (ECO distributor), CronaTech, Fränkische, Zehnder, ATS stainless steel distributor, Frese Optima (2.5 mm), Hesag/Herb (Profi-Line distributor), Luxor (CD distributor), TECE stainless steel (Strawa), Watts brass distributor (HKV-T), Tiemme valves, Watts (Vogel & Noot, Cosmo Objektline), Acome (Strawa), Multibeton HKV (Oventrop)

11 mm

0550389K101

Set of 100

Adapter like 0550389K001

11 mm

0550389K002

Set of 5

VA 16 adapter, plastic, red, M28 × 1.5 Suitable for: Polytherm (H), Buderus, Thermoval, KAN-Therm (brass distributor)

8.25 mm

0550389K102

Set of 100

Adapter like 0550389K002

8.25 mm

0550389K003

Set of 5

VA 17 adapter, plastic, dusty grey, M28 × 1.5 Suitable for: MMA (EDVH 25, FVXR 15, VXR 20), ICMA (BAS), industry technology Italy (DB VZ2)

11.5 mm

0550389K103

Set of 100

Adapter like 0550389K003

11.5 mm

0550389K004

Set of 5

VA 26 adapter, plastic, dusty grey, M30 × 1.5 Suitable for: Giacomini

4 mm

0550389K104

Set of 100

Adapter like 0550389K004

4 mm

5)

Closing dimension

Explanation of abbreviations in the “Additional technical information” section of this product data sheet and in the appendix to SAUTER product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

167


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

V

Type

Delivery quantity Description

0550389K005

Set of 5

VA 50 adapter, plastic, dark grey, M30 × 1.5 Suitable for: Honeywell & Braukmann, Broen (type: Ballorex Dynamic), Böhnisch/SBK (before 1998), Cazzaniga, Reich, MNG (before 1998), Frese, Schütz, Seppelfricke, Cufix, KaMo (from Sept. 2005), FAR (from 2007), Pantherm, Unicor, emcal (stainless steel from March 2013), Comap HKV module, black (H)

0550389K105

Set of 100

Adapter like 0550389K005

0550389K006

Set of 5

VA 64 adapter, plastic, pure white Suitable for: Pettinaroli

17.8 mm

0550389K106

Set of 100

Adapter like 0550389K006

17.8 mm

0550389K007

Set of 5

VA 78 adapter, plastic, pure white Suitable for: Danfoss RA, Oventrop type: V3D, GD & GDF, Jaga

28.8 mm

0550389K107

Set of 100

Adapter like 0550389K007

28.8 mm

0550389K008

Set of 5

VA 80 adapter, plastic, pure white, M30 × 1.5 Suitable for: Heimeier, Herb, Onda, IVAR, Thermoval, Schlösser (from 1993), Kermi, Cazzaniga, Oventrop, Multiblock (from 1997), Frank (from 2003), Athe-Therm (brass up to Feb. 2005), Athe-Therm (stainless steel), BHS distributor, Jupiter, Böhnisch/SBK (from 1998), Simplex, RBM, Emmeti, Cosmo, Watts, Roth, Delphis-Therm, GC distributor, Cuprotherm, Caleffi distributor series 670 (plastic), Wieland, Caleffi, SKV distributor, Aquatechnik Italy (Multirapid, before 2007, from 2009), Brugman, TKM, Bianchi, Jaga, Gomacal, Nereus angle valve DN 10, Strasshofer, Taco (Vogel & Noot, Cosmo stainless steel and CMV module distributor), Caleffi (with thread ring on manufacturer side), Watts, Vogel & Noot (Cosmo brass distributor), RDZ (brass distributor), VIR (series 9520), Herz regulating valve and distributor

10.5 mm

0550389K108

Set of 100

Adapter like 0550389K008

10.5 mm

0550389K009

Set of 5

VA 90 adapter, plastic, crimson, M30 × 1.5 Suitable for: Chemidro, TECE (plastic distributor), KWH Pipe, Prandelli (brass HKV), Athe-Therm (brass from Feb. 2005), Roth DE (H) (type: Universal HK2), Uponor stainless steel distributor, Reliance stainless steel, SAS brass distributor, Luxor, Tiemme brass distributor (series: ‘Floor’), Honeywell VSMF, Afriso pro Calida EF1 (plastic)

11.5 mm

0550389K109

Set of 100

Adapter like 0550389K009

11.5 mm

0550389K010

Set of 5

VA 41 adapter, plastic, dark green, M30 × 1.5 Suitable for: Danfoss AB-QM (DN 10–DN 20) (4 mm actuator), Danfoss AB-QM (DN 25–DN 32) (5 mm actuator), RDZ (plastic distributor), Vescal (Cazzaniga), Frese Optima Compact and EVA (from 2016) + 5 mm actuator

9.5 mm

0550389K110

Set of 100

Adapter like 0550389K010

9,5 mm

0550600103

1x 1 metre

Power cable, 0…10 V, 3-core, 0.22 mm², type LiYY, PVC

−

0550600203

1x 2 metres

Power cable, 0…10 V, 3-core, 0.22 mm², type LiYY, PVC

−

0550600503

1x 5 metres

Power cable, 0…10 V, 3-core, 0.22 mm², type LiYY, PVC

−

0550600113

1x 1 metre

Power cable, 0…10 V, 3-core, 0.22 mm², type LiZ1Z1, halogen-free

−

0550600213

1x 2 metres

Power cable, 0…10 V, 3-core, 0.22 mm², type LiZ1Z1, halogen-free

−

0550600513

1x 5 metres

Power cable, 0…10 V, 3-core, 0.22 mm², type LiZ1Z1, halogen-free

−

0550600114

1x 1 metre

Power cable, 0…10 V, 4-core, 0.22 mm², type LiZ1Z1, halogen-free, position feedback

−

0550600214

1x 2 metres

Power cable, 0…10 V, 4-core, 0.22 mm², type LiZ1Z1, halogen-free, position feedback

−

0550600514

1x 5 metres

Power cable, 0…10 V, 4-core, 0.22 mm², type LiZ1Z1, halogen-free, position feedback

−

A

168

Closing dimension

10 mm

10 mm

Special covers to prevent theft or vandalism, for example, are available on request

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

AXF 217S: Motorised actuator for unit valves with positioner Features • Stepping motor with electronic activation and cut-out • Attached to valve with M30 × 1.5 thread • Version with direction of operation 1 (direct acting) or 2 (reverse acting), adjustable • Adjustable valve strokes • Automatic stroke adjustment

AXF217SF404

• Electrical reset function

AXF217SF405

• Maintenance-free gear unit • Suitable for retrofitting existing installations using the appropriate adapters • Status and diagnostic indicator via integrated bi-colour LED

V 2

Power supply

Power supply Power consumption

24 V~ ±15%, 50…60 Hz 24 V= ±15% 5 VA while charging, 2,5 VA during operation, 1 W at standstill

of o

Technical data

n n io tio ct ra ire e D f op o

100%

pe Dire ra ct tio io n n 1

• Fitting position vertically upright to horizontal, not suspended

0% 0V

Output signal y

10 V

Parameters1)

Direction of operation Nominal stroke

Feedback signal Charging time

1 or 2 (adjustable) Max. 6 mm Automatic stroke adjustment 8 s/mm H0:10 mm 160 N < 30 dB (A) 0(2)…10 V; 5…10 V; 0…5 V Ri > 100 kΩ; 0(4)…20 mA Ri = 500 Ω 0…10 V=, ±5% 150 s (supercapacitor)

Ambient temperature Max. operating temperature at valve Storage and transport temperature Ambient humidity

0...50 °C, no condensation 95 °C −20…65 °C < 90% rh

Weight Housing Housing material Thread Power cable

0.2 kg Two-piece, light grey (RAL 7035) Plastic Nickel-plated brass M30 × 1.5 1.50 m long, halogen-free 4 × 0.5 mm², light grey, insertable

Type of protection

IP54 (EN 60529)

Running time Closing dimension Actuating power Sound pressure level Control signal

Ambient conditions

Construction

Standards, directives

1)

The direction of operation and the control voltage can be set using accessory 0550360010 (configurator); factory setting “1” (DA). Direction of operation 1: Control signal increasing = actuator moves out (valve VUT, VUL, VXL, VDL, BUL, BUT closes, valve BXL (control passage) opens). Direction of operation2: Control signal increasing = actuator moves in (valve VUT, VUL, VXL, VDL, BUL, BUT opens, valve BXL (control passage) closes)

Right of amendment reserved © 2024 Fr. Sauter AG

169


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

CE conformity according to

Protection class EMC Directive 2014/30/EU

III (IEC 60730) 60730-1, 60730-2-14

Overview of types Type

Features

AXF217SF404

Motorised actuator for unit valves with positioner, automatic stroke adjustment, electrical reset function:Spindle extends (EFSD)

AXF217SF405

Motorised actuator for unit valves with positioner, automatic stroke adjustment, electrical reset function:Spindle retracts (EFSU)

Accessories Type

Description

0550360010

Configurator for changing control signal, direction of operation, characteristic, direction of reset function

V

170

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

AXM 217: Motorised actuator for unit valves Features • Reliable actuation in efficient control systems • For 2-point or 3-point controllers in conjunction with single-room control systems • Stepping motor with electronic activation and cut-out • Attached to valve with M30 × 1.5 thread • Maintenance-free gear unit

AXM217F20

• Suitable for retrofitting existing installations using the appropriate adapters • Operating status indicated by integrated LED • Fitting position vertically upright to horizontal, not suspended

V

Technical data Parameters

Nominal stroke Running time Actuating power1) Sound pressure level

6.3 mm 13 s/mm 120 N < 30 dB (A)

Max. operating temperature at valve Ambient temperature Ambient humidity

90 °C 0...50 °C < 75% rh

Weight Housing Housing material Thread Power cable

0.15 kg Two-piece, light grey RAL 7035 Plastic Nickel-plated brass M30 × 1.5 1.50 m long, 3 × 0,5 mm², light grey, insertable

Type of protection EMC Directive 2014/30/EU

IP43 (EN 60529) CE as per EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 CE as per EN 60730-1 and EN 60730-2-14

Ambient conditions

Construction

Standards and directives

Low-Voltage Directive 2014/35/EU

Overview of types Type

Power supply

Power consumption

Protection class

AXM217F200

230 V~, ±10%, 50...60 Hz

6.5 VA, 2 W

II (IEC 60730)

AXM217F202

24 V~, ±15%, (50...60 Hz)

2.5 VA, 1.5 W

III (IEC 60730)

A

AXM217F202: Voltage 24V= with relay circuit only

Accessories Type

Description

0550603001

Cable: 24 V, PVC, pluggable, 3 m long

0550603005

Cable: 24 V, halogen-free, pluggable, 3 m long

1)

Actuating power min. 100 N, max. 150 N

Right of amendment reserved © 2024 Fr. Sauter AG

171


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves

AXM 217S: Motorised actuator for unit valves with positioner Features • Stepping motor with electronic activation and cut-out • Attached to valve with M30 × 1.5 thread • Version with direction of operation 1 (direct acting) or 2 (reverse acting), adjustable • Adjustable valve strokes • Automatic stroke adjustment (AXM217SF404)

AXM217SF402

• Maintenance-free gear unit

AXM217SF404

• Suitable for retrofitting existing installations using the appropriate adapters • Status and diagnostic indicator via integrated bi-colour LED

V

• Fitting position vertically upright to horizontal, not suspended

2

Power supply Power consumption

24 VAC/DC ±15 %, 50...60 Hz 2.5 VA / 1.5 W

Direction of operation Nominal stroke Running time Sound pressure level Control signal

1 or 2 (adjustable) 3.2 mm, 4.3 mm, 5.5 mm (adjustable) Automatic stroke adjustment (F404) 8 s/mm < 30 dB (A) 0(2)...10 V; 5...10 V; 0...5 V Ri > 100 kΩ; 0(4)...20 mA Ri = 500 Ω

Ambient temperature Max. operating temperature at valve Storage and transport temperature Ambient humidity

0…50 °C, no condensation 95 °C −20…65 °C < 75% rh

Weight Housing Housing material Thread Power cable

0.15 kg Two-piece, light grey (RAL 7035) Plastic Nickel-plated brass M30 × 1.5 1.50 m long, 3 × 0.5 mm², light grey, pluggable 3.0 m long, halogen-free (F404)

Type of protection Protection class EMC Directive 2014/30/EU

IP43 (EN 60529) III (IEC 60730) 61000-6-1, 61000-6-2, 61000-6-3 and EN 61000-6-4

Parameters1)

0% 0V

Power supply

of o

pe Dire ra ct tio io n n 1

Technical data n n io tio ct ra ire e D f op o

100%

Output signal y

10 V

Ambient conditions

Construction

Standards, directives

CE conformity according to

1)

172

Direction of operation and control signal can be adjusted using DIP switches. Direction of operation 1: Control signal increasing = actuator moves out (valve VUT, VUL, VCL, VDL, BUL closes and valve BXL (control passage) opens). Direction of operation 2: Control signal increasing = actuator moves in (valve VUT, VUL, VCL, VDL, BUL opens and valve BXL (control passage) closes). Factory setting: Direction of operation 2 (RA)

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Unit valves and actuators for unit valves Overview of types Type

Features

Actuating power

AXM217SF402

Motorised actuator for unit valves with positioner

120 N

AXM217SF404

Motorised actuator for unit valves with positioner and au- 160 N tomatic stroke adjustment

A

AXM217SF402: Actuating power min. 100 N, max. 150 N

Accessories Type

Description

0550603009

Cable: 24 V, PVC, pluggable, 3 m long

0550603010

Cable: 24 V, PVC, pluggable, 7 m long

0550603011

Cable: 24 V, halogen-free, pluggable, 3 m long

0550603012

Cable: 24 V, halogen-free, pluggable, 7 m long

V

Right of amendment reserved © 2024 Fr. Sauter AG

173


Regulating valves SAUTER regulating valves provide flexible combinations for all requirements. The wide product range at SAUTER comprises threaded valves made of DZR cast brass and flanged valves made of grey cast iron, ductile cast iron or cast steel, ensuring that you will find products that suit your requirements perfectly. These regulating valves can be used for the continuous control of hot and cold water in closed circuits.

Overview of regulating valves

Type designation Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Version 2-way 3-way Female thread Male thread Nominal diameter (DN) Nominal pressure Combination options with actuator Further information

174

VUN

BUN

V6R

B6R

• • −

• − −

• • −

• − −

• • • • • • −

• • • • − • −

• − • • • • −

• − • • − • −

• − − • 15...50 PN 16 AVM 105(S), AVM 115(S), AVF 124 AVF 125S AVM 321(S) Page 177

− • − • 15...50 PN 16 AVM 105(S), AVM 115(S), AVF 124 AVF 125S AVM 321(S) Page 180

• − • − 15...50 PN 16 AVM 234S, AVF 234S AVM 322(S)

− • • − 15...50 PN 16 AVM 234S, AVF 234S AVM 322(S)

Page 183

Page 186

Right of amendment reserved © 2024 Fr. Sauter AG


Type designation

VUD

VQD

BUD

BQD

• • −

• • −

• − −

• − −

• • • − • • −

• • • − • • −

• • • − • • −

• • • − • • −

Further information

• − • 15...50 PN 6 AVM 105(S), AVM 115(S), AVM 321(S) Page 189

• − • 65...100 PN 6 AVM 234S, AVM 322(S), AVF 234S Page 192

− • • 15...50 PN 6 AVM 105(S), AVM 115(S), AVM 321(S) Page 194

− • • 65...100 PN 6 AVM 234S, AVM 322(S), AVF 234S Page 197

Type designation

VUE

VQE

BUE

BQE

• • −

• • −

• − −

• − −

• • • − • • −

• • • − • • −

• • • − • • −

• • • − • • −

• − • 15...50 PN 16/10 AVM 105, AVM 115, AVM 321(S) Page 199

• − • 65...150 PN 16 AVM 234S, AVM 322(S), AVF 234S Page 203

− • • 15...50 PN 16/10 AVM 105, AVM 115, AVM 321(S) Page 205

− • • 65...150 PN 16 AVM 234S, AVM 322(S), AVF 234S Page 209

Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator

Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator Further information

Right of amendment reserved © 2024 Fr. Sauter AG

175


Type designation Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Steam Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator Further information

Type designation Application Preheater for ventilation & air-conditioning Cooler for ventilation & air-conditioning Steam humidifier for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling, underfloor heating Static heating Cooling tower (open systems) Multi-boiler system Local heating District heating Steam Version 2-way 3-way Flange Nominal diameter (DN) Nominal pressure Combination options with actuator Further information

176

VUG

BUG

VUP

• • •

• − −

• • −

• − • − • • • •

• − • − • • • −

• − • − • • • •

• − • 15...150 PN 25/16 AVM 234S, AVF 234S, AVN 224S, AVM 322(S)

− • • 15...150 PN 25/16 AVM 234S, AVF 234S, AVN 224S, AVM 322(S)

• − • 40...150 PN 25 AVM 234S, AVF 234S, AVN 224S, AVM 322(S)

Page 212

Page 216

Page 220

VUS

BUS

• • •

• − •

• − • − • • • •

• − • − • • • −

• − • 15...100 PN 40 AVM 234S, AVF 234S, AVM 322(S)

− • • 15...100 PN 40 AVM 234S, AVF 234S, AVM 322(S)

Page 222

Page 225

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VUN: 2-way valve with male thread, PN 16 Features • Regulating valve free of silicone grease with male thread (DIN EN ISO 228-1) for cold or hot water in

closed and open circuits In combination with valve actuators AVM 105(S), 115(S), 321(S) and AVF 124, 125S as a control unit • • Equal-percentage (F300) / linear (F200) characteristic, can be set with SUT valve actuators

(SAUTER Universal Technology) • The valve is closed when the spindle is moved out • Closing procedure against the pressure or with the pressure • Stainless-steel spindle

VUN032F300

• Valve body and valve seat in dezincification-resistant (DZR) cast brass • Plug made of dezincification-resistant cast brass (DZR) with EPDM sealing ring

V

• Stuffing box with wiper ring made of dezincification-resistant (DZR) cast brass and double O-ring seal

made of EPDM Technical data Parameters

Nominal pressure Control ratio Valve characteristic Nominal stroke Leakage rate

16 bar > 50:1 F200 = linear F3*0 = equal-percentage 8 mm ≤ 0.02% of Kvs value

Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C

−10...130 °C 16 bar 13 bar

Ambient conditions

Overview of types Type

Nominal diameter

Kvs value

Connection

Weight

VUN015F350

DN 15

0.4 m³/h

G1" B

0.82 kg

VUN015F340

DN 15

0.63 m³/h

G1" B

0.82 kg

VUN015F330

DN 15

1 m³/h

G1" B

0.82 kg

VUN015F320

DN 15

1.6 m³/h

G1" B

0.82 kg

VUN015F310

DN 15

2.5 m³/h

G1" B

0.82 kg

VUN015F300

DN 15

4 m³/h

G1" B

0.82 kg

VUN020F300

DN 20

6.3 m³/h

G1¼" B

1 kg

VUN025F300

DN 25

10 m³/h

G1½" B

1.3 kg

VUN032F300

DN 32

16 m³/h

G2" B

1.74 kg

VUN040F300

DN 40

22 m³/h

G2¼" B

2.52 kg

VUN050F300

DN 50

28 m³/h

G2¾" B

3.44 kg

VUN050F200

DN 50

40 m³/h

G2¾" B

3.44 kg

Accessories Type

Description

0361951015

Screw fitting for male thread with flat seal DN 15

0361951020

Screw fitting for male thread with flat seal DN 20

0361951025

Screw fitting for male thread with flat seal DN 25

0361951032

Screw fitting for male thread with flat seal DN 32

1)

Use stuffing box heater at temperatures below 0 °C; use temperature adapter (accessory) at temperatures above 100 °C

Right of amendment reserved © 2024 Fr. Sauter AG

177


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Description

0361951040

Screw fitting for male thread with flat seal DN 40

0361951050

Screw fitting for male thread with flat seal DN 50

0372240001

Manual adjustment for valves with 8 mm stroke

0372249001

Adaptor required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)

0372249002

Adaptor required when temperature of the medium is 130...150 °C

0378284100

Stuffing box heater 230V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24V~, 15 W for medium below 0 °C

0378368001

Complete replacement stuffing box for DN 15...50

Combination of VUN with electric actuators

/

V

/

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM105F100

AVM105SF132

230

AVM105F120 AVM105F122 230

Page

AVM115SF132

233

AVM115F120 AVM115F122 231

Actuating power

250 N

Control signal

2-/3-point

250 N

250 N

500 N

500 N

2-/3-point

2-/3-point, 0...10 V 2-/3-point

Running time

30 s

2-/3-point, 0...10 V

120 s

35/60/120 s

60/120 s

120 s

233

Closes against the pressure

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

VUN015F350 VUN015F340 VUN015F330 VUN015F320 VUN015F310 VUN015F300

4.0

4.0

4.0

6.0

6.0

VUN020F300

4.0

4.0

4.0

5.0

5.0

VUN025F300

4.0

4.0

4.0

4.0

4.0

VUN032F300

3.0

3.0

3.0

3.5

3.5

VUN040F300

1.9

1.9

1.9

3.0

3.0

VUN050F300 VUN050F200

1.0

1.0

1.0

2.4

2.4

Cannot be used to close with the pressure Actuator

AVM321SF132

Page

AVM321F110 AVM321F112 239

242

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

Actuating power

1000 N

1000 N

500 N

500 N

Control signal

2-/3-point

2-/3point, 0...10 V, 4...20 m 3-point A

2-/3pt., 0...10 V, 4...20 mA

Running time

48/96 s

32/96 s

60/120 s

Closes against the pressure VUN015F350 VUN015F340 VUN015F330 VUN015F320 VUN015F310 VUN015F300 VUN020F300

178

60/120 s

∆pmax [bar]

∆pmax [bar]

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]

10.0

10.0

6.0

16.0

6.0

16.0

10.0

10.0

5.0

12.0

5.0

12.0

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page

AVM321F110 AVM321F112 239

AVM321SF132 242

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

VUN025F300

10.0

10.0

4.0

8.0

4.0

8.0

VUN032F300

10.0

10.0

3.5

6.0

3.5

6.0

VUN040F300

6.0

6.0

3.0

3.5

3.0

3.5

VUN050F300 VUN050F200

4.0

4.0

2.4

2.4

2.4

2.4

Closes with the pressure

∆pmax [bar]

∆pmax [bar]

VUN015F350 VUN015F340 VUN015F330 VUN015F320 VUN015F310 VUN015F300

6.0

6.0

4.0

16.0

4.0

16.0

VUN020F300

6.0

6.0

2.8

16.0

2.8

16.0

VUN025F300

5.0

5.0

2.8

8.0

2.8

16.0

VUN032F300

4.0

4.0

2.0

16.0

2.0

16.0

VUN040F300

2.5

2.5

1.5

16.0

1.5

16.0

VUN050F300 VUN050F200

2.0

2.0

0.8

16.0

0.8

16.0

A

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]

V

At temperatures above 100 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG

179


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

BUN: 3-way valve with male thread, PN 16 Features • Regulating valve free of silicone grease with male thread (DIN EN ISO 228-1) for cold and hot water in

closed and open circuits In combination with valve actuators AVM 105(S), 115(S), 321(S) and AVF 124, 125S as a control unit • • Equal-percentage (F300) / linear (F200) characteristic, can be set with SUT valve actuators

(SAUTER Universal Technology) • The valve is closed when the spindle is moved out • Can be used as a control valve or a distribution valve

BUN032F300

• Stainless-steel spindle • Valve body with valve seat made from dezincification-resistant cast brass (DZR) • Plug made of dezincification-resistant cast brass (DZR) with EPDM sealing ring

V

• Stuffing box with wiper ring made from dezincification-resistant cast brass (DZR) and double O-ring seal

made from EPDM Technical data Parameters

Nominal pressure Valve characteristic, control passage

Distribution valve

Control valve

Mixing passage valve characteristic Control ratio Control passage leakage rate Mixing passage leakage rate Nominal stroke

16 bar F200 = linear F3*0 = equal percentage Linear > 50:1 ≤ 0.05% of kvs value ≤ 1% of Kvs value 8 mm

Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C

–10...130 °C 16 bar 13 bar

Ambient conditions

Overview of types Type

Nominal diameter

Kvs value

Connection

Weight

BUN015F330

DN 15

1 m³/h

G1" B

0.82 kg

BUN015F320

DN 15

1.6 m³/h

G1" B

0.82 kg

BUN015F310

DN 15

2.5 m³/h

G1" B

0.82 kg

BUN015F300

DN 15

4 m³/h

G1" B

0.82 kg

BUN020F300

DN 20

6.3 m³/h

G1¼" B

1 kg

BUN025F300

DN 25

10 m³/h

G1½" B

1.3 kg

BUN032F300

DN 32

16 m³/h

G2" B

1.74 kg

BUN040F300

DN 40

22 m³/h

G2¼" B

2.52 kg

BUN050F300

DN 50

28 m³/h

G2¾" B

3.44 kg

BUN050F200

DN 50

40 m³/h

G2¾" B

3.44 kg

Accessories Type

Description

0361951015

Screw fitting for male thread with flat seal DN 15

0361951020

Screw fitting for male thread with flat seal DN 20

0361951025

Screw fitting for male thread with flat seal DN 25

0361951032

Screw fitting for male thread with flat seal DN 32

1)

180

Use stuffing box heater at temperatures below 0 °C; use temperature adapter (accessory) at temperatures above 100 °C

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Description

0361951040

Screw fitting for male thread with flat seal DN 40

0361951050

Screw fitting for male thread with flat seal DN 50

0372240001

Manual adjustment for valves with 8 mm stroke

0372249001

Adaptor required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)

0372249002

Adaptor required when temperature of the medium is 130...150 °C

0378284100

Stuffing box heater 230V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24V~, 15 W for medium below 0 °C

0378368001

Complete replacement stuffing box for DN 15...50

Combination of BUN with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

V

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM105F100

AVM105SF132

230

AVM105F120 AVM105F122 230

Page

AVM115SF132

233

AVM115F120 AVM115F122 231

Actuating power

250 N

Control signal

2-/3-point

250 N

250 N

500 N

500 N

2-/3-point

2-/3-point, 0...10 V 2-/3-point

Running time

30 s

2-/3-point, 0...10 V

120 s

35/60/120 s

60/120 s

120 s

233

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BUN015F330 BUN015F320 BUN015F310 BUN015F300

4.0

4.0

4.0

6.0

6.0

BUN020F300

4.0

4.0

4.0

5.0

5.0

BUN025F300

3.0

3.0

3.0

4.0

4.0

BUN032F300

2.0

2.0

2.0

3.7

3.7

BUN040F300

1.2

1.2

1.2

2.7

2.7

BUN050F300 BUN050F200

0.8

0.8

0.8

1.8

1.8

Cannot be used as distribution valve Actuator

AVM321SF132

Page

AVM321F110 AVM321F112 239

242

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3point, 0...10 V, 4...20 m 3-point A

500 N

500 N 2-/3pt., 0...10 V, 4...20 mA

Running time

48/96 s

32/96 s

60/120 s

60/120 s

As control valve

∆pmax [bar]

∆pmax [bar]

BUN015F330 BUN015F320 BUN015F310 BUN015F300

10.0

10.0

6.0

16.0

6.0

16.0

BUN020F300

10.0

10.0

5.0

9.5

5.0

9.5

BUN025F300

10.0

10.0

4.0

6.5

4.0

6.5

BUN032F300

10.0

10.0

3.7

4.3

3.7

4.3

BUN040F300

6.0

6.0

2.7

2.7

2.7

2.7

Right of amendment reserved © 2024 Fr. Sauter AG

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]

181


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page

V

AVM321SF132 242

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

BUN050F300 BUN050F200

4.0

4.0

As distribution valve

∆pmax [bar]

∆pmax [bar]

BUN015F330 BUN015F320 BUN015F310 BUN015F300

6.0

6.0

4.0

16.0

4.0

16.0

BUN020F300

6.0

6.0

2.8

16.0

2.8

16.0

BUN025F300

5.0

5.0

2.8

16.0

2.8

16.0

BUN032F300

4.0

4.0

2.0

16.0

2.0

16.0

BUN040F300

2.5

2.5

1.5

16.0

1.5

16.0

BUN050F300 BUN050F200

2.0

2.0

0.8

16.0

0.8

16.0

A

182

AVM321F110 AVM321F112 239

1.8

1.8

1.8

1.8

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]

At temperatures above 100 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

V6R: 2-way valve with female thread, PN 16 (el.) Features • Regulating valve free of silicone grease with female thread DIN EN ISO 228-1 G for the control of

cold/hot water in closed and open circuits • In combination with valve actuators AVM 322, AVM 322S, AVM 234S, AVF 234S • Equal-percentage or linear characteristic, can be set with SUT valve actuators (SAUTER Universal

Technology) to linear or equal-percentage • Control passage A–AB closed when the spindle is moved out • Closing procedure against the pressure or with the pressure

V6R15F300

• Valve body and seat made of gunmetal • Stainless-steel spindle • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM

V

Technical data Parameters

Control ratio Leakage rate Valve stroke Nominal pressure

> 50:1 ≤ 0.05% of Kvs value 14 mm 16 bar

Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C

−15...130 °C 16 bar 13 bar

Pressure and temperature data Flow parameters

DIN 2401 VDI/VDE 2173

Ambient conditions

Standards, directives

ValveDim app

Overview of types Type

Nominal di- Kvs value ameter

Valve characteristic Materials for valve plug

V6R15F350

DN 15

0.4 m³/h

Equal-percentage Stainless steel

G½"

1.2 kg

V6R15F340

DN 15

0.63 m³/h Equal-percentage Stainless steel

G½"

1.2 kg

V6R15F330

DN 15

1 m³/h

Equal-percentage Stainless steel

G½"

1.2 kg

V6R15F320

DN 15

1.6 m³/h

Equal-percentage Stainless steel

G½"

1.2 kg

V6R15F310

DN 15

2.5 m³/h

Equal-percentage Brass

G½"

1.2 kg

V6R15F300

DN 15

4 m³/h

Equal-percentage Brass

G½"

1.2 kg

V6R15F200

DN 15

4 m³/h

Linear

Brass

G½"

1.2 kg

V6R25F310

DN 25

6.3 m³/h

Equal-percentage Brass

G1"

1.6 kg

V6R25F300

DN 25

10 m³/h

Equal-percentage Brass

G1"

1.6 kg

V6R25F210

DN 25

6.3 m³/h

Linear

Brass

G1"

1.6 kg

V6R25F200

DN 25

10 m³/h

Linear

Brass

G1"

1.6 kg

V6R40F310

DN 40

16 m³/h

Equal-percentage Brass

G1½"

3.4 kg

V6R40F300

DN 40

25 m³/h

Equal-percentage Brass

G1½"

3.4 kg

V6R40F210

DN 40

16 m³/h

Linear

Brass

G1½"

3.4 kg

V6R40F200

DN 40

25 m³/h

Linear

Brass

G1½"

3.4 kg

V6R50F300

DN 50

35 m³/h

Equal-percentage Brass

G2"

4.6 kg

V6R50F200

DN 50

35 m³/h

Linear

G2"

4.6 kg

1)

Brass

Type of Weight connection

At temperatures below 0 °C, use stuffing box heater (accessory)

Right of amendment reserved © 2024 Fr. Sauter AG

183


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0217268001

Stuffing box heater 15 W, 24 V

0217268004

Stuffing box heater 15 W, 230 V

0360391015

Screw fitting, DN 15, incl. seal, 2 pcs. required

0360391025

Screw fitting, DN 25, incl. seal, 2 pcs. required

0360391040

Screw fitting incl. seal, 2 pcs. required, Rp1½ - G1½

0360391050

Screw fitting incl. seal, 2 pcs. required, Rp2 - G2

0360427000

Stuffing box, complete with O-ring, max. 130 °C

A

0217268*** Stuffing box heater 15 W, light alloy housing, IP54, 3 × 0.75 mm² power cable, earth connector, length 1 m, ferrule

Combination of V6R with electrical actuators

V

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM234SF132

AVM322F120 AVM322F122 239

AVM322SF132

250

AVF234SF132 AVF234SF232 257

Page Actuating power

2500 N

2000 N

1000 N

1000 N

Control signal

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

Running time

28/56/84 s

28/56/84 s

120/240 s

120/80 s

Closes against the pressure

∆pmax [bar] ∆ps [bar]

∆pmax [bar]

∆pmax [bar]

V6R15F350 V6R15F340 V6R15F330 V6R15F320 V6R15F310 V6R15F300 V6R15F200 V6R25F310 V6R25F300 V6R25F210 V6R25F200

4.0

4.0

16.0

4.0

4.0

V6R40F310 V6R40F300 V6R40F210 V6R40F200

3.0

3.0

11.5

3.0

3.0

V6R50F300 V6R50F200

2.0

2.0

8.6

2.0

2.0

∆pmax [bar]

∆pmax [bar]

Closes with the pressure V6R15F350 V6R15F340 V6R15F330 V6R15F320 V6R15F310 V6R15F300 V6R15F200 V6R25F310 V6R25F300 V6R25F210 V6R25F200

184

∆pmax [bar]

242

∆pmax [bar]

∆pmax [bar] ∆ps [bar]

3.0

3.0

16.0

4.0

4.0

2.0

2.0

16.0

4.0

4.0

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator

AVM234SF132

Page

250

AVF234SF132 AVF234SF232 257

AVM322F120 AVM322F122 239

AVM322SF132 242

V6R40F310 V6R40F300 V6R40F210 V6R40F200

1.5

1.5

16.0

3.0

3.0

V6R50F300 V6R50F200

1.0

1.0

16.0

2.0

2.0

A A

Accessories required: Mounting set 0372338001 for AVM 234 and AVF 234 Accessories required: Mounting set 0510240012 for AVM 322(S)

V

Right of amendment reserved © 2024 Fr. Sauter AG

185


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

B6R: 3-way valve with female thread, PN 16 (el.) Features • Regulating valve free of silicone grease with female thread DIN EN ISO 228-1 G for the control of

cold/hot water in closed and open circuits • In combination with valve actuators AVM 322, AVM 322S, AVM 234S, AVF 234S • Equal-percentage or linear characteristic, can be set with SUT valve actuators (SAUTER Universal

Technology) to linear or equal-percentage • Control passage A–AB closed when the spindle is moved out

B6R25F300

• Can be used as a control valve or a distribution valve • Valve body and seat made of gunmetal • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM • Stainless-steel spindle

V

Technical data Parameters

Control ratio Leakage rate of control passage A-AB Leakage rate of mixing passage B-AB Valve stroke Mixing passage valve characteristic

> 50:1 ≤ 0.05% of Kvs value ≤ 1% of Kvs value 14 mm Linear

Operating temperature1) Operating pressure up to 120 °C Operating pressure up to 130 °C

−15...130 °C 16 bar 13 bar

Pressure and temperature data Flow parameters

DIN 2401 VDI/VDE 2173

Ambient conditions

Standards, directives

ValveDim app

Overview of types Type

Nominal di- Kvs value ameter

B6R15F330

DN 15

1 m³/h

Equal-percentage Stainless steel

G½"

1.2 kg

B6R15F320

DN 15

1.6 m³/h

Equal-percentage Stainless steel

G½"

1.2 kg

B6R15F310

DN 15

2.5 m³/h

Equal-percentage Brass

G½"

1.2 kg

B6R15F300

DN 15

4 m³/h

Equal-percentage Brass

G½"

1.2 kg

B6R15F200

DN 15

4 m³/h

Linear

Brass

G½"

1.2 kg

B6R25F310

DN 25

6.3 m³/h

Equal-percentage Brass

G1"

1.6 kg

B6R25F300

DN 25

10 m³/h

Equal-percentage Brass

G1"

1.6 kg

B6R25F210

DN 25

6.3 m³/h

Linear

Brass

G1"

1.6 kg

B6R25F200

DN 25

10 m³/h

Linear

Brass

G1"

1.6 kg

B6R40F310

DN 40

16 m³/h

Equal-percentage Brass

G1½"

3.4 kg

B6R40F300

DN 40

25 m³/h

Equal-percentage Brass

G1½"

3.4 kg

B6R40F210

DN 40

16 m³/h

Linear

Brass

G1½"

3.4 kg

B6R40F200

DN 40

25 m³/h

Linear

Brass

G1½"

3.4 kg

B6R50F300

DN 50

35 m³/h

Equal-percentage Brass

G2"

4.6 kg

B6R50F200

DN 50

35 m³/h

Linear

G2"

4.6 kg

1)

186

Valve characteristic Materials for valve plug

Brass

Type of Weight connection

At temperatures below 0 °C, use stuffing box heater (accessory)

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0217268001

Stuffing box heater 15 W, 24 V

0217268004

Stuffing box heater 15 W, 230 V

0360391015

Screw fitting, DN 15, incl. seal, 3 pcs. required

0360391025

Screw fitting, DN 25, incl. seal, 3 pcs. required

0360391040

Screw fitting, DN 40, incl. seal, 3 pcs. required

0360391050

Screw fitting, DN 50, incl. seal, 3 pcs. required

0360427000

Stuffing box, comlete with o-ring, max. 130 °C

0360429000

Adhesive label for distribution valve

A

0217268*** Stuffing box heater 15 W, light alloy housing, IP54, 3 × 0.75 mm² power cable, earth connector, length 1 m, ferrule

A

0360429 Sheet with 21 adhesive labels for flow change; see combinations

V

Combination of B6R with electrical actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM234SF132

AVM322F120 AVM322F122 239

AVM322SF132

250

AVF234SF132 AVF234SF232 257

Page Actuating power

2500 N

2000 N

1000 N

1000 N

Control signal

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

Running time

28/56/84 s

28/56/84 s

120/240 s

120/80 s

As control valve

∆pmax [bar]

B6R15F330 B6R15F320 B6R15F310 B6R15F300 B6R15F200 B6R25F310 B6R25F300 B6R25F210 B6R25F200

∆pmax [bar] ∆ps [bar]

4.0

4.0

B6R40F310 B6R40F300 B6R40F210 B6R40F200

3.0

B6R50F300 B6R50F200

2.0

As distribution valve

∆pmax [bar]

B6R15F330 B6R15F320 B6R15F310 B6R15F300 B6R15F200

3.0

3.0

B6R25F310 B6R25F300 B6R25F210 B6R25F200

2.0

2.0

242

∆pmax [bar]

∆pmax [bar]

16.0

4.0

4.0

3.0

11.5

3.0

3.0

2.0

8.6

2.0

2.0

∆pmax [bar]

∆pmax [bar]

16.0

4.0

4.0

16.0

4.0

4.0

∆pmax [bar] ∆ps [bar]

Right of amendment reserved © 2024 Fr. Sauter AG

187


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator

AVM234SF132

Page

250

AVF234SF132 AVF234SF232 257

AVM322F120 AVM322F122 239

AVM322SF132 242

B6R40F310 B6R40F300 B6R40F210 B6R40F200

1.5

1.5

16.0

3.0

3.0

B6R50F300 B6R50F200

1.0

1.0

16.0

2.0

2.0

A A

Accessories required: Mounting set 0372338001 for AVM 234 and AVF 234 Accessories required: Mounting set 0510240012 for AVM 322(S)

V

188

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VUD: 2-way flanged valve, PN 6 (el.) Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and

AVF 125(S) as a control unit • Not suitable for steam or drinking water or potentially explosive atmospheres • Valve with flange connection as per EN 1092-2, seal form B

VUD032F300

• Regulating valve, free of silicone grease, painted black • Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-

percentage or quadratic • The valve is closed when the spindle is moved out

V

• Closing procedure against the pressure or with the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM

Technical data Parameters

Nominal pressure Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Control ratio from valve Stuffing box Leakage rate Valve stroke

PN 6 Flange as per EN 1092-2, form B Linear

Operating temperature2) Operating pressure

−10...150 °C Up to 120 °C; 6 bar At 150 °C; 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed

Pressure and temperature data Flow parameters Pressure Equipment Directive

EN 764, EN 1333 EN 60534 (page 3) 97/23/EC (fluid group II) No CE label Article 3.3

Equal-percentage > 50:1 2 EPDM O-rings ≤ 0.05% of Kvs value 8 mm

Ambient conditions1)

Standards, directives

Overview of types Type

Nominal diameter

Kvs value

Weight

VUD015F320

DN 15

1.6 m³/h

3.2 kg

VUD015F310

DN 15

2.5 m³/h

3.2 kg

VUD015F300

DN 15

4 m³/h

3.2 kg

VUD020F300

DN 20

6.3 m³/h

4.1 kg

VUD025F300

DN 25

10 m³/h

4.7 kg

1) 2)

Humidity must not exceed 75% At temperatures below 0 °C, use stuffing box heater. Use adapter (accessory) at temperatures above 100 °C

Right of amendment reserved © 2024 Fr. Sauter AG

189


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Nominal diameter

Kvs value

Weight

VUD032F300

DN 32

16 m³/h

7.3 kg

VUD040F300

DN 40

22 m³/h

8.6 kg

VUD050F300

DN 50

28 m³/h

11.2 kg

VUD050F200

DN 50

40 m³/h

11.2 kg

Accessories

V

Type

Description

0372240001

Manual adjustment for valves with 8 mm stroke

0372249001

Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50

0372249002

Adaptor required when temperature of the medium is 130...150 °C, DN 15...50

0378284100

Stuffing box heater 230 VAC, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 VAC, 15 W for medium below 0 °C

0378368001

Complete replacement stuffing box for DN 15...50

Combination of VUD with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Combination of VUD with electric actuator, actuating power 250 N, 500 N Actuator

AVM105F100

AVM105SF132

230

AVM105F120 AVM105F122 230

Page Actuating power

250 N

250 N

Control signal

2-/3-point

2-/3-point

2-/3-point, 0...10 V 2-/3-point

2-/3-point, 0...10 V

Running time

30 s

120 s

35/60/120 s

60/120 s

Closes against the pressure VUD015F320 VUD015F310 VUD015F300 VUD020F300

AVM115SF132

233

AVM115F120 AVM115F122 231

250 N

500 N

500 N

120 s

233

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

4.0

4.0

4.0

6.0

6.0

VUD025F300

2.8

2.8

2.8

6.0

6.0

VUD032F300

2.1

2.1

2.1

5.2

5.2

VUD040F300

1.2

1.2

1.2

3.3

3.3

VUD050F300 VUD050F200

0.9

0.9

0.9

2.0

2.0

Cannot be used to close with the pressure

190

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of VUD with electric actuator with spring return, actuating power 500 N Actuator Page

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

Actuating power

500 N

500 N

Control signal

3-point

2-/3-pt., 0...10 V, 4...20 mA

Running time

60/120 s

60/120 s

Closes against the pressure

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

VUD015F320 VUD015F310 VUD015F300 VUD020F300 VUD025F300

6.0

6.0

6.0

6.0

VUD032F300

5.2

5.2

5.2

5.2

VUD040F300

3.3

3.3

3.3

3.3

VUD050F300 VUD050F200

2.0

2.0

2.0

2.0

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

6.0

6.0

6.0

6.0

VUD025F300

5.0

6.0

5.0

6.0

VUD032F300

4.0

6.0

4.0

6.0

VUD040F300

2.5

6.0

2.5

6.0

VUD050F300 VUD050F200

1.5

6.0

1.5

6.0

Closes with the pressure VUD015F320 VUD015F310 VUD015F300 VUD020F300

A

V

At temperatures above 100 °C, accessories are required

Combination of VUD with electric actuator, actuating power 1000 N Actuator Page

AVM321F110 AVM321F112 239

AVM321SF132 242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0...10 V, 4...20 mA

Running time

48/96 s

32/96 s

Closes against the pressure

∆pmax [bar]

∆pmax [bar]

VUD015F320 VUD015F310 VUD015F300 VUD020F300 VUD025F300 VUD032F300 VUD040F300

6.0

6.0

VUD050F300 VUD050F200

4.0

4.0

∆pmax [bar]

∆pmax [bar]

6.0

6.0

Closes with the pressure VUD015F320 VUD015F310 VUD015F300 VUD020F300 VUD025F300

5.0

5.0

VUD032F300

4.0

4.0

VUD040F300

2.5

2.5

VUD050F300 VUD050F200

1.5

1.5

A

At temperatures above 100 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG

191


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VQD: 2-way flanged valve, PN 6 Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for steam or drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black

VQD

• Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-

percentage or quadratic • The valve is closed when the spindle is moved out

V

• Closing procedure against the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of stainless steel with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM

Technical data Parameters

Nominal pressure Connection Valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke

PN 6 Flange as per EN 1092-2, form B Equal-percentage > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65...80) 40 mm (DN 100)

Ambient conditions1)

Operating temperature2) Operating pressure

−10...150 °C Up to 120 °C 6 bar At 150 °C 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed

Pressure and temperature data Flow parameters Pressure Equipment Directive

EN 764, EN 1333 EN 60534, (page 3) 2014/68/EU (fluid group II) No CE label as per article 4.3

Standards, directives

Overview of types Type

Nominal diameter

Kvs value

Weight

VQD065F300

DN 65

63 m³/h

18.0 kg

VQD080F300

DN 80

100 m³/h

25.3 kg

VQD100F300

DN 100

160 m³/h

37.1 kg

1) 2)

192

Humidity must not exceed 75% At temperatures below 0 °C, use stuffing box heater

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0372336180

Intermediate piece (required when temperature of the medium is 130...180 °C)

0378284100

Stuffing box heater 230 VAC, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 VAC, 15 W for medium below 0 °C

0378369101

Complete replacement stuffing box for DN 65...150

Combination of VQD with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the

V

valve.

Combination of VQD with electric actuator, actuating power 1000 N Actuator Page

AVM322F120 AVM322F122 239

242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

Running time

120/240 s

120/80 s

Closes against the pressure VQD065F300

AVM322SF132

∆pmax [bar]

VQD080F300

∆pmax [bar]

2.5

2.5

1.5

1.5

Cannot be used to close with the pressure

A

Maximum media temperature: 100 °C

Combination of VQD with electric actuator, actuating power 2500 N, 2000 N Actuator Page

AVF234SF132 AVF234SF232 257

AVM234SF132

Actuating power

2000 N

2500 N

Control signal

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 65, DN 80

40/80/120 s

40/80/120 s

Running time for DN 100...150

80/160/240 s

80/160/240 s

250

Closes against the pressure

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

VQD065F300

3.0

5.1

1.2

VQD080F300

3.0

3.4

3.0

VQD100F300

2.0

2.2

2.0

Cannot be used to close with the pressure

A A

Spring return: AVF234SF132 normally closed (NC); AVF234SF232 normally open (NO) At temperatures above 130 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG

193


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

BUD: 3-way flanged valve, PN 6 (el.) Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and

AVF 125(S) as a control unit • Not suitable for drinking water

BUD032F300

• Valve with flange connection as per EN 1092-2, seal form B, for PN 16 and PN 10 • Regulating valve, free of silicone grease, painted black • Characteristic can be set with SUT valve actuators to linear, equal-percentage or quadratic • The control passage is closed when the spindle is moved out

V

• Used as control valve or as distribution valve • Valve body with seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM

Control valve

Technical data Parameters

Nominal pressure Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Mixing passage valve characteristic Control ratio from valve Stuffing box Control passage leakage rate Mixing passage leakage rate Valve stroke

Distribution valve

PN 6 Flange as per EN 1092-2, form B Linear Equal-percentage Linear > 50:1 2 EPDM O-rings < 0.05% of Kvs value < 1% of Kvs value 8 mm

Ambient conditions1)

Operating temperature2) Operating pressure

−10...150 °C Up to 120 °C; 6 bar At 150 °C; 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 EN 60534 (page 3) Fluid group II, liquid or steam pressure, no CE label as per article 4.3

Standards, directives

Overview of types Type

Nominal diameter

Kvs value

Weight

BUD015F320

DN 15

1.6 m³/h

3200 g

BUD015F310

DN 15

2.5 m³/h

3200 g

BUD015F300

DN 15

4 m³/h

3200 g

BUD020F300

DN 20

6.3 m³/h

4100 g

1) 2)

194

Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 100 °C

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Nominal diameter

Kvs value

Weight

BUD025F300

DN 25

10 m³/h

4700 g

BUD032F300

DN 32

16 m³/h

7100 g

BUD040F300

DN 40

22 m³/h

8400 g

BUD050F300

DN 50

28 m³/h

10900 g

BUD050F200

DN 50

40 m³/h

11200 g

Accessories Type

Description

0372240001

Manual adjustment for valves with 8 mm stroke

0372249001

Adapter required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)

0372249002

Adapter required when temperature of the medium is 130...150 °C

0378284100

Stuffing box heater 230 V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 V~, 15 W for medium below 0 °C

0378368001

Complete replacement stuffing box for DN 15...50

V

Combination of BUD with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Combination of BUD with electric actuator, actuating power 250 N, 500 N Actuator

AVM105F100

AVM105SF132

230

AVM105F120 AVM105F122 230

Page Actuating power

AVM115SF132

233

AVM115F120 AVM115F122 231

250 N

250 N

250 N

500 N

Control signal

2-/3-point

2-/3-point

2-/3-point, 0...10 V 2-/3-point

500 N 2-/3-point, 0...10 V

Running time

30 s

120 s

35/60/120 s

60/120 s

120 s

233

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BUD015F320 BUD015F310 BUD015F300 BUD020F300

4.0

4.0

4.0

6.0

6.0

BUD025F300

2.8

2.8

2.8

6.0

6.0

BUD032F300

2.1

2.1

2.1

5.2

5.2

BUD040F300

1.2

1.2

1.2

3.3

3.3

BUD050F300 BUD050F200

0.9

0.9

0.9

2.0

2.0

Cannot be used as distribution valve

Right of amendment reserved © 2024 Fr. Sauter AG

195


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of BUD with electric actuator with spring return, actuating power 500 N Actuator

V

Page

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

Actuating power

500 N

500 N

Control signal

3-point

2-/3-pt., 0...10 V, 4...20 mA

Running time

60/120 s

60/120 s

As control valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

BUD015F320 BUD015F310 BUD015F300 BUD020F300 BUD025F300

6.0

6.0

6.0

6.0

BUD032F300

5.2

5.2

5.2

5.2

BUD040F300

3.3

3.3

3.3

3.3

BUD050F300 BUD050F200

2.0

2.0

2.0

2.0

As distribution valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

BUD015F320 BUD015F310 BUD015F300 BUD020F300

6.0

6.0

6.0

6.0

BUD025F300

5.0

6.0

5.0

6.0

BUD032F300

4.0

6.0

4.0

6.0

BUD040F300

2.5

6.0

2.5

6.0

BUD050F300 BUD050F200

1.5

6.0

1.5

6.0

A

At temperatures above 100 °C, accessories are required

Combination of BUD with electric actuator, actuating power 1000 N Actuator Page

AVM321F110 AVM321F112 239

242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0...10 V, 4...20 mA

Running time

48/96 s

32/96 s

As control valve

∆pmax [bar]

∆pmax [bar]

BUD015F320 BUD015F310 BUD015F300 BUD020F300 BUD025F300 BUD032F300 BUD040F300

6.0

6.0

BUD050F300 BUD050F200

4.0

4.0

As distribution valve

∆pmax [bar]

∆pmax [bar]

BUD015F320 BUD015F310 BUD015F300 BUD020F300

6.0

6.0

BUD025F300

5.0

5.0

BUD032F300

4.0

4.0

BUD040F300

2.5

2.5

BUD050F300 BUD050F200

1.5

1.5

A

196

AVM321SF132

At temperatures above 100 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

BQD: 3-way flanged valve, PN 6 Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black • Equal-percentage control passage characteristic, can be set with SUT (SAUTER Universal Technology)

BQD

valve actuators to linear or quadratic • Mixing passage, linear characteristic

V

• The control passage is closed when the spindle is moved out • Used as control valve or as distribution valve • Valve body with seat made of grey cast iron • Stainless-steel spindle • Plug made of stainless steel with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM

Control valve

Technical data Parameters

Nominal pressure Connection Control passage valve characteristic Mixing passage valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke

PN 6 Flange as per EN 1092-2, form B Equal-percentage Linear > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65...80) 40 mm (DN 100)

Distribution valve

Ambient conditions1)

Operating temperature2) Operating pressure

−10...150 °C Up to 120 °C 6 bar At 150 °C 5.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed

Pressure and temperature data Flow parameters Pressure Equipment Directive

EN 764, EN 1333 EN 60534, (page 3) 2014/68/EU (fluid group II) No CE label as per article 4.3

Standards, directives

Overview of types Type

Nominal diameter

Kvs value

Weight

BQD065F300

DN 65

63 m³/h

14.8 kg

BQD080F300

DN 80

100 m³/h

21 kg

BQD100F300

DN 100

160 m³/h

31 kg

1) 2)

Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater

Right of amendment reserved © 2024 Fr. Sauter AG

197


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0372336180

Adapter (required when temperature of the medium is 130...150 °C)

0378284100

Stuffing box heater 230 V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 V~, 15 W for medium below 0 °C

0378369101

Complete replacement stuffing box

Combination of BQD with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

V

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Combination of BQD with electric actuator, actuating power 1000 N Actuator Page

AVM322F120 AVM322F122 239

AVM322SF132 242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

Running time

120/240 s

120/80 s

As control valve

∆pmax [bar]

BQD065F300

2.5

2.5

BQD080F300

1.5

1.5

∆pmax [bar]

∆pmax [bar]

As distribution valve BQD065F300 BQD080F300

A

∆pmax [bar]

1.0

1.0

0.7

0.7

At media temperature above 100 °C, accessories are required.

Combination of BQD with electric actuator, actuating power 2500 N, 2000 N Actuator Page

AVF234SF132 AVF234SF232 257

Actuating power

2000 N

2500 N

Control signal

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 65, DN 80

40/80/120 s

40/80/120 s

Running time for DN 100...150

80/160/240 s

80/160/240 s

250

As control valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

BQD065F300

3.0

5.1

3.0

BQD080F300

3.0

3.4

3.0

BQD100F300

2.0

2.2

2.0

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

As distribution valve BQD065F300

1.0

6.0

1.0

BQD080F300

0.8

6.0

0.8

BQD100F300

0.5

6.0

0.5

A

198

AVM234SF132

At temperatures above 130 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VUE: 2-way flanged valve, PN 16/10 (el.) Features • Continuous control of cold/hot water and low-pressure steam up to 115 °C in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and

AVF 125(S) as a control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B, for PN 16 and PN 10 • Regulating valve, free of silicone grease, painted black

VUE032F300

• Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-

percentage or quadratic • The valve is closed when the spindle is moved out

V

• Closing procedure against the pressure or with the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM

Technical data Parameters

Nominal pressure Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Control ratio from valve Stuffing box Leakage rate Valve stroke

PN 16/10 Flange as per EN 1092-2, form B Linear

Operating temperature2) Operating pressure

-10…150 °C PN 16: Up to 120 °C, 16 bar At 150 °C, 14.4 bar PN 10: Up to 120 °C, 10 bar At 150 °C, 9 bar Between 120 °C and 150 °C, a linear interpolation can be performed

Equal-percentage > 50:1 2 EPDM O-rings < 0.05% of Kvs value 8 mm

Ambient conditions1)

ValveDim app

Standards, directives

Pressure and temperature data Flow parameters Pressure Equipment Directive

EN 764, EN 1333 EN 60534 (page 3) 97/23/EC (fluid group II) No CE label Article 3.3

Overview of types Type

Nominal diameter

Kvs value

Weight

VUE015F350

DN 15

0.4 m³/h

3.2 kg

VUE015F340

DN 15

0.63 m³/h

3.2 kg

1) 2)

Humidity must not exceed 75%. At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 100 °C

Right of amendment reserved © 2024 Fr. Sauter AG

199


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Nominal diameter

Kvs value

Weight

VUE015F330

DN 15

1 m³/h

3.2 kg

VUE015F320

DN 15

1.6 m³/h

3.2 kg

VUE015F310

DN 15

2.5 m³/h

3.2 kg

VUE015F300

DN 15

4 m³/h

3.2 kg

VUE020F300

DN 20

6.3 m³/h

4.1 kg

VUE025F300

DN 25

10 m³/h

4.7 kg

VUE032F300

DN 32

16 m³/h

7.3 kg

VUE040F300

DN 40

22 m³/h

8.6 kg

VUE050F300

DN 50

28 m³/h

11.2 kg

VUE050F200

DN 50

40 m³/h

11.2 kg

Accessories

V

Type

Description

0372240001

Manual adjustment for valves with 8 mm stroke

0372249001

Adapter required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)

0372249002

Adapter required when temperature of the medium is 130...150 °C

0378284100

Stuffing box heater 230 V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 V~, 15 W for medium below 0 °C

0378368001

Complete replacement stuffing box for DN 15...50

Combination of VUE with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Combination of VUE with electric actuator, actuating power 250 N, 500 N Actuator

AVM105F100

AVM105SF132

230

AVM105F120 AVM105F122 230

Page Actuating power

250 N

250 N

Control signal

2-/3-point

2-/3-point

2-/3-point, 0...10 V 2-/3-point

2-/3-point, 0...10 V

Running time

30 s

120 s

35/60/120 s

60/120 s

Closes against the pressure VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300

AVM115SF132

233

AVM115F120 AVM115F122 231

250 N

500 N

500 N

120 s

233

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

4.0

4.0

4.0

6.0

6.0

VUE025F300

2.8

2.8

2.8

6.0

6.0

VUE032F300

2.1

2.1

2.1

5.2

5.2

VUE040F300

1.4

1.4

1.4

3.3

3.3

VUE050F300 VUE050F200

0.9

0.9

0.9

2.0

2.0

Cannot be used to close with the pressure

200

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of VUE with electric actuator with spring return, actuating power 500 N Actuator Page

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

Actuating power

500 N

500 N

Control signal

3-point

2-/3-pt., 0...10 V, 4...20 mA

Running time

60/120 s

60/120 s

Closes against the pressure

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300

6.0

16.0

6.0

16.0

VUE020F300

6.0

11.0

6.0

11.0

VUE025F300

6.0

6.8

6.0

6.8

VUE032F300

5.2

5.2

5.2

5.2

VUE040F300

3.3

3.3

3.3

3.3

VUE050F300 VUE050F200

2.0

2.0

2.0

2.0

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

6.0

16.0

6.0

16.0

VUE025F300

5.0

16.0

5.0

16.0

VUE032F300

4.0

16.0

4.0

16.0

VUE040F300

2.5

16.0

2.5

16.0

VUE050F300 VUE050F200

1.5

16.0

1.5

16.0

Closes with the pressure VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300

A

V

At temperatures above 100 °C, accessories are required

Combination of VUE with electric actuator, actuating power 1000 N Actuator Page

AVM321F110 AVM321F112 239

242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0...10 V, 4...20 mA

Running time

48/96 s

32/96 s

Closes against the pressure VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300 VUE025F300 VUE032F300

AVM321SF132

∆pmax [bar]

∆pmax [bar]

10.0

10.0

VUE040F300

6.0

6.0

VUE050F300 VUE050F200

4.0

4.0

Right of amendment reserved © 2024 Fr. Sauter AG

201


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page

V

AVM321SF132 242

Closes with the pressure

∆pmax [bar]

∆pmax [bar]

VUE015F350 VUE015F340 VUE015F330 VUE015F320 VUE015F310 VUE015F300 VUE020F300

6.0

6.0

VUE025F300

5.0

6.0

VUE032F300

4.0

6.0

VUE040F300

2.5

2.5

VUE050F300 VUE050F200

1.5

1.5

A

202

AVM321F110 AVM321F112 239

At temperatures above 100 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VQE: 2-way flanged valve, PN 16 Features • Continuous control of cold and hot water and low-pressure steam up to 115 °C in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black • Characteristic can be set with SUT (SAUTER Universal Technology) valve actuators to linear, equal-

VQE

percentage or quadratic • The valve is closed when the spindle is moved out

V

• Closing procedure against the pressure • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of stainless steel with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM

Technical data Parameters

Nominal pressure Connection Valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke

PN 16 Flange as per EN 1092-2, form B Equal-percentage > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65, 80) 40 mm (DN 100...150)

Ambient conditions1)

Operating temperature2) Operating pressure

−10…150 °C Up to 120 °C 16 bar At 150 °C 14.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed

Pressure and temperature data Flow parameters Pressure Equipment Directive

EN 764, EN 1333 EN 60534-3 2014/68/EU (fluid group II) No CE label as per article 4.3

Standards, directives

Overview of types Type

Nominal diameter

Kvs value

Weight

VQE065F300

DN 65

63 m³/h

23.8 kg

VQE080F300

DN 80

100 m³/h

30.2 kg

VQE100F300

DN 100

160 m³/h

41.3 kg

VQE125F300

DN 125

220 m³/h

62 kg

VQE150F300

DN 150

320 m³/h

89 kg

1) 2)

Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 130 °C

Right of amendment reserved © 2024 Fr. Sauter AG

203


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0372336180

Adapter (required when temperature of the medium is 130...150 °C)

0378284100

Stuffing box heater 230 V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 V~, 15 W for medium below 0 °C

0378369101

Complete replacement stuffing box

Combination of VQE with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

V

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Combination of VQE with electric actuators, actuating power 1000 N Actuator Page

AVM322F120 AVM322F122 239

242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

Running time

120/240 s

120/80 s

Closes against the pressure VQE065F300

AVM322SF132

∆pmax [bar]

VQE080F300

∆pmax [bar]

2.5

2.5

1.5

1.5

Cannot be used to close with the pressure

A

At media temperature above 100 °C, accessories are required.

Combination of VQE with electric actuators, actuating power 2500 N, 2000 N Actuator Page

AVF234SF132 AVF234SF232 257

AVM234SF132

Actuating power

2000 N

2500 N

Control signal

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 65, DN 80

40/80/120 s

40/80/120 s

Running time for DN 100...150

80/160/240 s

80/160/240 s

250

Closes against the pressure

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

VQE065F300

3.0

5.1

3.0

VQE080F300

3.0

3.4

3.0

VQE100F300

2.0

2.2

2.0

VQE125F300

1.4

1.4

1.5

VQE150F300

1.0

1.1

1.0

Cannot be used to close with the pressure

A A

204

Spring return: AVF234SF132 normally closed (NC); AVF234SF232 normally open (NO) At temperatures above 130 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

BUE: 3-way flanged valve, PN 16/10 (el.) Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 105(S), AVM 115(S), AVM 321(S) and AVF 124 and AVF

125(S) as a control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B, for PN 16 and PN 10 • Regulating valve, free of silicone grease, painted black

BUE032F300

• Equal-percentage characteristic with F300, can be set with SUT valve actuators (SAUTER Universal

Technology) to linear or quadratic • Valve passage A–AB is closed when the spindle is moved out

V

• Can be used as a control valve or a distribution valve • Valve body and seat made of grey cast iron • Stainless-steel spindle • Plug made of brass with glass-fibre reinforced PTFE sealing ring • Stuffing box made of brass with wiper ring and double O-ring seal made of EPDM

Control valve

Technical data Parameters

Connection Connection Valve characteristic, control passage F200 Valve characteristic, control passage F300 Mixing passage valve characteristic Control ratio from valve Stuffing box Control passage leakage rate Mixing passage leakage rate Valve stroke

PN 16/10 Flange as per EN 1092-2, form B Linear Equal-percentage

Distribution valve

Linear > 50:1 2 EPDM O-rings < 0.05% of Kvs value < 1% of Kvs value 8 mm

Ambient conditions1)

Operating temperature2) Operating pressure

−10...150 °C PN 16: Up to 120 °C, 16 bar At 150 °C, 14.4 bar PN 10: Up to 120 °C, 10 bar At 150 °C, 9 bar Between 120 °C and 150 °C, a linear interpolation can be performed

Pressure and temperature data Flow parameters Pressure Equipment Directive

EN 764, EN 1333 EN 60534 (page 3) 97/23/EC (fluid group II) No CE label Article 3.3

Standards, directives

1) 2)

Humidity must not exceed 75% At temperatures below 0 °C, use a stuffing box heater. Use adapter (accessory) at temperatures above 100 °C

Right of amendment reserved © 2024 Fr. Sauter AG

205


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Overview of types Type

Nominal diameter

Kvs value

Weight

BUE015F330

DN 15

1 m³/h

3.2 kg

BUE015F320

DN 15

1.6 m³/h

3.2 kg

BUE015F310

DN 15

2.5 m³/h

3.2 kg

BUE015F300

DN 15

4 m³/h

3.2 kg

BUE020F300

DN 20

6.3 m³/h

4.1 kg

BUE025F300

DN 25

10 m³/h

4.7 kg

BUE032F300

DN 32

16 m³/h

7.1 kg

BUE040F300

DN 40

22 m³/h

8.4 kg

BUE050F300

DN 50

28 m³/h

11.2 kg

BUE050F200

DN 50

40 m³/h

11.2 kg

Accessories

V

Type

Description

0372240001

Manual adjustment for valves with 8 mm stroke

0372249001

Adapter required when temperature of the medium is 100...130 °C (recommended for temperatures <10 °C)

0372249002

Adapter required when temperature of the medium is 130...150 °C

0378284100

Stuffing box heater 230 V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 V~, 15 W for medium below 0 °C

0378368001

Complete replacement stuffing box for DN 15...50

Combination of BUE with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Combination of BUE with electric actuator, actuating power 250 N, 500 N Actuator

AVM105F100

AVM105SF132

230

AVM105F120 AVM105F122 230

Page Actuating power

AVM115SF132

233

AVM115F120 AVM115F122 231

250 N

250 N

250 N

500 N

Control signal

2-/3-point

2-/3-point

2-/3-point, 0...10 V 2-/3-point

500 N 2-/3-point, 0...10 V

Running time

30 s

120 s

35/60/120 s

60/120 s

120 s

233

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BUE015F330 BUE015F320 BUE015F310 BUE015F300 BUE020F300

4.0

4.0

4.0

6.0

6.0

BUE025F300

2.8

2.8

2.8

6.0

6.0

BUE032F300

2.1

2.1

2.1

5.2

5.2

BUE040F300

1.4

1.4

1.4

3.3

3.3

BUE050F300 BUE050F200

0.9

0.9

0.9

2.0

2.0

Cannot be used as distribution valve

206

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of BUE with electric actuator with spring return, actuating power 500 N Actuator Page

AVF124F130 AVF124F230 252

AVF125SF132 AVF125SF232 255

Actuating power

500 N

500 N

Control signal

3-point

2-/3-pt., 0...10 V, 4...20 mA

Running time

60/120 s

60/120 s

As control valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

BUE015F330 BUE015F320 BUE015F310 BUE015F300

6.0

16.0

6.0

16.0

BUE020F300

6.0

11.0

6.0

11.0

BUE025F300

6.0

6.8

6.0

6.8

BUE032F300

5.2

5.2

5.2

5.2

BUE040F300

3.3

3.3

3.3

3.3

BUE050F300 BUE050F200

2.0

2.0

2.0

2.0

As distribution valve

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

BUE020F300

6.0

16.0

6.0

16.0

BUE025F300

5.0

16.0

5.0

16.0

BUE032F300

4.0

16.0

4.0

16.0

BUE040F300

2.5

16.0

2.5

16.0

BUE050F300 BUE050F200

1.5

16.0

1.5

16.0

A A

V

Spring return: 18 ± 10 s At temperatures above 100 °C, accessories are required

Combination of BUE with electric actuator, actuating power 1000 N Actuator Page

AVM321F110 AVM321F112 239

AVM321SF132 242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0...10 V, 4...20 mA

Running time

48/96 s

32/96 s

As control valve

∆pmax [bar]

∆pmax [bar]

BUE015F330 BUE015F320 BUE015F310 BUE015F300 BUE020F300 BUE025F300 BUE032F300

10.0

10.0

BUE040F300

6.0

6.0

BUE050F300 BUE050F200

4.0

4.0

∆pmax [bar]

∆pmax [bar]

6.0

6.0

As distribution valve BUE015F330 BUE015F320 BUE015F310 BUE015F300 BUE020F300 BUE025F300

6.0

5.0

BUE032F300

6.0

4.0

BUE040F300

2.5

2.5

BUE050F300 BUE050F200

1.5

1.5

Right of amendment reserved © 2024 Fr. Sauter AG

207


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

A

At temperatures above 100 °C, accessories are required

V

208

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

BQE: 3-way flanged valve, PN 16 Features • Continuous control of cold and hot water in closed circuits • Water quality as per VDI 2035 • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, painted black • Equal-percentage control passage characteristic, can be set with SUT (SAUTER Universal Technology) valve

BQE

actuators to linear or quadratic • Mixing passage, linear characteristic

V

• The control passage is closed when the spindle is moved out • Used as control valve or as distribution valve • Valve body with seat made of grey cast iron • Spindle and plug made of stainless steel; plug with metal-to-metal seal • Stuffing box made of stainless steel with wiper ring and double O-ring seal made of EPDM

Control valve

Technical data Parameters

Nominal pressure Connection Control passage valve characteristic Mixing passage valve characteristic Control ratio from valve Stuffing box Leakage rate Valve stroke

PN 16 Flange as per EN 1092-2, form B Equal-percentage Linear > 30:1 2 EPDM O-rings Class III as per DIN EN 60534-4 (0.001 x Kvs) 20 mm (DN 65, 80) 40 mm (DN 100...150)

Distribution valve

Ambient conditions

Operating temperature1) Operating pressure

Air humidity

−10…150 °C Up to 120 °C 16 bar At 150 °C 14.4 bar Between 120 °C and 150 °C, a linear interpolation can be performed Max. 75% rh, no condensation

Standards, directives

Pressure and temperature data Flow parameters Pressure Equipment Directive

EN 764, EN 1333 EN 60534, (page 3) 2014/68/EU (fluid group II) With CE label

ValveDim app

Overview of types Type

Nominal diameter

Kvs value

Weight

BQE065F300

DN 65

63 m³/h

19 kg

BQE080F300

DN 80

100 m³/h

24 kg

BQE100F300

DN 100

160 m³/h

34 kg

BQE125F300

DN 125

220 m³/h

52 kg

BQE150F300

DN 150

320 m³/h

76 kg

1)

At temperatures below 0 °C, use a stuffing box heater. Use adapter at temperatures above 130 °C (see accessories)

Right of amendment reserved © 2024 Fr. Sauter AG

209


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0372336180

Adapter (required when temperature of the medium is 130...150 °C)

0378284100

Stuffing box heater 230 V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 V~, 15 W for medium below 0 °C

0378369101

Complete replacement stuffing box

Combination of BQE with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

V

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Combination of BQE with electric actuators, actuating power 1000 N Actuator Page

AVM322F120 AVM322F122 239

AVM322SF132 242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

Running time

120/240 s

120/80 s

As control valve

∆pmax [bar]

BQE065F300

2.5

2.5

BQE080F300

1.5

1.5

∆pmax [bar]

∆pmax [bar]

As distribution valve BQE065F300 BQE080F300

A

∆pmax [bar]

1.0

1.0

0.7

0.7

At media temperature above 100 °C, accessories are required.

Combination of BQE with electric actuators, actuating power 2000 N and 2500 N Actuator

AVF234SF132 AVF234SF232 257

Page

250

Actuating power

2500 N

2000 N

Control signal

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 65, DN 80

40/80/120 s

40/80/120 s

Running time for DN 100...150

80/160/240 s

80/160/240 s

As control valve

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

BQE065F300

3.0

3.0

5.1

BQE080F300

3.0

3.0

3.4

BQE100F300

2.0

2.0

2.2

BQE125F300

1.5

1.4

1.4

BQE150F300

1.0

1.0

1.1

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

As distribution valve BQE065F300

210

AVM234SF132

1.0

1.0

16.0

BQE080F300

0.8

0.8

16.0

BQE100F300 BQE125F300 BQE150F300

0.5

0.5

16.0

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

A

At temperatures above 130 °C, accessories are required.

V

Right of amendment reserved © 2024 Fr. Sauter AG

211


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VUG: 2-way flanged valve, PN 25/16 (el.) Features • Continuous control of cold and hot water in closed circuits, and of steam • In combination with valve actuators AVM 322(S), AVM 234S, AVN 234S and AVF 234S as a control unit • Water quality as per VDI 2035 • Valve with flange connection as per EN 1092-2, seal form B • Nominal pressure 25 bar (VUG065F316: 16 bar) • Not suitable for drinking water • Standard compliance for control units according to DIN EN 14597 (VUG065F316 does not have TÜV

approval) VUG032F304

V

• Regulating valve, free of silicone grease, painted black • Equal-percentage characteristic, can be set with SUT (SAUTER Universal Technology) valve actuators to

linear or quadratic • The valve is closed when the spindle is moved out • Closing procedure against the pressure or with the pressure • Valve body made of ductile cast iron; seat and spindle made of stainless steel • Plugs of nominal diameter DN 15...50 made of stainless steel with glass-fibre-reinforced PTFE sealing ring • Plugs of nominal diameter DN 65...150 made of stainless steel with metal-to-metal seal • Maintenance-free stuffing box in brass with spring-loaded PTFE washer

Technical data Parameters

Nominal pressure Connection Valve characteristic Control ratio from valve Leakage rate at max. ∆ps

PN 16/25 Flange as per EN 1092-2, form B Equal-percentage > 50:1 ≤ 0.05% of Kvs value

Operating temperature1) Operating pressure2)

−10…200 °C PN 16: –16 bar at 30…120 °C 14 bar at 200 °C PN 25: 25 bar at 30…120 °C 21.7 bar at 200 °C

Pressure and temperature data Flow parameters Test mark3)

EN 764, EN 1333 EN 60534 TÜV ID: 14392

Ambient conditions

Standards, directives

1)

ValveDim app

2) 3)

212

For cold water applications from −20...30 °C, the VUG***F3**S versions with a stuffing box containing silicone (e.g. VUG015F304S) must be used. The VUG***F3**S valves do not comply with the standard for control units as per DIN EN 14597. VUG***F3**S are only available up to DN 125. VUG***F3**S do not have TÜV approval and must not be combined with AVN224 actuators. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution For operating pressures, see diagram “Pressure / temperature assignment” VUG065F316 does not have TÜV approval. The valve does not bear the test centre identification number and falls under category I of the Pressure Equipment Directive. The valve can be used with the AVN224SF*** actuator, but not as a safety device. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution. For use as per DIN EN 14597. When the VUG065F316 is combined with the AVN224S actuator, the permissible media temperature is > 0 °C.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators PED 2014/68/EU (CE) PESR-2016 (UKCA)

Fluid group II, liquid or steam pressure Fluid group II, liquid or steam pressure

Overview of types Type

Nominal diame- Kvs value ter

Valve stroke

Connection

Weight

Approval

VUG015F374

DN 15

20 mm

PN 25/16

4 kg

CE, TÜV

VUG015F364

DN 15

0.25 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

VUG015F354

DN 15

0.4 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

VUG015F344

DN 15

0.63 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

VUG015F334

DN 15

1 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

VUG015F324

DN 15

1.6 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

VUG015F314

DN 15

2.5 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

VUG015F304

DN 15

4 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

VUG020F304

DN 20

6.3 m³/h

20 mm

PN 25/16

5 kg

CE, TÜV

VUG025F304

DN 25

10 m³/h

20 mm

PN 25/16

5.6 kg

CE, TÜV

VUG032F304

DN 32

16 m³/h

20 mm

PN 25/16

9.1 kg

CE, TÜV

VUG040F304

DN 40

25 m³/h

20 mm

PN 25/16

11.2 kg

CE, TÜV

VUG050F304

DN 50

40 m³/h

20 mm

PN 25/16

13.8 kg

CE, TÜV, UKCA

VUG065F316

DN 65

63 m³/h

40 mm

PN 16

25 kg

CE, UKCA

VUG065F304

DN 65

63 m³/h

40 mm

PN 25

25 kg

CE, TÜV, UKCA

VUG080F304

DN 80

100 m³/h

40 mm

PN 25/16

37 kg

CE, TÜV, UKCA

VUG100F304

DN 100

160 m³/h

40 mm

PN 25

50 kg

CE, TÜV, UKCA

VUG125F304

DN 125

250 m³/h

40 mm

PN 25

75 kg

CE, TÜV, UKCA

VUG150F304

DN 150

340 m³/h

40 mm

PN 25

100 kg

CE, TÜV

A

0.16 m³/h

V

VUG with DN 150: Not used in the United Kingdom of Great Britain and Northern Ireland (UK)

Markets for valve-actuator combinations AVM322F120 AVM322F122

AVM322SF132 AVM234SF132

AVF234SF132 AVF234SF232

AVN224SF132

AVN224SF232

1, 3

1, 3

1, 3

2, 3, 4

2, 3

1, 3 2, 3

1, 3 2, 3

1, 3 2, 3

2, 3 2, 3, 4

2, 3 2, 3

VUG015F374 VUG015F364 VUG015F354 VUG015F344 VUG015F334 VUG015F324 VUG015F314 VUG015F304 VUG020F304 VUG025F304 VUG032F304 VUG040F304 VUG050F304 VUG065F304 VUG080F304 VUG100F304 VUG125F304 VUG065F316 VUG150F304 Key:

1 2 3 4

Intended for the United Kingdom of Great Britain and Northern Ireland (UK) Combination not allowed in UK Intended for the European Union (EU) for control functions Approval in the EU for safety functions. Cat. IV of the PED. TÜV certificate

Right of amendment reserved © 2024 Fr. Sauter AG

213


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0372336180

Intermediate piece (required when temperature of the medium is 130...180 °C)

0372336240

Adapter (required when temperature of the medium is 180...200 °C)

0378284100

Stuffing box heater 230 VAC, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 VAC, 15 W for medium below 0 °C

0378384001

Torsion protection DN 65...150

0560260001

Stuffing box for VUG/BUG for cold water application with grease containing silicone

Combination of VUG with electric actuators

/ /

V

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM322SF132

AVM234SF132

Page

AVM322F120 AVM322F122 239

242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 15...50

120/240 s

Running time for DN 65...150

–

Closes against the pressure VUG015F374 VUG015F364 VUG015F354 VUG015F344 VUG015F334 VUG015F324 VUG015F314 VUG015F304 VUG020F304

250

AVF234SF132 AVF234SF232 257

AVN224SF132 AVN224SF232 260

2500 N

2000 N

1100 N

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

80/120 s

40/80/120 s

40/80/120 s

40/80/120 s

–

80/160/240 s

80/160/240 s

80/160/240 s

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

16.0

16.0

16.0

16.0

25.0

16.0

25.0

VUG025F304

15.2

15.2

16.0

16.0

25.0

16.0

17.0

VUG032F304

9.4

9.4

16.0

16.0

21.0

10.5

10.5

VUG040F304

6.1

6.1

16.0

13.5

13.5

6.5

6.5

VUG050F304

4.0

4.0

11.0

8.5

8.5

4.0

4.0

VUG065F316

–

–

7.1

5.6

5.6

–

–

VUG065F304

–

–

7.1

5.6

5.6

3.0

3.0

VUG080F304

–

–

4.7

3.4

3.4

2.0

2.0

VUG100F304

–

–

3.0

2.2

2.2

1.1

1.1

VUG125F304

–

–

2.0

1.6

1.6

0.8

0.8

VUG150F304

–

–

1.5

1.2

1.2

0.6

0.6

214

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page

AVM322F120 AVM322F122 239

AVM322SF132

AVM234SF132

242

250

AVF234SF132 AVF234SF232 257

AVN224SF132 AVN224SF232 260

Closes with the pressure

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

VUG015F374 VUG015F364 VUG015F354 VUG015F344 VUG015F334 VUG015F324 VUG015F314 VUG015F304 VUG020F304 VUG025F304 VUG032F304

6.0

6.0

6.0

6.0

25.0

6.0

25.0

VUG040F304

5.5

5.5

6.0

6.0

25.0

6.0

25.0

VUG050F304

3.5

3.5

6.0

6.0

25.0

4.0

25.0

VUG065F316

–

–

4.5

4.5

25.0

–

–

VUG065F304

–

–

4.5

4.5

25.0

2.6

25.0

VUG080F304

–

–

3.5

3.4

25.0

1.7

25.0

VUG100F304

–

–

3.0

2.2

25.0

1.1

25.0

VUG125F304

–

–

2.0

1.6

25.0

0.8

25.0

VUG150F304

–

–

1.5

1.0

25.0

0.6

25.0

A A

At temperatures above 130 °C, accessories are required Combination with AVN 224S: with safety function as per DIN EN 14597

Right of amendment reserved © 2024 Fr. Sauter AG

215

V


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

BUG: 3-way flanged valve, PN 25/16 (el.) Features • Continuous control of cold and hot water in closed circuits • In combination with valve actuators AVM 322(S), AVM 234S, AVN 234S and AVF 234S as a control unit • Water quality as per VDI 2035 • Valve with flange connection as per EN 1092-2, seal form B • Nominal pressure 25 bar (BUG065F316: 16 bar) • Not suitable for drinking water • Standard compliance for control units according to DIN EN 14597 (BUG065F316 does not have TÜV

BUG032F304

V

approval) • Regulating valve, free of silicone grease, painted black • Equal-percentage characteristic, can be set with SUT valve actuators to linear or quadratic • The control passage is closed when the spindle is moved out • Can be used as a control valve or a distribution valve • Valve body made of ductile cast iron • Stainless-steel seat and spindle • Plugs of nominal diameter DN 15...50 made of stainless steel with glass-fibre-reinforced PTFE sealing ring • Plugs of nominal diameter DN 65...150 made of stainless steel with metal-to-metal seal • Maintenance-free stuffing box in brass with spring-loaded PTFE washer

Technical data Parameters

Leakage rate at max. ∆ps

Nominal pressure Connection Control ratio Control passage valve characteristic Mixing passage valve characteristic Control passage leakage rate Mixing passage leakage rate

PN 16/25 Flange as per EN 1092-2, form B > 50: 1 Equal-percentage Linear ≤ 0.05% of Kvs value ≤ 1.0% of Kvs value

Operating temperature1) Operating pressure2)

−10…200 °C PN 16: 16 bar at 30…120 °C 14 bar at 200 °C PN 25: 25 bar at 30…120 °C 21.7 bar at 200 °C

Pressure and temperature data Flow parameters

EN 764, EN 1333 EN 60534

Ambient conditions

Standards, directives

ValveDim app

1)

2)

216

For cold water applications from –20...30 °C, use versions BUG***F3**S with a stuffing box containing silicone (e.g.: BUG015F304S). The BUG***F3**S valves do not comply with the standard for control units as per DIN EN 14597. BUG***F3**S are only available up to DN 125. BUG***F3**S do not have TÜV approval and must not be combined with AVN224 actuators. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution. For operating pressures, see diagram “Pressure / temperature assignment”

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators TÜV ID: 18388 Fluid group II, liquid or steam pressure Fluid group II, liquid or steam pressure

Test mark3) PED 2014/68/EU (CE) PESR-2016 (UKCA)

Overview of types Type

Nominal diame- Kvs value ter

Valve stroke

BUG015F334

DN 15

1 m³/h

20 mm

PN 25/16

3.1 kg

CE, TÜV

BUG015F324

DN 15

1.6 m³/h

20 mm

PN 25/16

3.1 kg

CE, TÜV

BUG015F314

DN 15

2.5 m³/h

20 mm

PN 25/16

3.1 kg

CE, TÜV

BUG015F304

DN 15

4 m³/h

20 mm

PN 25/16

3.1 kg

CE, TÜV

BUG020F304

DN 20

6.3 m³/h

20 mm

PN 25/16

4 kg

CE, TÜV

BUG025F304

DN 25

10 m³/h

20 mm

PN 25/16

4.7 kg

CE, TÜV

BUG032F304

DN 32

16 m³/h

20 mm

PN 25/16

7.2 kg

CE, TÜV

BUG040F304

DN 40

25 m³/h

20 mm

PN 25/16

9.2 kg

CE, TÜV

BUG050F304

DN 50

40 m³/h

20 mm

PN 25/16

11.9 kg

CE, TÜV UKCA

BUG065F316

DN 65

63 m³/h

40 mm

PN 16

26.8 kg

CE, UKCA

BUG065F304

DN 65

63 m³/h

40 mm

PN 25

27.1 kg

CE, TÜV UKCA

BUG080F304

DN 80

100 m³/h

40 mm

PN 25/16

36.3 kg

CE, TÜV UKCA

BUG100F304

DN 100

160 m³/h

40 mm

PN 25

53 kg

CE, TÜV UKCA

BUG125F304

DN 125

250 m³/h

40 mm

PN 25

79.1 kg

CE, TÜV UKCA

BUG150F304

DN 150

340 m³/h

40 mm

PN 25

108.7 kg

CE, TÜV

A

Connection

Weight

Approval

V

BUG with DN 150: Not used in the United Kingdom of Great Britain and Northern Ireland (UK)

Markets for valve-actuator combinations AVM322F120 AVM322F122

AVM322SF132 AVM234SF132

AVF234SF132 AVF234SF232

AVN224SF132

AVN224SF232

1, 3

1, 3

1, 3

2, 3, 4

2, 3

1, 3 2, 3

1, 3 2, 3

1, 3 2, 3

2, 3 2, 3, 4

2, 3 2, 3

BUG015F334 BUG015F324 BUG015F314 BUG015F304 BUG020F304 BUG025F304 BUG032F304 BUG040F304 BUG050F304 BUG065F304 BUG080F304 BUG100F304 BUG125F304 BUG065F316 BUG150F304 Key:

3)

1 2 3 4

Intended for the United Kingdom of Great Britain and Northern Ireland (UK) Combination not allowed in UK Intended for the European Union (EU) for control functions Approval in the EU for safety functions. Cat. IV of the PED. TÜV certificate

BUG065F316 does not have TÜV approval. The valve does not bear the test centre identification number and falls under category I of the Pressure Equipment Directive. The valve can be used with the AVN224SF*** actuator, but not as a safety device. Use stuffing box heater at temperatures below 0 °C; use the relevant intermediate piece (accessory) at temperatures above 130 °C or 180 °C. Down to −10 °C, as per AD code of practice W 10, use water with anti-freeze and brine solution. For use as per DIN EN 14597. When the BUG065F316 is combined with the AVN224S actuator, the permissible media temperature is > 0 °C.

Right of amendment reserved © 2024 Fr. Sauter AG

217


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Accessories Type

Description

0372336180

Intermediate piece (required when temperature of the medium is 130...180 °C)

0372336240

Adapter (required when temperature of the medium is 180...200 °C)

0378284100

Stuffing box heater 230 VAC, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24 VAC, 15 W for medium below 0 °C

0378384001

Torsion protection DN 65...150

0560260001

Stuffing box for VUG/BUG for cold water application with grease containing silicone

Combination of BUG with electric actuators

/ /

V

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM322SF132

AVM234SF132

Page

AVM322F120 AVM322F122 239

250

AVF234SF132 AVF234SF232 257

AVN224SF132 AVN224SF232 260

242

Actuating power

1000 N

1000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

2500 N

2000 N

1100 N

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 15...50

120/240 s

80/120 s

40/80/120 s

40/80/120 s

40/80/120 s

Running time for DN 65...150

–

–

80/160/240 s

80/160/240 s

80/160/240 s

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

BUG015F334 BUG015F324 BUG015F314 BUG015F304 BUG020F304

16.0

16.0

16.0

16.0

25.0

16.0

25.0

BUG025F304

15.2

15.2

16.0

16.0

25.0

16.0

17.0

BUG032F304

9.4

9.4

16.0

16.0

21.0

10.5

10.5

BUG040F304

6.1

6.1

16.0

13.5

13.5

6.5

6.5

BUG050F304

4.0

4.0

11.0

8.5

8.5

4.0

4.0

BUG065F316

–

–

7.1

5.6

5.6

–

–

BUG065F304

–

–

7.1

5.6

5.6

3.0

3.0

BUG080F304

–

–

4.7

3.4

3.4

2.0

2.0

BUG100F304

–

–

3.0

2.2

2.2

1.1

1.1

BUG125F304

–

–

2.0

1.6

1.6

0.8

0.8

BUG150F304

–

–

1.5

1.2

1.2

0.6

0.6

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

6.0

6.0

6.0

6.0

25.0

6.0

25.0

As distribution valve BUG015F334 BUG015F324 BUG015F314 BUG015F304 BUG020F304 BUG025F304 BUG032F304 BUG040F304

5.5

5.5

4.0

6.0

25.0

6.0

25.0

BUG050F304

3.5

3.5

6.0

6.0

25.0

4.0

25.0

BUG065F316

–

–

4.5

4.5

25.0

–

–

BUG065F304

–

–

4.5

4.5

25.0

2.6

25.0

BUG080F304

–

–

3.5

3.4

25.0

1.7

25.0

218

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page

AVM322F120 AVM322F122 239

AVM322SF132

AVM234SF132

242

250

AVF234SF132 AVF234SF232 257

AVN224SF132 AVN224SF232 260

BUG100F304

–

–

3.0

2.2

25.0

1.1

25.0

BUG125F304

–

–

2.0

1.6

25.0

0.8

25.0

BUG150F304

–

–

1.0

1.0

25.0

0.6

25.0

A A

At temperatures above 130 °C, accessories are required Combination with AVN 224S: with safety function as per DIN EN 14597

V

Right of amendment reserved © 2024 Fr. Sauter AG

219


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VUP: Pressure-relieved 2-way flanged valve, PN 25 (el.) Features • Continuous control of cold and hot water in closed circuits, and of steam • In combination with valve actuators AVM 322(S), AVM 234S, AVF 234S and AVN 224S as a control unit • Water quality as per VDI 2035 • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, with pressure compensation, galvanised and painted black

VUP040F304

• Equal-percentage characteristic, can be set with SUT (SAUTER Universal Technology) valve actuators to

linear or quadratic • The valve is closed when the spindle is moved in

V

• Valve body made of ductile cast iron • Valve seat, plug and spindle made of stainless steel A

AB

• Closing procedure only against the pressure • Maintenance-free stuffing box in brass with spring-loaded PTFE-FKM-PTFE washer

Technical data Parameters

Nominal pressure Connection Valve characteristic Control ratio Leakage rate at max. ∆ps

PN 25 Flange as per EN 1092-2, form B Equal-percentage > 100:1 < 0.05% of Kvs value

Operating temperature1) Operating pressure

−20...200 °C Up to 120 °C, 25 bar Up to 200 °C, 20 bar

Test mark

TÜV ID: 06973

Admissible ambient conditions

Standards and directives

Overview of types Type

Nominal diameter

Kvs value

Valve stroke

Weight

VUP040F304

DN 40

25 m³/h

14 mm

10000 g

VUP050F304

DN 50

40 m³/h

25 mm

14000 g

VUP065F304

DN 65

63 m³/h

25 mm

18000 g

VUP080F304

DN 80

100 m³/h

25 mm

25500 g

VUP100F304

DN 100

160 m³/h

40 mm

36500 g

VUP125F304

DN 125

250 m³/h

40 mm

56500 g

VUP150F304

DN 150

350 m³/h

40 mm

84500 g

Accessories Type

Description

0372336180

Adaptor (required when temperature of the medium is 130...180 °C)

0372336240

Adaptor (required when temperature of the medium is 180...200 °C)

0378284100

Stuffing box heater 230V~, 15 W for medium below 0 °C

0378284102

Stuffing box heater 24V~, 15 W for medium below 0 °C

1)

220

Use stuffing box heater at temperatures below 0 °C; use the relevant adapter (accessory) at temperatures above 130 °C or 180 °C. Valve combined with AVN 224S: For use as per DIN EN 14597, the admissible media temperature is > 0 °C.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Description

0378356001

Replacement pack for stuffing box DN 40…80

0378357001

Replacement pack for stuffing box DN 100…150

Combination of VUP with electrical actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM322SF132

AVM234SF132

Page

AVM322F120 AVM322F122 239

242

Actuating power

1000 N

Control signal

V

250

AVF234SF132 AVF234SF232 257

AVN224SF132 AVN224SF232 260

1000 N

2500 N

2000 N

1100 N

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 40

84/168 s

56/84 s

28/56/84 s

28/56/84 s

28/56/84 s

Running time for DN 50...80

–

–

50/100/150 s

50/100/150 s

50/100/150 s

Running time for DN 100...150

–

–

80/160/240 s

80/160/240 s

80/160/240 s

Closes against the pressure

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

VUP040F304

25.0

25.0

25.0

25.0

25.0

25.0

25.0

VUP050F304

–

–

25.0

25.0

25.0

20.0

25.0

VUP065F304

–

–

25.0

25.0

25.0

16.0

17.0

VUP080F304

–

–

25.0

25.0

25.0

12.0

15.0

VUP100F304

–

–

25.0

20.0

22.0

9.0

12.0

VUP125F304

–

–

19.0

14.0

20.0

6.0

6.0

VUP150F304

–

–

15.0

10.0

15.0

4.0

4.0

Cannot be used to close with the pressure

A

Combination with AVN 224S: with safety function as per DIN EN 14597

Right of amendment reserved © 2024 Fr. Sauter AG

221


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

VUS: 2-way flanged valve, PN 40 (el.) Features • Continuous control of cold, warm and hot water in closed circuits, and of steam • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Water quality as per VDI 2035 • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B

VUS040F305

• Regulating valve, free of silicone grease, matt black • Equal-percentage characteristic, can be set with SUT valve actuators to linear or quadratic • The valve is closed when the spindle is moved in. Closing procedure only against the pressure • Valve body made of cast steel; spindle, seat and plug of stainless steel

V

• Maintenance-free stuffing box, made of stainless steel, with spring-loaded PTFE washer up to 220 °C, with

graphite seal up to 260 °C Technical data Parameters

Nominal pressure Operating pressure

Connection Valve characteristic Control ratio Leakage rate

PN 40 40 bar at −10...50 °C 36.3 bar at 120 °C 29.4 bar at 220 °C 27.8 bar at 260 °C Flange as per EN 1092-2, form B Equal-percentage > 50: 1 ≤ 0.05% of Kvs value

Operating temperature1)

−10...260 °C

Pressure and temperature data Flow parameters PED 2014/68/EU (CE)

EN 764, EN 1333 EN 60534 VdTÜV pressure information sheet 100, sheet 1, cat. IV EN 12952-11, EN 12953-9 Article 4.3 AD 2000 Rulebook

Ambient conditions

CE/UKCA conformity2)

ValveDim app

PESR-2016 (UKCA)

Overview of types Type

Nominal diameter

Kvs value

Valve stroke

Weight

VUS015F375

DN 15

0.16 m³/h

20 mm

5.1 kg

VUS015F365

DN 15

0.25 m³/h

20 mm

5.1 kg

VUS015F355

DN 15

0.4 m³/h

20 mm

5.1 kg

VUS015F345

DN 15

0.63 m³/h

20 mm

5.1 kg

VUS015F335

DN 15

1 m³/h

20 mm

5.1 kg

VUS015F325

DN 15

1.6 m³/h

20 mm

5.1 kg

VUS015F315

DN 15

2.5 m³/h

20 mm

5.1 kg

VUS015F305

DN 15

4 m³/h

20 mm

5.1 kg

VUS020F305

DN 20

6.3 m³/h

20 mm

5.9 kg

VUS025F305

DN 25

10 m³/h

20 mm

6.8 kg

VUS032F305

DN 32

16 m³/h

20 mm

8.4 kg

1)

2)

222

No stuffing box heater required down to –10 °C. Above 130 °C or 180 °C, use the relevant adapter (accessory). Above 200 °C and up to 260 °C, use stuffing box with graphite seal (accessory) Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Nominal diameter

Kvs value

Valve stroke

Weight

VUS040F305

DN 40

25 m³/h

20 mm

10.6 kg

VUS050F305

DN 50

40 m³/h

20 mm

13.2 kg

VUS065F305

DN 65

63 m³/h

30 mm

18.6 kg

VUS080F305

DN 80

100 m³/h

30 mm

25.1 kg

VUS100F305

DN 100

160 m³/h

30 mm

36.4 kg

CE/UKCA conformity

VUS015F375 VUS015F365 VUS015F355 VUS015F345 VUS015F335 VUS015F325 VUS015F315 VUS015F305 VUS020F305 VUS025F305 VUS032F305 VUS040F305 VUS050F305 VUS065F305 VUS080F305 VUS100F305

EU PED 2014/68/EU

Label

UK PESR-2016 (UKCA)

Label

Art. 4.3

Without CE

Art. 8.3

Without UKCA

Category I

CE

Category I

UKCA

V

Accessories Type

Description

0372336180

Adaptor (required when temperature of the medium is 130...180 °C)

0372336240

Adaptor (required when temperature of the medium is 180...260 °C)

0378373001

Stuffing box with graphite seal for temperatures of 220...260 °C; DN 15…50

0378373002

Stuffing box with graphite seal for temperatures of 220...260 °C; DN 65…100

Right of amendment reserved © 2024 Fr. Sauter AG

223


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Combination of VUS with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

V

AVM322SF132

AVM234SF132

Page

AVM322F120 AVM322F122 239

242

250

AVF234SF132 AVF234SF232 257

Actuating power

1000 N

1000 N

2500 N

2000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 15...50

120/240 s

80/120 s

40/80/120 s

40/80/120 s

Running time for DN 65...100

–

–

60/120/180 s

60/120/180 s

Closes against the pressure

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

VUS015F375 VUS015F365 VUS015F355 VUS015F345 VUS015F335 VUS015F325 VUS015F315 VUS015F305 VUS020F305

35.0

35.0

40.0

40.0

25.0

VUS025F305

17.4

17.4

37.8

29.6

25.0

VUS032F305

12.2

12.2

28.7

22.5

21.0

VUS040F305

6.2

6.2

16.4

12.8

13.5

VUS050F305

3.7

3.7

10.5

8.2

8.5

VUS065F305

–

–

6.1

4.7

5.6

VUS080F305

–

–

3.9

3.0

3.4

VUS100F305

–

–

1.5

1.5

2.2

Cannot be used to close with the pressure

A

224

At temperatures above 130 °C, accessories are required

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

BUS: 3-way flanged valve, PN 40 (el.) Features • Continuous control of cold/warm/hot water in HVAC installations in closed circuits • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit • Water quality as per VDI 2035 • Not suitable for drinking water • Valve with flange connection as per EN 1092-2, seal form B • Regulating valve, free of silicone grease, matt black • Control passage, linear characteristic, DN 15...100; adjustable with SUT (SAUTER Universal Technology)

BUS015F2*5

valve actuators to equal-percentage • Mixing passage, linear characteristic

V

• The control passage is closed when the spindle is moved out • For use only as a control valve • Valve body made of cast steel • Stainless-steel seat and plug • Stainless-steel spindle • Maintenance-free stuffing box, made of stainless steel, with spring-loaded PTFE washer up to 220 °C, with

graphite seal up to 260 °C Technical data Parameters

Nominal pressure Operating pressure

Connection Control ratio Mixing passage valve characteristic Control passage leakage rate Mixing passage leakage rate

PN 40 40 bar at −10...50 °C 36.3 bar at 120 °C 29.4 bar at 220 °C 27.8 bar at 260 °C Flange as per EN 1092-2, form B > 30: 1 Linear ≤ 0.05% of Kvs value ≤ 1.0% of Kvs value ValveDim app

Ambient conditions

Operating temperature1)

−10...260 °C

Pressure and temperature data Flow parameters PED 2014/68/EU (CE) PESR-2016 (UKCA)

EN 764, EN 1333 EN 60534 Fluid group II (liquids only) Fluid group II (liquids only)

CE/UKCA conformity2)

Overview of types Type

Nominal diame- Kvs value ter

Control passage valve characteristic

Valve stroke

Weight

BUS015F225

DN 15

1.6 m³/h

Linear

20 mm

7.2 kg

BUS015F215

DN 15

2.5 m³/h

Linear

20 mm

7.2 kg

BUS015F205

DN 15

4 m³/h

Linear

20 mm

7.2 kg

BUS020F205

DN 20

6.3 m³/h

Linear

20 mm

8.4 kg

1)

2)

No stuffing box heater required down to –10 °C. At temperatures below −10 °C and down to −60 °C, use special version with bellows seal (available on request, only to DN 100). Application: Water with anti-freeze (glycol up to 55% and brine solution), max. operating pressure 30 bar. Above 130 °C or 180 °C, use the relevant adapter (accessory). Above 220 °C and up to 260 °C, use stuffing box with graphite seal (accessory) Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

225


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Nominal diame- Kvs value ter

Control passage valve characteristic

Valve stroke

Weight

BUS025F205

DN 25

10 m³/h

Linear

20 mm

9.4 kg

BUS032F205

DN 32

16 m³/h

Linear

20 mm

12.4 kg

BUS040F205

DN 40

25 m³/h

Linear

20 mm

15.5 kg

BUS050F205

DN 50

40 m³/h

Linear

20 mm

19.2 kg

BUS065F205

DN 65

63 m³/h

Linear

30 mm

27.6 kg

BUS080F205

DN 80

100 m³/h

Linear

30 mm

36.5 kg

BUS100F205

DN 100

160 m³/h

Linear

30 mm

61.2 kg

CE/UKCA conformity

BUS015F225 BUS015F215 BUS015F205 BUS020F205 BUS025F205 BUS032F205 BUS040F205 BUS050F205 BUS065F205 BUS080F205 BUG100F205

V

EU PED 2014/68/EU

Label

UK PESR-2016 (UKCA)

Label

Art. 4.3

Without CE

Art. 8.3

Without UKCA

Category I

CE

Category I

UKCA

Accessories Type

Description

0372336180

Adaptor (required when temperature of the medium is 130...180 °C)

0372336240

Adaptor (required when temperature of the medium is 180...260 °C)

0378373001

Stuffing box with graphite seal for temperatures of 220...260 °C; DN 15…50

0378373002

Stuffing box with graphite seal for temperatures of 220...260 °C; DN 65…100

Combination of BUS with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AVM322SF132

AVM234SF132

Page

AVM322F120 AVM322F122 239

242

250

AVF234SF132 AVF234SF232 257

Actuating power

1000 N

1000 N

2500 N

2000 N

Control signal

2-/3-point

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

2-/3-point, 0…10 V, 4…20 mA

Running time for DN 15...50

120/240 s

80/120 s

40/80/120 s

40/80/120 s

Running time for DN 65...100

–

–

60/120/180 s

60/120/180 s

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆ps [bar]

BUS015F225 BUS015F215 BUS015F205

35.0

35.0

40.0

40.0

40.0

BUS020F205

35.0

35.0

40.0

34.7

40.0

BUS025F205

17.4

17.4

37.8

29.6

37.0

226

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Actuator Page

AVM322F120 AVM322F122 239

AVM322SF132

AVM234SF132

242

250

AVF234SF132 AVF234SF232 257

BUS032F205

12.2

12.2

27.0

21.1

27.0

BUS040F205

6.2

6.2

16.4

12.8

16.0

BUS050F205

3.7

3.7

10.5

8.2

10.0

BUS065F205

–

–

6.1

4.7

6.1

BUS080F205

–

–

3.9

3.0

3.9

BUS100F205

–

–

2.5

1.9

2.5

Cannot be used as distribution valve

A

At temperatures above 130 °C, accessories are required

V

Right of amendment reserved © 2024 Fr. Sauter AG

227


Valve actuators SAUTER actuators adapt themselves automatically to the valve. Their accurate control provides a high degree of energy efficiency and a low noise level. Furthermore, they can adjust the regulating valves themselves. To save energy, it is possible to include an electric cut-off. SAUTER valve actuators can be used for controllers with a switching or continuous output.

Overview of valve actuators

Type designation Technical data Max. nominal stroke (mm) Max. pushing force (N) Running time s Power supply (V) Control 2-point 3-point Positioner Spring return Combination options with valve Further information

228

AVM 105, 115

AVM 105S, 115S

AVM 215

AVM 215S

8 250, 500 30, 120 24/230

8 250, 500 35, 60, 120 24

8...20 mm 500 7.5 230 V~

10...20 mm 500 7.5 24 V~/=

• • − − VUN/BUN, VUD/BUD, VUE/BUE

• • • − VUN/BUN, VUD/BUD, VUE/BUE

• • − − VUG/BUG, VUS/BUS to DN 025

• • • − VUG/BUG, VUS/BUS to DN 025

Page 230

Page 232

Page 234

Page 236

Right of amendment reserved © 2024 Fr. Sauter AG


Type designation

AVM 321, 322

AVM 321S, 322S

8, 20 1000 6, 12 s/mm 24 / 230

8, 20 1000 4, 12 s/mm 24 / (230)

• • − − VUD/BUD/VQD/BQD, VUE/BUE/VQE/BQE, VUG/BUG VUN/BUN, VUS/BUS, VUP, V6R/B6R

• • • − VUD/BUD/VQD/BQD, VUE/BUE/VQE/BQE, VUG/BUG, VUN/BUN, VUS/BUS, VUP, V6R/B6R

Page 238

Page 241

Technical data Max. nominal stroke (mm) Max. pushing force (N) Running time Power supply (V) Control 2-point 3-point Positioner Spring return Combination options with valve Further information

Type designation

AVM 234S

AVF 234S

AVN 224S

Technical data Max. nominal stroke (mm) Max. pushing force (N) Running time Power supply (V)

40 2500 2, 4, 6, s/mm 24 / (230)

40 2000 2, 4, 6 s/mm 24 / (230)

40 1100 2, 4, 6 s/mm 24 / (230)

• • • − VQD/BQD, VQE/BQE, VUG/BUG, VUS/BUS, VUP, V6R/B6R Page 249

• • • • VQD/BQD, VQE/BQE, VUG/BUG, VUS/BUS, VUP, V6R/B6R Page 256

• • • • VQE/BQE, VUG/BUG, VUS/BUS, VUP, V6R/B6R

Control 2-point 3-point Positioner Spring return Combination options with valve Further information

Right of amendment reserved © 2024 Fr. Sauter AG

Page 259

229


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 105, 115: Valve actuator Features • Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series • For controllers with a switching (2-/3-point) output • Synchronous motor with electronic control unit and time-dependent cut-off • Direction of operation can be selected directly on the cable • Maintenance-free gearbox with magnetic coupling

AVM1*5F***

• Gear unit can be disengaged to position the valve by hand (hexagon key provided) • Connection with valve spindle performed automatically • Cap nut for valve fitting made of brass • Fitting vertically upright to horizontal, not suspended

V

Technical data Power supply

Power supply 24 VAC Power supply 230 VAC

±20%, 50...60 Hz ±15%, 50...60 Hz

Actuator stroke1) Response time

0...8 mm 200 ms

Ambient temperature Media temperature Ambient humidity

−10...55 °C Max. 100 °C 5...95% rh, no condensation

Control

2-/3-point

Weight Housing

0.7 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 3 × 0.75 mm²

Parameters

Ambient conditions

Function

Construction

Housing material Power cable Standards, directives

CE conformity according to

Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

Directive 2006/95/EC Machinery Directive 2006/42/EC (according to Appendix II, 1B)

IP54 (EN 60529), horizontal III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1 EN 60730-2-14 Over-voltage category III Degree of contamination II EEC (II B) EN ISO 12100:2018

Overview of types Type

Voltage

Actuating power

Running time

Power consumption

AVM105F100

230 V~

250 N

30.0 s

2.4 W, 4.5 VA

AVM105F120

230 V~

250 N

120.0 s

2.0 W, 4.0 VA

1)

230

Stroke 10 mm for AVM115F901

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Voltage

Actuating power

Running time

Power consumption

AVM105F122

24 V~

250 N

120.0 s

1.6 W, 1.7 VA

AVM115F120

230 V~

500 N

120.0 s

2.0 W, 4.0 VA

AVM115F122

24 V~

500 N

120.0 s

1.6 W, 1.7 VA

AVM115F901

230 V~

500 N

160.0 s

2.0 W, 4.0 VA

A

AVM115F901: For SAUTER Valveco VCL040 and VCL050, inverse scale, inverse connection

Accessories Type

Description

0372145001

Auxiliary change-over contacts, single

0372145002

Auxiliary change-over contacts, double

0372249001

Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C

0372273001

Adapter for Siemens valve VVG/VXG 44, 48

0372286001

Potentiometer 130 Ω

0372286002

Potentiometer 1000 Ω

0372286003

Potentiometer, 5000 Ω

0372320001

Hexagon key as visualisation for position indicator

A A

V

Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator

Right of amendment reserved © 2024 Fr. Sauter AG

231


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 105S, 115S: Valve actuator with SAUTER Universal Technology (SUT) Features • Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series • For controllers with a switching (2- and 3-point) or continuous (0...10 V) output • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic,

force-dependent cut-off • Automatic recognition of applied control signal (continuous or switched) • Coding switches for selecting characteristic and running time

AVM1*5SF***

• Type of characteristic (linear/equal-percentage) can be set on the actuator • Automatic adaptation to valve stroke

V

• Maintenance-free gear unit • Gear unit can be disengaged in order to position the valve by hand (hexagon key provided) • Connection with valve spindle performed automatically after control voltage is applied • Brass cap nut for fitting the valve • Fitting vertically upright to horizontal, not suspended

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC

±20%, 50...60 Hz -10...20%

Actuator stroke1) Response time Control signal Positional feedback signal Starting point U0 Control span ΔU Switching range Xsh

0...8 mm 200 milliseconds 0…10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 or 10 V 10 V 200 mV

Ambient temperature Ambient humidity Media temperature

-10...55 °C 5…95% rh, no condensation Max. 100 °C

Weight Housing

0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m, 5 × 0.75 mm²

Parameters

Positioner

Ambient conditions

Construction

Housing material Power cable Standards, directives

CE conformity

1)

232

Type of protection Protection class EMC Directive 2014/30/EU

IP54 (EN 60529), horizontal III (IEC 60730) EN 61000-6-1, EN 61000-6-3, EN 61000-6-4

Stroke 10 mm for AVM115SF901

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Overview of types Type

Voltage

Actuating power

Running time

Power consumption

AVM105SF132

24 V~/=

250 N

35/60/120 s

4.8 W, 8.5 VA

AVM115SF132

24 V~/=

500 N

60/120 s

4.9 W, 8.7 VA

AVM115SF901

24 V~/=

500 N

80/160 s

4.9 W, 8.7 VA

A A

AVM105SF132, AVM115SF132: Equal-percentage characteristic, can be converted to linear AVM115SF901: For SAUTER Valveco VCL040 and VCL050, inverse scale, inverse connection

Accessories Type

Description

0313529001

Split-range unit for adjusting sequences, fitted in separate junction box

0372145001

Auxiliary change-over contacts, single

0372145002

Auxiliary change-over contacts, double

0372249001

Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C

0372249002

Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 130… 150 °C

0372273001

Adapter for Siemens valve VVG/VXG 44, 48

0372286001

Potentiometer 130 Ω

0372286002

Potentiometer 1000 Ω

0372286003

Potentiometer, 5000 Ω

A A

V

Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator

Right of amendment reserved © 2024 Fr. Sauter AG

233


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 215: Valve actuator Features • Actuation of 2- and 3-way valves • For controllers with a switching (2-/3-point) output

AVM215F120R

• Synchronous motor with electronic control unit and cut-off • Maintenance-free gear unit • Gear unit can be disengaged in order to position the valve by hand with the provided hexagon key

(load-free) Connection with valve spindle performed semi-automatically • • Fitting vertically upright to horizontal, not suspended

V

Technical data Power supply

Power supply

230 V~ ±15%, 50...60 Hz

Actuator stroke Response time

8...20 mm 200 ms

Ambient temperature Media temperature Ambient humidity

-10...55 °C Max. 100 °C 5...85% rh, no condensation

Control

2-/3-point

Weight Housing

1 kg Lower section black, upper section yellow Flame-retardant plastic

Parameters

Ambient conditions

Function

Construction

Housing material Power cable

1.2 m long, 3 × 0.75 mm2

Standards and directives

CE conformity according to

Type of protection Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

Machinery Directive 2006/42/EC (according to Appendix II, 1B)

IP54 (EN 60529), horizontal 230 V: II (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 Over-voltage category III Degree of contamination II EN ISO 12100:2018

Overview of types Type

Voltage

Actuating power

Running time

Power consumption

AVM215F120R

230 V~

400 N

7.5 s/mm

3.2 W 7.0 VA

Accessories

234

Type

Description

0510390029

Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM215(S)F***R

0510390030

Mounting set for SAUTER VU*/BU* valves with 8 mm stroke for AVM215(S)F***R

0510390031

Mounting set for SAUTER VU*/BU* valves with 20 mm stroke for AVM215(S)F***R

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Description

0510390032

Mounting set for SAUTER V6*/B6* and VX*/BX* valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390033

Mounting set for IMI TA-Fusion valves, thread DN 32 to DN 50 for AVM215(S)F***R

0510390034

Mounting set for IMI TA-Fusion valves, thread DN 65 to DN 80 for AVM215(S)F***R

0510390035

Mounting set for IMI CV valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390036

Mounting set for IMI KTM 512 valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390037

Mounting set for IMI KTM 512 valves, thread DN 65 to DN 100 for AVM215(S)F***R

0510390038

Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM215(S)F***R

0510390039

Mounting set for Danfoss VFS/VL/VF valves: thread DN 15 to DN 50, VEFS2: DN 25 to DN 50 for AVM215(S)F***R

0510390040

Mounting set for Danfoss VRB/VRG valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390060

Adapter set for AVM 2*5 for Schneider V241/V341

0510480003

Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke

0510480004

Dual auxiliary switch unit

0372320001

Hexagon key as visualisation for position indicator

A A

V

Auxiliary change-over contacts: infinitely variable 0...100%, admissible load 3(1.5) A, 24...230 V Accessory 0510390029 can also be used for SAUTER Valveco compact DN 40 and DN 50

Right of amendment reserved © 2024 Fr. Sauter AG

235


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 215S: Valve actuator with SAUTER Universal Technology (SUT) Features • Actuation of 2- and 3-way valves • For controllers with a switching (2- and 3-point) or continuous (0...10 V) output

AVM215SF132

• Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-

dependent cut-off Automatic recognition of applied control signal (continuous or switched) • • Coding switches for selecting characteristic and running time • Type of characteristic (linear/equal-percentage) can be set on the actuator • Automatic adaptation to valve stroke

V

• Direction of operation can be selected directly on the cable • Maintenance-free gear unit • Gear unit can be disengaged in order to position the valve by hand with the hexagon key provided (load-

free) • Connection with valve spindle performed semi-automatically after control voltage is applied • Fitting vertically upright to horizontal, not suspended

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC

±20%, 50…60 Hz −10...20%

Actuator stroke Response time Control signal Position feedback signal Starting point U0 Control span ΔU Switching range Xsh

8...20 mm 200 milliseconds 0...10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 or 10 V 10 V 200 mV

Ambient temperature Ambient humidity Media temperature

−10…55 °C 5…85% rh, no condensation Max. 100 °C

Weight Housing

1 kg Lower section black, upper section yellow Flame-retardant plastic

Parameters

Positioner

Ambient conditions

Construction

Housing material Power cable

1.2 m, 5 × 0.5 mm2

Standards, directives

CE conformity according to

236

Type of protection Protection class EMC Directive 2014/30/EU

IP54 (EN 60529), horizontal III (IEC 60730) EN 61000-6-1, EN 61000-6-3, EN 61000-6-4

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Overview of types Type

Actuating power

Running time

Power consumption

AVM215SF132R 24 VAC/DC

500 N

7.5 s/mm 15 s/mm

3.5 W, 6.6 VA 2.7 W, 5.3 VA

AVM215SF132-7 24 V~/=

500 N

7.5 s/mm

3.5 W, 6.6 VA

A

Voltage

AVM215SF132-7 including adapter set for VDL flanged valves DN 50, DN 65 and DN 80

Accessories Type

Description

0510390029

Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM215(S)F***R

0510390030

Mounting set for SAUTER VU*/BU* valves with 8 mm stroke for AVM215(S)F***R

0510390031

Mounting set for SAUTER VU*/BU* valves with 20 mm stroke for AVM215(S)F***R

0510390032

Mounting set for SAUTER V6*/B6* and VX*/BX* valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390033

Mounting set for IMI TA-Fusion valves, thread DN 32 to DN 50 for AVM215(S)F***R

0510390034

Mounting set for IMI TA-Fusion valves, thread DN 65 to DN 80 for AVM215(S)F***R

0510390035

Mounting set for IMI CV valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390036

Mounting set for IMI KTM 512 valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390037

Mounting set for IMI KTM 512 valves, thread DN 65 to DN 100 for AVM215(S)F***R

0510390038

Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM215(S)F***R

0510390039

Mounting set for Danfoss VFS/VL/VF valves: thread DN 15 to DN 50, VEFS2: DN 25 to DN 50 for AVM215(S)F***R

0510390040

Mounting set for Danfoss VRB/VRG valves, thread DN 15 to DN 50 for AVM215(S)F***R

0510390060

Adapter set for AVM 2*5 for Schneider V241/V341

0510480003

Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke

0510480004

Dual auxiliary switch unit

0372320001

Hexagon key as visualisation for position indicator

A A

V

Auxiliary change-over contacts: infinitely variable 0...100%, admissible load 3(1.5) A, 24...230 V Accessory 0510390029 can also be used for SAUTER Valveco compact DN 40 and DN 50

Right of amendment reserved © 2024 Fr. Sauter AG

237


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 321, 322: Valve actuator Features • In ventilation air conditioning units

for actuation of 2- and 3-way valves of type series AVM 321: VUD, VUE, VUN, BUD, BUE, BUN and AVM 322: V6R, VQD, VQE, VUG, VUP, VUS, B6R, BQD, BQE, BUG, BUS For controllers with a switching output (2-point or 3-point control) • 1)

• Synchronous motor with electronic control unit and load-dependent cut-off • Direction of operation and running time can be set using coding switches

AVM32*F1**

• Crank handle for external manual adjustment with motor cut-off • Low operating noise • Simple assembly onto valve; spindle is automatically connected after nominal voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves

V

• Electrical parallel operation of five actuators • Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Mounting column made of aluminium • Fixing bracket made of cast light alloy for valve fitting with 20 mm stroke and made of plastic for valve

fitting with 8 mm stroke • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable gland made of plastic M20 × 1.5 • Fitting vertically upright to horizontal, not suspended

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption2)

±20%, 50...60 Hz −10...20% ±15% < 2.4 W, < 4.0 VA (at nominal voltage, with movement)

Nominal force3) Operating noise4) Response time Media temperature5)

1000 N < 30 dB (A) at nominal force > 200 ms 0...100 °C

Operating temperature Storage and transport temperature Humidity without condensation

−10...55 °C −40...80 °C 5...85% rh

Type of protection Protection class

IP54 (EN 60529) II (EN 60730), III (EN 60730)

Parameters

Ambient conditions

Standards, directives

1) 2)

3)

4) 5)

238

To be used outside HVAC applications only after consultation with the manufacturer For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V or 230 V, 25 °C ambient temperature, 50 Hz). With boundary conditions (19.2 V~ / 28.8 V~ / 21. V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and running time, the actuating/tensile force is minimised to 800 N Operating noise with the slowest running time, measuring distance 1 m At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater)

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)

EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 (AVM32*F110 and F120) III II 2000 m EN ISO 12100:2018

Overview of types Type

Voltage

Nominal stroke Running time

Power consump- DimenWeight tion sions W × H × D

AVM322F120

230 V~

20 mm

6 (12) s/mm

< 2.4 W, < 4.0 VA

160 × 241 × 88 mm

1.6 kg

AVM322F122

24 V~/=

20 mm

6 (12) s/mm

< 2.0 W, < 3.0 VA

160 × 241 × 88 mm

1.6 kg

AVM321F110

230 V~

8 mm

12 (6) s/mm

< 2.4 W, < 4.0 VA

160 × 187 × 88 mm

1.5 kg

AVM321F112

24 V~/=

8 mm

12 (6) s/mm

< 2.0 W, < 3.0 VA

160 × 187 × 88 mm

1.5 kg

A

AVM32*F1*2: CSA-certified actuators on request (only for devices with supply voltage 24 V~/=). Accessory is not CSA-certified.

A

Power consumption: at nominal voltage and with movement; for more power consumption data, see table “Power consumption for supply voltage”.

V

Accessories AVM 321, 322 Type

Description

0500570001

Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122

0510600001

Cable module, 1.2 m, 3-wire, PVC

0510600002

Cable module, 1.2 m, 3-wire, halogen-free

0510600003

Cable module, 1.2 m, 6-wire, PVC

0510600004

Cable module, 1.2 m, 6-wire, halogen-free

0510600005

Cable module, 5 m, 3-wire, PVC

0510600006

Cable module, 5 m, 3-wire, halogen-free

0510600007

Cable module, 5 m, 6-wire, PVC

0510600008

Cable module, 5 m, 6-wire, halogen-free

AVM 321 Type

Description

0372249001

Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50

0372249002

Adaptor required when temperature of the medium is 130...150 °C, DN 15...50

0510480003

Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke

AVM 322 Type

Description

0372336180

Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)

0372336240

Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)

0510240012

Mounting set for SAUTER V6** / B6** and VX*/BX* valves with 14 mm stroke for AVM322(S)

0510390006

Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)

0510390007

Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)

0510390008

Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)

0510390009

Mounting set for LDM valves up to 20 mm stroke for AVM322(S)

0510390010

Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)

Right of amendment reserved © 2024 Fr. Sauter AG

239


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Description

0510390012

Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)

0510390028

Adapter set for non-SAUTER valves (Frese), stroke 20 mm

0510480004

Double auxiliary contact

A

Accessory is not CSA-certified.

V

240

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 321S, 322S: Valve actuator Features • In ventilation and air conditioning units for actuating 2- and 3-way valves of type series AVM 321S:

VUD, VUE, VUN, BUD, BUE, BUN and AVM 322S: V6R, VQD, VQE, VUG, VUP, VUS, B6R, BQD, BQE, BUG, BUS For controllers with constant output (0...10 V / 4...20 mA) or switching output (2-point or 3-point control) • • BLDC motor (brushless DC) with SUT (SAUTER Universal Technology) electronic control unit of the third

generation and electronic load-dependent cut-off • Automatic detection of applied control signal (continuous or switching), operating indicator using bi-colour

LED • Automatic adaptation to the stroke of the valve, between 8 and 20 mm

AVM32*SF132

• Low operating noise

V

• With the built-in absolute distance measurement system, the position is always maintained in the case of

power failure The direction of operation, characteristic (linear/equal percentage), running time and control signal • (voltage/current) can be adjusted via coding switches • Integrated forced operation can be set via coding switches (with selectable direction of operation) • Easy re-initialisation using a coding switch • Crank handle for external manual adjustment with motor cut-off • Simple assembly onto valve; spindle is automatically connected after control voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Electrical parallel operation of five actuators • Parameterisation option via the BUS interface • Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Mounting column made of aluminium • Fixing bracket made of cast light alloy for valve fitting with 20 mm stroke and made of plastic for valve

fitting with 8 mm stroke • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable glands made of plastic M20 × 1.5 • Fitting vertically upright to horizontal, not suspended • Nominal actuating power 1000 N

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption1)

±20%, 50...60 Hz −10...20% ±15% < 1.7 W, < 3.5 VA (at nominal voltage, with movement)

Nominal force2) Operating noise3) Response time

1000 N < 30 dB (A) at nominal force > 200 ms

Parameters

1)

2)

3)

For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V, 25 °C ambient temperature, 50 Hz). With boundary conditions (19.2 V~ / 28.8 V~ / 21.6 V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and running time, the actuating/tensile force is minimised to 800 N Noise level at the slowest running time, measuring distance 1 m

Right of amendment reserved © 2024 Fr. Sauter AG

241


Valves, control valves, dampers, actuators | Regulating valves and valve actuators 0...100 °C

Media temperature4) Nominal voltage Characteristic Control signal y5)

Linear/equal percentage 0...10 V, Ri ≥ 50 kΩ 4...20 mA, Ri ≤ 50 Ω 0...10 V, load ≥ 5 kΩ 0 or 10 V 4 or 20 mA 10 V 16 mA 160 mV 0.22 mA

Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Control span ΔI Hysteresis Xsh

Ambient conditions

V

Operating temperature Storage and transport temperature Air humidity without condensation

−10...55 °C −40...80 °C 5...85% rh

Type of protection Protection class EMC Directive 2014/30/EU

IP54 (EN 60529) III (EN 60730-1), EN 60730-2-14 EN 610000-6-1, EN 610000-6-2, EN 610000-6-3, EN 610000-6-4 EN 60730-1, EN 60730-2-14 (AVM32*F110 and F120) III II 2000 m EN ISO 12100:2018

Standards, directives

CE conformity according to

Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)

Overview of types Type

Voltage

Nominal stroke

Running time

Dimensions W × H × D

Weight

AVM321SF132

24 V~/=

8 mm

12 (4) s/mm

160 × 187 × 88 mm

1.5 kg

AVM322SF132

24 V~/=

20 mm

6 (4) s/mm

160 × 241 × 88 mm

1.6 kg

A

CSA-certified actuators on request (only for devices with supply voltage 24 V~/=). Accessory is not CSA-certified.

Accessories AVM 321S, 322S Type

Description

0500570003

Constant 230 V module for valve actuators AVM321S and AVM322S

0500420001

Split-range unit module for setting sequences for valve actuators AVM321S and AVM322S

0500420002

4...20 mA feedback module

0500570001

Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122

0510600001

Cable module, 1.2 m, 3-wire, PVC

0510600002

Cable module, 1.2 m, 3-wire, halogen-free

0510600003

Cable module, 1.2 m, 6-wire, PVC

0510600004

Cable module, 1.2 m, 6-wire, halogen-free

0510600005

Cable module, 5 m, 3-wire, PVC

0510600006

Cable module, 5 m, 3-wire, halogen-free

4)

5)

242

At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater) Positional feedback signal: also for 2- or 3-point, depending on type of connection

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Description

0510600007

Cable module, 5 m, 6-wire, PVC

0510600008

Cable module, 5 m, 6-wire, halogen-free

AVM 321S Type

Description

0372249001

Temperature adapter for AVM 321(S), required when temperature of the medium > 100...130 °C (recommended for temperatures < 10 °C) DN 15...50

0372249002

Adaptor required when temperature of the medium is 130...150 °C, DN 15...50

0510480003

Dual auxiliary switch unit for valve actuators AVM215(S), AVM321(S) with 8 mm stroke

AVM 322S Type

Description

0500240001

Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)

0500240002

Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)

0510240012

Mounting set for SAUTER V6** / B6** and VX*/BX* valves with 14 mm stroke for AVM322(S)

0510390006

Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)

0510390007

Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)

0510390008

Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)

0510390009

Mounting set for LDM valves up to 20 mm stroke for AVM322(S)

0510390010

Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)

0510390012

Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)

0510390028

Adapter set for non-SAUTER valves (Frese), stroke 20 mm

0510480004

Double auxiliary contact

A A

V

Accessory is not CSA-certified. The CASE Components configuration tool can be downloaded from the CASE Suite product page (GZS 100, 150) on the SAUTER homepage.

Right of amendment reserved © 2024 Fr. Sauter AG

243


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 322-R: Retrofit actuator Features • In ventilation and air conditioning units

1)

For actuation of 2- and 3-way valves

• For controllers with a switching output (2-point or 3-point control) • Synchronous motor with electronic control unit and load-dependent cut-off

AVM322F12*R

• Direction of operation and positioning time can be set using coding switches • Crank handle for external manual adjustment with motor cut-off • Low operating noise • Simple assembly onto valve; spindle is automatically connected after nominal voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Electrical parallel operation of five actuators

V

• Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable gland made of plastic M20 × 1.5 • Fitting position vertically upright to horizontal, not suspended

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption2)

±20%, 50...60 Hz -10...20% ±15% < 2.4 W, < 4.0 VA (at nominal voltage, with movement)

Nominal force3) Operating noise4) Response time Media temperature5)

1000 N < 30 dB (A) at nominal force > 200 ms 0...100 °C max.

Operating temperature Storage and transport temperature Humidity without condensation

-10...55 °C -40...80 °C 5...85% rh

Dimensions W × H × D Weight

160 × 114 × 88 0.94

Type of protection Protection class

IP54 (EN 60529) II (EN 60730), III (EN 60730)

Parameters

Ambient conditions

Construction

Standards and directives

1) 2)

3)

4) 5)

244

To be used outside HVAC applications only after consultation with the manufacturer For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V or 230 V, 25 °C ambient temperature, 50 Hz). With boundary conditions (19.2 V~ / 28.8 V~ / 21.6 V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and positioning time, the actuating/tensile force is minimised to 800 N Operating noise with the slowest positioning time, measuring distance 1 m At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater)

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)

EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 (AVM322F120R) III II 2,000 m EN ISO 12100:2018

Overview of types Type

Voltage

Nominal stroke

Running time

Power consumption

AVM322F120R

230 V~

20 mm

6 (12) s/mm

< 2.4 W, < 4.0 VA

AVM322F122R

24 V~/=

20 mm

6 (12) s/mm

< 2.4 W, < 4.0 VA

A

V

Power consumption: at nominal voltage and with movement; for more power consumption data, see table “Power consumption for supply voltage”

Accessories Type

Description

0500240001

Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)

0500240002

Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)

0500570001

Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122

0510390020

Mounting set for SAUTER VU*/BU* and VQ*/BQ* valves with 20 mm stroke for AVM322(S)***R

0510390021

Mounting set for SAUTER V6*/B6* and VX*/BX* valves with 14 mm stroke for AVM322(S)***R

0510390022

Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)***R

0510390023

Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)***R

0510390024

Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)***R

0510390025

Mounting set for LDM valves up to 20 mm stroke for AVM322(S)***R

0510390026

Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)***R

0510390027

Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)***R

0510390028

Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM322(S)***R

0510390041

Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM322(S)***R

0510390061

Mounting set for Schneider V241/V341 valves, DN 15 to DN 50 for AVM322(S)***R

0510480004

Dual auxiliary switch unit

Right of amendment reserved © 2024 Fr. Sauter AG

245


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 322S-R: Retrofit actuator Features • In ventilation and air conditioning units

1)

For actuation of 2- and 3-way valves

• For controllers with constant output (0...10 V / 4...20 mA) or switching output (2-point or 3-point control) • BLDC motor (brushless DC) with SUT (SAUTER Universal Technology) electronic control unit of the third

AVM322SF132R

generation and electronic load-dependent cut-off • Automatic detection of applied control signal (continuous or switching), operating indicator using bi-colour

LED • Automatic adaptation to the stroke of the valve, between 8 and 20 mm • Low operating noise • With the built-in absolute distance measurement system, the position is always maintained in the case of

power failure • The direction of operation, characteristic (linear/equal percentage), positioning time and control signal (voltage/current) can be adjusted via coding switches Integrated forced operation can be set via coding switches (with selectable direction of operation) •

V

• Easy re-initialisation using a coding switch • Crank handle for external manual adjustment with motor cut-off • Simple assembly onto valve; spindle is automatically connected after control voltage is applied • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Electrical parallel operation of five actuators • Parameterisation option via the BUS interface • Three-piece housing made of flame-retardant yellow/black plastic and seals with type of protection IP54 • Maintenance-free gearbox made of plastic; threaded spindle and gearbox base-plates made of steel • Patented actuator-valve coupling • Electrical connections (max. 1.5 mm²) with screw terminals • Two break-out cable inlets for metric cable glands made of plastic M20 × 1.5 • Fitting position vertically upright to horizontal, not suspended • Nominal actuating power 1000 N

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption2)

±20%, 50...60 Hz -10...20% ±15% < 1.7 W, < 3.5 VA (at nominal voltage, with movement)

Positioning time (s/mm) Nominal force3) Nominal stroke Operating noise4) Response time Media temperature5)

6 (4) 1000 N 20 mm < 30 dB (A) at nominal force > 200 ms 0...100 °C

Parameters

1) 2)

3)

4) 5)

246

To be used outside HVAC applications only after consultation with the manufacturer For power consumption in combination with accessory 0500570001, see section “Power consumption at nominal voltage” Actuating power 1000 N under nominal conditions (24 V, 25 °C ambient temperature, 50 Hz); With boundary conditions (19.2 V~ / 28.8 V~ / 21.6 V= / 28.8 V=, -10 °C / 55 °C, 60 Hz) and positioning time, the actuating/tensile force is minimised to 800 N Noise level with the slowest positioning time, measuring distance 1m At media temperature > 100 °C appropriate accessory must be used (temperature adapter); at media temperature < 0 °C appropriate accessory must be used (stuffing box heater)

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Nominal voltage Characteristic Control signal y6)

24 V~/= Linear/equal percentage 0...10 V, Ri ≥ 50 kΩ 4...20 mA, Ri ≤ 50 Ω 0...10 V, load ≥ 5 kΩ 0 or 10 V 4 or 20 mA 10 V 16 mA 160 mV 0.22 mA

Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Control span ΔI Hysteresis Xsh

Ambient conditions

Operating temperature Storage and transport temperature Air humidity without condensation

-10...55 °C -40...80 °C 5...85% rh

Dimensions W × H × D Weight

160 × 114 × 88 0.94

Type of protection Protection class EMC Directive 2014/30/EU

IP54 (EN 60529) II (EN 60730-1), EN 60730-2-14 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 III II 2,000 m EN ISO 12100:2018

V

Construction

Standards and directives

CE conformity according to

Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)

Overview of types Type

Voltage

AVM322SF132R 24 V~/=

Nominal stroke

Running time

Power consumption

20 mm

6 (4) s/mm

< 1.7 W, < 3.5 VA

Accessories Type

Description

0500240001

Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)

0500240002

Adaptor for media temperature above 130 °C to 200 °C for AVM322(S)

0500420001

Split-range unit module for setting sequences for valve actuators AVM321S and AVM322S

0500420002

4…20 mA feedback module for valve actuators AVM321S and AVM322S

0500570001

Energy module for reset function for valve actuators AVM321S/AVM322S and AVM321F112/AVM322F122

0500570003

Constant 230 V module for valve actuators AVM321S and AVM322S

0510390020

Mounting set for SAUTER VU*/BU* and VQ*/BQ* valves with 20 mm stroke for AVM322(S)***R

0510390021

Mounting set for SAUTER V6*/B6* and VX*/BX* valves with 14 mm stroke for AVM322(S)***R

0510390022

Mounting set for Siemens valves with 20 mm stroke, spindle diameter 10 mm for AVM322(S)***R

0510390023

Mounting set for Johnson Controls valves up to 20 mm stroke for AVM322(S)***R

0510390024

Mounting set for Honeywell valves up to 20 mm stroke for AVM322(S)***R

0510390025

Mounting set for LDM valves up to 20 mm stroke for AVM322(S)***R

0510390026

Mounting set for ITT-Dräger valves up to 20 mm stroke for AVM322(S)***R

0510390027

Mounting set for Belimo valves up to 20 mm stroke for AVM322(S)***R

0510390028

Mounting set for Frese valves up to 20 mm stroke, flange DN 50 to DN 80 for AVM322(S)***R

6)

Positional feedback signal: also for 2- or 3-point, depending on type of connection

Right of amendment reserved © 2024 Fr. Sauter AG

247


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Type

Description

0510390041

Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM322(S)***R

0510390061

Mounting set for Schneider V241/V341 valves, DN 15 to DN 50 for AVM322(S)***R

0510480004

Dual auxiliary switch unit

A A

Accessory is not CSA-certified. The CASE Components configuration tool can be downloaded from the CASE Suite product page (GZS 100, 150) on the SAUTER homepage.

V

248

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVM 234S: SUT valve actuator with positioner Features • Activation of 2-way and 3-way valves of the VQD/BQD and VQE/BQE series, as well as VUG/BUG,

VUS/BUS, VUP, V6R/B6R and VDL • For controllers with constant output (0...10 V or 4...20 mA) or switching output (2-point or 3-point control) • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-

dependent cut-off • Simple assembly with valve; spindle is automatically connected after control voltage is applied (patented

system) • Automatic detection of applied control signal (constant or switched); indicated by two LEDs

AVM234SF132

• Coding switches for selecting characteristic and running time • Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator

V

• Automatic adaptation to the stroke of the valve (min. valve stroke 8 mm, max. valve stroke 49 mm). The

measured stroke is saved and is not lost even in the event of a power failure • Direction of operation can be selected via screw terminals when making the electrical connection • Crank handle for external manual adjustment with motor cut-off and as trigger for a re-initialisation • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Power supply 230 V with module or direct connection for 24 VAC / 24 VDC; continuous activation also

admissible with 230 V • Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel • Mounting column made of stainless steel; mounting bracket made of cast light alloy for fitting the valve • Electrical connections (max. 2.5 mm²) with screw terminals • Three pre-scored cable inlets for M20 × 1.5 (2×) and M16 × 1.5 • Fitting vertically upright to horizontal, not suspended

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption1)

±20%, 50…60 Hz ±15% ±15%, 50...60 Hz (with accessories) 24 VAC/24 VDC 10 W/20 VA 230 VAC (with accessories) 13 W/28 VA

Running time Actuator stroke Response time for 3-point Control signal 1 Control signal 2 Position feedback signal Starting point U0 Control span ΔU Switching range Xsh

2/4/6 s/mm 0...49 mm 200 milliseconds 0...10 V, Ri >100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V, load > 10 kΩ 0 or 10 V 10 V 300 mV

Ambient temperature Ambient humidity Media temperature2)

−10…55 °C < 95% rh, no condensation Max. 120 °C

Parameters

Positioner

ValveDim app

Ambient conditions

1) 2)

Choose transformers for this value, otherwise malfunctions may occur For higher temperatures of the medium (180 °C or 240 °C), use an adapter (see accessories)

Right of amendment reserved © 2024 Fr. Sauter AG

249


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Construction

Weight Housing Housing material

4.1 kg Two-part, yellow Flame-retardant plastic

Type of protection Protection class Over-voltage categories Degree of contamination LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA)4) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

IP66 (EN 60529) III (IEC 60730) III III EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 61000-6-2, EN 61000-6-4 EN 61000-6-2, EN 61000-6-4 EN IEC 63000:2018

Standards, directives

CE/UKCA conformity3)

V

EN IEC 63000:2018

Overview of types

/ /

Actuator for valves: VQD/BQD, VQE/BQE, VUG/BUG, VUP, VUS/BUS Actuator with mounting set (see accessories) for valves: V6R, B6R

Type

Voltage

Actuating power

Running time

Power consumption

AVM234SF132

24 VAC/DC

2500 N

2/4/6 s/mm

10 W, 20 VA

AVM234SF132-5 24 VAC/DC

2500 N

2/4/6 s/mm

10 W, 20 VA

AVM234SF132-6 24 VAC/DC

2500 N

2/4/6 s/mm

10 W, 20 VA

AVM234SF132-7 24 VAC/DC

1700 N

2/4/6 s/mm

10 W, 20 VA

Accessories Type

Description

0313529001

Split-range unit for setting sequences

Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA Type

Description

0372332001

230 V ±15%, supply voltage

0372332002

100 V ±15%, supply voltage

Auxiliary change-over contacts (2 each) 12...250 VAC Type

Description

0372333001

Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A

0372333002

Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A

Potentiometers Type

Description

0372334001

Potentiometer, 2000 Ω, 1 W, 24 V

0372334006

Potentiometer, 1000 Ω, 1 W, 24 V

Adapters for high temperatures Type

Description

0372336180

Intermediate piece (required when temperature of the medium is 130...180 °C)

0372336240

Adapter (required when temperature of the medium is 180...200 °C)

3)

4)

250

Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues EN 61000-6-2: (HF immunity limitation. Feedback signal between 80 MHz and 1000 MHz criterion B, otherwise criterion A)

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Mounting set for AVM234SF132 on SAUTER valves (no adapter needed for 0372338 002) Type

Description

0372338001

V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm

0372338002

V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm

0372338003

Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132

0372338004

Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132

Adapter set for non-SAUTER valves Type

Description

0372376010

Siemens with 20 mm stroke or 10 mm spindle diameter

0372376014

Siemens with 40 mm stroke or 14 mm spindle diameter

0372376015

Siemens VXF32, PN 10, DN 100…150; VXF22, PN 6, DN 100

0372377001

Johnson Controls DN 15…150, 14, 25, 40 mm stroke, spindle diameter 10, 12, 14 mm

0372378001

Honeywell with 20 mm stroke

0372378002

Honeywell with 38 mm stroke

0372386001

LDM type RY113 R/M

0372389001

ITT-Dräger, DN 15…32

0372389002

ITT-Dräger, DN 40…50

0378263001

End stop (needed for V/BXD, V/BXE DN 15…50, V/B6 DN 15 with kvs ≤ 1 m³/h)

0386263001

Cable gland M16 × 1.5

0386263002

Cable gland M20 × 1.5

0372461001

Forced operation for AV×2×4S

0372387001

SAUTER Satchwell VZF1727 mounting set

0510390052

Adapter set for non-SAUTER valves (Frese), stroke 20 mm

0510390053

Adapter set for non-SAUTER valves (Frese), stroke 40/43 mm

A

V

Adapter: Not needed for version AV*2*4SF132-6

Right of amendment reserved © 2024 Fr. Sauter AG

251


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVF 124: Valve actuator with spring return Features • Activation of 2- and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series, DN 15 to DN 50. • For controllers with a switching output (3-point control) • Spring return moves the unit to the end position in the event of a power failure or when a limit controller is

activated • Stepping motor with electronic control unit and electronic, force-dependent cut-off • Maintenance-free gear unit

AVF124F130

• LED display • Coding switch for changing the running time • Electrical connections (max. 1.5 mm²) with screw terminals

V

• Cable inlet M20 × 1.5

AVF124F130

• Fitting vertically upright to horizontal, not suspended

Technical data Power supply

AVF124F230

Power supply Power consumption

230 V~, ±15%, 50...60 Hz 4 W, 7.6 VA

Running time of motor Running time of spring Actuating power Actuator stroke Response time

60/120 s 18 s ±10 500 N 0...8 mm 200 ms

Ambient temperature Media temperature Ambient humidity

5...60 °C Max. 100 °C < 95% rh, no condensation

Weight Housing Housing material Materials for gearbox and fitting bracket

2.4 kg Lower section black, cover transparent Fire-retardant plastic Pressure-cast zinc

Type of protection1) Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Software Mode of operation

IP54 as per EN 60529 II (IEC 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III III A (EN 60730) Type 1 AA (200 ms, EN 60730)

Parameters

Ambient conditions

Construction

Standards and directives

Overview of types Type

Voltage

Nominal stroke

Running time

Power consumption Reset function

AVF124F130

230 V~

8 mm

60/120 s

4 W, 7.6 VA

Spindle retracted

AVF124F230

230 V~

8 mm

60/120 s

4 W, 7.6 VA

Spindle extended

1)

252

Type of protection IP54 only with cable gland

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

A A

AVF124F130: Valve normally closed (NC) with: VUD, BUD, VUE, BUE, VUN, BUN AVF124F230: Valve normally open (NO) with: VUD, BUD, VUE, BUE, VUN, BUN

Accessories Type

Description

0370881001

Auxiliary change-over contacts, single

0372249001

Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C

0372249002

Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 130… 150 °C

0372460001

Cable screw fitting (plastic M20 × 1,5) incl. locking nut and seal

A

Auxiliary change-over contacts: Infinitely variable, admissible load 2(1) A, 12...250 V~, min. load 250 mA, 12 V~

V

Right of amendment reserved © 2024 Fr. Sauter AG

253


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVF 125S: SUT valve actuator with spring return Features • Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series • For controllers with switching (2- and 3-point) or continuous output (0…10 V, 4…20 mA) • Spring return moves the unit to the end position in the event of a power failure or when a limit controller is

activated • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic,

force-dependent cut-off AVF125SF132

• Automatic recognition of applied control signal (continuous or switched) • Coding switches for selecting characteristic and running time • Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator • Direction of operation can be selected via screw terminals when making the electrical connection

V

• Maintenance-free gear unit

AVF125SF132

• LED display • Electrical connections (max. 1.5 mm²) with screw terminals • Cable inlet M20 × 1.5 • Fitting vertically upright to horizontal, not suspended

AVF125SF232

Technical data Power supply

Power supply Power consumption Power consumption on starting1)

24 V~, ±20%, 50...60 Hz 5 W, 8.4 VA 30 VA (max. 1 s)

Running time of motor Running time of spring Actuating power Actuator stroke Control signal 1 Control signal 2 Positional feedback signal Starting point U0 Control span ΔU Switching range Xsh

60/120 s 18 s ±10 500 N 0...8 mm 0...10 V, Ri = 100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V; load > 2.5 kΩ 0 or 10 V 10 V 200 mV

Ambient temperature Ambient humidity Media temperature

–10...55 °C < 95% rh, no condensation Max. 100 °C

Weight Housing Housing material Materials for gearbox and fitting bracket

2.4 kg Lower section black, cover transparent Fire-retardant plastic Pressure-cast zinc

Type of protection2) Protection class

IP54 as per EN 60529 III (IEC 60730)

Parameters

Positioner

Ambient conditions

Construction

Standards and directives

1) 2)

254

Only in the event of a restart or after a spring return Type of protection IP54 only with M20 cable gland

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators EMC Directive 2014/30/EU Software Mode of operation Machinery Directive 2006/42/EC (according to Appendix II, 1B)

EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 A (EN 60730) Type 1 AA (200 ms, EN 60730) EN ISO 12100:2018

Overview of types

/

For valves with equal-percentage characteristic; can be changed to linear

Type

Voltage

Nominal stroke

Running time

Power consumption Reset function

AVF125SF132

24 V~

8 mm

60/120 s

5 W, 8.4 VA

Spindle retracted

AVF125SF232

24 V~

8 mm

60/120 s

5 W, 8.4 VA

Spindle extended

A

AVF125SF132: Actuator spindle normally retracted; valve normally closed (NC) with: VUD, BUD, VUE, BUE, VUN, BUN

A

AVF125SF232: Actuator spindle normally extended; valve normally open (NO) with: VUD, BUD, VUE, BUE, VUN, BUN

V

Accessories Type

Description

0313529001

Split-range unit for adjusting sequences, fitted in separate junction box

0370881001

Auxiliary change-over contacts, single

0372249001

Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 100… 130 °C

0372249002

Temperature adapter for AVM1x5(S), AVF12x(S), AVM321(S), media temperature > 130… 150 °C

0372460001

Cable screw fitting (plastic M20 × 1,5) incl. locking nut and seal

A

Auxiliary change-over contacts: Infinitely variable, admissible load 2(1) A, 12...250 V~, min. load 250 mA, 12 V~

Right of amendment reserved © 2024 Fr. Sauter AG

255


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVF 234S: SUT valve actuator with spring return Features • Activation of 2-way and 3-way valves of the VQD/BQD, VQE/BQE, VUG/BUG, VUP, VUS/BUS and

V6R/B6R series • For controllers with switching (2- and 3-point) and continuous (0...10 V, 4...20 mA) output • Spring return moves to end position in the event of a power failure/interruption or when a limit controller is

activated • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-

AVF234SF132

dependent cut-off • Simple assembly with valve; spindle is automatically connected after control voltage is applied (patented

system) • Automatic detection of applied control signal (constant or switched); indicated by two LEDs • Coding switches for selecting characteristic and running time

V

• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator

AVF234SF132

• Automatic adaptation to the stroke of the valve (min. valve stroke 8 mm, max. valve stroke 49 mm). The

measured stroke is saved and is not lost even in the event of a power failure • Direction of operation can be selected via screw terminals when making the electrical connection • Crank handle for external manual adjustment with motor cut-off and as trigger for a re-initialisation • Numerous adapters enable the unit to be fitted onto non-SAUTER valves

AVF234SF232

• Power supply 230 V with module or direct connection for 24 VAC or 24 VDC; continuous activation also

admissible with 230 V Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel • • Spring pack and mounting column made of stainless steel; mounting bracket made of cast light alloy for

valve fitting Electrical connections (max. 2.5 mm²) with screw terminals • • Three pre-scored cable inlets for M20 × 1.5 (2×) and M16 × 1.5 • Fitting vertically upright to horizontal, not suspended

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption1)

±20%, 50...60 Hz ±15% ±15%, 50...60 Hz (with accessories) 24 VAC/24 VDC 10 W, 20 VA 230 VAC (with accessories) 13 W/28 VA

Running time of motor Running time of spring2) Actuating power Response time for 3-point Number of spring returns Control signal 1 Control signal 2 Positional feedback 0...10 V Starting point U0 Control span ΔU Switching range Xsh

2/4/6 s/mm 15...30 s 2000 N 200 ms > 40 000 0...10 V, Ri = 100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V, load > 10 kΩ 0 V or 10 V 10 V 300 mV

Parameters

ValveDim app

Positioner

1) 2)

256

Choose transformers for this value, otherwise malfunctions may occur Return time equates to a stroke of 14...40 mm and does not depend on the set running time

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Ambient conditions

Ambient temperature Ambient humidity Media temperature3)

−10...55 °C < 95% rh, no condensation Max. 130 °C (180 °C or 240 °C with accessories)

Weight Housing Housing material

5.6 kg Two-part, yellow Flame-retardant plastic

Type of protection Protection class Over-voltage categories Degree of contamination LV-D 2014/35/EU (CE) EESR-2016 (UKCA) EMC-D 2014/30/EU (CE) EMC-2016 (UKCA)5) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

IP66 (EN 60529) III (IEC 60730) III III EN 60730-1, EN 60730-2-14 EN 60730-1, EN 60730-2-14 EN 61000-6-2, EN 61000-6-4 EN 61000-6-2, EN 61000-6-4 EN IEC 63000:2018

Construction

Standards, directives

CE/UKCA conformity4)

V

EN IEC 63000:2018

Overview of types Type

Voltage

Stroke

Running time

Power consumption Direction of operation of spring

AVF234SF132

24 VAC/DC

14...40 mm

2/4/6 s/mm

10 W, 20 VA

Spindle retracted

AVF234SF132-5 24 VAC/DC

14 mm

2/4/6 s/mm

10 W, 20 VA

Spindle retracted

AVF234SF232

0...40 mm

2/4/6 s/mm

10 W, 20 VA

Spindle extended

24 VAC/DC

A

AVF234SF132: Valve normally closed (NC) with: VQD/BQD, VQE/BQE, VUG/BUG, BUS; valve normally open (NO) with: VUS, VUP

A A

AVF234SF132-5: Valve normally closed (NC) with: V6R, B6R AVF234SF232: Valve normally open (NO) with: VQD/BQD, VQE/BQE, VUG/BUG, BUS; valve normally closed (NC) with: VUS, VUP

Accessories Type

Description

0313529001

Split-range unit for setting sequences

Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA Type

Description

0372332001

230 V ±15%, supply voltage

0372332002

100 V ±15%, supply voltage

Auxiliary change-over contacts (2 each) 12...250 VAC Type

Description

0372333001

Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A

0372333002

Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A

3) 4) 5)

An adapter is needed for higher temperatures (180 °C or 240 °C) (see accessories) Explanation of abbreviations in “Additional technical data” section EN 61000-6-2: HF immunity, limitation of feedback signal between 80 MHz and 1000 MHz criterion B, otherwise criterion A

Right of amendment reserved © 2024 Fr. Sauter AG

257


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Potentiometers Type

Description

0372334001

Potentiometer, 2000 Ω, 1 W, 24 V

0372334006

Potentiometer, 1000 Ω, 1 W, 24 V

Adapters for high temperatures Type

Description

0372336180

Intermediate piece (required when temperature of the medium is 130...180 °C)

0372336240

Adapter (required when temperature of the medium is 180...200 °C)

Mounting set for AVF234SF*32 onto SAUTER valves (no adapter needed for 0372338 002)

V

Type

Description

0372338001

V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm

0372338002

V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm

0372338003

Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132

0372338004

Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132

Adapter set for non-SAUTER valves Type

Description

0372376010

Siemens with 20 mm stroke or 10 mm spindle diameter

0372376014

Siemens with 40 mm stroke or 14 mm spindle diameter

0372376015

Siemens VXF32, PN 10, DN 100…150; VXF22, PN 6, DN 100

0372377001

Johnson Controls DN 15…150, 14, 25, 40 mm stroke, spindle diameter 10, 12, 14 mm

0372378001

Honeywell with 20 mm stroke

0372378002

Honeywell with 38 mm stroke

0372386001

LDM type RY113 R/M

0372389001

ITT-Dräger, DN 15…32

0372389002

ITT-Dräger, DN 40…50

0378263001

End stop (needed for V/BXD, V/BXE DN 15…50, V/B6 DN 15 with kvs ≤ 1 m³/h)

0386263001

Cable gland M16 × 1.5

0386263002

Cable gland M20 × 1.5

0372387001

SAUTER Satchwell VZF1727 mounting set

0372461001

Forced operation for AV×2×4S

0510390052

Adapter set for non-SAUTER valves (Frese), stroke 20 mm

0510390053

Adapter set for non-SAUTER valves (Frese), stroke 40/43 mm

A A

258

Adapter: Not needed for version AV*2*4SF132-6 Potentiometer 130 Ω: This potentiometer must only be used as a voltage divider.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators

AVN 224S: SUT valve actuator with safety function Features • Actuation of 2-way or 3-way valves of type series VUG/BUG and VUP as per DIN EN 14597 • For controllers with constant output (0...10 V or 4...20 mA) and switching output (2-point or 3-point control) • Valve actuator with safety function (as per DIN EN 14597) and pushing force of 1100 N, in normally

closed (NC) or normally open (NO) version • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic, force-

dependent cut-off • Simple assembly with valve; spindle is automatically connected after control voltage is applied (patented

system) • Automatic recognition of applied control signal (constant or switched); indicated by two LEDs

AVN224SF132

• Coding switches for selecting characteristic and running time

V

• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator • Automatic adaptation to the valve stroke (min. valve stroke 8 mm, max. valve stroke 49 mm); the measured

stroke is stored and is not lost in the event of a power failure • Direction of operation can be selected via screw terminals when making the electrical connection

AVN224SF132

• Push-buttons on outside of housing for manual adjustment with motor cut-off and as trigger for re-

initialisation • Numerous adapters enable the unit to be fitted onto non-SAUTER valves • Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel

AVN224SF232

• Spring pack and mounting column made of stainless steel; mounting bracket made of cast light alloy for valve fitting Electrical connections (max. 2.5 mm2) with screw terminals • • Three break-out cable inlets for M20 × 1.5 (2×) and M16 × 1.5 • Fitting vertically upright to horizontal, not suspended

The following features and certifications do not apply to the United Kingdom of Great Britain and Northern Ireland (UK): • TÜV certification

The product is not designed for use in the United Kingdom. Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Power consumption

±20%, 50...60 Hz ±15% ±15%, 50...60 Hz (with accessories) 24 VAC/24 VDC 10 W, 18 VA 230 VAC (with accessories) 11 W / 24 VA

Running time of motor Running time of spring1) Actuating power Number of spring returns Response time for 3-point Control signal 1 Control signal 2 Position feedback signal Starting point U0 Control span ΔU

2/4/6 s/mm 15...30 s 1100 N > 40 000 200 ms 0...10 V, Ri = 100 kΩ 4...20 mA, Ri = 50 Ω 0...10 V, load > 10 kΩ 0 V or 10 V 10 V

Parameters

Positioner

1)

ValveDim app

Spring return time equates to a stroke of 14...40 mm and does not depend on the set running time

Right of amendment reserved © 2024 Fr. Sauter AG

259


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Switching range Xsh

300 mV

Ambient temperature Ambient humidity Media temperature

−10...55 °C < 95% rh, no condensation Max. 130 °C

Weight Housing Housing material

5.6 kg Two-part, yellow Flame-retardant plastic

Type of protection Protection class EMC Directive 2014/30/EU2) Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination PED 2014/68/EU, cat. IV3)

IP66 (EN 60529) III (IEC 60730) EN 61000-6-2, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III III Category IV, fluid group II, liquid or steam pressure modules B+D TÜV ID: 18388

Ambient conditions

Construction

Standards, directives

V

Test mark4)

Overview of types Type

Voltage

Nominal stroke

Running time

Power consumption Direction of operation of spring

AVN224SF132

24 VAC/DC

40 mm

2/4/6 s/mm

10 W, 18 VA

Spindle retracted

AVN224SF232

24 VAC/DC

40 mm

2/4/6 s/mm

10 W, 18 VA

Spindle extended

A

AVN224SF132: Valve normally closed (NC) with: VUG, BUG (as per DIN EN 14597); valve normally open (NO) with: VUP

A

AVN224SF232: Valve normally open (NO) with: VUG, BUG; valve normally closed (NC) with: VUP (as per DIN EN 14597)

Accessories Type

Description

0313529001

Split-range unit for setting sequences

Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA Type

Description

0372332001

230 V ±15%, supply voltage

0372332002

100 V ±15%, supply voltage

Auxiliary change-over contacts (2 each) 12...250 VAC Type

Description

0372333001

Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A

0372333002

Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A

Potentiometers Type

Description

0372334001

Potentiometer, 2000 Ω, 1 W, 24 V

0372334006

Potentiometer, 1000 Ω, 1 W, 24 V

2)

3) 4)

260

EN 61000-6-2: HF immunity, limitation of feedback signal between 80 MHz and 1000 MHz criterion B, otherwise criterion A Only for VUP, VUG and BUG valves. See PDS for the valves. For the United Kingdom of Great Britain and Northern Ireland (UK): Use is not permitted.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Regulating valves and valve actuators Adapters for high temperatures Type

Description

0372336180

Intermediate piece (required when temperature of the medium is 130...180 °C)

0372336240

Adapter (required when temperature of the medium is 180...200 °C)

Mounting set for AVN224SF*32 onto SAUTER valves (no adapter needed for 0372338 002) Type

Description

0372338001

V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm

0372338002

V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm

0372338003

Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132

0372338004

Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132

Adapter set for non-SAUTER valves Type

Description

0372376010

Siemens with 20 mm stroke or 10 mm spindle diameter

0372376014

Siemens with 40 mm stroke or 14 mm spindle diameter

0372377001

Johnson Controls DN 15…150, 14, 25, 40 mm stroke, spindle diameter 10, 12, 14 mm

0372378001

Honeywell with 20 mm stroke

0372378002

Honeywell with 38 mm stroke

0372386001

LDM type RY113 R/M

0372389001

ITT-Dräger, DN 15…32

0372389002

ITT-Dräger, DN 40…50

0378263001

End stop (needed for V/BXD, V/BXE DN 15…50, V/B6 DN 15 with kvs ≤ 1 m³/h)

0386263001

Cable gland M16 × 1.5

0386263002

Cable gland M20 × 1.5

0372387001

SAUTER Satchwell VZF1727 mounting set

0372461001

Forced operation for AVx2xS

0510390052

Adapter set for non-SAUTER valves (Frese), stroke 20 mm

0510390053

Adapter set for non-SAUTER valves (Frese), stroke 40/43 mm

A A

V

Adapter: Not needed for version AV*2*4SF132-6 Potentiometer 130 Ω: This potentiometer must only be used as a voltage divider.

Right of amendment reserved © 2024 Fr. Sauter AG

261


Dynamic regulating valves The automatic hydronic balancing of water distribution networks using dynamic SAUTER valves provides correct supply to air-conditioning, cooling and heating devices. These include fan coil units, chilled ceilings, central underfloor heating systems, remote heating, air recirculation devices and plant segments. SAUTER Valveco and eValveco prevent under- or oversupply and the resulting temperature variations caused by pressure changes in the distribution network.

Overview of dynamic regulating valves

Type designation Application Preheater for ventilation / air-conditioning, cooler Chilled ceiling, underfloor heating Static heating District heating Version 2-way 3-way 6-way Female thread Male thread Flange Temperature measurement Electronic control Nominal pressure Communication Interfaces Protocols Combination options with actuator Further information

262

UVC 106 eValveco

UVC102MF065…100 eValveco

−

•

• − −

− • −

− − • − • − • • PN 16

• − − − − • • • PN 16

− Modbus RTU, BACnet MS/TP integrated

Bluetooth Modbus RTU, BACnet MS/TP integrated

Page 264

Page 266

Right of amendment reserved © 2024 Fr. Sauter AG


Type designation

VDL 010…032 Valveco compact

VDL 040, 050 Valveco compact

VDL 050…100 Valveco flange

•

•

•

• • −

• • −

− • •

• − − − • − − − PN 25 AXM 217(S) AXT 301, 311, AXS 315S AXF 217S, AVM 215(S) Page 269

• − − • − − − − PN 25 AXM 217(S) AXT 301, 311, AXS 315S AXF 217S, AVM 215(S) Page 269

• − − − − • − − PN 16 AVM 215, AVM 234

Application Preheater for ventilation / air-conditioning, cooler Chilled ceiling, underfloor heating Static heating District heating Version 2-way 3-way 6-way Female thread Male thread Flange Temperature measurement Electronic control Nominal pressure Combination options with actuator Further information

Right of amendment reserved © 2024 Fr. Sauter AG

Page 274

263


Valves, control valves, dampers, actuators | Multi-function valves

UVC 106: Dynamic flow control system with 6-way ball valve, eValveco Features • Patented pressure-independent, variable flow control (EP 2307938) • Integrated flow measurement with feedback • Easy integration into every building management system • Variable flow rate setpoint for heating and cooling modes • For climate ceilings with changeover (4-pipe) • Integration into the building management system via BACnet MS/TP or Modbus/RTU with RS-485 interface

UVC106MF0*5

V

UVC106BF0*5

Technical data Electronic power supply

~

Power supply Rated power during continuous operation Power consumption when idle Peak inrush current Input signal

M Feedback signal1) Feedback signal resolution

24 VAC, ±20%, 50 Hz 3 W (4 VA) 1.5 W (2 VA) 5 A [3 ms] Xs: 0…10 VDC (0.17 mA), split-range 0.5…4.5 VDC heating 5.5…9.5 VDC cooling Ri ≥ 60 kΩ Xi: 0…10 VDC (max. 2 mA) Approx. 100 mV

Parameters

Setpoint adjustment Type of sensor Unit of measurement2)

Valve and actuator

Measuring accuracy Minimum controllable flow3) Readiness for operation Nominal pressure Differential pressure ∆p4) Medium5) Media temperature Leakage rate in % of Kvs Control characteristic Operating noise (unloaded)6)

Analogue (Y1) or via Modbus/RTU or BACnet MS/TP TTM ultrasonic sensor, no moving parts [m3/h], l/s, l/min, gpm (UK), gpm (US) ±3% of actual value 3 l/h 3…5 minutes after switching on PN16 Max. 2 bar (200 kPa) Water (glycol-free) 5…90 °C 0.001 % Equal-percentage (factory setting) or linear < 30 dB (A)

ValveDim app Interfaces, communication

BMS integration

Interface Protocol Connection7) Cable type

1) 2) 3) 4) 5) 6) 7)

264

STP cable, 1 × 2-wire, twisted Modbus/RTU, slave (MF) or BACnet MS/TP (BF) RS-485, 2-core twisted (with shared lead) Shielded 2-core cable, STP or FTP

In relation to the measured actual flow. Unit in [ ]: Factory setting In relation to the measured actual flow No minimum differential pressure required In accordance with VDI 2035 sheet 2 Measuring distance 1 m, actuator not under load Not electrically isolated

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Multi-function valves Baud rate8) Terminating resistor

9600, 19200, 38400 baud At both ends 120 Ω

Power cable

PVC cable, 7 × 0.5 mm2 (length 1 m) Flow sensor: ABS Actuator: Flame retardant plastic 6-way ball valve: CW617N Flow meter: CW617N DN 15 ISO228/1: 5 × G½" + 1 × G¾" (male thread) DN 25 ISO228/1: 6 × G1" (male thread)

Construction

Housing material

Connection

Ambient conditions

Ambient temperature Storage temperature Ambient humidity

10…45 °C −20…50 °C Max. 85% rh, non-condensing

Type of protection9) EMC Directive 2014/30/EU

IP54 (EN 60529), horizontal EN 61000-6-1 (2007) EN 61000-6-3 (2007) (A1: 2011 / AC: 2012) Fluid group II, no CE label (Art. 4.3)

V

Standards and directives

CE conformity according to

PED 2014/68/EU

Overview of types Type

Description

Kvs value

Weight

UVC106MF015

Flow control valve with 6-way ball Modbus/RTU 0...1400 l/h valve, DN 15

Protocol

Flow range

1.4 m3

2.5 kg

UVC106BF015

Flow control valve with 6-way ball BACnet MS/TP 0...1400 l/h valve, DN 15

1.4 m3

2.5 kg

UVC106MF025

Flow control valve with 6-way ball Modbus/RTU 0...2500 l/h valve, DN 25

2.5 m3

4 kg

UVC106BF025

Flow control valve with 6-way ball BACnet MS/TP 0...2500 l/h valve, DN 25

2.5 m3

4 kg

Accessories Type

Description

0560284015

Screw fitting in brass, flat-sealing, female thread/male thread for DN 15

0560284025

Screw fitting in brass, flat-sealing, female thread/male thread for DN 25

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

8) 9)

Factory setting: 38400 baud, 8 data bits, even parity, 1 stop bit See fitting instructions P100017045

Right of amendment reserved © 2024 Fr. Sauter AG

265


Valves, control valves, dampers, actuators | Multi-function valves

UVC102MF065…100: Dynamic flow control system with 2way valve and energy monitoring, eValveco Features • Patented pressure-independent variable flow control • Dynamic hydronic balancing at full and partial load • Integrated flow measurement with feedback and temperature measurement • Energy monitoring

UVC102MF065

• Remote commissioning and troubleshooting • Bluetooth interface for commissioning and maintenance via smartphone app • Available as 2-way globe valve, version DN 65...DN 100

V

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power consumption UVC102MF100

Power consumption when idle

UVC102

Input signal

M T

Feedback signal1) Additional sensor input Feedback signal resolution

~

T

±10%, 50 Hz ±10% DN 65: 6.5 W / 8 VA DN 80: 9.5 W / 11 VA DN 100: 13.5 W / 19 VA DN 65: 5.5 W / 6 VA DN 80: 8.5 W / 9 VA DN 100: 8.5 W / 9 VA Y1: 0…10 V= (0.17 mA) Ri ≥ 60 kΩ X1: 0…10 V= (max. 2 mA) Y2: 0…10 V= (0.17 mA) Approx. 100 mV

Parameters

Volume flow control

Setpoint adjustment2) Type of sensor Unit of measurement3) Readiness for operation Control characteristic4) Control accuracy Measuring accuracy

Valve

Temperature sensor

Analogue (Y1) or via Modbus RTU (can be switched to BACnet MS/TP) TTM ultrasonic sensor, no moving parts

Cable length

[m3/h], l/s, l/min, gpm (UK) 5…10 min. after switching on [Equal percentage] or linear 5% of setpoint ±3% (in relation to the measured actual flow) 4 s/mm PN 16 (16 bar) Water (glycol-free) According to VDI 2035 5…130 °C Class III as per DIN EN 60534-4 (0.001 × kvs) 2 × Pt1000 as per EN 60751, class B 2 m per sensor

Wireless

Bluetooth (max. range 10 m)

Actuator running time Nominal pressure Medium Media quality Media temperature5) Leakage rate Type of sensor

Interfaces, communication

ValveDim app 1) 2) 3) 4) 5)

266

In relation to the measured actual flow In relation to the measured actual flow Factory setting in [ ] Factory setting in [ ] For media temperatures above 100 °C, use temperature adapter (DN 65 and DN 80).

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Multi-function valves Electric wiring (incl. bus connection) Protocol Connection6) Cable type Baud rate7)

Topology Terminating resistor Indicator/display

PVC cable, 7 × 0.5 mm2, cable length 2 m Modbus RTU/TCP, slave BACnet MS/TP, slave RS-485 twisted pair cable with shared lead Shielded 2-core cable, STP or FTP 9600, 19 200 or [38 400] 1 start bit Parity [even]/odd/no parity 8 data bits 1 stop bit Multi-drop bus, max. length 1000 m At both ends 120 Ω Status LEDs

V

Construction

Material of water-bearing parts

Material of flow meter housing Material of actuator housing Connections

Brass, bronze, EPDM, stainless steel (1.4401, 1.4122,1.4301), thermoplastic, ceramic Steel, polypropylene Flame-retardant plastic PN16, flange as per EN 1092-2 type 21

Ambient conditions

Operating temperature Storage and transport temperature Air humidity Maintenance / calibration Max. altitude

10…45 °C −20…50 °C 5…85% rh (non-condensing) Maintenance-free / factory calibrated 2000 m above sea level

Type of protection Protection class Measuring Instruments Directive 2014/32/EU EMC Directive 2014/30/EU

IP54 (EN 60529), horizontal III EN 1434-4:2007

Standards, directives

CE conformity according to

PED 2014/68/EU Low-Voltage Directive 2014/35/EU Pressure and temperature data Flow parameters

Volume flow sensor: EN 61000-3-2, EN 61000-3-3 EN 61000-6-1, EN 61000-6-3 AVM234: EN 61000-6-2, EN 61000-6-4 AVM322: EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 Fluid group II, no CE label AVM 322 and AVM 234 EN 60730-1, EN 60730-2-14 EN 764, EN 1333 EN 60534

Overview of types Type

Nominal diam- Volume flow range eter

Volume flow at 30 kPa pressure drop

Kvs value

Weight

UVC102MF065

DN 65

0.175…48.8 m³/h

26.7 m³/h

48.8 m³/h

37.4 kg

UVC102MF080

DN 80

0.280…70.7 m³/h

38.7 m³/h

70.7 m³/h

46.1 kg

UVC102MF100

DN 100

0.420…118.7 m³/h

65 m³/h

118.7 m³/h

69.5 kg

6) 7)

Not electrically isolated Standard factory setting in [ ]

Right of amendment reserved © 2024 Fr. Sauter AG

267


Valves, control valves, dampers, actuators | Multi-function valves Accessories UVC102MF065, UVC102MF080 Type

Description

0510480004

Dual auxiliary switch unit

0500240001

Adaptor for media temperature above 100 °C to 150 °C for AVM322(S)

0378369101

Complete replacement stuffing box for DN 65...150

UVC102MF100

V

Type

Description

0372333001

Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and 12 V permissible load 6(2) A

0372333002

Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to max. 30 V, wider range 3(1) A

0378369101

Complete replacement stuffing box for DN 65...150

Flow rate DN [mm] UVC102MF065 UVC102MF080 UVC102MF100 Δp VMin

65 80 100

Kvs [m3/h] 48.8 70.7 118.7

VMin [m3/h] 0.175 0.280 0.420

V5 [m3/h] 10.9 15.8 26.5

V10 [m3/h] 15.4 22.3 37.5

V20 [m3/h] 21.8 31.6 53.0

V30 [m3/h] 26.7 38.7 65.0

VMax [m3/h] 48.8 70.7 118.7

Maximum closing pressure Minimum controllable flow

Kvs

Actual flow rate with valve fully open and 1 bar (100 kPa) pressure difference

V5

Flow range at Δp 5 kPa

V10

Flow range at Δp 10 kPa

V20

Flow range at Δp 20 kPa

V30

Flow range at Δp 30 kPa

VMax Maximum controllable flow. The maximum flow is reached at a differential pressure of 1 bar (100 kPa). The target flow can be set to a value that is equal to or less than the maximum flow

268

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Multi-function valves

VDL 010...050: 2-way regulating valve for dynamic hydronic balancing, PN 25, Valveco compact Features • Dynamic volume flow control in closed water circuits in conjunction with AXM 217(S), AXT 301, 311 or

AXS 315S unit valve actuators • Range 30…11500 l/h • Easy to preset the max. required volume flow • Automatic flow regulation • Versions with and without pressure measurement nipple • The valve is closed when the spindle is moved in

VDL015F210

• Closing procedure against the pressure

V

• Slight adaptation of the proven SAUTER actuator technology • Regulating valve with male (DN 10...DN 32) or female thread (DN 40 and DN 50) according to

DIN EN ISO 228-1 • Flat-sealing regulating valve • Differential pressure across the control unit is kept constant; valve authority 1 • Valve body and plug made of dezincification-resistant (DZR) brass • Stainless-steel spindle • Temperature range of medium 0…120 °C

Technical data Parameters

Nominal pressure Operating pressure Operating temperature Valve characteristic Leakage rate

PN 25 Max. 25 bar (up to 120 °C) 0…120 °C Linear 0.01%

Operating temperature at valve

Max. 100 °C in combination with AXM 217(S), AXT 301, 311, AXS 315S or AVM 215(S)

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 EN 60534, page 3 Fluid group II, No CE label (article 4.3)

VDL040F201

Ambient conditions

Standards, directives

Overview of types Type

Nominal Volume flow diameter range (l/h) (DN)

Control range Valve min ∆p...max stroke ∆p (kPa) (mm)

Connection / tolerance class

VDL010F200

10

65...370

14...800

5

G½" B

−

0.36

VDL010F201

10

65...370

14...800

5

G½" B

•

0.45

VDL010F210

10

30...200

14...800

2.5

G½" B

−

0.36

VDL010F211

10

30...200

14...800

2.5

G½" B

•

0.45 0.38

Pressure Weight (kg) measurement nipple

VDL015F200

15

100...575

14...800

2.5

G¾" B

−

VDL015F200H

15

220...1330

8...800

5

G¾" B

−

0.38

VDL015F201

15

100...575

14...800

2.5

G¾" B

•

0.47

VDL015F210

15

65...370

14...800

5

G¾" B

−

0.38

VDL015F201H

15

220...1330

8...800

5

G¾" B

•

0.47

VDL015F211

15

65...370

14...800

5

G¾" B

•

0.47

Right of amendment reserved © 2024 Fr. Sauter AG

ValveDim app

269


Valves, control valves, dampers, actuators | Multi-function valves

V

Type

Nominal Volume flow diameter range (l/h) (DN)

Control range Valve min ∆p...max stroke ∆p (kPa) (mm)

Connection / tolerance class

VDL015F220

15

30...200

14...800

2.5

G¾" B

−

VDL015F221

15

30...200

14...800

2.5

G¾" B

•

0.47

VDL020F200

20

220...1330

15...800

5

G1" B

−

0.4

VDL020F201

20

220...1330

15...800

5

G1" B

•

0.5

VDL020F210

20

160...990

15...800

4

G1" B

−

0.4

VDL020F210H

20

300...1800

8...800

5.5

G1" B

−

0.4

VDL020F211

20

160...990

15...800

4

G1" B

•

0.5

VDL020F211H

20

300...1800

8...800

5.5

G1" B

•

0.5

VDL020F220

20

100...575

14...800

2.5

G1" B

−

0.4

VDL020F221

20

100...575

14...800

2.5

G1" B

•

0.5

VDL025F200

25

600...3609

8...800

5.5

G 1¼" B

−

1.02

VDL025F201

25

600...3609

8...800

5.5

G 1¼" B

•

1.12

VDL025F210

25

280...1800

8...800

5.5

G 1¼" B

−

0.51

VDL025F211

25

280...1800

8...800

5.5

G 1¼" B

•

0.62

VDL032F200

32

550...4001

8...800

5.5

G 1½" B

−

1.17

VDL032F201

32

550...4001

8...800

5.5

G 1½" B

•

1.27

VDL040F201

40

1370...9500

8...800

15

G 1½" B

•

3.28

VDL050F201

50

1400...11500

8...800

15

G2" B

•

3.71

A

Pressure Weight (kg) measurement nipple

0.38

DN 10…DN 32 valves with male thread DN 40 and DN 50 valves with female thread

Accessories

270

Type

Description

0378133010

1 threaded sleeve, R⅜, flat-sealing, with cap nut and flat seal, G½ - R⅜

0378133015

1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½

0378133020

1 threaded sleeve, R¾, flat-sealing, with cap nut and flat seal, G1 - R¾

0378134010

1 solder nipple, Ø 12, flat-sealing, with cap nut and flat seal, G½

0378134015

1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾

0378134020

1 solder nipple, Ø 22, flat-sealing, with cap nut and flat seal, G1

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0510390029

Mounting set for SAUTER VDL valves with 15 mm stroke, thread DN 40 and DN 50 for AVM215(S)F***R

0361951015

Screw fitting for male thread with flat seal, G1 - Rp½

0361951020

Screw fitting for male thread with flat seal, G1¼ - Rp¾

0361951025

Screw fitting for male thread with flat seal, G1½ - Rp1

0360391040

Screw fitting incl. seal, 2 pcs. required, Rp1½ - G1½

0360391050

Screw fitting incl. seal, 2 pcs. required, Rp2 - G2

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Multi-function valves Combination of VDL with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences with motorised actuators Actuator

AXM217F200

AXM217F202

Page

171

171

AXM217SF402 AXM217SF404 173

Voltage

230 VAC

24 VAC/DC

24 VAC/DC

Control signal

2-/3-point

2-/3-point

0/2…10 V, 0…5 V, 5…10 V, 0/4…20 mA

Laufzeit

13 s/mm

13 s/mm

8 s/mm

Closes against the pressure VDL010F200 VDL010F201 VDL010F210 VDL010F211 VDL015F200 VDL015F200H VDL015F201 VDL015F210 VDL015F201H VDL015F211 VDL015F220 VDL015F221 VDL020F200 VDL020F201 VDL020F210 VDL020F210H VDL020F211 VDL020F211H VDL020F220 VDL020F221 VDL025F210 VDL025F211 VDL025F200 VDL025F201 VDL032F200 VDL032F201

V

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

8.0

6.0

8.0

6.0

8.0

6.0

8.0

8.0

8.0

8.0

8.0

8.0

Cannot be used to close with the pressure Actuator Page

AVM215F120R 234

AVM215SF132R 237

Voltage

230 VAC

24 VAC/DC

Control signal

2-/3-pt.

0…10 V

Laufzeit

7.5 s/mm

7.5 s/mm

Closes against the pressure VDL040F201 VDL050F201

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

8.0

8.0

8.0

8.0

Cannot be used to close with the pressure

Right of amendment reserved © 2024 Fr. Sauter AG

271


Valves, control valves, dampers, actuators | Multi-function valves Pressure differences with thermal actuators Actuator

AXT301F102 AXT301F112 164

AXT301HF110

AXT301HF112

Page

AXT301F100 AXT301F110 164

164

164

Voltage

230 VAC

24 VAC/DC

230 VAC

24 VAC/DC

Control signal

2-point

2-point

2-point

2-point

Laufzeit

33 s/mm

33 s/mm

40 s/mm

40 s/mm

Closes against the ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] pressure

V

VDL010F200 VDL010F201 VDL010F210 VDL010F211 VDL015F200 VDL015F200H VDL015F201 VDL015F210 VDL015F201H VDL015F211 VDL015F220 VDL015F221 VDL020F200 VDL020F201 VDL020F210 VDL020F210H VDL020F211 VDL020F211H VDL020F220 VDL020F221 VDL025F210 VDL025F211

8.0

6.0

8.0

6.0

8.0

6.0

8.0

6.0

VDL025F200 VDL025F201 VDL032F200 VDL032F201

8.0

8.0

8.0

8.0

8.0

6.0

8.0

6.0

Cannot be used to close with the pressure

272

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Multi-function valves

A

In combination with AXT301HF110, the following valves only open up to approx. 60%, including a closing safety tolerance of 0.8 mm: VDL010F20*, VDL015F21*, VDL015F20*H, VDL020F20*, VDL020F21*, VDL020F21*H, VDL025F20*, VDL025F21*, VDL032F20*

Pressure differences with thermal, continuous actuators Actuator Page

AXS315SF102 167

AXS315SF202 167

AXT311F110 164

AXT311F112 164

Voltage

24 VAC/DC

24 VAC/DC

230 VAC

24 VAC/DC

Control signal

0…10 V

0…10 V

2-point

2-point

Laufzeit

30 s/mm

30 s/mm

52 s/mm

52 s/mm

Closes against the ∆pmax [bar] ∆ps [bar] pressure

∆pmax [bar]

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]

VDL010F200 VDL010F201 VDL010F210 VDL010F211 VDL015F200 VDL015F200H VDL015F201 VDL015F210 VDL015F201H VDL015F211 VDL015F220 VDL015F221 VDL020F200 VDL020F201 VDL020F210 VDL020F210H VDL020F211 VDL020F211H VDL020F220 VDL020F221 VDL025F210 VDL025F211

8.0

6.0

8.0

8.0

6.0

8.0

6.0

VDL025F200 VDL025F201 VDL032F200 VDL032F201

8.0

8.0

8.0

8.0

8.0

8.0

8.0

V

Cannot be used to close with the pressure

A

In combination with AXT311F11*, the white spindle extension must be removed from the following valves before fitting: VDL010F20*, VDL015F21*, VDL015F20*H, VDL020F20*, VDL020F21*H, VDL025F20*, VDL025F21*, VDL032F20*

Right of amendment reserved © 2024 Fr. Sauter AG

273


Valves, control valves, dampers, actuators | Multi-function valves

VDL 050…100: 2-way regulating valve for dynamic hydronic balancing, PN 16, Valveco flange Features • Regulating valve with three functions: Control, preset maximum volume flow, automatic flow regulation • Control of low and mean temperature domestic hot water, cooled water, water with anti-freeze in closed

circuits1) • Volume flow range: 3.7…90.9 m3/h • Easy to preset the max. required volume flow • All types with three pressure measurement nipples • The valve is closed when the spindle is moved in

V

• Closing procedure against the pressure

VDL065F501 P1

P2

• Simple connection to SAUTER actuators AVM 215 for DN 50...80 and AVM 234 for DN 100 P3

• Regulating valve with flange connection (DN 50...DN 100) according to EN ISO 7005-2 • Flat-sealing regulating valve • Differential pressure across the control unit is kept constant; valve authority 1 • Valve body DN 50…80 made of grey cast iron (GJL‑250); DN 100 made of ductile cast iron (GJS‑400) • Stainless-steel spindle

Technical data Parameters

Nominal pressure Volume flow setting range

16 bar

Maximum operating pressure Connection Valve characteristic Control ratio Leakage rate

3.7...90.9 m3/h PN 16 (EN 1333) Flange as per ISO 7005-2 Linear (VDI/VDE 2173) 1:100 Max. 0.01% of the volume flow with the valve fully open (Class IV, EN 1349)

Operating temperature for valve

1…120 °C

Pressure measurement nipple

3 pcs, G¼ inch, suitable for 2 × 40 mm probes

Pressure and temperature data Flow parameters PED 2014/68/EU2)

EN 764, EN 1333 EN 60534, page 3 Fluid group 2 as per Art. 13 Pressure equipment as per Art. 1.1 All types EAC-compliant (Eurasian conformity)

Ambient conditions

ValveDim app Construction

Standards, directives

EAC Directive

Overview of types Type

Nominal diameter (DN)

Volume flow range Control range min Valve stroke (mm) ∆p...max ∆p (kPa)

Weight (kg)

VDL050F501

50

3.7…14.3

15

VDL050F501H

50

5.7…24.6

30…600

20

15

VDL065F501

65

4.5…24.4

28…600

20

19

1) 2)

274

13…600

20

Water quality must comply with VDI 2035, water with anti-freeze permissible No special valve test required at operating temperature ≤ 110 °C. This also applies to valves with PS x DN < 1000. In both cases, the valves do not have a CE label

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Multi-function valves Type

Nominal diameter (DN)

Volume flow range Control range min Valve stroke (mm) ∆p...max ∆p (kPa)

Weight (kg)

VDL065F501H

65

6.4…37.7

19

30…600

20

VDL080F501

80

6.8…35.7

18…600

20

28

VDL080F501H

80

8.5…49.0

22…600

20

28

VDL100F501

100

12.2…69.6

18…600

40

46

VDL100F501H

100

14.8…90.9

20…600

40

46

Type VDL050F501 VDL050F501H VDL065F501 VDL065F501H VDL080F501 VDL080F501H VDL100F501 VDL100F501H

Fluid group 2

Average flow accuracy

No CE marking as per PED, Article 4.3 ± 10% of ∆pmin ± 5% up to 70 kPa at 70...600 kPa

With CE marking as per PED, Article 14.2 (conformity assessment procedure: Category I, Module A)

V

± 10% of ∆pmin ± 5% up to 105 kPa at 150...600 kPa

With CE marking as per PED, Article 14.2

Combination of VDL with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers. Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

/

Definition of ∆p min: Minimum differential pressure across the control passage of the valve for the differential pressure regulator to operate reliably.

Pressure differences Actuator Page

AVM215SF132-7 237

AVM234SF132-7 250

Voltage

24 V~/=

24 VAC/DC

Control signal

0…10 V

0…10 V

Running time

7.5 s/mm

2/4/6 s/mm

Actuating power

500 N

1700 N

Media temperature Max. 120 °C Closes against the pressure VDL050F501 VDL050F501H VDL065F501 VDL065F501H VDL080F501 VDL080F501H VDL100F501 VDL100F501H

Max. 120 °C

∆pmax [bar]

∆ps [bar]

∆pmax [bar]

∆ps [bar]

6.0

7.0

–

–

–

–

6.0

6.0

Cannot be used to close with the pressure

Right of amendment reserved © 2024 Fr. Sauter AG

275


Ball valves The body of the ball valves from SAUTER is made of top-quality DZR brass. This enables the continuous control of cold or hot water in closed circuits, such as in domestic hot water systems. The dezincification-resistant, chrome-plated brass ball with its polished surface ensures the best possible control precision.

Overview of regulating ball valves

Type designation Application Single-room control Preheater for ventilation & air-conditioning Preheater, cooler for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling Static heating Multi-boiler system Local heating Version 2-way 3-way Female thread Male thread Nominal diameter (DN) Nominal pressure Combination options with actuator

Further information

276

VKR

VKRA

BKR

BKRA

• • •

• • •

• • •

• • •

• • • • •

• • • • •

• • • • •

• • • • •

• − • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 278

• − − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 282

− • • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 286

− • − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 289

Right of amendment reserved © 2024 Fr. Sauter AG


Overview of cut-off and changeover ball valves

Type designation Application Single-room control Preheater for ventilation & air-conditioning Preheater, cooler for ventilation & air-conditioning Reheater for ventilation & air-conditioning Version 2-way 3-way Female thread Male thread Nominal diameter (DN) Nominal pressure Combination options with actuator

Further information

VKAI

VKAA

BKLI

BKTI

BKTA

• • •

• • •

• • •

• • •

• • •

•

•

•

•

•

• − • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 292

• − − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 294

− • • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 297

− • • − 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 300

− • − • 15...50 PN 40 AKM 105(S) AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 303

Right of amendment reserved © 2024 Fr. Sauter AG

277


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

VKR: 2-way regulating ball valve with female thread, PN 40 Features • 2-way regulating ball valve for continuous control of cold and hot water in closed circuits • In combination with valve actuators AKM 105(S), 115(S), 115SA and AKF 112, 113(S) as a control unit • Equal-percentage ball valve characteristic; control contour in the ball directly integrated • Characteristic can be set with SUT rotary actuator (SAUTER Universal Technology) to linear or quadratic

VKR040F300

• Spindle with large sliding surface and PTFE glide ring • Low torque due to collar mounted on O-ring • Ball valve with female thread as per ISO 7/1 Rp or NPT • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring

V

• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Valve characteristic Control ratio of ball valve Control ratio with actuator Leakage rate

40 bar Equal-percentage 500:1 > 50:1 Watertight as per EN 60534-4 L/1, better than class 4 90°

Angle of rotation Ambient conditions

Operating temperature1) Operating pressure

−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)

Pressure and temperature data Flow parameters

EN 764, EN 1333 EN 60534 (page 3)

Standards, directives

Overview of types Type

Nominal diameter

Connection ISO 7/1 Rp Kvs value

Weight

VKR015F350-FF

DN 15

Rp ½"

1 m³/h

0.29 kg

VKR015F340-FF

DN 15

Rp ½"

1.6 m³/h

0.29 kg

VKR015F330-FF

DN 15

Rp ½"

2.5 m³/h

0.29 kg

VKR015F320-FF

DN 15

Rp ½"

4 m³/h

0.29 kg

VKR015F310-FF

DN 15

Rp ½"

6.3 m³/h

0.29 kg

VKR015F300-FF

DN 15

Rp ½"

10 m³/h

0.29 kg

VKR020F320-FF

DN 20

Rp ¾"

4 m³/h

0.32 kg

VKR020F310-FF

DN 20

Rp ¾"

6.3 m³/h

0.32 kg

VKR020F300-FF

DN 20

Rp ¾"

10 m³/h

0.32 kg

VKR025F320-FF

DN 25

Rp 1"

6.3 m³/h

0.49 kg

VKR025F310-FF

DN 25

Rp 1"

10 m³/h

0.49 kg

VKR025F300-FF

DN 25

Rp 1"

16 m³/h

0.49 kg

VKR032F320-FF

DN 32

Rp 1¼"

10 m³/h

0.73 kg

1)

278

At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type

Nominal diameter

Connection ISO 7/1 Rp Kvs value

Weight

VKR032F310-FF

DN 32

Rp 1¼"

16 m³/h

0.73 kg

VKR032F300-FF

DN 32

Rp 1¼"

25 m³/h

0.73 kg

VKR040F320-FF

DN 40

Rp 1½"

16 m³/h

1.1 kg

VKR040F310-FF

DN 40

Rp 1½"

25 m³/h

1.1 kg

VKR040F300-FF

DN 40

Rp 1½"

40 m³/h

1.1 kg

VKR050F320-FF

DN 50

Rp 2"

25 m³/h

1.76 kg

VKR050F310-FF

DN 50

Rp 2"

40 m³/h

1.76 kg

VKR050F300-FF

DN 50

Rp 2"

63 m³/h

1.76 kg

Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0560284015

Screw fitting in brass, flat-sealing, female thread/male thread for DN 15

0560284020

Screw fitting in brass, flat-sealing, female thread/male thread for DN 20

0560284025

Screw fitting in brass, flat-sealing, female thread/male thread for DN 25

0560284032

Screw fitting in brass, flat-sealing, female thread/male thread for DN 32

0560284040

Screw fitting in brass, flat-sealing, female thread/male thread for DN 40

0560284050

Screw fitting in brass, flat-sealing, female thread/male thread for DN 50

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

A

V

1 unit delivered in each case, unless otherwise specified. See last page for dimensions and scope of delivery of accessories.

Right of amendment reserved © 2024 Fr. Sauter AG

279


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Combination of VKR with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the ball valve) at which the actuator reliably closes the ball valve using the return spring.

/

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

Pressure differences Actuator

V

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

24 VAC

Operating voltage 230 VAC Closes against the pressure VKR015F350-FF VKR015F340-FF VKR015F330-FF VKR015F320-FF VKR015F310-FF VKR015F300-FF VKR020F320-FF VKR020F310-FF VKR020F300-FF VKR025F320-FF VKR025F310-FF VKR025F300-FF VKR032F320-FF VKR032F310-FF VKR032F300-FF VKR040F320-FF VKR040F310-FF VKR040F300-FF VKR050F320-FF VKR050F310-FF VKR050F300-FF

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

1.8

1.8

3.5

3.5

1.2

1.2

2.4

2.4

Cannot be used to close with the pressure

280

Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

Closes against the pressure

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

VKR015F350-FF VKR015F340-FF VKR015F330-FF VKR015F320-FF VKR015F310-FF VKR015F300-FF VKR020F320-FF VKR020F310-FF VKR020F300-FF VKR025F320-FF VKR025F310-FF VKR025F300-FF

1.8

3.5

3.5

3.5

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page

AKM105SF132 314

VKR032F320-FF VKR032F310-FF VKR032F300-FF VKR040F320-FF VKR040F310-FF VKR040F300-FF VKR050F320-FF VKR050F310-FF VKR050F300-FF

AKM115SF132 314

1.2

AKM115SAF232 133

2.4

2.4

AKM115SF152 316

2.4

Cannot be used to close with the pressure Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC

V

Closes against the ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] pressure VKR015F350-FF VKR015F340-FF VKR015F330-FF VKR015F320-FF VKR015F310-FF VKR015F300-FF VKR020F320-FF VKR020F310-FF VKR020F300-FF VKR025F320-FF VKR025F310-FF VKR025F300-FF

3.5

5.4

3.5

5.4

3.5

5.4

3.5

5.4

VKR032F320-FF VKR032F310-FF VKR032F300-FF VKR040F320-FF VKR040F310-FF VKR040F300-FF VKR050F320-FF VKR050F310-FF VKR050F300-FF

2.4

3.5

2.4

3.5

2.4

3.5

2.4

3.5

Cannot be used to close with the pressure

Right of amendment reserved © 2024 Fr. Sauter AG

281


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

VKRA: 2-way regulating ball valve with male thread, PN 40 Features • 2-way regulating ball valve for continuous control of cold and hot water in closed circuits • In combination with valve actuators AKM 105(S), 115(S), 115SA and AKF 112, 113(S) as a control unit • Equal-percentage ball valve characteristic; control contour in the ball directly integrated

VKRA0**F300

• Characteristic can be set with SUT rotary actuator (SAUTER Universal Technology) to linear or quadratic • Spindle with large sliding surface and PTFE glide ring • Low torque due to collar mounted on O-ring • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring

V

• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Valve characteristic Control ratio of ball valve Control ratio with actuator Leakage rate

40 bar Equal-percentage 500:1 > 50:1 Waterproof as per EN 60534-4 L/1, better than class 5 90°

Angle of rotation Ambient conditions

Operating temperature1) Operating pressure

−10...130 °C, no condensation Liquids: 40 bar (–10...50 °C), 35 bar Gases: 20 bar

Pressure and temperature data Flow parameters

EN 764, EN 1333 EN 60534 (page 3)

Standards, directives

Overview of types Type

Nominal diameter

Connection ISO 228-1

Kvs value

Weight

VKRA015F350

DN 15

G 1" B

1 m³/h

360 g

VKRA015F340

DN 15

G 1" B

1.6 m³/h

360 g

VKRA015F330

DN 15

G 1" B

2.5 m³/h

360 g

VKRA015F320

DN 15

G 1" B

4 m³/h

360 g

VKRA015F310

DN 15

G 1" B

6.3 m³/h

360 g

VKRA020F320

DN 20

G 1¼" B

4 m³/h

440 g

VKRA020F310

DN 20

G 1¼" B

6.3 m³/h

440 g

VKRA020F300

DN 20

G 1¼" B

10 m³/h

440 g

VKRA025F320

DN 25

G 1½" B

6.3 m³/h

570 g

VKRA025F310

DN 25

G 1½" B

10 m³/h

570 g

VKRA025F300

DN 25

G 1½" B

16 m³/h

570 g

VKRA032F320

DN 32

G 2" B

10 m³/h

840 g

VKRA032F310

DN 32

G 2" B

16 m³/h

840 g

1)

282

At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type

Nominal diameter

Connection ISO 228-1

Kvs value

Weight

VKRA032F300

DN 32

G 2" B

25 m³/h

840 g

VKRA040F320

DN 40

G 2¼" B

16 m³/h

1290 g

VKRA040F310

DN 40

G 2¼" B

25 m³/h

1290 g

VKRA040F300

DN 40

G 2¼" B

40 m³/h

1290 g

VKRA050F320

DN 50

G 2¾" B

25 m³/h

1980 g

VKRA050F310

DN 50

G 2¾" B

40 m³/h

1980 g

VKRA050F300

DN 50

G 2¾" B

63 m³/h

1980 g

Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0361951015

Screw fitting for male thread with flat seal, G1 - Rp½

0361951020

Screw fitting for male thread with flat seal, G1¼ - Rp¾

0361951025

Screw fitting for male thread with flat seal, G1½ - Rp1

0361951032

Screw fitting for male thread with flat seal DN 32

0361951040

Screw fitting for male thread with flat seal DN 40

0361951050

Screw fitting for male thread with flat seal DN 50

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

V

Combination of VKRA with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the ball valve) at which the actuator reliably closes the ball valve using the return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

24 VAC

Operating voltage 230 VAC Closes against the pressure VKRA015F350 VKRA015F340 VKRA015F330 VKRA015F320 VKRA015F310 VKRA020F320 VKRA020F310 VKRA020F300 VKRA025F320 VKRA025F310 VKRA025F300

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

1.8

1.8

3.5

3.5

Right of amendment reserved © 2024 Fr. Sauter AG

283


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page

AKM105F100 AKM105F120 311

VKRA032F320 VKRA032F310 VKRA032F300 VKRA040F320 VKRA040F310 VKRA040F300 VKRA050F320 VKRA050F310 VKRA050F300

AKM105F122

AKM115F120

AKM115F122

311

311

311

1.2

1.2

2.4

2.4

Cannot be used to close with the pressure

V

Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

Closes against the pressure

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

VKRA015F350 VKRA015F340 VKRA015F330 VKRA015F320 VKRA015F310 VKRA020F320 VKRA020F310 VKRA020F300 VKRA025F320 VKRA025F310 VKRA025F300

1.8

3.5

3.5

3.5

VKRA032F320 VKRA032F310 VKRA032F300 VKRA040F320 VKRA040F310 VKRA040F300 VKRA050F320 VKRA050F310 VKRA050F300

1.2

2.4

2.4

2.4

Cannot be used to close with the pressure Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC

Closes against the ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] pressure VKRA015F350 VKRA015F340 VKRA015F330 VKRA015F320 VKRA015F310 VKRA020F320 VKRA020F310 VKRA020F300 VKRA025F320 VKRA025F310 VKRA025F300

284

3.5

5.4

3.5

5.4

3.5

5.4

3.5

5.4

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page VKRA032F320 VKRA032F310 VKRA032F300 VKRA040F320 VKRA040F310 VKRA040F300 VKRA050F320 VKRA050F310 VKRA050F300

AKF112F120 317

2.4

AKF112F122 317

3.5

2.4

AKF113F122 317

3.5

2.4

AKF113SF122 318

3.5

2.4

3.5

Cannot be used to close with the pressure

V

Right of amendment reserved © 2024 Fr. Sauter AG

285


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

BKR: 3-way regulating ball valve with female thread, PN 40 Features • 3-way regulating ball valve for continuous control of cold and hot water in closed circuits • In combination with valve actuators AKM 105(S), 115(S), 115SA and AKF 112, 113(S) as a control unit • Control contour in the ball directly integrated • Control passage characteristic can be set to linear or quadratic with SUT rotary actuator

BKR025F310

• Low torque due to collar mounted on O-ring • Spindle with large sliding surface and PTFE ring • Ball valve with female thread as per ISO 7/1 Rp or NPT • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring

V

• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Kvs value, mixing passage Control passage valve characteristic Mixing passage valve characteristic Control ratio of ball valve Control ratio with actuator Control passage leakage rate Mixing passage leakage rate Angle of rotation

40 bar −10...−30% through the control passage Equal-percentage Linear 500:1 Approx. 50:1 Watertight as per EN 60534-4 L/1, better than class 4 < 1% 90°

Ambient conditions

−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)

Operating temperature1) Operating pressure

Overview of types Type

Nominal diameter

Connection ISO 7/1 Rp Kvs value, control pas-

Weight

sage

BKR015F340-FF

DN 15

Rp ½"

1.6 m³/h

0.31 kg

BKR015F330-FF

DN 15

Rp ½"

2.5 m³/h

0.31 kg

BKR015F320-FF

DN 15

Rp ½"

4 m³/h

0.31 kg

BKR015F310-FF

DN 15

Rp ½"

6.3 m³/h

0.33 kg

BKR020F320-FF

DN 20

Rp ¾"

4 m³/h

0.4 kg

BKR020F310-FF

DN 20

Rp ¾"

6.3 m³/h

0.4 kg

BKR025F310-FF

DN 25

Rp 1"

10 m³/h

0.63 kg

BKR032F310-FF

DN 32

Rp 1¼"

16 m³/h

0.97 kg

BKR040F310-FF

DN 40

Rp 1½"

25 m³/h

1.4 kg

BKR050F310-FF

DN 50

Rp 2"

40 m³/h

2.67 kg

1)

286

At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0560284015

Screw fitting in brass, flat-sealing, female thread/male thread for DN 15

0560284020

Screw fitting in brass, flat-sealing, female thread/male thread for DN 20

0560284025

Screw fitting in brass, flat-sealing, female thread/male thread for DN 25

0560284032

Screw fitting in brass, flat-sealing, female thread/male thread for DN 32

0560284040

Screw fitting in brass, flat-sealing, female thread/male thread for DN 40

0560284050

Screw fitting in brass, flat-sealing, female thread/male thread for DN 50

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

A

V

1 unit delivered in each case, unless otherwise specified. See last page for dimensions and scope of delivery of accessories.

Combination of BKR with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

Operating voltage 230 VAC

24 VAC

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKR015F340-FF BKR015F330-FF BKR015F320-FF BKR015F310-FF BKR020F320-FF BKR020F310-FF BKR025F310-FF

1.8

1.8

2.0

2.0

BKR032F310-FF BKR040F310-FF BKR050F310-FF

1.2

1.2

2.0

2.0

Cannot be used as distribution valve

Right of amendment reserved © 2024 Fr. Sauter AG

287


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

V

Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKR015F340-FF BKR015F330-FF BKR015F320-FF BKR015F310-FF BKR020F320-FF BKR020F310-FF BKR025F310-FF

1.8

2.0

2.0

2.0

BKR032F310-FF BKR040F310-FF BKR050F310-FF

1.2

2.0

2.0

2.0

Cannot be used as distribution valve Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC As control valve

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]

BKR015F340-FF BKR015F330-FF BKR015F320-FF BKR015F310-FF BKR020F320-FF BKR020F310-FF BKR025F310-FF

2.0

5.4

2.0

5.4

2.0

5.4

2.0

5.4

BKR032F310-FF BKR040F310-FF BKR050F310-FF

2.0

3.5

2.0

3.5

2.0

3.5

2.0

3.5

Cannot be used as distribution valve

288

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

BKRA: 3-way regulating ball valve with male thread, PN 40 Features • 3-way regulating ball valve for continuous control of cold and hot water in closed circuits • As a control unit in combination with valve actuators AKM105(S), 115(S), 115SA and AKF112, 113(S) • Control contour in the ball directly integrated • Control passage characteristic can be set to linear or quadratic with SUT rotary actuator • Low torque due to collar mounted on O-ring

BKRA0**F3*0

• Spindle with large sliding surface and PTFE ring • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of DZR (dezincification-resistant) cast brass • Spindle made of DZR brass with PTFE glide ring

V

• Ball made of DZR brass, chrome-plated and polished surface • Spindle seal with double O-ring made of EPDM • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Kvs value, mixing passage Valve characteristic, control passage Mixing passage valve characteristic Control ratio of ball valve Control ratio with actuator Control passage leakage rate Mixing passage leakage rate Angle of rotation

40 bar –10...–30% through the control passage Equal-percentage Linear 500:1 Approx. 50:1 Watertight as per EN 60534-4 L/1, better than class 4 < 1% of the Kvs value 90°

Ambient conditions

−10...130 °C, no condensation 40 bar (–10...50 °C) 35 bar (130 °C) Gases: 20 bar

Operating temperature1) Operating pressure

Overview of types Type

Nominal diameter

Connection ISO 228-1

Kvs value, control pas-

Weight

sage

BKRA015F340

DN 15

G 1" B

1.6 m³/h

0.41 kg

BKRA015F330

DN 15

G 1" B

2.5 m³/h

0.41 kg

BKRA015F320

DN 15

G 1" B

4 m³/h

0.41 kg

BKRA015F310

DN 15

G 1" B

6.3 m³/h

0.45 kg

BKRA020F320

DN 20

G 1¼" B

4 m³/h

0.52 kg

BKRA020F310

DN 20

G 1¼" B

6.3 m³/h

0.4 kg

BKRA025F310

DN 25

G 1½" B

10 m³/h

0.75 kg

BKRA032F310

DN 32

G 2" B

16 m³/h

1.2 kg

BKRA040F310

DN 40

G 2¼" B

25 m³/h

1.84 kg

BKRA050F310

DN 50

G 2¾" B

40 m³/h

2.83 kg

1)

At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.

Right of amendment reserved © 2024 Fr. Sauter AG

289


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories

V

Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0361951015

Screw fitting for male thread with flat seal, G1 - Rp½

0361951020

Screw fitting for male thread with flat seal, G1¼ - Rp¾

0361951025

Screw fitting for male thread with flat seal, G1½ - Rp1

0361951032

Screw fitting for male thread with flat seal DN 32

0361951040

Screw fitting for male thread with flat seal DN 40

0361951050

Screw fitting for male thread with flat seal DN 50

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

Combination of BKRA with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

Operating voltage 230 VAC

24 VAC

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKRA015F340 BKRA015F330 BKRA015F320 BKRA015F310 BKRA020F320 BKRA020F310 BKRA025F310

1.8

1.8

2.0

2.0

BKRA032F310 BKRA040F310 BKRA050F310

1.2

1.2

2.0

2.0

Cannot be used as distribution valve

290

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKRA015F340 BKRA015F330 BKRA015F320 BKRA015F310 BKRA020F320 BKRA020F310 BKRA025F310

1.8

2.0

2.0

2.0

BKRA032F310 BKRA040F310 BKRA050F310

1.2

2.0

2.0

2.0

V

Cannot be used as distribution valve Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC As control valve

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar]

BKRA015F340 BKRA015F330 BKRA015F320 BKRA015F310 BKRA020F320 BKRA020F310 BKRA025F310

2.0

5.4

2.0

5.4

2.0

5.4

2.0

5.4

BKRA032F310 BKRA040F310

2.0

3.5

2.0

3.5

2.0

3.5

2.0

3.5

BKRA050F310

1.0

3.5

2.0

3.5

2.0

3.5

2.0

3.5

Cannot be used as distribution valve

Right of amendment reserved © 2024 Fr. Sauter AG

291


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

VKAI: 2-way cut-off ball valve with female thread, PN 40 Features • 2-way cut-off ball valve for use in closed circuits in heating, ventilation and air conditioning systems • As a cut-off device and control unit for 2-point control in combination with valve actuators AKM 105(S),

115(S), 115SA and AKF 112, 113(S) • Fast cut-off in six seconds with the AKM115SF152 valve actuator

VKAI040F300

• Low torque due to collar mounted on O-ring • Ball valve with female thread as per ISO 7/1 Rp • Body made of dezincification-resistant cast brass • Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories

V

• Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Leakage rate Angle of rotation

40 bar 0.0001 x Kvs value 90°

Operating temperature1) Operating pressure

−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)

Ambient conditions

Overview of types Type

Nominal diameter (DN) Connection ISO 7/1 Rp Kvs value

Weight

275 g

VKAI015F300

DN 15

Rp ½"

15 m3/h

VKAI020F300

DN 20

Rp ¾"

22 m3/h

370 g

VKAI025F300

DN 25

Rp 1"

22 m3/h

456 g

VKAI032F300

DN 32

Rp 1¼"

35 m3/h

700 g

VKAI040F300

DN 40

Rp 1½"

68 m3/h

1120 g

VKAI050F300

DN 50

Rp 2"

96 m3/h

1750 g

Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0560284015

Screw fitting in brass, flat-sealing, female thread/male thread for DN 15

0560284020

Screw fitting in brass, flat-sealing, female thread/male thread for DN 20

0560284025

Screw fitting in brass, flat-sealing, female thread/male thread for DN 25

0560284032

Screw fitting in brass, flat-sealing, female thread/male thread for DN 32

0560284040

Screw fitting in brass, flat-sealing, female thread/male thread for DN 40

0560284050

Screw fitting in brass, flat-sealing, female thread/male thread for DN 50

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

1)

292

At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type

Description

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

Combination of VKAI with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

Operating voltage 230 VAC

V

24 VAC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

VKAI015F300 VKAI020F300 VKAI025F300

1.8

1.8

3.5

3.5

VKAI032F300 VKAI040F300 VKAI050F300

1.2

1.2

2.4

2.4

– Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

VKAI015F300 VKAI020F300 VKAI025F300

1.8

3.5

3.5

3.5

VKAI032F300 VKAI040F300 VKAI050F300

1.2

2.4

2.4

2.4

Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

–

Operating voltage 230 VAC

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] VKAI015F300 VKAI020F300 VKAI025F300

3.5

5.4

3.5

5.4

3.5

5.4

3.5

5.4

VKAI032F300 VKAI040F300 VKAI050F300

2.4

5.4

2.4

5.4

2.4

5.4

2.4

5.4

–

Right of amendment reserved © 2024 Fr. Sauter AG

293


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

VKAA: 2-way cut-off ball valve with male thread, PN 40 Features • 2-way cut-off ball valve for use in closed circuits in heating, ventilation and air conditioning systems • As a cut-off device and control unit for 2-point control in combination with valve actuators AKM 105(S),

115(S), 115SA and AKF 112, 113(S) VKAA0**F300

• Fast changeover in six seconds with the AKM115SF152 valve actuator • Low torque due to collar mounted on O-ring • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of dezincification-resistant cast brass • Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories

V

• Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Leakage rate

40 bar Waterproof as per EN 60534-4 L/1, better than class 5 90°

Angle of rotation Ambient conditions

Operating temperature Operating pressure

−10...130 °C, no condensation Liquids: 40 bar (–10...50 °C) 35 bar (130 °C) Gases: 20 bar

Overview of types Type

Nominal diameter (DN) Connection ISO 228-1

Kvs value

Weight

VKAA015F300

DN 15

G 1" B

9 m3

360 g

VKAA020F300

DN 20

G 1¼" B

17 m3

550 g

VKAA025F300

DN 25

G 1½" B

22 m3

570 g

VKAA032F300

DN 32

G 2" B

35 m3

840 g

VKAA040F300

DN 40

G 2¼" B

68 m3

1290 g

VKAA050F300

DN 50

G 2¾" B

96 m3

1980 g

Accessories

294

Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0361951015

Screw fitting for male thread with flat seal, G1 - Rp½

0361951020

Screw fitting for male thread with flat seal, G1¼ - Rp¾

0361951025

Screw fitting for male thread with flat seal, G1½ - Rp1

0361951032

Screw fitting for male thread with flat seal DN 32

0361951040

Screw fitting for male thread with flat seal DN 40

0361951050

Screw fitting for male thread with flat seal DN 50

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type

Description

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

Combination of VKAA with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

/

Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

Operating voltage 230 VAC

V

24 VAC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

VKAA015F300 VKAA020F300 VKAA025F300

1.8

1.8

3.5

3.5

VKAA032F300 VKAA040F300 VKAA050F300

1.2

1.2

2.4

2.4

– Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

VKAA015F300 VKAA020F300 VKAA025F300

1.8

3.5

3.5

3.5

VKAA032F300 VKAA040F300 VKAA050F300

1.2

2.4

2.4

2.4

Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

–

Operating voltage 230 VAC

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] VKAA015F300 VKAA020F300 VKAA025F300

3.5

5.4

3.5

5.4

Right of amendment reserved © 2024 Fr. Sauter AG

3.5

5.4

3.5

5.4

295


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page VKAA032F300 VKAA040F300 VKAA050F300

AKF112F120 317 2.4

AKF112F122 317 5.4

2.4

AKF113F122 317 5.4

2.4

AKF113SF122 318 5.4

2.4

5.4

–

V

296

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

BKLI: 3-way changeover ball valve (L) with female thread, PN 40 Features • 3-way changeover ball valve with L-bore for use in closed circuits in heating, ventilation and air

conditioning systems • For changing over volume flows in combination with valve actuators AKM 105(S), 115(S), 115SA and

AKF 112, 113(S). • Fast changeover in six seconds with the AKM115SF152 valve actuator

BKLI025F300

• Low torque due to collar mounted on O-ring • Spindle with friction ring and double O-ring seal • Ball valve with female thread as per ISO 7/1 Rp • Body made of dezincification-resistant cast brass

V

• Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Leakage rate, through passage Leakage rate, bypass Angle of rotation

40 bar 0.0001 x Kvs value 0.0001 x Kvs value 90°

Operating temperature1) Operating pressure

−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)

Ambient conditions

Overview of types Type

Nominal diameter (DN) Connection ISO 7/1 Rp Kvs value, control pas-

Weight

sage

BKLI015F300

DN 15

Rp ½"

5 m³/h

306 g

BKLI020F300

DN 20

Rp ¾"

9 m³/h

375 g

BKLI025F300

DN 25

Rp 1"

9 m³/h

604 g

BKLI032F300

DN 32

Rp 1¼"

13 m³/h

949 g

BKLI040F300

DN 40

Rp 1½"

25 m³/h

1364 g

BKLI050F300

DN 50

Rp 2"

37 m³/h

2215 g

Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0560284015

Screw fitting in brass, flat-sealing, female thread/male thread for DN 15

0560284020

Screw fitting in brass, flat-sealing, female thread/male thread for DN 20

0560284025

Screw fitting in brass, flat-sealing, female thread/male thread for DN 25

0560284032

Screw fitting in brass, flat-sealing, female thread/male thread for DN 32

0560284040

Screw fitting in brass, flat-sealing, female thread/male thread for DN 40

0560284050

Screw fitting in brass, flat-sealing, female thread/male thread for DN 50

1)

At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.

Right of amendment reserved © 2024 Fr. Sauter AG

297


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type

Description

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

Combination of BKLI with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

V

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

Operating voltage 230 VAC

24 VAC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKLI015F300 BKLI020F300 BKLI025F300

1.8

1.8

2.0

2.0

BKLI032F300 BKLI040F300 BKLI050F300

1.2

1.2

2.0

2.0

– Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKLI015F300 BKLI020F300 BKLI025F300

1.8

2.0

2.0

2.0

BKLI032F300 BKLI040F300 BKLI050F300

1.2

2.0

2.0

2.0

–

298

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] BKLI015F300 BKLI020F300 BKLI025F300 BKLI032F300 BKLI040F300 BKLI050F300

2.0

5.4

2.0

5.4

2.0

5.4

2.0

5.4

–

V

Right of amendment reserved © 2024 Fr. Sauter AG

299


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

BKTI: 3-way changeover ball valve (T) with female thread, PN 40 Features • 3-way changeover ball valve with T-bore for use in closed circuits in heating, ventilation and air

conditioning systems • For changing over volume flows in combination with valve actuators AKM 105(S), 115(S), 115SA and

AKF 112, 113(S) BKTI025F300

• Fast changeover in six seconds with the AKM115SF152 valve actuator • Low torque due to collar mounted on O-ring • Spindle with friction ring and double O-ring seal • Ball valve with female thread as per ISO 7/1 Rp • Body made of dezincification-resistant cast brass

V

• Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Leakage rate, through passage Leakage rate, bypass Angle of rotation

40 bar 0.0001 x Kvs value < 0.01 x Kvs value 90°

Operating temperature1) Operating pressure

−10...130 °C, no condensation 40 bar (−10...50 °C) 35 bar (130 °C)

Ambient conditions

Overview of types Type

Nominal diameter

Connection ISO 7/1 Rp Kvs value, control pas-

Weight

sage

BKTI015F300

DN 15

Rp ½"

12 m³/h

306 g

BKTI020F300

DN 20

Rp ¾"

16 m³/h

375 g

BKTI025F300

DN 25

Rp 1"

16 m³/h

604 g

BKTI032F300

DN 32

Rp 1¼"

25 m³/h

949 g

BKTI040F300

DN 40

Rp 1½"

49 m³/h

1364 g

BKTI050F300

DN 50

Rp 2"

73 m³/h

2215 g

Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0560284015

Screw fitting in brass, flat-sealing, female thread/male thread for DN 15

0560284020

Screw fitting in brass, flat-sealing, female thread/male thread for DN 20

0560284025

Screw fitting in brass, flat-sealing, female thread/male thread for DN 25

0560284032

Screw fitting in brass, flat-sealing, female thread/male thread for DN 32

0560284040

Screw fitting in brass, flat-sealing, female thread/male thread for DN 40

0560284050

Screw fitting in brass, flat-sealing, female thread/male thread for DN 50

1)

300

At operating temperatures <5 °C and >100 °C, the appropriate accessories must be used.

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type

Description

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

Combination of BKTI with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

V

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

Operating voltage 230 VAC

24 VAC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKTI015F300 BKTI020F300 BKTI025F300

1.8

1.8

2.0

2.0

BKTI032F300 BKTI040F300 BKTI050F300

1.2

1.2

2.0

2.0

– Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKTI015F300 BKTI020F300 BKTI025F300

1.8

2.0

2.0

2.0

BKTI032F300 BKTI040F300 BKTI050F300

1.2

2.0

2.0

2.0

–

Right of amendment reserved © 2024 Fr. Sauter AG

301


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] BKTI015F300 BKTI020F300 BKTI025F300 BKTI032F300 BKTI040F300 BKTI050F300

2.0

5.4

2.0

5.4

2.0

5.4

2.0

5.4

–

V

302

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

BKTA: 3-way changeover ball valve (T) with male thread, PN 40 Features • 3-way changeover ball valve with T-bore for use in closed circuits in heating, ventilation and air

conditioning systems • For changing over volume flows in combination with valve actuators AKM 105(S), 115(S), 115SA and

AKF 112, 113(S) • Fast changeover in six seconds with the AKM115SF152 valve actuator

BKTA0**F300

• Low torque due to collar mounted on O-ring • Spindle with friction ring and double O-ring seal • Ball valve with male thread as per ISO 228-1 (G x" B) • Body made of dezincification-resistant cast brass

V

• Ball made of dezincification-resistant brass, chrome-plated and polished surface • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

Technical data Parameters

Nominal pressure Leakage rate, through passage Leakage rate, bypass Angle of rotation

40 bar Waterproof as per EN 60534-4 L/1, better than class 4 < 1% of the Kvs value 90°

Ambient conditions

Operating temperature Operating pressure

−10...130 °C, no condensation 40 bar (–10...50 °C) 35 bar (130 °C) Gases: 20 bar

Overview of types Type

Nominal diameter

Connection ISO 228-1

Kvs value, control pas-

Weight

sage

BKTA015F300

DN 15

G 1" B

8 m³/h

450 g

BKTA020F300

DN 20

G 1¼" B

13 m³/h

680 g

BKTA025F300

DN 25

G 1½" B

13 m³/h

750 g

BKTA032F300

DN 32

G 2" B

25 m³/h

1200 g

BKTA040F300

DN 40

G 2¼" B

49 m³/h

1840 g

BKTA050F300

DN 50

G 2¾" B

73 m³/h

2830 g

Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

0510240011

Adaptor required when temperature of the medium < 5 °C

0510420001

Adaptor required when temperature of the medium > 100 °C

0361951015

Screw fitting for male thread with flat seal, G1 - Rp½

0361951020

Screw fitting for male thread with flat seal, G1¼ - Rp¾

0361951025

Screw fitting for male thread with flat seal, G1½ - Rp1

0361951032

Screw fitting for male thread with flat seal DN 32

0361951040

Screw fitting for male thread with flat seal DN 40

0361951050

Screw fitting for male thread with flat seal DN 50

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

Right of amendment reserved © 2024 Fr. Sauter AG

303


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Type

Description

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

0560332032

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 32

0560332040

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 40

0560332050

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 50

Combination of BKTA with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆pmax: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the ball valve.

/

V

Definition of ∆ps: Maximum admissible pressure drop in the event of a malfunction (pipe break after the valve) at which the actuator reliably closes the valve by means of a return spring.

Pressure differences Actuator

AKM105F122

AKM115F120

AKM115F122

Page

AKM105F100 AKM105F120 311

311

311

311

Rotational torque

4 Nm

4 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point

Running time

30/120 s

30/120 s

120 s

120 s

24 VAC

230 VAC

Operating voltage 230 VAC

24 VAC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKTA015F300 BKTA020F300 BKTA025F300

1.8

1.8

2.0

2.0

BKTA032F300 BKTA040F300 BKTA050F300

1.2

1.2

2.0

2.0

– Actuator Page

AKM105SF132 314

AKM115SF132 314

AKM115SAF232 133

AKM115SF152 316

Rotational torque

4 Nm

8 Nm

8 Nm

7 Nm

Control signal

2-/3-point, 0...10 V

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

2-/3-point, 0...10 V, 4...20 mA

Running time

35/60/120 s

35/60/120 s

35/60/120 s

6s

Operating voltage 24 VAC/DC

24 VAC/DC

24 VAC/DC

24 VAC/DC

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

BKTA015F300 BKTA020F300 BKTA025F300

1.8

2.0

2.0

2.0

BKTA032F300 BKTA040F300 BKTA050F300

1.2

2.0

2.0

2.0

–

304

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] BKTA015F300 BKTA020F300 BKTA025F300 BKTA032F300 BKTA040F300 BKTA050F300

2.0

5.4

2.0

5.4

2.0

5.4

2.0

5.4

–

V

Right of amendment reserved © 2024 Fr. Sauter AG

305


6-way ball valves The 6-way ball valve from SAUTER is a compact and precise alternative for regulating heated/chilled ceilings and fan coils in four-pipe systems. It doubles as a regulating and changeover ball valve. While conventional solutions operate with up to four 2-way valves, four actuators and two controllers, now only one 6-way ball valve and an actuator are required. Their compact construction enables the devices to be installed in false ceilings without difficulty.

Overview of 6-way ball valves

Type designation Application Single-room control Preheater for ventilation & air-conditioning Preheater, cooler for ventilation & air-conditioning Reheater for ventilation & air-conditioning Chilled ceiling Static heating Multi-boiler system Local heating Version Nominal pressure Combination options with actuator Further information

306

B2KL • • • • • • • • PN 16 AKM 115(S) AKM 115SA AKF 112 AKF 113(S) Page 307

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

B2KL: 6-way ball valve with male thread, PN 16 Features • 6-way ball valve for changeover or continuous control of heating and cooling circuits in a 4-pipe system • Body made of moulded brass CW602N (dezincification-resistant) or CW617N • With male thread as per ISO 228 • Kvs selection with exchangeable orifice plates • In combination with valve actuators AKM 115(S), 115SA and AKF 112, 113(S) as a control unit • Strainer and screw fitting available as accessories • Water quality as per VDI 2035

B2KL015F400

Technical data

V

Parameters

Nominal pressure Valve characteristic Leakage rate Total angle of rotation

PN 16 Quasi-linear Class A as per EN 12266-1 90° (valve closed at 45°)

Operating temperature

5…90 °C

Pressure and temperature data Flow parameters PED 2014/68/EU

EN 764, EN 1333 EN 60534 Fluid group II, liquid No CE label as per article 4.3

Connection

Material

Weight

M

Ambient conditions

Standards, directives

Overview of types Type

Nominal diameter

Kvs value without orifice plate

B2KL015F400

DN 15

G ¾" B

1.25 m³/h

Moulded brass CW617N

980 g

B2KL015F401

DN 15

G ¾" B

1.25 m³/h

Moulded brass CW602N

980 g

B2KL020F411

DN 20

G ¾" B

2.8 m³/h

Moulded brass CW602N

1870 g

A

Kvs value without orifice plate. Kvs values can be adapted using orifice plates.

Orifice plates for setting the Kvs value Orifice plate set for B2KL DN15 Kvs value 0.25 m3/h

Part number 0589540001 Supplied with the 6-way ball valve

0.4 m3/h 0.63 m3/h 1 m3/h Orifice plate set for B2KL DN20 Kvs value 0.7 m3/h

Part number 0589540002 Supplied with the 6-way ball valve

1 m3/h 1.6 m3/h 2.1 m3/h

Right of amendment reserved © 2024 Fr. Sauter AG

307


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories

V

Type

Description

0378133015

1 threaded sleeve, R½, flat-sealing, with cap nut and flat seal, G¾ - R½

0378134015

1 solder nipple, Ø 15, flat-sealing, with cap nut and flat seal, G¾

0580240002

Insulation shell for 6-way ball valve DN 15

0580240003

Insulation shell for 6-way ball valve DN 20

0560284015

Screw fitting in brass, flat-sealing, female thread/male thread for DN 15

0560284020

Screw fitting in brass, flat-sealing, female thread/male thread for DN 20

0580090001

Pliers for changing orifice plate on 6-way ball valve DN 15 and DN 20

0580240001

Fitting bracket for 6-way ball valve DN 15 and DN 20

0560332015

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.5 mm, DN 15

0560332020

Strainer in gun metal, –10…150 °C, mesh aperture 0.8 mm, DN 20

0560332025

Strainer in gun metal (bronze), −10…150 °C, mesh aperture 0.8 mm, DN 25

Combination of B2KL with electrical actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after the ball valve) at which the actuator reliably closes the ball valve using the return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Pressure differences Actuator Page

AKM115F120 311

AKM115F122 311

AKM115SF132 314

AKM115SAF232 133

Rotational torque

8 Nm

8 Nm

8 Nm

8 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point, 0...10 V

0…10 V, BACnet MS/TP

Running time

120 s

120 s

35/60/120 s

35/60/120 s

24 VAC

24 VAC/DC

24 VAC/DC

Operating voltage 230 VAC ∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

2.0

2.0

2.0

2.0

Actuator Page

AKF112F120 317

AKF112F122 317

AKF113F122 317

AKF113SF122 318

Torque

7 Nm

7 Nm

7 Nm

7 Nm

Control signal

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

24 VAC/DC

24 VAC/DC

24 VAC/DC

B2KL015F400 B2KL015F401 B2KL020F411 –

Operating voltage 230 VAC

∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] ∆pmax [bar] ∆ps [bar] B2KL015F400 B2KL015F401 B2KL020F411

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

–

308

Right of amendment reserved © 2024 Fr. Sauter AG


Actuators for ball valves SAUTER actuators for ball valves adapt themselves automatically to the ball valves and enable them to be controlled accurately. The actuators are switched off as a function of the torque. These SAUTER actuators are suitable for operating two- and three-way ball valves. Furthermore, they can be used for controllers with switching or continuous outputs.

Overview of actuators for ball valves

Type designation

AKM 105, 115

AKM105SF132 AKM115SF132

AKM115SAF232

AKM115SF152

Technical data Adjustable characteristic

Equal-percentage

30/120 − 24, 230

Equal-percentage, linear, quadratic 35/60/120 − 24

Equal-percentage, linear, quadratic 35/60/120 − 24

Equal-percentage, linear, quadratic 6 − 24

• • − − − − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL Page 311

• • − • − − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL Page 313

− − • • − − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL Page 131

• • − • • − VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA Page 315

Running time (s) Return time (s) Power supply (V) Control 2-point 3-point BACnet MS/TP Positioner High-speed Spring return Combination options with ball valve Further information

Right of amendment reserved © 2024 Fr. Sauter AG

309


Type designation Technical data Adjustable characteristic Running time (s) Return time (s) Power supply (V) Control 2-point 3-point BACnet MS/TP Positioner High-speed Spring return Combination options with ball valve Further information

310

AKF 112, 113

AKF 113S

− 90 15 24, 230

− 90 15 24, 230

• • − − − • VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL

• • − • − • VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, B2KL

Page 317

Page 318

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

AKM 105, 115: Rotary actuator for ball valve Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way

ball valve B2KL • For controllers with a switching output (2-/3-point control) • Assembly with ball valves without the use of tools • Synchronous motor with electronic activation and cut-out • Maintenance-free gear unit • Gear unit can be disengaged in order to position the ball valve manually (using the lever)

AKM115F12

• Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve • Fitting vertically upright to horizontal, not suspended

V

Technical data Power supply

Power supply 230 VAC Power supply 24 VAC

±15%, 50...60 Hz ±20%, 50...60 Hz

Power cable Response time Angle of rotation

1.2 m, 3 × 0.75 mm2 Min. 200 ms 90°

Ambient temperature Ambient humidity Media temperature1)

–10...55 °C 5...95% rh, no condensation Max. 100 °C

Control

2-/3-point

Weight Housing

0.7 kg Lower section black, upper section yellow Fire-retardant plastic

Parameters

Ambient conditions

Function

Construction

Housing material Standards and directives

CE conformity according to

IP54 (EN 60529), horizontal III (EN 60730) II (EN 60730) III II EN 60730-1/EN 60730-2-14 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4

Type of protection2) Protection class 24 V Protection class 230 V Over-voltage categories Degree of contamination Directive 2006/95/EC EMC Directive 2014/30/EU

Overview of types Type

Voltage

Running time

Rotational torque

Power consumption

AKM105F100

230 VAC

30.0 s

4 Nm

2.4 W, 4.5 VA

AKM105F120

230 VAC

120.0 s

4 Nm

2.0 W, 4.0 VA

AKM105F122

24 VAC

120.0 s

4 Nm

1.6 W, 1.7 VA

AKM115F120

230 VAC

120.0 s

8 Nm

2.0 W, 4.0 VA

AKM115F122

24 VAC

120.0 s

8 Nm

1.6 W, 1.7 VA

1) 2)

At media temperatures < 5 °C or > 100 °C, appropriate accessory must be used See fitting instructions P100001578

Right of amendment reserved © 2024 Fr. Sauter AG

311


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Accessories Type

Description

0510420001

Adaptor required when temperature of the medium > 100 °C

0510240011

Adaptor required when temperature of the medium < 5 °C

0510480001

Auxiliary change-over contacts, single

0510480002

Auxiliary change-over contacts, double

A

Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V

V

312

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

AKM 105S, 115S: Rotary actuator with SAUTER Universal Technology (SUT) for ball valve Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way

ball valve B2KL • For controllers with constant output (0...10 V) or switching output (2-/3-point control) • Assembly with ball valve without the use of tools • Stepping motor with SAUTER Universal Technology (SUT) electronic control unit • Electronic force-dependent motor cut-off • Automatic recognition of applied control signal (continuous or switched)

AKM115SF132

• Coding switch for selecting characteristic and running time (35 s, 60 s, 120 s)

V

• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator • Direction of operation can be selected directly on the cable • Maintenance-free gear unit • Gear unit can be disengaged in order to position the ball valve manually (using the lever) • Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power consumption

±20%, 50...60 Hz −10%...20% 4.9 W, 8.7 VA

Running time1) Angle of rotation Response time Power cable

35/60/120 s 90° 200 ms

Parameters

Positioner

Positioning signal y Position feedback signal Starting point U0 Control span ΔU Switching range Xsh

1.2 m, 5 × 0.5 mm2 0...10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 V or 10 V 10 V 200 mV

Media temperature2) Ambient temperature Ambient humidity

Max. 100 °C −10...55 °C 5...95% rh, no condensation

Fitting

Vertically upright to horizontal, not suspended 0.7 kg Lower section black, upper section yellow Flame-retardant plastic

Ambient conditions

Construction

Weight Housing Housing material Standards, directives

CE conformity according to

1) 2)

Type of protection Protection class EMC Directive 2014/30/EU

IP54 as per EN 60529 III as per IEC 60730 EN 61000-6-1, EN 61000-6-3 EN 61000-6-4

For a running time of 35 s, the torque is halved At media temperatures < 5 °C or > 100 °C, appropriate accessory must be used

Right of amendment reserved © 2024 Fr. Sauter AG

313


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators Overview of types Type

Voltage

Rotational torque

Running time

Power consumption

AKM105SF132

24 VAC/DC

4 Nm

35/60/120 s

4.9 W, 8.7 VA

AKM115SF132

24 VAC/DC

8 Nm

35/60/120 s

4.9 W, 8.7 VA

Accessories Type

Description

0313529001

Split-range unit for setting sequences

0510420001

Adaptor required when temperature of the medium > 100 °C

0510240011

Adaptor required when temperature of the medium < 5 °C

0510480001

Auxiliary change-over contacts, single

0510480002

Auxiliary change-over contacts, double

A

Auxiliary change-over contacts: Infinitely variable 0...100%, admissible load 5(2) A, 24...230 V

V

314

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

AKM 115S F152: High-speed rotary actuator with SAUTER Universal Technology (SUT) for ball valve Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way

ball valve B2KL • For controllers with constant output (0...10 V / 4...20 mA) or switching output (2-/3-point control) • Assembly with ball valve without the use of tools • Brushless motor with electronic activation and cut-out • Intelligent adaptation of rotation angle, incl. feedback adjustment • Electronic force-dependent cut-off

AKM115SF152

• Direction of rotation selected with DIP switch

V

• Pulse length correction in 3-point operation, i.e. internal adjustment of start-up time • Gear unit can be disengaged in order to position the ball valve manually (using the lever) • Maintenance-free • Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power consumption

±20%, 50…60 Hz −10%...20% 6.5 W, 9 VA (at nominal voltage)

Rotational torque Operating noise (unloaded) Response time Angle of rotation Running time Characteristic Positioning signal y Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI Switching range Xsh

8 Nm < 49 dB(A) 10 ms 90° 6.0 s linear 0…10 V / 2…10 V, Ri = 100 kΩ, 0…20 mA / 4…20 mA, Ri = 500 Ω 0...10 V, load > 10 kΩ 0 or 10 V / 2 or 10 V 0 or 20 mA / 4 or 20 mA 10 V 100 mV 20 mA 0.1 mA

Operating temperature Media temperature1) Storage and transport temperature Ambient humidity

−20…55 °C Max. 100 °C −30…65 °C 5…85% rh, no condensation

Fitting Dimensions W × H × D Weight Housing

Vertically upright to horizontal 70 × 138 × 127 mm 0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m, 6 × 0.5 mm²

Parameters

Positioner

Ambient conditions

Construction

Housing material Power cable 1)

At media temperature > 100 °C, appropriate accessory must be used

Right of amendment reserved © 2024 Fr. Sauter AG

315


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

Standards and directives

CE conformity according to

Type of protection Protection class EMC Directive 2014/30/EU

IP54 (EN 60529), horizontal III (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4

Overview of types Type

Voltage

Rotational torque

Running time

Power consumption

AKM115SF152

24 VAC/DC

7 Nm

6s

6.5 W, 9 VA

Accessories

V

316

Type

Description

0313529001

Split-range unit for setting sequences

0510420001

Adaptor required when temperature of the medium > 100 °C

0510240011

Adaptor required when temperature of the medium < 5 °C

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

AKF 112, 113: Rotary actuator with spring return for control ball valves Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and 6-way

ball valve B2KL • For controllers with a switching output (2-/3-point control) • Returns to the starting position in the event of a power failure or the activation of a safety device • Electronic torque-dependent cut-off • Direction of rotation can be selected during fitting

AKF112F122

Technical data

V

Power supply

Power supply 230 VAC Power supply 24 VAC Power supply 24...48 V=

±10%, 50...60 Hz ±20%, 50...60 Hz ±20%

Rotational torque and holding torque Angle of rotation Power cable Running time for 90° motor Running time for 90° spring

7 Nm Max. 95° 0.9 m, 0.75 mm² (fixed to housing) 90 s 15 s

Ambient temperature Ambient humidity

–32...55 °C 5...95% rh

Weight Housing Housing material

1.2 kg Two-piece Cast aluminium

Type of protection

IP54 as per EN 60529 IP42 depending on fitting position II (EN 60730) III (EN 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 III II

Parameters

Ambient conditions

Construction

Standards and directives

CE conformity according to Only for AKF120F120

Protection class 230 V Protection class 24 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination

Overview of types Type

Power consumption

Control function

Voltage

AKF112F120

4.5 W, 7.0 VA

2-point

230 VAC

AKF112F122

3.5 W, 5.0 VA

2-point

24 VAC / 24…48 VDC

AKF113F122

3.5 W, 5.0 VA

3-point

24 VAC / 24…48 VDC

Accessories Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

Right of amendment reserved © 2024 Fr. Sauter AG

317


Valves, control valves, dampers, actuators | Ball valves and ball valve actuators

AKF 113S: Rotary actuator with spring return and positioner Features • For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA and

6‑way ball valve B2KL • For controllers with a continuous output (0…10 V) • Returns to the starting position in the event of a power failure or the activation of a safety device • Electronic torque-dependent cut-off • Direction of rotation can be selected during fitting

AKF113SF122

Technical data Power supply

V

Power supply 24 VAC Power supply 24...48 V= Rated power during continuous operation Power consumption when idle

±20%, 50...60 Hz ±20% 3.5 W, 5 VA

Positioning signal y Position feedback signal Admissible load Starting point U0 Control span ΔU Switching range Xsh Rotational torque and holding torque Angle of rotation Power cable Running time for 90° motor Running time for 90° spring

0...10 V, Ri = 100 kΩ 0...10 V (0...100%) > 10 kΩ 0V 10 V 0.2 V 7 Nm Max. 95° 0.9 m, 4 × 0.75 mm² (fixed to housing) 90 s 15 s

Ambient temperature Ambient humidity

–32...55 °C < 95% rh

Weight Housing Housing material

1.3 kg Two-piece Cast aluminium

Type of protection Protection class EMC Directive 2014/30/EU

IP54 as per EN 60529 III as per IEC 60730 EN 61000-6-2, EN 61000-6-3

2.5 W, 2.5 VA

Parameters

Positioner

Ambient conditions

Construction

Standards and directives

CE conformity according to

Overview of types Type

Features

AKF113SF122

Rotary actuator with spring return and positioner

Accessories

318

Type

Description

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

Right of amendment reserved © 2024 Fr. Sauter AG


Control valves and butterfly valves SAUTER control valves are used to control heating and cooling systems. The 3‑way version is suitable for controlling and change-over functions, while the 4‑way version is employed for higher temperatures in the return circuit. SAUTER butterfly valves are very versatile and are used for control and shut-off functions. Because they close absolutely tightly, they reduce energy consumption.

Overview of control valves and butterfly valves

Type designation

M3R, M4R

MH32F, MH42F

DEF

Application Preheater for ventilation & air-conditioning Static heating Cooling tower Multi-boiler system

• • − −

• • − −

− − • •

Version Control valve Butterfly valve

• −

• −

− •

15...50 PN 10 AR30 W, ASM 105, 115, 124 ADM 322(S)

20...150 PN 6 AR30 W, ASM 105, 115, 124 ADM 322(S)

Page 320

Page 322

25...200 PN 16 AR30 W, A44 W, ASF 122, 123 ASM 124(S) ASM 134(S) ADM 322(S) Page 324

Technical data Nominal diameter (DN) Nominal pressure Combination options with actuator

Further information

Right of amendment reserved © 2024 Fr. Sauter AG

319


Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators

M3R, M4R: Control valve with threaded connection, PN 10 Features • M3R: 3-way valves with nominal diameters DN 15...50 • M4R: 4-way valves with nominal diameters DN 20...50 • Used in combination with the ADM 322 and ASM 105, 115, 124 motorised actuators • Manual adjustment by means of lever and end stops • Body, cover, front gate and spindle made of brass

M3R015F200

Technical data Parameters

V M3R0**F200

Nominal pressure Angle of rotation Valve characteristic Leakage rate

10 bar 90° Linear < 0.1%

Operating temperature Operating pressure

2...110 °C Max. 10 bar

Ambient conditions

M4R0**F200

Overview of types Type

Nominal diameter

Kvs value

Weight

M3R015F200

DN 15 (Rp½)

2.5 m³/h

0.8 kg

M3R020F200

DN 20 (Rp¾)

6 m³/h

0.7 kg

M3R025F200

DN 25 (Rp1)

12 m³/h

1.2 kg

M3R032F200

DN 32 (Rp1¼)

18 m³/h

1.2 kg

M3R040F200

DN 40 (Rp1½)

26 m³/h

2.2 kg

M3R050F200

DN 50 (Rp2)

40 m³/h

2.3 kg

M4R020F200

DN 20 (Rp¾)

6 m³/h

0.8 kg

M4R025F200

DN 25 (Rp1)

12 m³/h

1.2 kg

M4R032F200

DN 32 (Rp1¼)

18 m³/h

1.3 kg

M4R040F200

DN 40 (Rp1½)

26 m³/h

2.3 kg

M4R050F200

DN 50 (Rp2)

40 m³/h

2.5 kg

Accessories

320

Type

Description

0510240013

ADM322 mounting kit with M3R, M4R, MH32, MH42

0361977001

Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124

0361977002

Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Combination of M3R/M4R with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Maximum admissible pressure drop in the event of a malfunction (pipe break after control valve) at which the actuator reliably closes the valve by means of a return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the valve.

Actuator Page

ASM105F100 334

ASM105F120 334

ASM105F122 334

ASM105SF132 336

ASM115F120 334

ASM115F122 334

ASM115SF132 336

Rotational torque

5 Nm

5 Nm

5 Nm

5 Nm

10 Nm

10 Nm

10 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point, 0...10 V 2-/3-point

2-/3-point

2-/3-point, 0...10 V

Running time

30 s

120 s

120 s

35/60/120 s

120 s

120 s

60/120 s

230 V~

24 V~

24 V =/~

230 V~

24 V~

24 V =/~

Operating voltage 230 V~ As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

M3R015F200

2.0

2.0

2.0

2.0

–

–

–

M3R020F200 M4R020F200

1.0

1.0

1.0

1.0

–

–

–

M3R025F200 M3R032F200 M3R040F200 M3R050F200 M4R025F200 M4R032F200 M4R040F200 M4R050F200

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Cannot be used as distribution valve Actuator

ADM322SF122 ADM322SF152

ASM124F120 ASM124F122

ASM124SF132

Page

ADM322F120 ADM322F122 ADM322HF120 ADM322HF122 ADM322PF120 ADM322PF122 330

332

340

345

Torque

15 Nm

15 Nm

18 Nm

15 Nm

Control signal

3-point

2-/3-point, 0...10 V

2-/3-point

2-/3-point, 0...10 V

Running time

120 s

30/60/120 s

120 s

60/120 s

24 VAC/DC

24 V=/~ / 230 V

24 V=/~ / 230 V

Operating voltage 24 V~/= / 230 V As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

M3R015F200

2.0

2.0

–

–

M3R020F200 M3R025F200 M4R020F200 M4R025F200

1.0

1.0

–

–

M3R032F200 M3R040F200 M3R050F200 M4R032F200 M4R040F200 M4R050F200

1.0

1.0

1.0

1.0

Cannot be used as distribution valve

A

Accessories required: Assembly materials; see accessories. With ASM 124, it is not possible to fit auxiliary contacts or a potentiometer

Right of amendment reserved © 2024 Fr. Sauter AG

321

V


Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators

MH32F, MH42F: Control valve with flange connection, PN 6 Features • MH32F: 3-way valves with nominal diameters DN 20...150 • MH42F: 4-way valves with nominal diameters DN 32...50 • Can be combined with motorised actuators ADM 322 and ASM 105, 115, 124 • Manual adjustment via lever • Body made of grey cast iron; brass gate

MH32F40F200

• Spindle made of brass up to DN 25 and stainless steel from DN 32 • Stuffing box with double O-ring guarantees the tightness of the seal at the spindle

Technical data

V

MH32F**F200

MH42F**F200

Parameters

Nominal pressure Angle of rotation Valve characteristic

6 bar 90° Linear

Operating temperature Operating pressure

2...110 °C Max. 6 bar

Ambient conditions

Overview of types 3-way control valve

4-way control valve

Type

Nominal diameter

Kvs value

Leakage rate in % of Kvs Weight

MH32F20F200

DN 20

12 m³/h

1%

2.7 kg

MH32F25F200

DN 25

18 m³/h

1%

3.5 kg

MH32F32F200

DN 32

28 m³/h

1%

4.6 kg

MH32F40F200

DN 40

44 m³/h

1%

5.6 kg

MH32F50F200

DN 50

66 m³/h

1%

7.9 kg

MH32F65F200

DN 65

100 m³/h

1%

9.2 kg

MH32F80F200

DN 80

150 m³/h

1%

14.2 kg

MH32F100F200 DN 100

225 m³/h

1%

19 kg

MH32F125F200 DN 125

310 m³/h

1%

25.8 kg

MH32F150F200 DN 150

420 m³/h

1%

35.5 kg

MH42F32F200

DN 32

28 m³/h

1.5 %

5.7 kg

MH42F40F200

DN 40

44 m³/h

1.5 %

7.1 kg

MH42F50F200

DN 50

66 m³/h

1.5 %

8.3 kg

A A A

MH32F20...25: 3-way valve: Zinc cover, brass spindle MH32F32...150: 3-way valve: Cover made of grey cast iron, spindle made of stainless steel MH42F32...50: 4-way valve: Cover made of grey cast iron, spindle made of stainless steel

Accessories

322

Type

Description

0360392020

Welding flange, DN 20, smooth, PN 6, incl. asbestos-free seal

0360392025

Welding flange, DN 25, smooth, PN 6, incl. asbestos-free seal

0360392032

Welding flange, DN 32, smooth, PN 6, incl. asbestos-free seal

0360392040

Welding flange, DN 40, smooth, PN 6, incl. asbestos-free seal

0360392050

Welding flange, DN 50, smooth, PN 6, incl. asbestos-free seal

0360392065

Welding flange, DN 65, smooth, PN 6, incl. asbestos-free seal

0360392080

Welding flange, DN 80, smooth, PN 6, incl. asbestos-free seal

0360392100

Welding flange, DN 100, smooth, PN 6, incl. asbestos-free seal

0360392125

Welding flange, DN 125, smooth, PN 6, incl. asbestos-free seal

0360392150

Welding flange, DN 150, smooth, PN 6, incl. asbestos-free seal

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Type

Description

0361977001

Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124

0361977002

Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115

0510240013

ADM322 mounting kit with M3R, M4R, MH32, MH42

Combination of MH32F/MH42F with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Max. admissible pressure drop in the event of a malfunction (pipe break after control valve) at which the actuator reliably closes the control valve using the return spring.

/

Definition of ∆p max: Maximum admissible pressure drop in control mode at which the actuator reliably opens and closes the control valve.

Pressure differences Actuator Page

ASM105F100 334

ASM105F120 334

ASM105F122 334

ASM105SF132 336

ASM115F120 334

ASM115F122 334

ASM115SF132 336

10 Nm

10 Nm

10 Nm

Rotational torque

5 Nm

5 Nm

5 Nm

5 Nm

Control signal

2-/3-point

2-/3-point

2-/3-point

2-/3-point, 0...10 V 2-/3-point

2-/3-point

2-/3-point, 0...10 V

Running time

30 s

120 s

120 s

35/60/120 s

120 s

120 s

60/120 s

230 V~

24 V~

24 V =/~

230 V~

24 V~

24 V =/~

Operating voltage 230 V~ As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

MH32F20F200 MH32F25F200 MH32F32F200 MH32F40F200

1.0

1.0

1.0

1.0

1.0

1.0

1.0

MH32F50F200 MH32F65F200 MH32F80F200

–

–

–

–

0.5

0.5

0.5

Cannot be used as distribution valve Actuator

ADM322SF122 ADM322SF152

ASM124F120 ASM124F122

ASM124SF132

Page

ADM322F120 ADM322F122 ADM322HF120 ADM322HF122 ADM322PF120 ADM322PF122 330

332

340

345

Torque

15 Nm

15 Nm

18 Nm

15 Nm

Control signal

3-point

2-/3-point, 0...10 V

2-/3-point

2-/3-point, 0...10 V

Running time

120 s

30/60/120 s

120 s

60/120 s

24 VAC/DC

24 V=/~ / 230 V

24 V=/~ / 230 V

Operating voltage 24 V~/= / 230 V As control valve

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

MH32F20F200 MH32F25F200 MH32F32F200 MH32F40F200 MH42F32F200 MH42F40F200

1.0

1.0

1.0

1.0

MH32F50F200 MH32F65F200 MH32F80F200 MH32F100F200 MH32F125F200 MH32F150F200 MH42F50F200

0.5

0.5

0.5

0.5

Cannot be used as distribution valve

A

Accessories required: Assembly materials; see accessories. With ASM 124, it is not possible to fit auxiliary contacts or a potentiometer

Right of amendment reserved © 2024 Fr. Sauter AG

323

V


Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators

DEF: Tight-sealing butterfly valve, PN 16 Features • For cutting off and regulating water and low-pressure steam up to 110 °C • Butterfly valve with 3-way brass bearing bush as spindle bearing • Fits PN 6, PN 10 and PN 16 flanges • Can be combined with motorised actuators of the ADM 322 and A44W type or damper actuators with

spring return of the ASM 124, 134 and ASF 122, 123 type Damper body made of grey cast iron • DEF100F200

• Collar made of ethylene-propylene rubber • Butterfly disc made of stainless steel • Spindle made of stainless steel with two O-rings

V

Technical data Parameters

Nominal pressure Valve characteristic Angle of rotation Leakage rate1)

16 bar Linear 90° < 0,0001% of the Kvs value

Operating temperature Maximum operating pressure

–10...130 °C 16 bar

Ambient conditions

Overview of types Type

Nominal diameter

Kvs value

Weight

DEF025F200

DN 25

36 m³/h

1 kg

DEF032F200

DN 32

40 m³/h

1.15 kg

DEF040F200

DN 40

50 m³/h

2.75 kg

DEF050F200

DN 50

85 m³/h

3.05 kg

DEF065F200

DN 65

215 m³/h

4.05 kg

DEF080F200

DN 80

420 m³/h

4.3 kg

DEF100F200

DN 100

800 m³/h

4.85 kg

DEF125F200

DN 125

1010 m³/h

7.2 kg

DEF150F200

DN 150

2100 m³/h

9.5 kg

DEF200F200

DN 200

4000 m³/h

12 kg

Accessories Type

Description

0361632***

Two welding flanges, complete PN 6 as per EN 1092-1 DN 25, DN 32, DN 40, DN 50, DN 65, DN 80, DN 100, DN 125, DN 150, DN 200

0361633***

Two welding flanges, complete PN 10 (DN 25...100) as per EN 1092-1 and PN 16 (DN 25...200) as per EN 1092-1 DN 25, DN 32, DN 40, DN 50, DN 65, DN 80, DN 100, DN 125, DN 150, DN 200

0361634200

2 welding flanges complete PN 10 (DN 200) as per EN 1092-1

0378110001

Assembly parts; DEF DN 25…65 for A44

0378111001

Assembly parts; DEF DN 80…125 for A44

0378112001

Assembly parts; DEF DN 150…200 for A44

0378113001

Assembly parts; DEF DN 25…100 for ASF122/123

0372455001

Assembly part; DEF DN25...65 for ASM 124/134

0372455002

Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134

0372455003

Assembly part; DEF DN150...200 for ASM 134

1)

324

At Δp 1.5 bar

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Type

Description

0510240014

ADM322 fitting kit with DEF DN20...65

0510240015

ADM322 fitting kit with DEF DN80...100

A

Ordering information: DN 25 = /025, DN 100 = /100

Combination of DEF with electric actuators

/ /

Warranty: The technical data and pressure differences indicated here are applicable only in combination with SAUTER valve actuators. The warranty does not apply if used with valve actuators from other manufacturers.

Definition of ∆p s: Max. admissible pressure drop in the event of a malfunction (pipe break after the damper) at which the actuator reliably closes the damper using the return spring.

/

Definition of ∆p max: Max. admissible pressure drop in control mode at which the actuator reliably opens and closes the damper.

V

Pressure differences Actuator

ADM322SF122 ADM322SF152

ASM124F120 ASM124F122

ASM124SF132

Page

ADM322F120 ADM322F122 ADM322HF120 ADM322HF122 ADM322PF120 ADM322PF122 330

332

340

345

Torque

15 Nm

15 Nm

18 Nm

15 Nm

Control signal

3-point

2-/3-point, 0...10 V

2-/3-point

2-/3-point, 0...10 V

Running time

120 s

30/60/120 s

120 s

60/120 s

24 VAC/DC

24 V=/~ / 230 V

24 V=/~ / 230 V

Operating voltage 24 V~/= / 230 V Closes against the pressure

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

DEF025F200 DEF032F200 DEF040F200 DEF050F200

10.0

10.0

10.0

10.0

DEF065F200

7.0

7.0

7.0

7.0

DEF080F200

4.0

4.0

4.0

4.0

DEF100F200

2.0

2.0

2.0

2.0

Cannot be used to close with the pressure Actuator

ASF122F122

ASF122F222

ASF123F122

ASF123SF122

Page

ASF122F120 ASF122F220 350

350

350

350

352

Torque

18 Nm

18 Nm

18 Nm

18 Nm

18 Nm

Control signal

2-point

2-point

2-point

3-point

0...10 V

Running time

90 s

90 s

90 s

90 s

90 s

Operating voltage 230 V~

24 V~

24V~

24V~

24V~

Closes against the pressure

∆pmax [bar]

∆pmax ∆ps [bar] [bar]

∆pmax ∆ps [bar] [bar]

∆pmax ∆ps [bar] [bar]

DEF025F200 DEF032F200 DEF040F200 DEF050F200

10.0

10.0

10.0

10.0

10.0

10.0

DEF065F200

7.0

7.0

7.0

7.0

7.0

DEF080F200

4.0

4.0

4.0

4.0

DEF100F200

2.0

2.0

2.0

2.0

∆ps [bar]

∆pmax [bar]

∆ps [bar]

10.0

10.0

10.0

10.0

7.0

7.0

7.0

7.0

7.0

4.0

4.0

4.0

4.0

4.0

4.0

2.0

2.0

2.0

2.0

2.0

2.0

Cannot be used to close with the pressure

Right of amendment reserved © 2024 Fr. Sauter AG

325


Valves, control valves, dampers, actuators | Control valves and rotary and damper actuators Actuator Page

A44W2F001

A44W2F020

A44W2SF001

ASM134SF132 345

Rotational torque

30 Nm

30 Nm

30 Nm

30 Nm

30 Nm

Control signal

3-point

3-point

0...10 V; 4...20 mA 0...10 V

3-point

Running time

120 s

120 s

120 s

120/240 s

120/240 s

24 V~

24V~

24 V~

230 V~

Operating voltage 230 V~ Closes against the pressure

V

ASM134F130 342

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

∆pmax [bar]

DEF025F200 DEF032F200 DEF040F200 DEF050F200

16.0

16.0

16.0

–

–

DEF065F200

16.0

16.0

16.0

7.0

7.0

DEF080F200 DEF100F200

10.0

10.0

10.0

7.0

7.0

DEF125F200

6.0

6.0

6.0

7.0

7.0

DEF150F200

5.0

5.0

5.0

6.0

6.0

DEF200F200

3.0

3.0

3.0

2.0

2.0

Cannot be used to close with the pressure

A

326

Accessories required: Assembly parts; see accessories

Right of amendment reserved © 2024 Fr. Sauter AG


Damper and rotary actuators SAUTER damper and rotary actuators provide a torque- and time-dependent cut-off facility for efficient energy use. They operate air dampers, shut-off dampers and multi-leaf dampers. The overload protection and the end position detector in the rotary actuators ensures the efficient use of energy. SAUTER rotary actuators can be used for controllers with a switching or continuous output.

Overview of damper and rotary actuators

Type designation

ADM322F12*

ADM322SF1*2

15 120 (240) 24, 230

15 30, 60 24

• − Page 329

• • Page 331

Technical data Torque (Nm) Running time for 90°/(s) Power supply (VAC) Control 3-point Positioner Further information

Type designation

ASM 105, 115

ASM 105S, 115S F132

ASM 105S, 115S F152

ASM 124

Technical data Torque (Nm) Running time (s) Power supply (V)

5, 10 30, 120 24, 230

5, 10 35, 60, 120 24

5, 10 3, 6 24

18 120 24, 230

• • − − − Page 334

• • • − − Page 336

• • • • − Page 338

• • − − − Page 340

Control 2-point 3-point Positioner High-speed Spring return Further information

Right of amendment reserved © 2024 Fr. Sauter AG

327


Type designation

ASM 134

ASM 124S, 134S

ASF 112, 113

ASF 113S

Technical data Torque (Nm) Running time (s) Power supply (V)

30 120, 240 230

15, 30 60, 120, 240 24, 230

7 90 24

7 90 24

− • − − − Page 342

• • • − − Page 344

• • − − • Page 346

− − • − • Page 348

Control 2-point 3-point Positioner High-speed Spring return Further information

Type designation

ASF 122, 123

ASF 123S

Technical data Torque (Nm) Running time (s) Power supply (V)

18 90 24, 230

18 90 230

• • − − • Page 350

− − • − • Page 352

Control 2-point 3-point Positioner High-speed Spring return Further information

328

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators

ADM 322: Rotary actuator Features • For operating control units such as control valves, butterfly valves etc. • For controllers with a switching output (2-point or 3-point control) • 15 Nm nominal torque and holding torque • Synchronous motor with electronic control unit and load-dependent cut-off

ADM322F12*

• Low operating noise • Direction of operation and running time can be set using coding switches • Gear unit can be disengaged for manual adjustment • Electrical parallel operation of up to five actuators possible • Numerous adapters enable the unit to be fitted onto defined non-SAUTER control valves

V

• Maintenance-free gearbox made of plastic and steel, and gearbox base-plates made of steel • Mounting columns made of aluminium

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC Power supply 230 VAC Connections (screw terminals) ADM322(H, P)F120 ADM322(H, P)F122

± 20%, 50…60 Hz −10%…20% ± 15%

Power consumption Power consumption

Max. 1.5 mm2 < 2.2 W < 2.5 W

Operating noise1) Running time for 90° Response time Angle of rotation Rotational torque and holding torque

< 30 dB(A) (loaded) 120 (240) s < 200 ms Max. 95° 15 Nm

Operating temperature Storage and transport temperature Air humidity without condensation

−20…55 °C −40…80 °C 5…85% rh

Dimensions W × H × D Weight Fitting position

194 × 116 × 86 mm 1.5 Vertically upright to horizontal, not fitted upside down Three-part Flame retardant yellow/black plastic With break-outs, for metric screw fittings M20×1.5

Parameters

Ambient conditions

Construction

Housing Housing material Cable inlet

Standards and directives

Type of protection Protection class CE conformity according to

EMC Directive 2014/30/EU

Low-Voltage Directive 2014/35/EU

1)

IP54 (EN 60529) II (EN 60730-1), EN 60730-2-14 III (EN 60730-1), EN 60730-2-14 EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 60730-1 EN 60730-2-14

Operating noise with the slowest running time

Right of amendment reserved © 2024 Fr. Sauter AG

329


Valves, control valves, dampers, actuators | Damper and rotary actuators Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)

III II 2000 metres EN ISO 12100:2018

Overview of types

V

Type

Nominal voltage

Type

ADM322F120

230 V~

–

ADM322F122

24 V~/=

–

ADM322HF120

230 V~

Auxiliary contacts

ADM322HF122

24 V ~/=

Auxiliary contacts

ADM322PF120

230 V~

Potentiometer

ADM322PF122

24 V~/=

Potentiometer

Accessories

330

Type

Description

0510600001

Cable module, 1.2 m, 3-wire, PVC

0510600002

Cable module, 1.2 m, 3-wire, halogen-free

0510600003

Cable module, 1.2 m, 6-wire, PVC

0510600004

Cable module, 1.2 m, 6-wire, halogen-free

0510600005

Cable module, 5 m, 3-wire, PVC

0510600006

Cable module, 5 m, 3-wire, halogen-free

0510600007

Cable module, 5 m, 6-wire, PVC

0510600008

Cable module, 5 m, 6-wire, halogen-free

0510240013

ADM322 mounting kit with M3R, M4R, MH32, MH42

0510240014

ADM322 fitting kit with DEF DN20...65

0510240015

ADM322 fitting kit with DEF DN80...100

0510390002

Adapter set for control valve, Honeywell, DZ/ZR valves only

0510390003

Adapter set for control valve, Danfoss

0510390004

Adapter set for Caleffi control valve

0510390005

Adapter set for control valve, Coster

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators

ADM 322S: Rotary actuator with positioner Features • For operating control units such as control valves, butterfly valves etc. • For controllers with a continuous output • 15 Nm nominal torque and holding torque • ADM322SF122: Synchronous motor with electronic control unit and load-dependent cut-off

ADM322SF1*2

• ADM322SF152: Brushless DC motor with SUT (SAUTER Universal Technology) electronic control unit and

electronic, load-dependent cut-off • Low operating noise • Automatic recognition of applied control signal • With the built-in absolute distance measurement system, the position is always maintained in the case of

power failure

V

• The direction of operation, running time and control signal (voltage/current) can be adjusted via coding

switches • High-speed variant ADM322SF152 with 30 s or 60 s for angle of rotation 90° • Gear unit can be disengaged for manual adjustment • Easy re-initialisation using a coding switch • Electrical parallel operation of up to five actuators possible • Numerous adapters enable the unit to be fitted onto defined non-SAUTER control valves • ADM322SF152: Integrated forced operation can be set via coding switches (with selectable direction of

operation) • Maintenance-free gearbox made of plastic and steel, and gearbox base-plates made of steel • Mounting columns made of aluminium

Technical data Power supply

Power supply

24 VDC −10%…20% 24 VAC ± 20% (50…60 Hz)

ADM322SF122 positioner

Operating noise1) Response time Angle of rotation Rotational torque and holding torque Control signal y

ADM322SF152 positioner

Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI Max. admissible line resistance Control signal y

< 30 dB(A) (loaded) < 200 ms Max. 95° 15 Nm 0...10 V, Ri ≥ 50 kΩ, 0...20 mA, Ri ≤ 50 Ω 2...10 V (4...20 mA) 0…10 V, load ≥ 5 kΩ 0 or 10 V 0 or 20 mA 10 V 130 mV, 0.26 mA 20 mA 3Ω 0...10 V, Ri ≥ 50 kΩ, 4...20 mA, Ri ≤ 50 Ω 0…10 V, load ≥ 5 kΩ 0 or 10 V 4 or 20 mA 10 V 130 mV, 0.26 mA 20 mA

Parameters

Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI 1)

Operating noise with the slowest running time

Right of amendment reserved © 2024 Fr. Sauter AG

331


Valves, control valves, dampers, actuators | Damper and rotary actuators Max. admissible line resistance

3Ω

Operating temperature Storage and transport temperature Humidity without condensation

−20…55 °C −40…80 °C 5…85% rh

Connection terminals Cable inlet

Screw terminals, max. 1.5 mm² With break-outs, for metric screw fittings M20 × 1.5 Three-part Flame-retardant yellow/black plastic 194 × 166 × 86 mm Vertically upright to horizontal, not fitted upside down 1.5 kg

Ambient conditions

Construction

Housing Housing material Dimensions W × H × D Fitting position

V

Weight Standards and directives

Type of protection Protection class EMC Directive 2014/30/EU

CE conformity according to

Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Max. altitude Machinery Directive 2006/42/EC (according to Appendix II, 1B)

IP54 (EN 60529) III (EN 60730-1), EN 60730-2-14 EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1 EN 60730-2-14 III II 2000 m EN ISO 12100:2018

Overview of types Type

Description

ADM322SF122

Rotary actuator, continuous, 24 VDC/AC, running time 120 s, 15 Nm

ADM322SF152

Rotary actuator, continuous, 24 VDC/AC, running time 30 s, 15 Nm

Power consumption at nominal voltage Type ADM322SF122

Running time for 90° [s] 120

ADM322SF152

30 (60)

Status Active power P [W] Operation < 2.5 Standstill < 0.3 Sizing 3.0 Operation < 2.3 Standstill < 0.5 Sizing 3.0

Apparent power S [VA] 5.0 – 6.0 4.5 – 6.0

Accessories

332

Type

Description

0510600001

Cable module, 1.2 m, 3-wire, PVC

0510600002

Cable module, 1.2 m, 3-wire, halogen-free

0510600003

Cable module, 1.2 m, 6-wire, PVC

0510600004

Cable module, 1.2 m, 6-wire, halogen-free

0510600005

Cable module, 5 m, 3-wire, PVC

0510600006

Cable module, 5 m, 3-wire, halogen-free

0510600007

Cable module, 5 m, 6-wire, PVC

0510600008

Cable module, 5 m, 6-wire, halogen-free

0313529001

Split-range unit for setting sequences

0510240013

ADM322 mounting kit with M3R, M4R, MH32, MH42

0510240014

ADM322 fitting kit with DEF DN20...65

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Type

Description

0510240015

ADM322 fitting kit with DEF DN80...100

0510390002

Adapter set for control valve, Honeywell, DZ/ZR valves only

0510390003

Adapter set for control valve, Danfoss

0510390004

Adapter set for Caleffi control valve

0510390005

Adapter set for control valve, Coster

ADM322SF152 only Type

Description

0500420002

4…20 mA feedback module for valve actuators AVM321S and AVM322S

0500570003

Constant 230 V module for valve actuators AVM321S and AVM322S

V

Right of amendment reserved © 2024 Fr. Sauter AG

333


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASM 105, 115: Damper actuator Features • For controllers with switching output (2- and 3-point) • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Synchronous motor with electronic activation and cut-out • Maintenance-free

ASM105F122

• Suitable for all fitting positions

Technical data Parameters

V

Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time

Max. 95° Ø 8...16 mm, □ 6,5...12.5 mm Max. 300 HV < 30 dB (A) 200 ms

Ambient temperature1) Ambient humidity

–20...65 °C 5...85% rh, no condensation

Control

2-/3-point

Weight Housing

0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m long, 3 × 0.75 mm²

Ambient conditions

Function

Construction

Housing material Power cable Standards and directives

CE conformity according to

Type of protection Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Directive 2006/95/EC Low-Voltage Directive 2014/35/EU2)

IP54 (EN 60529) III (EN 60730) II (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 1050 EN 60730-1, EN 60730-2-14 Over-voltage category III Degree of contamination II

Overview of types Type

Rotational torque and holding torque

Running time for 90°

Power supply

Power consumption

ASM105F100

5 Nm

30 s

230 V~

2.4 W, 5.4 VA

ASM105F120

5 Nm

120 s

230 V~

2.0 W, 5.0 VA

ASM105F122

5 Nm

120 s

24 V~

1.6 W, 1.7 VA

ASM115F120

10 Nm

120 s

230 V~

2.0 W, 5.0 VA

ASM115F122

10 Nm

120 s

24 V~

1.6 W, 1.7 VA

1) 2)

334

Operating time approx. 80% up to 65 °C, 100% up to 55 °C Only for ASM1*5F1*0

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type

Description

0361977002

Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115

0372145001

Auxiliary change-over contacts, single

0372145002

Auxiliary change-over contacts, double

0372286001

Potentiometer, 130 Ω

0372286002

Potentiometer, 1000 Ω

0372286003

Potentiometer, 5000 Ω

0372300001

Torsion protection, long (230 mm)

0372301001

Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.

0372320001

Hexagon key as visualisation for position indicator

A A

Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator

V

Right of amendment reserved © 2024 Fr. Sauter AG

335


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASM 105S, 115S F132: Damper actuator with SAUTER Universal Technology (SUT) Features • For controllers with switching (2- and 3-point) or continuous output (0…10 V) • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Stepping motor with electronic activation and cut-out • Maintenance-free

ASM105SF132

• Intelligent adaptation of rotation angle, incl. feedback adjustment • Free configuration using the CASE Drive PC tool • Suitable for all fitting positions

V

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC

±20%, 51...60 Hz ±20%

Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time Control signal y Positional feedback signal y0 Starting point U0 Control span ΔU Switching range Xsh

Max. 95° Ø 8...16 mm, □ 6,5...12.5 mm Max. 300 HV < 30 dB (A) 200 ms 0...10 V, Ri > 100 kΩ 0...10 V; load > 10 kΩ 0 or 10 V 10 V 200 mV

Ambient temperature Ambient humidity

–20...55 °C < 95% rh, no condensation

Weight Housing

0.7 kg Lower section black, upper section yellow Fire-retardant plastic 1.2 m long, 5 × 0.5 mm²

Parameters

Positioner

Ambient conditions

Construction

Housing material Power cable Standards and directives

Type of protection Protection class EMC Directive 2014/30/EU

CE conformity

IP54 (EN 60529) III (IEC 60730) EN 61000-6-1 EN 61000-6-3 EN 61000-6-4 EN 1050

Directive 2006/95/EC

Overview of types

336

Type

Rotational torque and holding tor- Running time for 90° que (Nm)

Power consumption

ASM105SF132

5

35/60/120 s

5.0 W, 9.0 VA

ASM115SF132

10

60/120 s

4.8 W, 8.7 VA

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type

Description

0313529001

Split-range unit for setting sequences

0361977002

Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115

0372145001

Auxiliary change-over contacts, single

0372145002

Auxiliary change-over contacts, double

0372286001

Potentiometer, 130 Ω

0372286002

Potentiometer, 1000 Ω

0372286003

Potentiometer, 5000 Ω

0372300001

Torsion protection, long (230 mm)

0372301001

Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.

0372320001

Hexagon key as visualisation for position indicator

A A

Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V

V

Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator

Right of amendment reserved © 2024 Fr. Sauter AG

337


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASM 105S, 115S F152: High-speed damper actuator with SAUTER Universal Technology (SUT) Features • For controllers with switching (2- and 3-point) or continuous output (0…10 V) • Brushless motor with electronic activation and cut-out • Intelligent adaptation of rotation angle • Electronic force-dependent cut-off • Direction of rotation selection via DIP switch

ASM115SF152

• Pulse length correction in 3-point operation, i.e. internal adjustment of start-up time • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment

V

• Maintenance-free • Fitting: Vertically upright to horizontal, not suspended

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC

±20%, 50…60 Hz +20%, -10%

Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise (unloaded) Response time Positioning signal y Positional feedback signal y0 Starting point U0 Starting point I0 Control span ΔU Switching range Xsh Control span ΔI Switching range Xsh

Max. 95° Ø 8…16 mm, □ 6.5…12.5 mm Max. 300 HV < 49 dB (A) 10 ms (electrically compensated) 0…10 V / 2…10 V, Ri = 100 kΩ, 0…20 mA / 4…20 mA, Ri = 500 Ω 0...10 V, load > 10 kΩ 0 or 10 V / 2 or 10 V 0 or 20 mA / 4 or 20 mA 10 V 100 mV 20 mA 0.1 mA

Operating temperature Storage and transport temperature Ambient humidity

−20…55 °C −30…65 °C 5…85% rh, no condensation

Dimensions W × H × D Weight Housing Housing material Power cable

70 × 63 × 133 mm 0.7 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 6 × 0.5 mm²

Type of protection Protection class

IP54 (EN 60529) III (EN 60730)

Parameters

Positioner

Ambient conditions

Construction

Standards, directives

338

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators CE conformity

EMC Directive 2014/30/EU

UL and CAN compliance (ASM105SF152U only)

Electrical safety

EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 UL 60730-1 Part 1, UL 60730-2-14 Part 2, CAN/CSA-E60730-1:02 Part 1 and Annex 1

Overview of types

/

Rotational torque and holding torque: Holding torque is typically 1.5 Nm when the actuator is without power

Type

Rotational torque and holding tor- Running time for 90° que

Power consumption

ASM105SF152

5 Nm

3s

6.0 W, 8.5 VA

ASM115SF152

10 Nm

6s

6.5 W, 9.0 VA

ASM105SF152U 3 Nm

3s

6.0 W, 8.5 VA

V

Accessories Type

Description

0313529001

Split-range unit for setting sequences

0361977002

Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105, 115

0372300001

Torsion protection, long (230 mm)

0372301001

Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.

A

The UL compliances of the ASM105SF152U do not apply to the accessories

Right of amendment reserved © 2024 Fr. Sauter AG

339


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASM 124: Damper actuator Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) output • Synchronous motor with electronic activation and cut-out • Maintenance-free gear unit • Electronic end position detector and motor cut-off

ASM124F12*

• Self-centring spindle adapter for fitting onto damper spindle • Gear unit can be disengaged to position the damper and for manual adjustment • Suitable for all fitting positions • Threaded holes (M5) for fitting to bracket

V

• Version with halogen-free cable on demand

Technical data Power supply

Power supply 230 VAC Power supply 24 VAC

±15%, 50...60 Hz ±20%, 50...60 Hz

Rotational torque and holding torque Running time for 90° Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time

18 Nm 120 s Max. 95° Ø 12...20 mm, □ 10...16 mm Max. 300 HV < 30 dB (A) 200 ms

Ambient temperature Ambient humidity

−20...55 °C < 95% rh, no condensation

Weight Housing

1.2 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 3 × 0.75 mm²

Parameters

Ambient conditions

Construction

Housing material Power cable Standards, directives

Type of protection Protection class 230 V Protection class 24 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Mode of operation Software

IP40 (EN 60529), IP43 (EN 60529), IP54 (EN 60529), IP55 (EN 60529) II (EN 60730) III (EN 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III II Type 1 AB (EN 60730) Type 1 C (EN 60730) A (EN 60730)

Overview of types

340

Type

Voltage

Power consumption

ASM124F120

230 V~

2.9 W, 5.6 VA

ASM124F122

24 V~

2.3 W, 2.4 VA

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators

A A A

Power consumption when idle: ASM124F120: 0.5 W, 5.1 VA ASM124F122: 0.03 W, 0.4 VA

Accessories Type

Description

0361977001

Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124

0370059000

Clamping lever for shaft, Ø 8...18 mm

0370990001

Auxiliary change-over contacts, single

0370990002

Auxiliary change-over contacts, double

0370992001

Potentiometer, 2000 Ω, 1 W

0370992002

Potentiometer, 130 Ω, 1 W

0372200001

Fitting bracket

0372201001

Spindle extension with coupling

0372202001

Lever, fitting strip

0372203001

Driver axle for auxiliary contacts

0372204001

Spindle for clamping lever 0370059000

0372455001

Assembly part; DEF DN25...65 for ASM 124/134

0372455002

Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134

A

V

Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V

Right of amendment reserved © 2024 Fr. Sauter AG

341


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASM 134: Damper actuator Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with a switching (3-point) output • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Stepping motor with electronic activation and cut-out

ASM134F130

• Direction of rotation changed by transposing the connections • Suitable for all fitting positions • Maintenance-free • Version with halogen-free cable on demand

V

Technical data Power supply

Power supply Power consumption

230 V~, ±15%, 50 Hz 3.7 W, 4.7 VA

Rotational torque and holding torque Running time for 90° Angle of rotation Admissible damper shaft Admissible damper shaft (hardness) Operating noise Response time

30 Nm 120/240 s Max. 95° Ø 12...20 mm, □ 10...16 mm Max. 300 HV < 30 dB (A) 200 ms

Ambient temperature Ambient humidity

−20...55 °C < 95% rh, no condensation

Weight Housing

1.8 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 3 × 0.75 mm²

Parameters

Ambient conditions

Construction

Housing material Power cable Standards, directives

Type of protection

Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination Mode of operation Software

IP40 (EN 60529) IP54 (EN 60529) IP55 (EN 60529) II (IEC 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1, EN 60730-2-14 III III Type 2 B (EN 60730) A (EN 60730)

Overview of types

342

Type

Rated power during continuous operation

Power consumption when idle

ASM134F130

3.7 W, 4.7 VA

1.1 W, 2.7 VA

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type

Description

0361977001

Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124

0370059000

Clamping lever for shaft, Ø 8...18 mm

0370990001

Auxiliary change-over contacts, single

0370990002

Auxiliary change-over contacts, double

0370992001

Potentiometer, 2000 Ω, 1 W

0370992002

Potentiometer, 130 Ω, 1 W

0372200001

Fitting bracket

0372201001

Spindle extension with coupling

0372202001

Lever, fitting strip

0372203001

Driver axle for auxiliary contacts

0372204001

Spindle for clamping lever 0370059000

0372455001

Assembly part; DEF DN25...65 for ASM 124/134

0372455002

Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134

0372455003

Assembly part; DEF DN150...200 for ASM 134

A

V

Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V

Right of amendment reserved © 2024 Fr. Sauter AG

343


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASM 124S, 134S: Damper actuator with SAUTER Universal Technology (SUT) Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) or continuous output (0…10 V) • Self-centring spindle adapter • Gear unit can be disengaged to position the damper and for manual adjustment • Stepping motor with electronic activation and cut-out

ASM1*4SF132

• Maintenance-free • Intelligent adaptation of rotation angle, incl. feedback adjustment • Direction of rotation changed by transposing the connections

V

• Suitable for all fitting positions • Version with halogen-free cable on demand

Technical data Power supply

Power supply 24 VAC Power supply 24 VDC1)

±20%, 50...60 Hz ±20%

Angle of rotation Admissible damper shaft (hardness) Operating noise Response time Control signal Positional feedback signal Starting point U0 Control span ΔU Switching range Xsh

Max. 95° Max. 300 HV < 30 dB(A) 200 ms 0...10 V, Ri > 100 kΩ 0...10 V, load > 10 kΩ 0 or 10 V 10 V 200 mV

Ambient temperature Ambient humidity

−20...55 °C < 95% rh, no condensation

Weight Housing

1.6 kg Lower section black, upper section yellow Flame-retardant plastic 1.2 m long, 2 × 0.75 mm²

Parameters

Positioner

Ambient conditions

Construction

Housing material Power cable Standards, directives

Type of protection Protection class EMC Directive 2014/30/EU Mode of operation Software

1)

344

IP40 (EN 60529), IP43 (EN 60529), IP54 (EN 60529) III (IEC 60730) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 Type 1 AB (EN 60730) Type 1 C (EN 60730) A (EN 60730)

24 V= only for control signals 0...10 V

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Overview of types Type

Rotational torque

Holding torque

Running time for 90°

Power consumption Admissible damper shaft

ASM124SF132

15 Nm

15 Nm

60, 120 s

2.4 W, 4.4 VA

Ø 12...20 mm, □ 10...16 mm

ASM134SF132

30 Nm

30 Nm

120, 240 s

2.4 W, 4.3 VA

Ø 12...20 mm, □ 10...16 mm

A A A

Power consumption when idle: ASM124SF132: 0.25 W, 0.46 VA ASM134SF132: 0.26 W, 0.48 VA

Accessories Type

Description

0313529001

Split-range unit for setting sequences

0361977001

Assembly materials for M3R, M4R, MH32F, MH42F with ASM 124

0370059000

Clamping lever for shaft, Ø 8...18 mm

0370990001

Auxiliary change-over contacts, single

0370990002

Auxiliary change-over contacts, double

0370992001

Potentiometer, 2000 Ω, 1 W

0370992002

Potentiometer, 130 Ω, 1 W

0372200001

Fitting bracket

0372201001

Spindle extension with coupling

0372202001

Lever, fitting strip

0372203001

Driver axle for auxiliary contacts

0372204001

Spindle for clamping lever 0370059000

0372455001

Assembly part; DEF DN25...65 for ASM 124/134

0372455002

Assembly part; DEF DN80...100 for ASM 124; DN125 for ASM 134

0372455003

Assembly part; DEF DN150...200 for ASM 134

A

V

Auxiliary change-over contacts: Infinitely variable 0...90°, admissible load 5(2) A, 24...230 V

Right of amendment reserved © 2024 Fr. Sauter AG

345


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASF 112, 113: Damper actuator with spring return Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) output • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Maintenance-free

ASF112F122

• Suitable for all fitting positions

Technical data Power supply

V

Power supply 230 VAC Power supply 24 VAC Power supply 24...48 V=

±10%, 50...60 Hz ±20%, 50...60 Hz ±20%

Rotational torque and holding torque Angle of rotation Admissible damper shaft Running time for 90° motor Running time for 90° spring

7 Nm Max. 95° Ø 6.4...20.5 mm, □ 6.4...13 mm 90 s 15 s

Ambient temperature Ambient humidity

–32...55 °C 5...95% rh, no condensation

Housing Power cable

Cast aluminium 0.9 m, 0.75 mm²

Type of protection

IP54 (EN 60529), suspended IP42 (EN 60529), not suspended III (EN 60730) II (EN 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 II III

Parameters

Ambient conditions

Construction

Standards and directives

Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Degree of contamination Over-voltage categories

Overview of types Type

Control function

Voltage

Power consumption

Weight

ASF112F120

2-point

230 V~

4.5 W, 7.0 VA

1.2 kg

ASF112F122

2-point

24 V~/24...48 V=

3.5 W, 5.0 VA

1.2 kg

ASF112F220

2-point

230 V~

4.5 W, 7.0 VA

1.3 kg

ASF112F222

2-point

24 V~/24...48 V=

3.5 W, 5.0 VA

1.3 kg

ASF113F122

3-point

24 V~/24...48 V=

3.5 W, 5.0 VA

1.2 kg

A

346

ASF112F220, ASF112F222: Double auxiliary contacts 6(2) A; 24...250 V~ with cable 0.9 m; 6 × 0.75 mm²

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type

Description

0372245001

Lever adaptor for converting rotation into stroke

0372245002

Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

V

Right of amendment reserved © 2024 Fr. Sauter AG

347


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASF 113S: Damper actuator with spring return and positioner Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with a continuous output (0...10 V) • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Maintenance-free

ASF113SF122

• Suitable for all fitting positions

Technical data

V

Power supply

Power supply 24 VAC Power supply 24...48 V= Power consumption

±20%, 50...60 Hz ±20% 3.5 W, 5.0 VA

Running time for 90° motor Running time for 90° spring Rotational torque Holding torque Angle of rotation Admissible damper shaft Admissible damper surface area1) Control signal Positional feedback signal Admissible load Switching range Xsh Starting point U0 Control span ΔU

90 s 15 s 7 Nm 7 Nm Max. 95° Ø 6.4...20.5 mm, □ 6.4...13 mm 1.5 m2 0...10 V, Ri = 100 kΩ 0...10 V (0...100%) > 10 kΩ 0.2 V 0V 10 V

Ambient temperature Ambient humidity

–32...55 °C < 95% rh

Weight Housing Power cable

1.3 kg Cast aluminium 0.9 m, 4 × 0.75 mm²

Type of protection

IP54 (EN60529), suspended IP 42 (EN 60529), not suspended III (IEC 60730) II III EN 60730-1, EN 60730-2-14 EN 61000-6-2, EN 61000-6-3

Parameters

Positioner

Setting range

Ambient conditions

Construction

Standards and directives

Protection class Degree of contamination Over-voltage categories Low-Voltage Directive 2014/35/EU EMC Directive 2014/30/EU

Overview of types Type

Features

ASF113SF122

Damper actuator with spring return and positioner

1)

348

Recommended value for smooth-running air dampers

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type

Description

0372245001

Lever adaptor for converting rotation into stroke

0372245002

Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth

0510240001

Assembly kit for VK**/BK** ball valves as spare part and as accessory for rotary actuators ASF 112, 113 from index B

V

Right of amendment reserved © 2024 Fr. Sauter AG

349


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASF 122, 123: Damper actuator with spring return Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with switching (2- and 3-point) output • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Wear-free brushless motor

ASF122F122

• Maintenance-free • Change direction of rotation by simply turning the actuator • Suitable for all fitting positions

V

Technical data Power supply

Power supply 24 VAC Power supply 230 VAC Power supply 24...48 V=

±20%, 50...60 Hz ±10%, 50...60 Hz ±20%

Running time for 90° motor Running time for 90° spring Rotational torque and holding torque Angle of rotation Admissible damper shaft

90 s 15 s 18 Nm Max. 90° Ø 8...25 mm, □ 6...18 mm

Ambient temperature Ambient humidity

−32...55 °C 5...95% rh

Housing Power cable

Cast aluminium 0.9 m, 0.75 mm²

Type of protection

IP54 (EN60529), suspended IP42 (EN 60529), not suspended III (EN 60730) II (EN 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 III II

Parameters

Ambient conditions

Construction

Standards and directives

Protection class 24 V Protection class 230 V EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination

Overview of types Type

Control function

Voltage

Power consumption

Weight

ASF122F120

2-point

230 V~

6 W, 8 VA

2 kg

ASF122F122

2-point

24 V~/24...48 V=

5 W, 7 VA

2 kg

ASF122F220

2-point

230 V~

6 W, 8 VA

2.1 kg

ASF122F222

2-point

24 V~/24...48 V=

5 W, 7 VA

2.1 kg

ASF123F122

3-point

24 V~/24...48 V=

5 W, 7 VA

2 kg

A

350

ASF122F220, ASF122F222: With double auxiliary contacts 6(2) A; 24...250 V~; with cable 0.9 m; 6 × 0.75 mm²

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type

Description

0370997001

Lever adaptor for converting rotation into stroke

0370998001

Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth

0378113001

Assembly parts; DEF DN 25…100 for ASF122/123

V

Right of amendment reserved © 2024 Fr. Sauter AG

351


Valves, control valves, dampers, actuators | Damper and rotary actuators

ASF 123S: Damper actuator with spring return and positioner Features • For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers • For controllers with a continuous output (0...10 V) • Self-centring spindle adapter • Manual adjustment using hexagon socket, including locking of gear unit • Wear-free brushless motor

ASF123SF122

• Maintenance-free • Change direction of rotation by simply turning the actuator • Suitable for all fitting positions

V

Technical data Power supply

Power supply 24...48 V= Power consumption

±20% 5.4 W, 7.5 VA

Running time for 90° motor Running time for 90° spring Rotational torque and holding torque Angle of rotation Admissible damper shaft Control signal Positional feedback signal Admissible load Switching range Xsh Starting point U0 Control span ΔU

90 s 15 s 18 Nm Max. 95° Ø 8...25 mm, □ 6...18 mm 0...10 V, Ri = 100 kΩ 0...10 V (0...100%) > 10 kΩ 0.2 V 0V 10 V

Ambient temperature Ambient humidity

–32...55 °C < 95% rh

Weight Housing Power cable

2 kg Cast aluminium 0.9 m, 4 × 0.75 mm²

Type of protection1)

IP54 (EN60529), suspended IP42 (EN 60529), not suspended III (IEC 60730) EN 61000-6-2, EN 61000-6-3 EN 60730-1, EN 60730-2-14 III II

Parameters

Positioner

Setting range

Ambient conditions

Construction

Standards and directives

Protection class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU Over-voltage categories Degree of contamination

Overview of types Type

Features

ASF123SF122

Damper actuator with spring return and positioner

1)

352

Depending on fitting position, ensure IP54

Right of amendment reserved © 2024 Fr. Sauter AG


Valves, control valves, dampers, actuators | Damper and rotary actuators Accessories Type

Description

0370997001

Lever adaptor for converting rotation into stroke

0370998001

Lever adaptor for converting rotation into stroke, with carrier plate for mounting on wall or plinth

0378113001

Assembly parts; DEF DN 25…100 for ASF122/123

V

Right of amendment reserved © 2024 Fr. Sauter AG

353


HVAC automation

6 The new standard in building automation. SAUTER modulo 6 offers unprecedented performance in terms of data points, memory capacity and processing speed, all with minimal space requirements. The app with an augmented reality function shows real-time values and signal labels. Values can be adjusted via the touch screen. As an alternative to smartphone operation, the range also includes a local operating unit (LOI) with a high-resolution graphical colour display. The LOI is compatible with all available I/O modules and offers priority operation decoupled from the station. modulo 6 connects to the cloud and IoT just as securely as with the existing HVAC systems. BACnet/SC adds another security level to the product range. 354

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation HVAC automation EY6AS80: modular BACnet automation station and web server, modu680-AS

357

EY6AS60: modular BACnet automation station, modu660-AS

361

EY6LC01: Module for separate I/O module supply, modu601-LC

366

EY6LC02: Coupling kit for I/O modules in cabinet, modu602-LC

368

EY6LC12: IP coupler for I/O modules with web server, modu612‑LC

370

EY6IO30: 16 × DI/CI inputs I/O module, modu630-IO

373

EY6IO31: 8 × UI (DI/CI/AI), 8 × DI/CI I/O module, modu631-IO

375

EY6IO50: 6 x relay (2A) outputs I/O module, modu650-IO

377

EY6IO70: 8 × DI/CI/DO (OC) and 8 × DI/CI I/O module, modu670‑IO

379

EY6IO71: 8 × AO and 8 × DI/CI I/O module, modu671-IO

381

EY6IO72: 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module, modu672-IO

383

EY6LO00: Operating and indicating unit for I/O modules, modu600-LO

386

EY6CM20: Modbus/RTU (RS‑485) communication module, modu620‑CM

389

EY6CM30: M-Bus communication module, modu630‑CM

391

EY6RT30: BACnet router and SC hub, modu630-RT

394

Right of amendment reserved © 2024 Fr. Sauter AG

¨

355


SAUTER modulo 6 automation stations SAUTER modulo 6 automation stations regulate, control, monitor and optimise the energy efficiency in HVAC installations. The installation network is based on BACnet/IP – the communication protocol for networked building intelligence.

Overview of automation stations

Type designation Product name Parameters Power supply Connection of I/O and COM extension modules Interfaces, communication Interfaces Ethernet/LAN Ethernet/WAN SLC/RS-485 interfaces Modbus/RS-485 interfaces Protocols BACnet profile AMEV profile Objects Data points (BACnet objects) Historical data (Trend Log) Control (Loop) Sequences, scenes (Command) Calendars (Calendar) Time programmes (Schedule) Alarms (Notification Class) Further information

356

EY6AS80 modu680-AS

EY6AS60 modu660-AS

24 VDC ecoLink I/O modules, COM modules, ASV actuators, ecoUnit room operating units, EnOcean wireless interface 24 with modu601-LC (5 of which are COM modules) 2 × RS-485, WAN, LAN, REST API, Bluetooth, USB, microSD 3 × RJ45 (switched) 1 × RJ45

RS-485, LAN, REST API, Bluetooth, USB, microSD 2 × RJ45 (switched) −

1 1 BACnet/IP, SLC, Modbus RTU, HTTP(S), NTP, SMTP, SMPP B-BC AS-B 1600 I/O, 3200 total 1600 96

− BACnet/IP, SLC, HTTP(S), NTP, SMTP, SMPP

800 I/O, 1600 total 800 48 16 32 64 32

Page 357

Page 361

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6AS80: Modular BACnet automation station and web server, modu680-AS Features • Part of the SAUTER modulo 6 system family • Modular automation station, expandable with I/O modules and communication modules • Regulation, control, monitoring and optimisation of operational systems in HVAC • Locally expandable with up to 24 modules via the SAUTER Extension Bus • Can be locally equipped with ecoLink I/O modules and ASV actuators via SLC interface • RS-485 interface for field bus integration (Modbus/RTU / ASCII) • Four RJ45 connections for two separate IP networks (OT/IT; Operational/Information Technology). Three

EY6AS80F021

connections switched for daisy chain • BACnet/IP communication (EN ISO 16484-5) • BACnet profile B-BC • AMEV profile AS-B • REST API interface • MQTT interface (MQTT Broker/Client)

¨

• Integrated web server for local commissioning, visualisation and operation • User administration for identification, authentication and access control • Encryption of communication with TLS • Bluetooth interface for mobile commissioning and maintenance • Programming/parameterisation via PC using CASE Suite (based on IEC 61131-3) • Control libraries • Time and calendar function • Predictive control based on meteorological forecast data • Data recording on removable media (microSD card) • User administration and user identification (web server) • Alive signal output pulsed

Technical data Power supply

Power supply Power consumption1) Dissipated power Peak inrush current2)

24 VDC ± 10% ≤ 2 W without load ≤ 24 W at maximum load ≤ 2 W without load ≤ 4 W at maximum load ≤ 20 A, ≤ 1 ms on the 24 V side

Parameters

Connection

Battery (buffer: RTC) Earth connector

5-pin spring-type terminal, pluggable, 0.5...1.5 mm2 (rigid) 0.5...2.5 mm2, min. 8 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal

Ambient conditions

Operating temperature Storage and transport temperature

1) 2)

0…45 °C −20…70 °C

Maximum load with 12 I/O modules Measured value with EY-PS021F021 power supply unit

Right of amendment reserved © 2024 Fr. Sauter AG

357


HVAC automation | HVAC automation Ambient humidity

10…90% rh, no condensation

BACnet data point objects

Up to 1600 I/O objects, 3200 total 600 (Peer-to-Peer) 96 (Loop) 4800 128 (Structured View) 16 (Command) 64 (Schedule) 32 (Calendar) 32 (Notification Class) intrinsically or extrinsically with Event Enrolment 1600 (Trend Log) up to 4 million entries 32 32 moduWeb Unity, MQTT Commissioning Tool moduWeb Unity Number of topics/alias topics for BACnet objects max. 3200 Number of topics max. ??? (depending on CPU/memory resources) Number of client connections max. ??? SMTP, SMPP NTP client, BACnet master or client, local or UTC With modu615-BM

Function

BACnet

Dynamic objects

BACnet client links Control Active COV subscription Structured view Sequences, scenes Time programmes Calendar Notification Historical data

Services

BBMD in BDT FD in FDT Embedded web server Web API (REST) MQTT Client

¨

MQTT Broker

Notification (client) Time synchronisation Data integrity (client) Architecture

Processor RAM (memory) Flash Application data Processes (BACnet programs)

Cycle time

ARM Cortex A8, 32-bit, 1 GHz 512 MB (DDR3) 512 MB Via CASE Engine Supports separated processes with different cycle times and independent booting Adjustable for each process, min. 50 ms (50, 100, 500, 1000)

Interfaces, communication

Ethernet network #1 (WAN)

Communication protocols

Ethernet network #2 (LAN)

Ethernet network 10/100 BASE-T(X) Communication protocols

Connection, I/O and COM modules

Ethernet network 10/100 BASE-T(X) switched Use3)

RS-485 A connection

Communication protocol Bus physics Bus speed Connection

3)

358

HTTP(S), NTP, SMTP, SMPP, DHCP, MQTT/TCP(TLS), MQTT/WS(S) 1 × RJ45 connector 10/100 Mbit/s BACnet/IP (DIX), HTTP(S), NTP, SMTP, SMPP, DHCP, MQTT/TCP(TLS), MQTT/WS(S) 3 × RJ45 connector 10/100 Mbit/s 1 × integrated iSEB interface for max. 12 modules, expandable with modu601-LC for max. 24 modules in total Modbus/RTU / ASCII Modbus master according to V1.02 1 unit load (UL), electrically isolated 600...115,200 bit/s Parity bit, stop bit, Rx/Tx bus timing Spring-type terminal, pluggable 0.2...1.5 mm2 stiff/flexible

Performance-dependent

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation Line4) Use Participant Functions

RS-485 B connection

120 Ω bus termination and pullup/pull-down Communication protocol Use Participant Power supply

Connection Line Line length

Bluetooth

USB SD memory expansion

120 Ω bus termination and pullup/pull-down Version Range Frequency band Radiation Version Current limitation Type

3-/4-wire (D+/D−/COM reference), twisted, shielded, up to 1000 m Integration of Modbus slaves in an RS-485 segment (line) Up to 31 RS-485 unit loads (UL) Up to 600 Modbus channels for BACnet I/O/V objects for up to 247 Modbus devices; FC01-06, 15, 16, 22; unicast and broadcast; access optimisation Switchable via software (CASE Engine) SLC master ecoLink, ASV, ecoUnit, FCCP200 Max. 8 ecoLink modules and 4 ecoUnit modules, max. 12 ASV units 20…26 V=, max. 1.5 W, protected against short circuit, can be switched on/off (CASE Sun) Spring-type terminal, pluggable 0.2...1.5 mm2 stiff/flexible 4-wire, twisted, shielded Max. 100 m (30 m) with ecoUnit or ASV, up to 500 m, bus termination necessary (120 Ω) Switchable via software (CASE Sun)

¨

BLE 4.0 < 10 m 2.402…2.480 GHz 6 mW 2.0, type A 400 to max. 500 mA microSD, suitable for industrial use

Construction

Fitting

Dimensions W × H × D Weight

On metallic DIN rail 35 × 7.5/15 as per EN 60715. Rail housing as per DIN 43880 92.6 (5 HP) × 100.9 × 58.3 mm 260 g

Standards, directives

Type of protection

Protection class Environment class Software class5) Temperature controller class

CE/UKCA conformity6)

BACnet profile AMEV profile EMC-D 2014/30/EU (CE)

EMC-2016 (UKCA) LV-D 2014/35/EU (CE)

4) 5) 6)

Connections: IP00 Front in DIN cut-out: IP30 (EN 60730-1) I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) I to VIII = up to 5% as per 2009/125/EC, 2010/30/EU & 811/2013 (EU) B-BC (ISO 16484-5) AS-B EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 See EMC Directive EN 60730-1, EN 60730-2-9, EN 60950-1

Performance-dependent The product is not suitable for safety functions Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

359


HVAC automation | HVAC automation EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

See LVD EN 300328 (V2.1.1) EN 300328 (V2.1.1) EN IEC 63000 EN IEC 63000

Overview of types Type

Features

EY6AS80F021

Modular BACnet automation station and web server

Accessories Plug-in I/O modules

¨

Type

Description

EY6IO30F001

modu630-IO 16 × DI/CI inputs I/O module

EY6IO70F001

modu670-IO 8 × DI/CI/DO(OC), 8 × DI/CI I/O module

EY6IO31F001

modu631-IO 8 × UI(DI/CI/AI), 8 × DI/CI I/O module

EY6IO71F001

modu671-IO 8 × AO, 8 × DI/CI I/O module

EY6IO50F001

modu650-IO 6 × relay (2 A) outputs I/O module

EY6IO72F001

modu672-IO 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module

Connection modules Type

Description

EY6LC01F001

Module for separate I/O module supply

EY6LC02F001

Coupling kit for I/O modules in cabinet (P100017761 and P100017762)

EY6LC12F011

IP coupler for I/O modules with web server, modu612‑LC

Spare parts Type

Description

0929360602

AS bus cover with resistor, 5 pcs.

Function expansions Type

Description

Y6WS80F007

Activation code for reporting for modu680-AS

Y6WS80F008

Activation code for the REST API on modu680-AS

Y6WS80F009

Data point extension activation code for moduWeb Unity on modu680-AS

Y6WS80F031

Activation code for network option for modu680-AS

Y6FX02F001

Activation code for MQTT client

Y6FX02F002

Activation code for MQTT client and broker

Y6FX03F001

Activation code for RADIUS Supplicant

Y6FX04F001

Activation code for BACnet/SC DataLink

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

360

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6AS60: Modular BACnet automation station, modu660-AS Features • Part of the SAUTER modulo 6 system family • Modular automation station, expandable with I/O modules and communication modules • Regulation, control, monitoring and optimisation of operational systems in HVAC • Locally expandable with up to 24 modules via the SAUTER Extension Bus • Can be locally equipped with ecoLink I/O modules and ASV actuators via SLC interface • Two RJ45 connections switched for daisy chain • BACnet/IP communication (EN ISO 16484-5)

EY6AS60F011

• BACnet profile B-BC • AMEV profile AS-B • REST API interface • MQTT interface (MQTT Broker/Client) • Integrated web server for local commissioning, expandable with visualisation and operation • User administration for identification, authentication and access control

¨

• Encryption of communication with TLS • Bluetooth interface for mobile commissioning and maintenance • Programming/parameterisation via PC using CASE Suite (based on IEC 61131-3) • Control libraries • Time and calendar function • Predictive control based on meteorological forecast data • Data recording on removable media (microSD card) • User administration and user identification (web server) • Alive signal output pulsed

Technical data Power supply

Power supply Power consumption1) Dissipated power Peak inrush current2)

24 VDC ± 10% ≤ 2 W without load ≤ 24 W at maximum load ≤ 2 W without load ≤ 4 W at maximum load ≤ 20 A, ≤ 1 ms on the 24 V side

Parameters

Connection

Battery (buffer: RTC) Earth connector

5-pin spring-type terminal, pluggable, 0.5...1.5 mm² 0.5...2.5 mm², min. 8 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal

Ambient conditions

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

BACnet data point objects

Up to 800 I/O objects, 1600 total

Function

1) 2)

Maximum load with 12 I/O modules Measured value with EY-PS021F021 power supply unit

Right of amendment reserved © 2024 Fr. Sauter AG

361


HVAC automation | HVAC automation

Dynamic objects

Services

BACnet client links Control Active COV subscription Structured view Sequences, scenes Time programmes Calendar Notification

300 (Peer-to-Peer) 48 (Loop) 2400 128 (Structured View) 16 (Command) 64 (Schedule) 32 (Calendar) 32 (Notification Class) intrinsically or extrinsically with Event Enrolment 800 (Trend Log) up to 2 million entries 32 32 moduWeb Unity, MQTT Commissioning Tool moduWeb Unity Number of topics / alias topics for max. number of BACnet objects (600) Number of topics, depending on CPU/memory resources (> 1000) SMTP, SMPP NTP client, BACnet master or client, local or UTC With modu615-BM

Historical data BBMD in BDT FD in FDT Embedded web server Web API (REST) MQTT Client MQTT Broker Notification (client) Time synchronisation

¨

Data integrity (client) Architecture

Processor RAM (memory) Flash Application data Processes (BACnet programs)

ARM Cortex A8, 32-bit,1 GHz 512 MB (DDR3) 512 MB Via CASE Engine Supports separated processes with different cycle times and independent booting Adjustable via process, min. 50 ms (50, 100, 500, 1000)

Cycle time

Interfaces, communication

Ethernet network (LAN)

Communication protocols

Connection, I/O and COM modules

Ethernet network 10/100 BASE-T(X) switched Use3)

RS-485 B connection

Communication protocol Use Participant Power supply

Connection Line Line length

Bluetooth

3)

362

120 Ω bus termination and pullup/pull-down Version Range Frequency band

BACnet/IP (DIX), HTTP(S), NTP, SMTP, SMPP, DHCP, MQTT/TCP(TLS), MQTT/WS(S) 2 × RJ45 connector 10/100 Mbit/s 1 × integrated iSEB interface for max. 12 modules, expandable with modu601-LC for max. 24 modules in total SLC master ecoLink, ASV, ecoUnit, FCCP 200 Max. 8 ecoLink modules and 4 ecoUnit modules, max. 12 ASV units 20…26 VDC, max. 1.5 W, protected against short circuit, can be switched on/off (CASE Sun) Spring-type terminal, pluggable 0.2...1.5 mm² rigid/flexible 4-wire, twisted, shielded Max. 100 m (30 m) with ecoUnit or ASV, up to 500 m, bus termination necessary (120 Ω) Switchable via software (CASE Sun) BLE 4.0 < 10 m 2.402…2.480 GHz

Performance-dependent

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

USB SD memory expansion

Radiation Version Current limitation Type

6 mW 2.0, type A 400 to max. 500 mA microSD, suitable for industrial use

Fitting

On metallic DIN rail 35 × 7.5/15 as per EN 60715 Rail housing as per DIN 43880 92.6 (5 HP) x 100.9 x 58.3 mm 240 g

Construction

Dimensions W × H × D Weight Standards, directives

Type of protection

Protection class Environment class Software class4) Temperature controller class

CE/UKCA conformity5)

BACnet profile AMEV profile EMC-D 2014/30/EU (CE)

EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

Connections: IP00 Front in DIN cut-out: IP30 (EN 60730-1) I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) I to VIII = up to 5% as per 2009/125/EC, 2010/30/EU & 811/2013 (EU) B-BC (ISO 16484-5) AS-B EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 See EMC Directive EN 60730-1, EN 60730-2-9, EN 60950-1 EN 60730-1, EN 60730-2-9, EN 60950-1 EN 300328 (V2.1.1) EN 300328 (V2.1.1) EN IEC 63000

¨

EN IEC 63000

Overview of types Type

Description

EY6AS60F011

Modular BACnet automation station and web server

Accessories Plug-in I/O modules Type

Description

EY6IO30F001

modu630-IO 16 × DI/CI inputs I/O module

EY6IO31F001

modu631-IO 8 × UI(DI/CI/AI), 8 × DI/CI I/O module

EY6IO50F001

modu650-IO 6 × relay (2 A) outputs I/O module

EY6IO70F001

modu670-IO 8 × DI/CI/DO(OC), 8 × DI/CI I/O module

EY6IO71F001

modu671-IO 8 × AO, 8 × DI/CI I/O module

EY6IO72F001

modu672-IO 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module

4) 5)

The product is not suitable for safety functions Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

363


HVAC automation | HVAC automation Connection modules Type

Description

EY6LC01F001

Module for separate I/O module supply

EY6LC02F001

Coupling kit for I/O modules in cabinet (P100017761 and P100017762)

EY6LC12F011

IP coupler for I/O modules with web server, modu612‑LC

Spare parts Type

Description

0929360602

AS bus cover with resistor, 5 pcs.

Function expansions

¨

Type

Description

Y6WS60F007

Activation code for reporting for modu660-AS (requires Y6WS60F021)

Y6WS60F008

Activation code for the REST API on modu660-AS (requires Y6WS60F021)

Y6WS60F009

Data point extension activation code for moduWeb Unity on modu660 AS (requires Y6WS60F021)

Y6WS60F021

Activation code for visualisation on modu660 AS

Y6FX02F001

Activation code for MQTT client

Y6FX02F002

Activation code for MQTT client and broker

Y6FX03F001

Activation code for RADIUS Supplicant

Y6FX04F001

Activation code for BACnet/SC DataLink

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

364

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

Right of amendment reserved © 2024 Fr. Sauter AG


SAUTER modulo 6 connection modules The SAUTER modulo 6 connection modules offer more flexibility in the cabinet installation (modu602‑LC) and more freedom for a decentralised topology (modu612‑LC). The modu601‑LC ensures the functionality of the I/O modules if the operation of the automation station is interrupted.

Overview of connection modules

Type designation Product name Power supply IP network interfaces I/O and COM extension modules Cloud Connector Further information

EY6LC01F001 modu601-LC 24 VDC − −

EY6LC02F001 modu602-LC − − −

− Page 366

− Page 368

Right of amendment reserved © 2024 Fr. Sauter AG

EY6LC12F011 modu612-LC 24 VDC 2 (switch) Max. 24 (of which 5 are COM modules) MQTT Page 370

365


HVAC automation | HVAC automation

EY6LC01: Module for separated I/O module supply, modu601-LC Features • Part of the SAUTER modulo 6 system family • Enables separate supply between automation station and I/O modules • Power supply of I/O modules and connected LOI units (Local Override and Indication Device) • Allows extension to up to 24 I/O modules • Enables simple wiring tests of the I/O modules without the station, together with modu600-LO on the I/O

modules EY6LC01

Technical data Power supply

¨

Power supply Dissipated power Power consumption Peak inrush current1)

24 V= ± 10% < 0.5 W < 19 W at max. load ≤ 2 A, ≤ 10 ms

Connection

3-pin spring-type terminal, pluggable, 0.5...1.5 mm2 (rigid) 0.5...2.5 mm2, min. 8 mm wire stripped

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C −25...70 °C 10...90% rh, no condensation

Connection, I/O bus

6-pin spring contacts left and 7-pin right Spring contact against DIN rail and PE feed connection

Parameters

Ambient conditions

Interfaces, communication

Earth connector

Construction

Fitting

On metal DIN rail 35 × 7.5/15 as per EN 60715 DIN rail housing as per DIN 43880 56 × 97 × 59 mm 98 g

Dimensions W × H × D Weight Standards, directives

Protection type (as per EN 60730)

CE conformity according to

Protection class Environment class EMC Directive 2014/30/EU

Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Overview of types Type

Description

EY6LC01F001

Module for separate I/O module supply

1)

366

Measured value with EY‑PS021F021 power supply unit

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

¨

Right of amendment reserved © 2024 Fr. Sauter AG

367


HVAC automation | HVAC automation

EY6LC02: Coupling kit for I/O modules in cabinet, modu602LC Features • Part of the SAUTER modulo 6 system family • Arrangement of I/O modules in up to three rows for space-optimised cabinet installation • Minimum space requirement of the transmitter and receiver modules (1.5 HP) • Up to two modu602-LC per station

Technical data EY6LC02

Power supply

Power supply Dissipated power

From AS or LC via I/O bus < 0.3 W incl. 3 m cable

Max. number per station Max. cable length per station

2 3m

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C −25...70 °C 10...90% rh, no condensation

Connection Cable type

RJ45 connector RJ45 type S/FTP, not crossed, at least AWG 24 P100017761: 7-pin spring contacts, only left P100017762: 7-pin spring contacts, only right Spring contact against DIN rail

Parameters

¨

Ambient conditions

Interfaces, communication

Connection, I/O bus

Earth connector Construction

Fitting

On metal DIN rail 35 × 7.5/15 as per EN 60715 DIN rail housing as per DIN 43880 27 × 97 × 59 mm 95 g

Dimensions W × H × D Weight1) Standards, directives

Protection type (as per EN 60730) Protection class Environment class EMC Directive 2014/30/EU

CE conformity according to

Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Overview of types Type

Description

EY6LC02F001

Coupling kit for I/O modules in cabinet (P100017761 and P100017762)

Manuals Document number D100397589 D100408512 1)

368

Language de de

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I

Total weight

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation Document number D100402674 D100410201 D100402676 D100410203

Language en en fr fr

Title SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

¨

Right of amendment reserved © 2024 Fr. Sauter AG

369


HVAC automation | HVAC automation

EY6LC12: IP coupler for I/O modules, with web server, modu612‑LC Features • Part of the SAUTER modulo 6 system family • Enables decentralised installation and connection of the modulo 6 COM and IO modules with the

automation station via IP network • Locally expandable with up to 10 modules • Two RJ45 connections switched for daisy chain • Integrated web server for local commissioning

EY6LC12F011

• Bluetooth interface for mobile commissioning and maintenance • User administration and user identification (web server)

Technical data Power supply

Power supply Power consumption1)

¨

24 VDC ± 10% ≤ 2 W without load ≤ 24 W at maximum load ≤ 2 W without load ≤ 4 W at maximum load ≤ 20 A, ≤ 1 ms on the 24 V side

Dissipated power Peak inrush current2) Parameters

Connection

3-pin spring-type terminal, pluggable, 0.5...1.5 mm² (rigid) 0.5...2.5 mm², min. 8 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal

Battery (buffer: RTC) Earth connector

Ambient conditions

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

Processor Embedded web server Application data

ARM Cortex A8, 32-bit, 600 MHz moduWeb Unity From the automation station

Ethernet network 10/100 BASE-T(X) switched

2 × RJ45 connector, switched 10/100 Mbit/s

Dimensions W × H × D Fitting

92.6 (5 HP) × 97 × 58.3 mm On metal DIN rail 35 × 7.5/15 as per EN 60715. Rail housing as per DIN 43880

Type of protection

Connections: IP00 Front in DIN cut-out: IP30 (EN 60730-1) I (IEC 60730-1) 3K3 (IEC 60721)

Architecture

Interfaces, communication

Ethernet network

Construction

Standards, directives

Protection class Environment class 1) 2)

370

Maximum load with 12 I/O modules Measured value with EY-PS021F021 power supply unit

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation Software class Energy class

CE/UKCA conformity3)

EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

A (EN 60730-1, Appendix H) I to VIII = up to 5% as per EU 811/2013, 2010/30/EU, 2009/125/EC EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 See EMC Directive EN 60730-1, EN 60730-2-9, EN 62479 EN 60730-1, EN 60730-2-9, EN 62479 EN 300328 (V2.1.1) EN 300328 (V2.1.1) EN IEC 63000 EN IEC 63000

Overview of types Type

Description

EY6LC12F011

IP coupler for I/O modules, with web server

¨

Accessories Plug-in I/O modules Type

Description

EY6IO30F001

modu630-IO 16 × DI/CI inputs I/O module

EY6IO31F001

modu631-IO 8 × UI(DI/CI/AI), 8 × DI/CI I/O module

EY6IO50F001

modu650-IO 6 × relay (2 A) outputs I/O module

EY6IO70F001

modu670-IO 8 × DI/CI/DO(OC), 8 × DI/CI I/O module

EY6IO71F001

modu671-IO 8 × AO, 8 × DI/CI I/O module

EY6IO72F001

modu672-IO 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module

Plug-in communication modules (COM) Type

Description

EY6CM20F011

Modbus/RTU (RS-485) communication module

EY6CM30F031

modu630-CM M-Bus communication module

Connection modules Type

Description

EY6LC01F001

Module for separate I/O module supply

EY6LC02F001

Coupling kit for I/O modules in cabinet (P100017761 and P100017762)

3)

Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

371


SAUTER modulo 6 I/O modules SAUTER I/O modules are compatible with the modulo 6 series and are used to capture digital and analogue signals in HVAC installations. They control devices such as contactors, relays and valve actuators.

Overview of I/O modules

Type designation Product name Power supply Control panel optional

EY6IO30F001 modu630 From AS modulo 6 modu600-LO

EY6IO31F001 modu631 From AS modulo 6 modu600-LO

EY6IO50F001 modu650 From AS modulo 6 modu600-LO

Further information

16 − − − − Page 373

8 8 − − − Page 375

− − 6 − − Page 377

Type designation Product name Power supply Control panel optional

EY6IO70F001 modu670 From AS modulo 6 modu600-LO

EY6IO71F001 modu671 From AS modulo 6 modu600-LO

EY6IO72F001 modu672 From AS modulo 6 modu600-LO

8 − − − 8 Page 379

8 − − 8 − Page 381

− 4 4 4 − Page 383

Inputs/outputs Digital inputs Universal inputs Digital outputs Analogue outputs Digital inputs/outputs

Inputs/outputs Digital inputs Universal inputs Digital outputs Analogue outputs Digital inputs/outputs Further information

372

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6IO30: 16 × DI/CI inputs I/O module, modu630-IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC

link coupler • Receiving digital inputs (alarm, status or pulse counter) in operational systems, e.g. in HVAC engineering • 16 digital inputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module

(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)

EY6IO30F001

Technical data Power supply

Power supply Dissipated power1)

From AS or LC via I/O bus ≤ 0.8 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

Number of inputs Power supply for DI Pulse counter2)

16 Internal, ~13 V= ≤ 50 Hz

Connection, LOI Connection, I/O bus Connection terminals

4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail

¨

Ambient conditions

Inputs/outputs

Digital inputs (DI/CI)

Interfaces, communication

Earth connector Construction

Fitting Dimensions W × H × D Weight

On metal DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 130 g

Standards, directives

Protection type (as per EN 60730)

CE conformity according to

Environment class Software class3) EMC Directive 2014/30/EU

Connections and terminals: IP00 Front in DIN cut-out: IP30 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Overview of types Type

Features

EY6IO30F001

16 x DI/CI inputs I/O module

1) 2) 3)

Measured value without accessories 50 Hz only with PC module, otherwise 5 Hz The product is not suitable for safety functions

Right of amendment reserved © 2024 Fr. Sauter AG

373


HVAC automation | HVAC automation Accessories Type

Description

EY6LO00F001

Local operating and indicating unit for I/O modules

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

¨

374

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6IO31: 8 × UI (DI/CI/AI), 8 × DI/CI I/O module, modu631IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC

link coupler • Receiving digital inputs (alarm, status or pulse counter) and analogue inputs (Ni/Pt1000, R, U) in

operational systems, e.g. in HVAC • Eight digital inputs and eight universal inputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module

(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)

EY6IO31F001

Technical data Power supply

Power supply Dissipated power1)

From AS or LC via I/O bus ≤ 0.8 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

Number of inputs Power supply for DI Pulse counter Number of inputs Analogue Digital2)

8 Internal, ~13 V= ≤ 50 Hz 8 0...10 V, Ni1000, Pt1000, R DI/CI: ≤ 50 Hz

Connection, LOI Connection, I/O bus Connection terminals

4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail

¨

Ambient conditions

Inputs/outputs

Digital inputs (DI/CI)

Universal inputs (UI)

Interfaces, communication

Earth connector Construction

Fitting Dimensions W × H × D Weight

On metal DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 131 g

Standards, directives

Protection type (as per EN 60730)

CE conformity according to

1) 2) 3)

Protection class Environment class Software class3) EMC Directive 2014/30/EU

Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Measured value without accessories DI: 50 Hz only with PC module, otherwise 5 Hz The product is not suitable for safety functions

Right of amendment reserved © 2024 Fr. Sauter AG

375


HVAC automation | HVAC automation Overview of types Type

Features

EY6IO31F001

8 x UI(DI/CI/AI) and 8 x DI/CI I/O module

Accessories Type

Description

EY6LO00F001

Local operating and indicating unit for I/O modules

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

¨

376

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6IO50: 6 × relay (2A) outputs I/O module, modu650‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC

link coupler • Activation of displays in operational systems, such as HVAC engineering • Activation of actuators such as contactors or valve actuators, in operational systems • Six digital outputs (relay) • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module

(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)

EY6IO50F001

Technical data Power supply

Power supply Dissipated power1)

From AS or LC via I/O bus ≤ 1,3 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

Number of outputs Type of outputs

6 Relay (0-I), normally-open contact, galvanically isolated 24 VDC, 24...250 VAC Resistive load: 2 A Inductive load: ≤ 1 A, cos φ ≥ 0.8 Start-up current: ≤ 5 A 300,000 cycles for 2 A

¨

Ambient conditions

Inputs/outputs

Digital outputs (DO)

Load

Switching frequency, mechanical Interfaces and communication

Connection, LOI Connection, I/O bus Connection terminals Earth connector

4-pin 7-pin, spring contact 6 x 2-pin spring-loaded plug-in connectors Spring contact against DIN rail

Construction

Fitting Dimensions W × H × D Weight

On metallic DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 124 g

Standards and directives

Protection type (as per EN 60730)

CE conformity according to

Protection class Environment class Software class2) EMC Directive 2014/30/EU

Low-Voltage Directive 2014/35/EU 1) 2)

Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 EN 60730-1

Measured value without accessories The product is not suitable for safety functions

Right of amendment reserved © 2024 Fr. Sauter AG

377


HVAC automation | HVAC automation Overview of types Type

Features

EY6IO50F001

6 x relay (2 A) outputs I/O module

Accessories Type

Description

EY6LO00F001

Local operating and indicating unit for I/O modules

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

¨

378

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6IO70: 8 × DI/CI/DO (OC) and 8 × DI/CI I/O module, modu670‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC

link coupler • Activation of actuators such as relays and displays of operational systems, e.g. in HVAC engineering • Activation of displays in operational systems • Receiving digital inputs (alarm, status or pulse counter) in operational systems • Eight digital inputs and eight digital inputs/outputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module

EY6IO70F001

(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)

Technical data

¨

Power supply

Power supply Dissipated power1)

From AS or LC via I/O bus ≤ 0,8 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

Number of inputs Pulse counter2) Number of inputs/outputs Type of inputs/outputs

8 ≤ 50 Hz 8 Open collector, normally-open contacts (0-I), outputs switched with respect to ground (any arrangement) External, positive ≤ 28 V= 0...100 mA (max. 2 V voltage drop) Internal, ~13 V= ≤ 50 Hz

Ambient conditions

Inputs/outputs

Digital inputs (DI/CI) Digital inputs/outputs (DIO)

Power supply for DO Load Power supply for DI Pulse counter3) Interfaces and communication

Connection, LOI Connection, I/O bus Connection terminals Earth connector

4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail

Construction

Fitting Dimensions W × H × D Weight

On metallic DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 131 g

Standards and directives

Protection type (as per EN 60730) Protection class 1) 2) 3)

Connections and terminals:IP00 Front in DIN cut-out:IP30 I

Measured value without accessories 50 Hz only with PC module, otherwise 5 Hz 50 Hz only with PC module, otherwise 5 Hz

Right of amendment reserved © 2024 Fr. Sauter AG

379


HVAC automation | HVAC automation Environment class Software class4) EMC Directive 2014/30/EU5)

CE conformity according to

3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Overview of types Type

Features

EY6IO70F001

8 x DI/CI/DO(OC) and 8 x DI/CI I/O module

Accessories Type

Description

EY6LO00F001

Local operating and indicating unit for I/O modules

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

¨

4) 5)

380

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

The product is not suitable for safety functions EN 61000-6-2: To comply with the standard, the connecting cables for the digital open collector outputs (DO-OC) may not be longer than 30 m

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6IO71: 8 × AO and 8 × DI/CI I/O module, modu671‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu6*2‑LC

link coupler • Activation with a standard signal (0(2)...10 V) in operational systems, such as HVAC engineering • Receiving digital inputs (alarm, status or pulse counter) in operational systems • Eight digital inputs and eight analogue outputs • Power supply from automation station (modu6**-AS), link coupler (modu6*2‑LC) or supply module

(modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)

EY6IO71F001

Technical data Power supply1)

Power supply Power consumption Dissipated power

From AS or LC via I/O bus ≤1W ≤ 0,8 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

Number of inputs Power supply for DI Pulse counter2) Number of outputs Analogue Load

8 Internal, ~13 V= ≤ 50 Hz 8 0(2)…10 V= ≤ 2 mA

Connection, LOI Connection, I/O bus Connection terminals

4-pin 7-pin, spring contact 4 x 8-pin spring-loaded plug-in connectors Spring contact against DIN rail

¨

Ambient conditions

Inputs/outputs

Digital inputs (DI/CI)

Analogue outputs (AO)

Interfaces and communication

Earth connector Construction

Fitting Dimensions W × H × D Weight

On metallic DIN rail 35 x 7.5/15 as per EN 60715 55.7 (3 HP) x 100 x 59 mm 130 g

Standards and directives

Protection type (as per EN 60730)

CE conformity according to

1) 2) 3)

Protection class Environment class Software class3) EMC Directive 2014/30/EU

Connections and terminals:IP00 Front in DIN cut-out:IP30 I 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Measured values without accessories 50 Hz only with PC module, otherwise 5 Hz The product is not suitable for safety functions

Right of amendment reserved © 2024 Fr. Sauter AG

381


HVAC automation | HVAC automation Overview of types Type

Features

EY6IO71F001

8 x AO and 8 x DI/CI I/O module

Accessories Type

Description

EY6LO00F001

Local operating and indicating unit for I/O modules

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

¨

382

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6IO72: 4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module, modu672‑IO Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu660‑AS and modu680‑AS automation stations and modu612‑LC

link coupler • Activation with a standard signal (0(2)…10 V, 0(4)…20 mA) in operational systems, such as HVAC

engineering • Receiving digital inputs (alarm/status) and analogue inputs (Ni/Pt1000, U, I, R, pot.) in operational

systems • Four universal inputs, four analogue outputs and four digital outputs

EY6IO72F001

• Power supply from automation station (modu6**-AS), link coupler (modu612‑LC) or supply module (modu601‑LC) • Can be equipped with a local operating and indicating unit (modu600‑LO)

Technical data

¨

Power supply

Power supply Power consumption Dissipated power

From AS or LC via I/O bus ≤ 3.4 W ≤ 0,75 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

Number of inputs Analogue

4 U: 0(2)…10 V I: 0(4)…20 mA R: 200…2500 Ω, Ni/Pt1000, Poti 3 V (potentiometer) DI/CI (≤ 50 Hz) 4 U: 0(2)…10 V I: 0(4)…20 mA 0…10 V / 2…10 V 0…20 mA / 4…20 mA 4 Open collector, NO contacts (0-I), outputs switched with respect to ground External, positive ≤ 28 VDC 0…100 mA (max. 2 V voltage drop)

Ambient conditions

Inputs/outputs

Universal inputs (UI)

Analogue outputs (AO)

Voltage output (U) Current output (I) Digital outputs (DO)

Reference voltage Digital1) Number of outputs Analogue Load > 6 kΩ Load < 500 Ω Number of outputs Type of outputs

Power supply for DO Load Interfaces, communication

Connection, LOI Connection, I/O bus Connection terminals Earth connector

4-pin 7-pin, spring contact 4 × 8-pin spring-loaded plug-in connectors Spring contact against DIN rail

Construction

Fitting Dimensions W × H × D

1)

On DIN rail 35 × 7.5/15 as per EN 60715 55.7 (3 HP) × 100 × 59 mm

50 Hz only with PC module, otherwise 5 Hz

Right of amendment reserved © 2024 Fr. Sauter AG

383


HVAC automation | HVAC automation Weight

130 g

Type of protection

Connections and terminals:IP00 Front in DIN cut-out:IP30 As per 60730-1 I 3K3 (IEC 60721) EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Standards, directives

Protection class Environment class EMC Directive 2014/30/EU

CE conformity according to

Overview of types Type

Features

EY6IO72F001

4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module

Accessories Type

Description

EY6LO00F001

Local operating and indicating unit for I/O modules

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

¨

384

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

Right of amendment reserved © 2024 Fr. Sauter AG


SAUTER modulo 6 operating unit The SAUTER modulo 6 operating unit allows you to display the current status of the inputs and to directly override the outputs of the I/O modules – local priority operation as per EN ISO 16484‑2.

Overview of operating unit

Type designation Product name Power supply Device Function Display Use Further information

Right of amendment reserved © 2024 Fr. Sauter AG

EY6LO00F001 modu600-LO From I/O module Operating device with 4 push-buttons Visualisation, operation Display of analogue, digital and multi-state signals Universally for I/O modules Page 386

385


HVAC automation | HVAC automation

EY6LO00: Operating and indicating unit for I/O modules, modu600-LO Features • Part of the SAUTER modulo 6 system family • Pluggable element for direct operation and visualisation of displays for the modu6** I/O modules • Automatic detection of the current I/O module configuration • Display of values and statuses of the inputs and outputs on an LCD colour display • Detailed display of the individual inputs and outputs including labelling, type, status and graphics • Simple 4-button operation

EY6LO00F001

• LED indicator of I/O module modu6**-IO • Local priority operation • Ready for use without parameterising

Technical data Power supply

¨

Power supply Current consumption Dissipated power

From I/O module modu6**-IO ≤ 12.5 mA ≤ 0,3 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −25…60 °C 10…90% rh, no condensation

Resolution Operation

240 × 240 pixels, colour LCD Four buttons: Back/reject, Reverse/reduce, Forward/increase, Confirm

Connection Protocol

4-pin, spring contacts Proprietary

Type of protection

Connections: IP00 front, plugged in: IP30 (EN 60730-1) III 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3

Ambient conditions

Indicators, display, operation

Interfaces and communication

Standards and directives

CE conformity according to

Protection class Environment class EMC Directive 2014/30/EU

Overview of types Type

Features

EY6LO00F001

modu600-LO, operating and indicating unit for I/O modules

Manuals Document number D100386646 D100397589 D100408512 D100408262 D100402674

386

Language de de de en en

Title modu600‑LO Bedienungsanleitung Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I modu600-LO Operating instructions SAUTER modulo system description

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation Document number D100410201 D100408261 D100402676 D100410203

Language en fr fr fr

Title EY-modulo 6 – Best Practice I modu600-LO Notice d'emploi Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

¨

Right of amendment reserved © 2024 Fr. Sauter AG

387


SAUTER modulo 6 communication modules SAUTER communication modules enable third-party systems to be integrated on the automation level. Field-bus protocols, based on EIA-232 or EIA-485, such as Modbus/RTU and M-Bus, can be integrated directly on the automation station. The data is mapped in BACnet objects and is visible on the BACnet/IP network.

Overview of communication modules

Type designation Product name Interfaces Protocol Further information

388

EY6CM20F011 modu620-CM RS-485 Modbus RTU / ASCII Page 389

EY6CM30F031 modu630-CM RS-232, M-Bus M-Bus Page 391

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6CM20: Modbus/RTU (RS‑485) communication module, modu620‑CM Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu680‑AS and modu660‑AS automation stations or modu612‑LC link

coupler • Up to five COM modules per automation station • Connection to non-SAUTER systems (PLC, chillers, meters etc.) • RS-485, half duplex, electrically isolated interface for Modbus/RTU, Modbus/ASCII • Electrical isolation

EY6CM20F011

• Configurable RS-485 network resistors (software) • Baud rate 600...115 200 bit/s • Modbus master with up to four Modbus communication profiles • Integrated tunnelling function for commissioning and monitoring with serial Modbus master tools

¨

Technical data Power supply

Power supply Power consumption Dissipated power

From AS or LC via I/O bus 30 mA (AS-LC) ≤ 0.7 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −25…70 °C 10…90% rh, no condensation

Communication protocol

Modbus/RTU and Modbus/ASCII master as per V1.02, 2-wire (2W) 1 unit load (unit load (UL)); electrically isolated; integrated RS-485 network resistors (LT, PU, PD) configurable via software 600...115 200 bit/s, parity bit, stop bit, Rx/Tx bus timing Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible 3-/4-wire (D+/D−/COM reference), twisted, shielded, up to 1000 m Integration of Modbus slaves in an RS-485 segment (line) Up to 31 RS-485 unit loads (UL) 600 Modbus channels for BACnet I/O/V objects for up to 247 Modbus devices; FC01-06, 15, 16, 22; unicast and broadcast; access optimisation Switchable via software (CASE Engine)

Ambient conditions

Interfaces, communication

RS-485 (Modbus)

Bus physics

Bus speed Connection

Line Use Participant Functions

120 Ω bus termination and pullup/pull-down Construction

Fitting Dimensions W × H × D Weight

Right of amendment reserved © 2024 Fr. Sauter AG

On metal DIN rail 35 × 7.5/15 as per EN 60715 55.7 (3 HP) × 100 × 59 mm 110 g

389


HVAC automation | HVAC automation Standards, directives

Type of protection Environment class Software class1) EMC Directive 2014/30/EU2)

CE conformity according to

RoHS Directive 2011/65/EU

Connections and terminals: IP00 Front in DIN cut-out: IP30 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 EN IEC 63000

Overview of types Type

Features

EY6CM20F011

Modbus/RTU (RS-485) communication module

Accessories Type

Description

0920360601

Placeholder module for modu6**CM

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203 Additional information P100018041 MD 91.200

¨

1) 2)

390

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

Fitting instructions SAUTER Declaration on materials and the environment

The product is not suitable for safety functions HBES/BACS: 3 metres max. between EY-PS and AS

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation

EY6CM30: M-Bus communication module, modu630‑CM Features • Part of the SAUTER modulo 6 system family • Plug-in element for extending the modu680‑AS and modu660‑AS automation stations or modu612‑LC link

coupler • Up to four COM modules per automation station • M-Bus master • Connection to M-Bus meter networks for the integration of heat meters, electricity meters etc. • 2-wire M-Bus network for up to 80 unit loads, galvanically isolated

EY6CM30F031

• 2-wire RS-232 connection for point-to-point communication • Up to 256 devices and 600 values • M-Bus master with up to four M-Bus communication profiles • Integrated tunnelling function for commissioning and monitoring on the modulo 6 stations

Technical data

¨

Power supply

Power supply Power consumption Power consumption Dissipated power

From AS or LC via I/O bus ≤ 0.35 mA 7.42 W 2.56 W

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −25…70 °C 10…90% rh, no condensation

Communication protocol Bus physics

M-Bus master (EN 13757-3) M-Bus (EN 13757-2), electrically isolated, mark voltage 36 V, short-circuit proof, overcurrent monitoring and protection (max. 135 mA) 300...9600 (19 200, 38 400) bit/s Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible 2-wire (M+/M−) up to 1000 m; RS-232 (D+/D−/GND) up to 3 m Integration of M-Bus meters Up to 80 M-Bus unit loads (UL of 1.5 mA); up to 256 M-Bus devices (with external M-Bus level converter via RS-232) 600 M-Bus channels for BACnet I/O/V objects for up to 256 M-Bus devices; REQ_UD2, SND_NKE, SND_UD, primary/secondary addressing, readout (triggered, by offset or filter)

Ambient conditions

Interfaces, communication

RS-232 (M‑Bus)

Bus speed Connection

Line1) Use Participant

Functions

Construction

Fitting Dimensions W × H × D Weight 1)

On metal DIN rail 35 × 7.5/15 as per EN 60715 55.7 (3 HP) × 100 × 59 mm 118 g

M-Bus cable lengths depend on the cable type (J-Y(ST)Y 4 × 0.5 mm2 max. 1000 m, LiYY 2 × 1.5 mm2 max. 4000 m), number of bus segments and the baud rate; see engineering notes

Right of amendment reserved © 2024 Fr. Sauter AG

391


HVAC automation | HVAC automation

Standards, directives

Type of protection Environment class Software class2) EMC Directive 2014/30/EU3)

CE conformity according to

RoHS Directive 2011/65/EU

Connections and terminals: IP00 Front in DIN cut-out: IP30 3K3 (IEC 60721) A (EN 60730-1, Appendix H) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 50491-5-1, EN 50491-5-2, EN 50491-5-3 EN IEC 63000

Overview of types Type

Features

EY6CM30F031

M-Bus communication module

Accessories Type

Description

0920360601

Placeholder module for modu6**CM

Manuals

¨

Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203 Additional information P100018041 MD 91.205

2) 3)

392

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

Fitting instructions SAUTER Declaration on materials and the environment

The product is not suitable for safety functions HBES/BACS: 3 metres max. between EY-PS and AS

Right of amendment reserved © 2024 Fr. Sauter AG


Security in the building network The IoT provides incredible opportunities for building automation thanks to its openness, availability and variety of solutions. On the other hand, it can pose a threat for exactly the same reasons. New devices must therefore be secure from the outset. Because of this, modulo 6 was developed according to the recommendations of IEC 62443-3-3. With modulo 6, the latest generation of building automation systems, SAUTER offers a security-oriented solution. The security concept is based on the international standard for cybersecurity in industrial automation, IEC 62443, which defines system security requirements and security levels. With BACnet Secure Connect (BACnet/SC), modulo 6 is now even more secure. The new BACnet data connection only supports encrypted communication and is based on the latest version of the encryption protocol, TLS 1.3. BACnet/SC is also ideally suited for enterprise IT due to the basic technologies used (TCP, WebSocket, TLS, IPv4, IPv6). Seamless integration into the existing infrastructure is made easy with BACnet/SC BACnet/IP routers. Proven security technologies provide encryption, authentication and access protection. This means the system is already well protected against cyber attacks on the automation level.

Right of amendment reserved © 2024 Fr. Sauter AG

393


HVAC automation | HVAC automation

EY6RT30: BACnet router and SC hub, B/IP <-> B/SC, modu630-RT Features • Part of the SAUTER modulo 6 system family • Suitable for use as BACnet router between BACnet networks • Suitable for use as BACnet Secure Connect Hub (B/SC-Hub) • BACnet profiles: B-RTR, B-SCHUB, B-BBMD • BACnet data links: BACnet/IP, BACnet/SC • BACnet/IP-BBMD or FD function

EY6RT30F001

• Four RJ45 connections for two separate IP networks • Three connections switched for daisy chain • Encryption of communication with TLS 1.3

Technical data Power supply

¨

Power supply Power consumption Dissipated power Peak inrush current1)

24 VDC ± 10% ≤3W ≤3W ≤ 20 A, ≤ 1 ms, on the 24 V side

Connection

Spring-type terminal, pluggable, 0.5...1.5 mm2 (rigid) 0.5...2.5 mm2(flexible) 8...10 mm wire stripped CR2032, pluggable Spring contact against DIN rail and PE terminal

Parameters

Battery (buffer: RTC) Earth connector

Ambient conditions

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…90% rh, no condensation

BACnet profiles

BACnet router

B-RTR (BACnet router) B-SCHUB (BACnet SC hub) B-BBMD (BACnet Broadcast Manager) BACnet/IP, BACnet/SC Data Links

Processor RAM (memory) Flash Operating system

ARM Cortex A8, 32-bit, 1 GHz 512 MB (DDR3) 512 MB Embedded Linux

Communication

Via BACnet/IP (UDP) BACnet/SC (web sockets, TCP) TLS V.1.3 (BACnet/SC) BACnet/IP, BACnet/SC 1 × RJ45 connector 10/100 Mbit/s BACnet/IP, BACnet/SC 3 × RJ45 connector

Function

Architecture

Interfaces, communication

Ethernet network #1

Ethernet network #2

1)

394

Encryption Communication protocols Ethernet network 10/100 BASE-T(X) Communication protocols Ethernet network

Measured value with EY-PS021F021 power supply unit

Right of amendment reserved © 2024 Fr. Sauter AG


HVAC automation | HVAC automation 10/100 BASE-T(X) switched

10/100 Mbit/s

Fitting

On metal DIN rail 35 × 7.5/15 as per EN 60715. Rail housing as per DIN 43880 92.6 (5 HP) × 100.9 × 58.3 mm 260 g

Construction

Dimensions W × H × D Weight Standards, directives

Type of protection

CE/UKCA conformity2)

Protection class Environment class EMC-D 2014/30/EU (CE) EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

Connections and terminals: IP00 Front in DIN cut-out: IP30 I 3K3 (IEC 60721) EN 55024, EN 55032 Class B EN 55024, EN 55032 Class B EN 62368-1 EN 62368-1 EN IEC 63000 EN IEC 63000

¨

Overview of types Type

Features

EY6RT30F001

BACnet router and SC hub, BACnet/SC <-> BACnet/IP

Manuals Document number D100397589 D100408512 D100402674 D100410201 D100402676 D100410203

2)

Language de de en en fr fr

Title Systembeschreibung SAUTER modulo EY-modulo 6 – Best Practice I SAUTER modulo system description EY-modulo 6 – Best Practice I Description du système SAUTER modulo EY-modulo 6 – Meilleures pratiques I

Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG

395


Room automation 5 High-performance, modular, communicative and ready for IoT. SAUTER ecos guarantees seamless integration into the building management system as well as the automation system of the primary plants while also providing maximum flexibility with the minimum use of energy. Integrated room automation from SAUTER controls not only the room climate, but also the lighting and sunshading. Individual daily programs and realtime monitoring ensure comfort for users. 396

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation Room automation EY-RC 504/505: Room automation station, ecos504/505

399

EY-CM 581: Wireless interface, EnOcean, ecosCom581

423

EY-RC 311: Room controller, ecos311

404

FMS 116, 196: Smart Sensor viaSens116/196

426

EY-RU 310...316: Room operating unit, ecoUnit310...316

408

EY-EM 510...512: Remote I/O module, ecoLink510...512

432

EY-RU 365: Touch room operating unit, ecoUnit365

410

EY-EM 514, 515: Remote I/O module, ecoLink514, 515

434

EY-RU 355: Room operating unit, ecoUnit355

413

EY-EM 522, 523: Remote I/O module, ecoLink522, 523

436

EY-SU 358: Push-button unit for room operating unit, ecoUnit358

416

EY-EM 527: Remote I/O module, ecoLink527

438

EY-RU 110: Room sensor, EnOcean, ecoUnit110

418

EY-PS 031: Power supply, DIN rail, 230 V / 24 VDC

441

EY-RU 146: Room operating unit, EnOcean, ecoUnit146

420

EY-SU 106: Push-button unit for EnOcean room operating unit, ecoUnit106

422

HVAC automation Overview of communication modules

443

EY-BU 292: novaNet-Ethernet interface, moduNet292

444

EYZ 291: Router, novaNet291

446

N

Right of amendment reserved © 2024 Fr. Sauter AG

397


SAUTER ecos room automation stations The areas of use for the SAUTER ecos room automation stations range from precise room control with heating and cooling to integrated room automation with demand-controlled ventilation, lighting and sunshading. The scalable solutions for controlling and regulating the rooms are individually adjusted to the required functional scope and the usage profile. You thus reduce your energy consumption, your costs and the CO2 emissions while providing maximum comfort and well-being. The ecos devices enable the area usage to be adjusted flexibly during operation by dividing the area on each floor into room segments.

Overview of room automation stations

Type designation Product name

EY-RC504F*** ecos504

Parameters Power supply Room segments Room operating units I/O extension modules

EY-RC505F0** ecos505

EY-RC311F001 ecos311

24 V=/~ 8 2×4 2×8

230 V~ 1 1 2

Inputs/outputs Universal inputs Digital inputs Analogue outputs Digital outputs Relay outputs (2 A / 10 A)

− − − − −

5 − 3 4 3/1

Interfaces, communication Interfaces Protocols BACnet profile

RS-485, Ethernet BACnet/IP, MQTT, Modbus RTU, M-Bus, SLC, KNX, DALI, SMI B-BC

RS-485 BACnet MS/TP, SLC B-ASC

Objects Data points (value objects) Control (Loop) Calendars (Calendar) Time programmes (Schedule) Historical data (Trend Log) Alarms (Notification Class)

600 32 16 32 256 16

50 6 3 4 − − Page 404

Further information

398

Page 399

Page 399

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation

EY-RC 504/505: Room automation station, ecos504/505 Features • Part of the SAUTER modulo 5 system family • Modular room automation station (AS) for up to eight rooms or eight flexible room segments • BACnet/IP communication (EN ISO 16484-5) as BACnet Building Controller (B-BC) • The ecoUnit 3 and ecoUnit 1 room operating units enable individual adjustment of the room climate

EY-RC 504

• Optimises energy consumption thanks to presence function, window contact monitoring, demand-controlled

ventilation, control of lighting and window blinds, and time-dependent setpoint specification • Function libraries for climate, lighting and sunshading • Expansion bus for remote ecoLink modules, ecoUnit room operating units and EnOcean wireless interface • KNX interface to connect KNX operating units, sensors and actuators • Integrated KNX tunnelling function (KNX/IP) for the commissioning of KNX with ETS • DALI interface with DALI bus power supply for the connection of DALI electronic ballasts (EB) and DALI

sensors • Web-based commissioning tool for DALI network

EY-RC 505

• SMI interface (SMI/SMI LoVo) for activating SMI motors for sunshading (window blinds, roller shutters) • Integrated tunnelling function for commissioning with SMI-easyMonitor • RS‑485 half duplex, electrically isolated interface for Modbus/RTU, Modbus/ASCII • Baud rate 600 to 115,200 bit/s with configurable RS-485 network resistors

N

• Modbus master with up to four simultaneous communication profiles • Integrated tunnelling function for commissioning and monitoring with serial Modbus master tools • Physical M-Bus interface and RS‑232 interface for external M-Bus level converters • Supports M-Bus baud rates of 300 to 38,400 bit/s • M-Bus master function with up to four simultaneous communication profiles • Integrated tunnelling function for commissioning and monitoring with M-Bus tools • Time programme and calendar function; data recording • Integrated (EY‑RC504F202 only) or licensable MQTT functionality (MQTT Broker / Client) • Engineering/programming using SAUTER CASE Suite (based on IEC 61131-3) • Integration into the building management system via BACnet/IP with Ethernet interface

Technical data Power supply

Power supply Max. peak inrush current Connection

24 VDC ±10% 24 VAC +25%/−15%, 48…63 Hz 23 A (10 milliseconds) Spring-type terminals 0.2...2.5 mm2 rigid/flexible Ampacity max. 5 A

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −25…70 °C 10…85% rh, no condensation

BACnet profile BACnet data point objects Control Active COV subscription BACnet client links Time programmes Calendar

B-BC (EN ISO 16484-5) 600 (incl. HW) 32 (Loop) 1500 200 (Peer-to-Peer) 32 (Schedule) 16 (Calendar)

Ambient conditions

Function

BACnet

Dynamic objects

Right of amendment reserved © 2024 Fr. Sauter AG

399


Room automation | Room automation Notification Historical data

Services Gateway

16 (Notification Class) 256 (Trend Log) up to 60,000 entries 32 (Log View), moduWeb (F101) only 16 (Command) 32 32 KNX, DALI, SMI, Modbus, M-Bus, SLC, SLC/EnOcean BACnet/IP as per ISO 16484-5, HTTP for moduWeb (F101 only), MQTT protocol V3.1.1/V5 as per ISO/IEC 20922 via TCP or TCP/TLS 1.2 (F202 only / licence) Number of topics / alias topics for max. number of BACnet objects (600) Number of topics, depending on CPU/memory resources (> 1000)

Chart Command object Number of BBMDs in BDT Number of FDs in FDT Field bus protocols IP protocols

MQTT

MQTT Client MQTT Broker

Architecture

N

Processor SDRAM (synchronous dynamic RAM) SRAM (static RAM) Flash Operating system Cycle time Application data

32-bit, 600 MHz (ARM) 128 MB 64 kB 128 MB Embedded Linux 100 milliseconds Via CASE Engine

Communication protocol

BACnet/IP, HTTP (F101 only), MQTT (F202 only or with licence), NTP client 2 × RJ-45 connector 10/100 BASE-TX switched 2 × RS-485, SLC ecoLink I/O modules; ecoUnit 1, ecoUnit 3 operating units; ASV 2 VAV actuators Max. 2 × 8 ecoLink modules Max. 2 × 4 ecoUnit 1, 3 or FCCP 2 Max. 2 × 12 ASV 2 5 V ±5% < 200 mA (sum of both RS-485), protected against short circuit Pluggable spring-type terminals 2 × 4-pin 0.2...1.5 mm2 rigid/flexible 4-wire, twisted, shielded Max. 100 m (30 m) with ecoUnit, up to 500 m, bus termination necessary KNX TP1 (ISO/IEC 14543-3) KNX bus max. 6 mA Via external KNX power supply KNX bus terminal x4 0.6...0.8 mm rigid lines KNX cable, 2-wire, twisted KNX actuators and sensors Up to 64 KNX devices, depending on the external KNX power supply

Interfaces, communication

Ethernet network

RS-485 A, RS-485 B

Connection Type Communication protocol Use

Participant

Power supply Connection

Line1) Line length2)

KNX

Communication protocol Power consumption Bus power supply Connection Line Use Participant

1) 2)

400

Example cable CAT-5, J-Y(ST)Y, RS-485 bus cable (e.g. Belden 9842) With the cable length and the conductor cross-section, the supply voltage (+5 V) for the ecoUnit 3 must not fall below the minimum required voltage due to the voltage drop.

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Functions DALI (per COM module)

Communication protocol Power consumption Bus power supply

Connection Line Use Participant

Functions

SMI (per COM module)

Communication protocol Bus power supply

Connection Line Use Participant Functions

RS-485 (COM module)

Communication protocol

Bus physics

Bus speed Connection

Line3) Use Participant Functions

M-Bus/RS-232 (COM module)

Communication protocol Bus physics

Bus speed Connection

3)

256 KNX group addresses for BACnet I/O objects (256 channels) DALI (IEC 62386-101/-103) DALI bus max. 2 mA (only when operating with external power supply) Typ. 16 V, max. 116 mA (can be switched off for external bus power supply) Spring-type terminals 0.2...2.5 mm2 rigid/flexible 2-wire, NYM…, up to 300 m DALI ballasts (IEC 62386-102) DALI sensors (see list) Up to 64 DALI ballasts and 64 DALI sensors (depending on type and bus power supply) 256 DALI functions for BACnet I/O objects (256 channels) with addressable 64 DALI short addresses and 16 group addresses SMI master (SMI standard V2.3.2) Typ. 17 V, max. 20 mA, for 16 motors typ. 12.8 mA (0.8 mA/motor), protected against short circuit (30 mA) Spring-type terminals 0.2...2.5 mm2 rigid/flexible 2-wire, NYM…, up to 350 m SMI actuators, SMI (230 V) or SMI LoVo (see list) Up to 16 SMI motors 128 SMI functions for BACnet I/O objects (128 channels) for up to 16 single and group addresses each Modbus/RTU and Modbus/ASCII Master as per V1.02 2-wire (2W) 1 unit load (UL); electrically isolated; integrated RS-485 network resistors (LT, PU, PD) configurable via software 600...115,200 bit/s Parity bit, stop bit, Rx/Tx bus timing Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible 3-/4-wire (D+/D−/COM reference), twisted, shielded, up to 1000 m Integration of Modbus slaves in an RS-485 segment (line) Up to 31 RS-485 unit loads (UL) 600 Modbus channels for BACnet I/O/V objects for up to 247 Modbus devices; FC01-06, 15, 16, 22; unicast and broadcast; access optimisation M-Bus master (EN 13757-3) M-Bus (EN 13757-2); electrically isolated, mark voltage 36 V, short-circuit proof, overcurrent monitoring and protection 300...9600 (19 200, 38 400) bit/s Pluggable spring-type terminals 2 × 5-pin 0.2...1.5 mm2 rigid/flexible

N

Example cable CAT-5, J-Y(ST)Y, RS-485 bus cable (e.g. Belden 9842)

Right of amendment reserved © 2024 Fr. Sauter AG

401


Room automation | Room automation 2-wire (M+/M-) up to 1000 m; RS-232 (RX/TX/C) up to 15 m Integration of M-Bus meters Up to 40 M-Bus unit loads (UL of 1.5 mA); up to 256 M-Bus devices (with external M-Bus level converter via RS-232) 400 M-Bus channels for BACnet I/O/V objects for up to 256 M-Bus devices; REQ_UD2, SND_NKE, SND_UD, primary/secondary addressing, readout (triggered, by offset or filter)

Line4) Use Participant

Functions

Construction

Fitting

DIN rail 35 × 7.5/15 EN 50022 Rail housing DIN 43880 EY-RC 504: 105 (6 HP) × 90 × 58 mm EY-RC 505: 210 (12 HP) × 90 × 58 mm

Dimensions W × H × D

Standards, directives

Type of protection

N

Energy class5)

Environment class Protection class EMC Directive 2014/30/EU

CE conformity according to

eu.bac certificate

Energy Performance of Buildings Directive 2010/31/EU eu.bac licence

Connections and terminals: IP00 Front in DIN cut-out: IP30 IP30 (EN 60529), with accessory terminal cover I to VIII = up to 5% as per EU 811/2013, 2010/30/EU, 2009/125/EC 3K3 (IEC 60721) I (EN 61140) EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 15500 No. 2166

Overview of types Type

COM2

COM3

Weight

Current consumption (max.)

Power consumption

EY-RC504F001

--

--

--

220 g

0.33 A

4 W / 8 VA

EY-RC504F202

--

--

–

220 g

0.33 A

4 W / 8 VA

EY-RC504F011

KNX

--

–

240 g

0.33 A

4 W / 8 VA

EY-RC504F021

DALI

--

--

245 g

0.43 A

6 W / 10 VA

EY-RC504F041

SMI

--

–

240 g

0.33 A

4 W / 8 VA

EY-RC504F0C1

RS-485

--

--

243 g

0.33 A

5 W / 9.5 VA

EY-RC504F0D1

M-Bus

--

--

253 g

0.48 A

6.9 W / 10 VA

EY-RC505F031

KNX

DALI

--

385 g

0.61 A

7 W / 10 VA

EY-RC505F051

SMI

DALI

--

410 g

0.61 A

7 W / 11 VA

EY-RC505F061

KNX

SMI

--

385 g

0.33 A

4 W / 8 VA

EY-RC505F071

KNX

SMI

DALI

420 g

0.61 A

7 W / 11 VA

EY-RC505F081

--

DALI

DALI

410 g

0.61 A

9 W / 14 VA

EY-RC505F091

SMI

SMI

DALI

430 g

0.61 A

8 W / 12 VA

EY-RC505F0A1

KNX

DALI

DALI

420 g

0.61 A

9 W / 14 VA

4)

5)

402

COM1

M-Bus cable lengths depend on the cable type (J-Y(ST)Y 4 × 0.5 mm2 up to 1000 m, LiYY 2 × 1.5 mm2 up to 4000 m), the number of bus segments and the baud rate; see engineering notes When the room automation station is being used as a temperature controller, most temperature controller classes can be fulfilled according to EU Directive 2010/30 / EU Regulation 811/2013. For information on the exact temperature class reached, please refer to the system integrator’s user program

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Type

COM1

COM2

COM3

Weight

Current consumption (max.)

Power consumption

EY-RC505F0B1

SMI

SMI

--

400 g

0.33 A

4 W / 8 VA

EY-RC505F0E1

RS-485

M-Bus

--

405 g

0.48 A

7.1 W / 10.6 VA

EY-RC505F0F1

RS-485

DALI

--

405 g

0.61 A

6 W / 10 VA

EY-RC505F0G1

RS-485

SMI

DALI

430 g

0.61 A

7 W / 10 VA

EY-RC505F0H1

KNX

RS-485

DALI

420 g

0.61 A

9 W / 14 VA

EY-RC505F0J1

RS-485

DALI

DALI

440 g

0.61 A

9 W / 14 VA

EY-RC505F0K1

KNX

RS-485

--

385 g

0.61 A

7 W / 10 VA

A A A A A A

EY-RC 504, 505: Room automation station, 8 rooms/segments, 2 × SLC/RS-485 COM1...3: Integrated communication interfaces F*0*: EY-RC504F001 (ecos504, standard), EY-RC504F202 (ecos504-IoT, BACnet MQTT gateway) DALI: DALI interface with bus power supply (116 mA) RS-485: RS-485 interface for Modbus/RTU and Modbus/ASCII SMI: SMI interface for SMI or SMI/LoVo

Accessories Type

Description

0940240001

ecos504/505 terminal covers (2 pcs)

0450573001

Transformer 230 VAC / 24 VAC, 42 VA; for DIN rail 35 mm, dimensions: 78 × 74 × 52 mm (W×H×D)

EY-CM581F081

ecosCom581 EnOcean wireless interface

EY-RU 1**

ecoUnit 1 room operating units with EnOcean wireless technology (via EY-CM581F081)

EY-RU 3**

ecoUnit 3 room operating units

EY-EM51*

Remote ecoLink I/O modules (24 V)

EY-EM52*

Remote ecoLink I/O modules (230 V)

YY-FX502F001

ecos-IoT: MQTT Client, licence for ecos504/505

YY-FX502F002

ecos-IoT: MQTT Client + Broker, licence for ecos504/505

YY-FX503F001

ecos504/505: RADIUS supplicant, licence

A

N

1 HP = one horizontal pitch with 17.5 mm

Right of amendment reserved © 2024 Fr. Sauter AG

403


Room automation | Room automation

EY-RC 311: Room controller, ecos311 Features • Part of the SAUTER modulo system family (BACnet MS/TP) • BACnet MS/TP communication (EN ISO 16484-5) • BACnet room controller (B-ASC) for fan coil unit, chilled beam, chilled ceiling, radiator heater, light, control

of window blinds, variable volume flow control (VAV) etc. EY-RC311F001

• Individual adjustment of the setpoints via ecoUnit 3 room operating units (EY-RU 3**) • Optimisation of energy consumption using presence function, monitoring of window contacts, demand-

controlled switching of fan speeds and time-dependent setpoint specification Freely configurable time programme (BACnet Schedule objects) • • Freely programmable with CASE Suite software (based on IEC 61131-3) • Expandable with ecoLink I/O modules for lighting and control of window blinds

Technical data Power supply

Power supply

N

Power consumption Dissipated power

230 V, 200 V min., 253 V max., 50...60 Hz Max. 14 VA 5 W / 8 VA

Operating temperature Storage and transport temperature Humidity

0...45 °C −20...70 °C 10...85% rh, no condensation

Type

0-I relays, normally-open contacts with shared power supply 230 VAC / 30 VDC 2 A resistive load, total max. 5 A 230 VAC; 10 A resistive load

Ambient conditions

Inputs / outputs

Relay outputs

Load

Switching frequency Semiconductor outputs (MOS-FET)

Type Load

Analogue outputs Universal inputs

Type Analogue Digital Potentiometer Resistance Ni1000/Pt1000

> 3 × 105 cycles (2 A) > 2 × 105 cycles (10 A) 0-I, 24 VAC/DC, switched to ground 0.5 A Max. peak current 1 A (< 20 ms) 0…10 V / 2 mA 0…10 V 0-I, max. 2 Hz 1…10 kΩ (for potentiometer) 100…2500 Ω -20...100 °C

Interfaces and communication

Interface Protocol Line Line length

1 × RS-485 electrically isolated, ½ load BACnet MS/TP 2-wire, twisted with reference, shielded 1000 m with bus termination

SAUTER Local Communication interfaces

Interface Protocol Cable Cable length

404

1 x RS-485 SLC 2×2-wire, twisted, shielded < 100 m with bus termination (with ROU) < 500 m with bus termination (without ROU)

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Room operating units I/O modules

Max. 1; EY-RU 31*/355/110/146 (via EY-CM581) Max. 2; EY-EM 51*, 52*

Dimensions W × H × D Weight Fitting

178 × 103 × 53 mm 674 g DIN rail; TH35×7.5/15 EN 50022

Type of protection

IP00 (EN 60529) IP20 (cover with front aperture) II (EN 60730-1) I to VIII = up to 5% as per EU 811/2013, 2010/30/EU, 2009/125/EC 3K3 (IEC 60721) EN 61000-6-1 EN 61000-6-3 EN 60730-1 EN 60730-2-9

Construction

Standards and directives

Protection class Energy class1)

CE conformity according to

Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

Overview of types Type

Description

EY-RC311F001

ecos311 - room controller B-ASC, MS/TP, 16IO, 230 V

Overview of I/O mix Universal inputs Relay outputs Digital outputs Analogue outputs

1)

N 5 3 (2 A) 1 (10 A) 4 3

When the automation station is being used as a temperature controller, most temperature controller classes can be fulfilled according to EU Directive 2010/30/EU, Regulation 811/2013. For information on the exact temperature class, please refer to the system integrator’s user program.

Right of amendment reserved © 2024 Fr. Sauter AG

405


SAUTER ecos room operating units SAUTER ecoUnit 3 and ecoUnit 1 room operating units combine technology with design. The buttons can be freely assigned with various functions. Due to the standard internal dimensions of 55 × 55 mm, these devices fit both SAUTER frames and common frames of third-party manufacturers of light switches.

Overview of room operating units

Type designation Product name Function

Use Interface Indicator/display Temperature sensor Button functions Fan speeds Setpoint correction Room occupancy Further information

406

EY-RU310F001 ecoUnit310 Temperature sensor

− • − − − − Page 408

EY-RU311F001 ecoUnit311 Temperature sensor, setpoint correction

EY-RU314F001 EY-RU316F001 ecoUnit314 ecoUnit316 Temperature sensor, setTemperature sensor, setpoint correction, occupan- point correction, occupancy, fan cy, fan, and control of lighting and window blinds ecos 5, ecos311 RS-485 − − − • • • − 2 4 − AUTO-0-1-2-3 Rotary knob − 3 modes Page 408 Page 408 Page 408

Right of amendment reserved © 2024 Fr. Sauter AG


Type designation Product name Housing colour Function

Use Interface Indicator/display Temperature sensor Button functions Fan speeds Setpoint correction Room occupancy Further information

Type designation Product name Function

Use Interface Indicator/display Temperature sensor Button functions Fan speeds Setpoint correction Room occupancy Further information

EY-RU365F0** EY-RU355F*** ecoUnit365 ecoUnit355 Traffic white/jet black Traffic white/jet black Temperature sensor, 12 setpoints Temperature sensor, setpoint corwith 4 functions (temperature, rection, occupancy, fan lights, blinds and fans) modulo 6, ecos 5 modulo 6, ecos 5, ecos 311 SLC/RS-485 TFT colour display LCD • • 32 on 6 pages with 6 tiles each 5 • AUTO-0-1-2-3 Digitally adjustable via buttons • 3 modes Page 410 Page 413

EY-RU110F201 ecoUnit110 Temperature sensor

EY-RU146F201 ecoUnit146 Temperature sensor, setpoint correction, occupancy, fan, and control of lighting and window blinds With ecosCom581 for: ecos 5, ecos311, modulo 6 EnOcean wireless − LCD • • − 6 − AUTO-0-1-2-3 − Digitally adjustable via buttons − 3 modes Page 418 Page 420

Right of amendment reserved © 2024 Fr. Sauter AG

EY-SU358F081 ecoUnit358 Traffic white/jet black Push-button unit

Connection to ecoUnit355 − − − 2, 4, 8 − − − Page 416

EY-SU106F100 ecoUnit106 Solar panel supply, control of lighting and window blinds Connection to ecoUnit1** − − − 6 − − − Page 422

407


Room automation | Room automation

EY-RU 310...316: Room operating unit, ecoUnit310...316 Features • Part of the SAUTER modulo 5 system family • Room operating unit for ecos504/505 • Can be extended with EY-SU 306 push-button unit • Operating unit to control and guarantee the highest possible room comfort • Temperature measurement and setpoint adjustment

EY-RU316F001

• Device insert with transparent front, fits into frame with 55 × 55 mm aperture • Frame can be ordered as an accessory • Room climate can be adapted individually • Operating mode can be set for room occupancy and actuation of a 3-speed fan • Control of window blinds, windows and lighting (ON/OFF/dim) • Multicolour LED indicators for visualisation of local energy consumption • Room operating unit with a wide range of functions, designs and colours

Technical data Power supply

N

EY-RU310F001

Power supply Current consumption

From automation station ≤ 25 mA ≤ 38 mA with 2 × EY-SU306

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C –25...70 °C 10...85% rh, no condensation

Measuring range Resolution Time constant Setpoint correction Room occupancy (presence) Fan speeds Position LED

0...40 °C 0.1 K Approx. 7 minutes Variable 3 modes, LED indicator 5 functions, LED indicator Switchable: green/red/OFF

Activation Interface Protocol Line Line length1) Connection terminals

ecos 5, modu521 RS-485 SLC 4-wire, twisted, shielded ≤ 100 m (30 m) with bus termination Pluggable; for wire of 0.12...0.5 mm² (Ø 0.4...0.8 mm)

Fitting Dimensions W × H × D Weight Housing Labelling insert

Recessed/surface-mounted (see accessories) 59.5 × 59.5 × 25 mm 0.1 kg Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C)

Type of protection

IP30 (EN 60529)

Ambient conditions

Parameters

Sensors

Functionality

Interfaces and communication

Connection to automation station

Construction

Standards and directives

1)

408

Max. 30 m for industrial applications as per EN 61000-6-2

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation

CE conformity according to

Protection class Environment class EMC Directive 2014/30/EU

III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3

Overview of types Type

Features

Buttons

EY-RU310F001

NTC sensor

−

EY-RU311F001

Operating unit, NTC sensor, dXs setpoint correc- − tion (rotary knob)

EY-RU314F001

Operating unit, NTC sensor, dXs setpoint correc- 2 tion (rotary knob), fan, occupancy

EY-RU316F001

Operating unit, NTC sensor, dXs setpoint correc- 4 tion (rotary knob), fan, occupancy, window blinds / light

Accessories Operating unit Type

Description

EY-SU306F001

Push-button unit, without frame

Fitting Type

Description

0940240***

For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055

0949360004

Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)

0949241301

Transparent cover for EY-RU and EY-SU, 10 pcs.

0949241302

RAL 9010 white cover for EY-CM581, EY-RU and EY-SU (10 pcs.)

Right of amendment reserved © 2024 Fr. Sauter AG

N

409


Room automation | Room automation

EY-RU 365: Touch room operating unit, ecoUnit365 Features • Part of the SAUTER modulo system family • High quality room operating unit with touch operation and tile display • 3.5" TFT colour display, 320x240 pixels • Scratch-resistant, capacitive touch interface • Navigation of up to 6 pages with up to 6 functions (tiles) each • Intuitive operation for predefined functions (temperature, lights, blinds, fans)

EY-RU365F00*

• Up to 32 values/channels can be defined as a reference for BACnet objects • Display of the energy efficiency function (“ECO 10”) • Mode and symbol displays, e.g. heating/cooling • Audio feedback when pressed • Supply voltage 24 VAC/DC • SLC/RS-485 communicative interface for ecos 5, modulo 6 • Can be located up to 500 m from the automation station • 6 digital inputs for connecting presence detector, door/window contacts, digital contact directly • Configuration with CASE Suite (CASE Engine “EY-RU365 module configuration”, RU_TOUCH module) • Optional: Bluetooth (BLE 4.0) for using the “ecoUnit” app on a smartphone

N EY-RU365F0A*

Technical data Power supply

Power supply

24 VAC/DC, ±20% – SELV 0 / 50/60 Hz or from EY-PS of station < 2.6 W

Rated power during continuous operation Ambient conditions

Operation Transport

Operating temperature Ambient humidity Ambient humidity Storage and transport temperature

0...45 °C 10...85% rh, no condensation < 85% rh, no condensation −25...70 °C

Values/channels

Up to 32 values/channels, parameterisable as setpoint, switching command or value display; 12 of which for complete setpoint inputs Various symbols: e.g. room mode – comfort/reduced/set-back; ECO mode – green-yellow-red; heating/cooling; windows; humidity; wind; alarm; block Up to 6 pages Up to 6 tiles per page Temperature, fan, light dimming, light switching, blind control (position/angle), value displays (feedback), switching function with various predefined symbols (lamp type, mode, scenes...) °C/°F changeover for temperature function; home button; navigation display; (title) labelling for pages, tiles and functions None, time, actual temperature or any value (channel) NTC 10kΩ 0...40 °C

Parameters

Symbol

Number of functions Tile function

Special functions

Screensaver display Temperature sensor

410

Type of sensor Measuring range

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Resolution Accuracy

Refresh interval Drift Position Number of inputs Type of inputs Polling voltage Polling current Internal resistance Input refresh interval Switching thresholds

Inputs

Audible feedback

Display with backlight

Touchpad

Switching hysteresis Type Application Screen diagonal Resolution Display refresh interval Type Number of colours Brightness Contrast ratio Perspective

Touchpad type Refresh rate

0.1 K ± 1 K at typ. 0.1 ms dependent on environment (e.g. air flow) 1s < 0.1 °C/year Bottom left 6 For potential-free switching contacts 24 VDC unregulated >3 mA (closed contact) > 4.7 kΩ 20 ms <10 V (voltage “rising”) >6 V (voltage “falling”) >1 V Piezoelectric signal Audio feedback when touch function is executed 3.5 inches (8.9 cm) 320 x 240 pixels 60 Hz TFT 262,000 500 cd/m² 300 From above: 15° From below: 35° From left/right: 45° Capacitive with gesture recognition 10 ms

N

Interfaces, communication

Connection terminals

SLC/RS-485, DI, power supply

Communication

Activation Interface Protocol Line

Line length Protection circuit Wireless

Bluetooth specification Module Number of app participants Supported OS Bluetooth app

2 x 6-pin screw terminals, pluggable, for solid or braided wires, max. 1.5 mm² (grid dimension 5 mm) From station (ecos 5, modulo 6) RS-485 with 115kbit/s (no integrated terminating resistor) SLC (SAUTER Local Communication) 2-wire twisted, shielded (D+, D-); MM terminal is reference for RS-485; shielded at controller ≤ 500 m with bus termination Protected against excess voltage and reversed polarity 4.0 Low Energy Class 2 Panasonic PAN1740 1 simultaneously 256 registered iOS 8.0 or higher Android 4.1 (Jelly Bean) or higher

Construction

Device dimensions

Fitting Dimensions W × H Surface depth T Recessed depth T (recessed junction box) Compatible recessed junction boxes

Right of amendment reserved © 2024 Fr. Sauter AG

Recessed mounting Glass front: 86 × 86 mm² Plastic housing: 85 × 85 mm² Max. 15 mm Min. 34 mm (incl. terminals) Swiss and European recessed junction boxes

411


Room automation | Room automation Housing

Colour

Weight

Weight

Glass front

Glass type Glass thickness Surface hardness

F00*: White (similar to RAL 9010) F0A*: Black (similar to RAL 9005) F0*1: 0.190 kg F0*2: 0.200 kg Float glass, chemically hardened sodalime glass 2.9 mm 6H

Standards, directives

CE/UKCA conformity1)

Software class Plastic fire classification Type of protection Protection class Environment class EMC-D 2014/30/EU (CE) EMC-2016 (UKCA)

N

Other applicable legal acts

LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA) Chemicals WEEE

A (EN 60730) UL94V2 IP30 (EN 60529) III (EN 60730) 3K3 (IEC 60721) EN 50491-5-2, EN 50491-5-3 ETSI EN 301 489-1 v.1.9.2 EN 50491-5-2, EN 50491-5-3 ETSI EN 301 489-1 v.1.9.2 EN 62311 EN 62311 ETSI EN 300 328 v2.1.1 ETSI EN 300 328 v2.1.1 EN IEC 63000:2018 EN IEC 63000:2018 REACH Regulation (EC) 1907/2006 WEEE Directive 2012/19/EU

Overview of types Type

Title

EY-RU365F001

ecoUnit365, white, touch, NTC, 6DI

EY-RU365F002

ecoUnit365, white, touch, NTC, 6DI, Bluetooth

EY-RU365F0A1

ecoUnit365, black, touch, NTC, 6DI

EY-RU365F0A2

ecoUnit365, black, touch, NTC, 6DI, Bluetooth

1)

412

Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation

EY-RU 355: Room operating unit, ecoUnit355 Features • Part of the SAUTER modulo system family • Room operating unit for ecos311, ecos504/505, modu680/660-AS, ASV2 and A*M***SA • Local, intuitive operation for temperature, fan and occupancy • Large backlit (BL) display for status information on the room condition • Ergonomic buttons with mechanical, tactile feedback • Individual adjustment of the room climate via temperature detection and setpoint adjustment • Operating mode can be set for room occupancy and actuation of a 3-speed fan

EY-RU355F051

• ECO button for resetting to automatic mode • Multicolour LED indicator for visualisation of energy consumption or as position LED • Sturdy surface of front cover • Fits into standard frame with 55 × 55 mm aperture • Individually assignable buttons with different symbols, can be ordered as accessories • Expandable with EY-SU 358 switching unit for operating lights, window blinds etc. • Frame can be ordered as an accessory • Room operating unit with various functions, designs and colours

N

Technical data Power supply

Power supply

Current consumption

F***: 12...24 VDC, ± 20% (with BL) F0**/A**: 5 VDC, ± 20% (without BL) from ecos 5/ecos311/ASV2: 5 VDC from ecos311: 15 VDC from EY-PS, modu6**-AS, A*M-SA: 24 VDC ≤ 7 mA (at 24 VDC, with BL) ≤ 10 mA (at 15 VDC, with BL) ≤ 9 mA (at 5 VDC, without BL) ≤ 12 mA with 2 x EY-SU 358 (24 VDC)

EY-RU355FA51

Ambient conditions

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C −25...70 °C 10...85% rh, no condensation

Measuring range Resolution Time constant Measuring accuracy Setpoint correction Room occupancy (presence) Fan speeds Position/energy LED Symbols in LCD

0...40 °C 0.1 K 14 min. 0.5 K in 15...35 °C range Can be set and reset; LCD 3 modes; LCD 3 levels, off, automatic; LCD 1; green, red, orange, off; switchable Time/date, air quality, heating/cooling, ECO, different units, state symbols (window, dew point, locked), SAUTER logo (can be hidden)

Activation

ecos 5**, ecos311, modu6*0-AS, ASV215, A*M***SA RS-485

Parameters

Sensor

Functionality

Interfaces, communication

Connection to automation station, controller

Interface

Right of amendment reserved © 2024 Fr. Sauter AG

413


Room automation | Room automation Protocol Line Line length1) Connection terminals

SLC 4-wire, twisted, shielded ≤ 100 m with bus termination Pluggable, for wire of 0.12...0.5 mm² (Ø 0.4...0.8 mm)

Fitting

Recessed/surface-mounted (see accessories) 55 × 55 × 23 mm 0.05 kg F0xx/F1xx: traffic white FAxx/FBxx: jet black F0xx/F1xx: black FAxx/FBxx: white

Construction

Dimensions W × H × D Weight Housing Button printing

Standards, directives

CE/UKCA conformity2)

Type of protection Protection class Environment class EMC-D 2014/30/EU (CE)

IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 EN IEC 63000:2018

EMC-2016 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

N

EN IEC 63000:2018

Overview of types Type

Features

Buttons _ = dummy button, PRA = presence

EY-RU355Fx02

Operating device, LCD, NTC, 0T

No buttons supplied

EY-RU355Fx21

Operating device, LCD, NTC, 2T

+|−|_|_|_

EY-RU355Fx31

Operating device, LCD, NTC, 3T

+ | − | _ | _ | PRA

EY-RU355Fx32

Operating device, LCD, NTC, 3T

+ | − | _ | FAN | _

EY-RU355Fx41

Operating device, LCD, NTC, 4T

+ | − | _ | FAN | PRA

EY-RU355Fx42

Operating device, LCD, NTC, 4T

+ | − | ECO | _ | PRA

EY-RU355Fx51

Operating device, LCD, NTC, 5T

+ | − | ECO | FAN | PRA

EY-RU355Fx52

Operating device, LCD, NTC, 5T

+ | − | UP | DOWN | PRA

EY-RU355Fx53

Operating device, LCD, NTC, 5T

+ | − | UP | DOWN | LIGHT

EY-RU355Fx54

Operating device, LCD, NTC, 5T

+ | − | ECO | FAN | °C/°F

EY-RU355Fx55

Operating device, LCD, NTC, 5T

+ | - | UP | DOWN | FAN

A

All types: x = 0 ≙ traffic white, 5/12...24 VDC x = 1 ≙ traffic white, 12...24 VDC x = A ≙ jet black, 5/12...24 VDC x = B ≙ jet black, 12...24 VDC

Accessories Type

Description

Colour

EY-SU358F021

Push-button unit with 2 button functions

Traffic white

EY-SU358FA21

Push-button unit with 2 button functions

Jet black

EY-SU358F041

Push-button unit with 4 button functions

Traffic white

EY-SU358FA41

Push-button unit with 4 button functions

Jet black

EY-SU358F081

Push-button unit with 8 button functions

Traffic white

EY-SU358FA81

Push-button unit with 8 button functions

Jet black

1) 2)

414

SLC/RS-485 permits a line length of up to 500 m (decentralised supply) Explanation of abbreviations in the “Further information” section of the product data sheet and in the appendix to SAUTER’s product catalogues

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Fitting accessories, spare parts Type

Description

0940240***

For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055

0940240103

Frame, single, recessed, white (RAL9016), 10 pcs.

0940240104

Frame, single, recessed, black (RAL9005), 10 pcs.

0940240703

Mounting plate, single, for recessed fitting (10 pcs.)

0940240203

Frame, double, recessed, white (RAL9016), 10 pcs.

0940240204

Frame, double, recessed, black (RAL9005), 10 pcs.

0940240802

Mounting plate, double, for recessed fitting (10 pcs.)

0940240302

Frame, single, surface-mounted, white (RAL9016), 10 pcs.

0940240303

Frame, single, surface-mounted, black (RAL9005), 10 pcs.

0940240402

Frame, double, surface-mounted, white (RAL9016), 10 pcs.

0940240403

Frame, double, surface-mounted, black (RAL9005), 10 pcs.

094013****

Buttons as accessories/spares, 10 pcs. (see product data sheet 94.055)

0949360004

Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)

0940360005

Terminal RU-SU, push-in, @3P (V,C,DQ), 10 pcs. (accessory for EY-SU 358)

0940360007

Terminal RU-SU, screw, @3P (V,C,DQ), 10 pcs. (optional accessory for EY-SU 358)

0940360006

Terminal and cable RU-SU, @3P (V,C,DQ), 15 cm, 10 pcs. (optional accessory for EY-SU 358)

0940360012

Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)

N

Right of amendment reserved © 2024 Fr. Sauter AG

415


Room automation | Room automation

EY-SU 358: Push-button unit for room operating unit, ecoUnit358 Features • Part of the SAUTER modulo system family • Push-button unit to supplement the ecoUnit355 (EY-RU 355) • Various designs and colour versions in black and white • For controlling window blinds and lighting (on/off, dim) • 2, 4 or 8 button functions • Labelling insert for individual labelling • Fits into frame with 55 × 55 mm aperture

EY-SU358F081

• Frame can be ordered as an accessory

Technical data Power supply

N

Power supply Current consumption

From ecoUnit355 ≤ 2.5 mA (at 24 V= for ROU) ≤ 3 mA (at 15 V= for ROU) ≤ 8.5 mA (at 5 V= for ROU)

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C −25...70 °C 10...85% rh, no condensation

Functionality

Position LED

Connection

Line Length

Labelling

Labelling insert

2; green, red, orange, off; can be connected parallel to EY-RU 355 LED 3-wire (V, C, DQ) ≤ 30 m (can be installed remotely from ecoUnit355) 1 to 3, depending on type; Colour: silver (similar to Pantone 877 C)

Ambient conditions

EY-SU358FA81

Parameters

Construction

Fitting Dimensions W × H × D Weight Buttons

Recessed/surface-mounted (see list of accessories) 55 × 55 × 23 mm 0.04 kg F021: two (dual buttons, dummy buttons) F041: four (dual buttons) F081: eight (single buttons)

Standards, directives

CE conformity according to

416

Type of protection Protection class Environment class EMC Directive 2014/30/EU

IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Overview of types Type

Description

Colour

EY-SU358Fx21

Push-button unit, ecoUnit358, 2T

x=0, traffic white x=A, jet black

EY-SU358Fx41

Push-button unit, ecoUnit358, 4T

x=0, traffic white x=A, jet black

EY-SU358Fx81

Push-button unit, ecoUnit358, 8T

x=0, traffic white x=A, jet black

Accessories Type

Description

0940360005

Terminal RU-SU, push-in, @3P (V,C,DQ), 10 pcs. (accessory for EY-SU 358)

0940360007

Terminal RU-SU, screw, @3P (V,C,DQ), 10 pcs. (optional accessory for EY-SU 358)

0940360006

Terminal and cable RU-SU, @3P (V,C,DQ), 15 cm, 10 pcs. (optional accessory for EY-SU 358)

0940240***

For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055

0940240103

Frame, single, recessed, white (RAL9016), 10 pcs.

0940240104

Frame, single, recessed, black (RAL9005), 10 pcs.

0940240703

Mounting plate, single, for recessed fitting (10 pcs.)

0940240203

Frame, double, recessed, white (RAL9016), 10 pcs.

0940240204

Frame, double, recessed, black (RAL9005), 10 pcs.

0940240802

Mounting plate, double, for recessed fitting (10 pcs.)

0940240302

Frame, single, surface-mounted, white (RAL9016), 10 pcs.

0940240303

Frame, single, surface-mounted, black (RAL9005), 10 pcs.

0940240402

Frame, double, surface-mounted, white (RAL9016), 10 pcs.

0940240403

Frame, double, surface-mounted, black (RAL9005), 10 pcs.

0940001501

Blank foil for EY-SU 358, silver, (10 pcs.)

094013****

Buttons as accessories/spares, 10 pcs. (see product data sheet 94.055)

Right of amendment reserved © 2024 Fr. Sauter AG

N

417


Room automation | Room automation

EY-RU 110: Room sensor, EnOcean, ecoUnit110 Features • Part of the SAUTER modulo system family • Room sensor with integrated digital temperature sensor • Compatible with ecosCom581 and EnOcean interfaces from third-party manufacturers • Battery-free with integrated solar panel • Expandable with ecoUnit106 as additional solar panel supply • Device insert with transparent front, fits into frame with 55 x 55 mm aperture

EY-RU110F201

• Frame can be ordered as an accessory • Frames and foils in many colours and designs possible

Technical data Power supply

Power supply

3 V, from integrated solar panel (external battery operation optional) Min. 250 lux, min. 5 hours daily in 5 of 7 days 60 h of full operation, additional 7 days at least in low power mode

Illuminance Dark period1)

N

Parameters

Technology Frequency Range

Sensor (temperature)

Measuring range Resolution2) Time constant Measuring accuracy, temperature

EnOcean, STM 300 868 MHz band (868.3 MHz) Up to 30 m, depending on building structure (planning recommendation: 10 m) 0…40 °C 0.2 K (hysteresis) Approx. 7 min. Typ. 0.5 K in the 15…35 °C range

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C −25…70 °C 5…85% rh, no condensation

Connection4)

EnOcean Equipment Profile5)

No wiring necessary, teach-in (pairing) with ecosCom581 or ecoMod580 wireless interface via SLC/RS-485 EEP: A5-10-01 (unidirectional)

Weight Dimensions W × H × D Housing Labelling insert

0.05 kg 59.5 × 59.5 × 27.8 mm Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C)

Ambient conditions3)

Interfaces, communication

Construction

1) 2) 3)

4) 5)

418

Bridging time without lighting when the internal energy storage/battery is fully charged Measurement value hysteresis for spontaneous transmission (EnOcean telegram) The device may be active during transport. The device is equipped with a permanently installed lithium cell (energy storage/battery) See quick reference for ecosCom581/ecoMod580 EEP V2.6.8 or higher The ecoUnit110 room sensor currently only supports the temperature value of EEP A5-10-01 and no other EEP as a temperature sensor, such as A5-02-05 (temp. sensor 0...40 °C)

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Fitting

Recessed/surface-mounted (see accessories)

Type of protection Protection class Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RED Directive 2014/53/EU RoHS Directive 2011/65/EU

IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3 EN 60730-1 ETSI EN 300220‑2 (V3.1.1) EN IEC 63000

Standards, directives

CE conformity according to

Overview of types Type

Description

EY-RU110F201

Room sensor, EnOcean, temperature sensor, solar panel

A A

The device is supplied with a silver-coloured labelling insert. Spare inserts: 0940001510 (10 pcs.) Order frame and mounting plate separately (see accessories)

Accessories Type

Description

EY-SU106F100

Push-button unit with solar panel, 6 push-buttons, without frame

0940240***

For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055

0949241301

Transparent cover for EY-RU and EY-SU, 10 pcs.

0949360004

Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)

0940360012

Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)

0949570001

Battery pack, 10 pcs.

0940001510

Labelling insert, foil, silver, without button symbols, 10 pcs.

A

EY‑SU106F100: Can be used as an extended solar panel for the EY-RU110F201 room sensor, but not as a pushbutton unit.

A

0949570001: Suitable as energy supply in permanently darkened rooms.

Right of amendment reserved © 2024 Fr. Sauter AG

N

419


Room automation | Room automation

EY-RU 146: Room operating unit, EnOcean, ecoUnit146 Features • Part of the SAUTER modulo system family • Room operating unit with integrated digital temperature sensor • Bidirectional and compatible with ecosCom581 (EnOcean SMART ACK) • Compatible with EnOcean interfaces of third-party manufacturers • Battery-free with LCD, ecoUnit106 push-button unit can be added • Display with extensive status information on room conditions

EY-RU146F201

• Device insert with transparent front, fits into frame with 55 x 55 mm aperture • Room climate can be adapted individually • Selection of three operating modes for room occupancy • Control of a fan with three speed levels • Control of window blinds, windows and lights (on/off/dim) • Frame can be ordered as an accessory • Frames and foils in many colours and designs possible

Technical data

N

Power supply

Power supply

3 V, from integrated solar panel (external battery operation optional) Min. 250 lux, min. 5 hours daily in 5 of 7 days 50 h of full operation, 60 h all of most important functions, additional 7 days at least in low power mode

Illuminance Dark period1)

Parameters

Technology Frequency Range

Sensor (temperature)

Measuring range Resolution2) Time constant Measuring accuracy, temperature

EnOcean, STM 300 868 MHz band (868.3 MHz) Up to 30 m, depending on building structure (planning recommendation: 10 m) 0…40 °C 0.1 K (display), 0.2 K (hysteresis) Approx. 7 min. Typ. 0.5 K in the 15...35 °C range

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −25…70 °C 5…85% rh, no condensation

Setpoint correction Room occupancy (presence) Fan speeds

Adjustable and resettable 3 modes, LCD 5 functions, LCD

Ambient conditions3)

Function

1) 2) 3)

420

Bridging time without lighting when the internal energy storage/battery is fully charged 0.2 K (hysteresis): Measurement value hysteresis for spontaneous transmission (EnOcean telegram) The device may be active during transport. The device is equipped with a permanently installed lithium cell (energy storage/battery)

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Interfaces, communication

Connection4)

EnOcean Equipment Profile5)

No wiring necessary, teach-in (pairing) with ecosCom581 or ecoMod580 wireless interface via SLC/RS-485 EEP: D2-00-01 (bidirectional, SMART ACK) EEP: A5-10-01 (unidirectional) EEP: F6-03-01 (buttons 3, 4, [7…12 with ecoUnit106])

Construction

Weight Dimensions W × H × D Housing Labelling insert Fitting

0.055 kg 59.5 × 59.5 × 27.8 mm Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C) Recessed/surface-mounted (see accessories)

Type of protection Protection class Environment class EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RED Directive 2014/53/EU RoHS Directive 2011/65/EU

IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3 EN 60730-1 ETSI EN 300220‑2 (V3.1.1) EN IEC 63000

Standards, directives

CE conformity according to

N

Overview of types Type

Description

EY-RU146F201

Room operating unit, EnOcean, LCD, temperature sensor, solar panel, 6 buttons: dXs setpoint correction (+/-), fan, presence, 2 free buttons (window blind/light)

A A

The device is supplied with a silver-coloured labelling insert. Spare inserts: 0940001533 (10 pcs.) Order frame and mounting plate separately (see accessories)

Accessories Type

Description

EY-SU106F100

Push-button unit with solar panel, 6 push-buttons, without frame

0940240***

For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055

0949241301

Transparent cover for EY-RU and EY-SU, 10 pcs.

0949360004

Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)

0940360012

Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)

0949570001

Battery pack, 10 pcs.

0940001511

Labelling insert, foil, silver, (symbols: +, −), 10 pcs.

0940001521

Labelling insert, foil, silver, (symbols: +, −, presence), 10 pcs.

0940001522

Labelling insert, foil, silver, (symbols: +, −, fan), 10 pcs.

0940001523

Labelling insert, foil, silver, (symbols: +, −, presence, fan), 10 pcs.

0940001531

Labelling insert, foil, silver, (symbols: +, −, presence, two lights), 10 pcs.

0940001532

Labelling insert, foil, silver, (symbols: +, −, fan, two lights), 10 pcs.

0940001533

Labelling insert, foil, silver, (symbols: +, −, presence, fan, two lights), 10 pcs.

4) 5)

See quick reference for ecosCom581/ecoMod580 EnOcean Equipment Profile (EEP) V2.6.8 or higher

Right of amendment reserved © 2024 Fr. Sauter AG

421


Room automation | Room automation

EY-SU 106: Push-button unit for EnOcean room operating unit, ecoUnit106 Features • Part of the SAUTER modulo system family • Integrated solar cell for additional solar panel supply of ecoUnit 1 EnOcean devices • Push-button unit to supplement the ecoUnit14* room operating unit • Control of window blinds and lighting (on/off, dim) • Up to six button functions • Device insert with transparent front, fits into frame with 55 x 55 mm aperture

EY-SU106F100

• Frame can be ordered as an accessory • Frames and foils in many colours and designs possible

Technical data Power supply

Power supply1)

Not required

Line Length2)

4-wire ≤1m

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −25…70 °C 10…85% rh, no condensation

Fitting Dimensions W × H × D Weight

Recessed/surface-mounted (see accessories) 59.5 × 59.5 × 27.8 mm 0.047 kg

Type of protection Protection class Environment class EMC Directive 2014/30/EU RoHS Directive 2011/65/EU

IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-3 EN IEC 63000

Parameters

Connection

N

Ambient conditions

Construction

Standards and directives

CE conformity according to

Overview of types Type

Features

EY-SU106F100

Push-button unit with up to 6 button functions, integrated solar cell

Accessories Type

0940240***

For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055

0949241301

Transparent cover for EY-RU and EY-SU, 10 pcs.

0949360004

Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)

0940360012

Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)

0940001541

Labelling insert, foil, silver, (symbols: two lights, two window blinds), 10 pcs.

0940001542

Labelling insert, foil, silver, (symbols: two lights), 10 pcs.

0940001543

Labelling insert, foil, silver, (symbols: two window blinds), 10 pcs.

1) 2)

422

Description

The power supply is provided by the connected device (ecoUnit14* or ecoUnit110) See connection diagram

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation

EY-CM 581: Wireless interface, EnOcean, ecosCom581 Features • Part of the SAUTER modulo system family • Bidirectional wireless communication according to EnOcean (ISO/IEC 14543-3-10) • Internal, optimised wireless antenna (no BNC antenna necessary) • Integration of EnOcean devices: SAUTER ecoUnit110 room sensor and ecoUnit146 room operating unit

and other EnOcean devices from third-party manufacturers Wide-range supply voltage for compatibility with ecos 5 and ecos311 room controllers and modulo 6 • automation stations • RS-485 interface for remote, optimum positioning of the wireless interface in the room • Firmware update via SLC/RS-485

EY-CM581F081

• Device insert with transparent front, fits into frame with 55 x 55 mm aperture • Frame and white cover front can be ordered as accessories • Frames and foils in many colours and designs possible

Technical data Power supply

Power supply

Current consumption

5…24 V DC ±20% ecos 5:+5 V, ecos311:+15 V/+5 V, modulo 6:+24 V 5 V: typ. 36 mA, 68 mA peak 15 V: typ. 14 mA, 24 mA peak 24 V: typ. 10 mA, 17 mA peak

N

Ambient conditions

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C −25…70 °C 5…85% rh, no condensation

Wireless technology Frequency Protocol Range

EnOcean, TCM 300 868 MHz band (868.3 MHz) EnOcean EEP (see EEP list) Up to 30 m, depending on building structure (planning recommendation: 10 m) RS-485, 115.2 kbit/s SLC (SAUTER Local Communication) ecos 5, ecos311, modulo 6 4-wire twisted (shielding, RS-485:line end resistance recommended) ≤ 100 m

Interfaces and communication

Connection to automation station

Interface Protocol Activation Line

Line length Construction

Weight Dimensions W × H × D Housing Labelling insert Fitting

0.07 kg 59.5 × 59.5 × 27.8 mm Pure white (similar to RAL 9010) Silver (similar to Pantone 877 C) Recessed/surface-mounted (see accessories)

Type of protection Protection class Environment class

IP30 (EN 60529) III (EN 60730-1) 3K3 (IEC 60721)

Standards and directives

Right of amendment reserved © 2024 Fr. Sauter AG

423


Room automation | Room automation CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU RED Directive 2014/53/EU RoHS Directive 2011/65/EU

EN 61000-6-1, EN 61000-6-3 EN 60730-1 ETSI EN 300220‑2 (V3.1.1) EN IEC 63000

Overview of types Type

Description

EY-CM581F081

COM module EnOcean, SLC/RS-485, 5...24 V DC, 868 MHz

Accessories Type

Description

0940240***

For frames, mounting plates and adapters for third-party frames, see product data sheet 94.055

0949241301

Transparent cover for EY-RU and EY-SU, 10 pcs.

0949241302

RAL 9010 white cover for EY-CM581, EY-RU and EY-SU (10 pcs.)

0949360004

Push-in terminal RU/SU (for wire), 2 × 10 pcs. 2-pin (01/02, 03/04)

0940360012

Screw terminal RU/SU (optional for stranded cable), 2 × 10 pcs. 2-pin (01/02, 03/04)

N

424

Right of amendment reserved © 2024 Fr. Sauter AG


SAUTER smart sensors Smart

multi-sensors

in

a

mesh

network

for

precise

detection

of

presence/motion, brightness, temperature, humidity, air quality (VOC) and noise levels in rooms or room zones for optimum indoor air and indoor environment quality.

Overview of smart sensors

Type designation Housing colour Sensors Temperature sensor (digital / FIR) Humidity sensor (digital) VOC sensor (air quality, digital) PIR sensor (presence and motion detector) Light sensor Noise level sensor (SL) Display and operation LED ring Push-button, capacitive Interfaces, communication Interfaces Ethernet protocols Bluetooth Mesh profile/model

FMS116F121 Traffic white

FMS116F121A Jet black

FMS196F121 Traffic white

FMS196F121A Jet black

•/• • • • • •

•/• • • • • •

•/• • • • • •

•/• • • • • •

•

•

12 LEDs, RGB colours •

•

Bluetooth Mesh, Bluetooth Beacon, NFC, UART −

Further information

Right of amendment reserved © 2024 Fr. Sauter AG

− Sensor server

Ethernet, Bluetooth Mesh, Bluetooth Beacon, NFC, UART MQTT client, MQTT TCP/TLS Sensor server and client Page 426

425


Room automation | Room automation

FMS 116, 196: Smart Sensor viaSens116/196 Features • Measurement of indoor air quality (IAQ ), such as temperature, humidity and air quality (VOC ) 1)

2)

• Measurement of indoor environment quality (IEQ ), such as motion/presence, brightness and sound 3)

pressure level • Sensor values can be linked together for more precise information on the state of the room (sensor fusion) • For ceiling mounting (recessed/surface-mounted) • Minimal sensor wiring thanks to Bluetooth® 4) mesh network

FMS1*6F121

• Controllable coloured LED ring for displaying the room status to room users • Parameterisable animation profiles for LED ring, e.g. room reserved/available, room air quality good/bad,

room ready for cleaning, etc.) • Bluetooth Beacon function for locating the room user with a smartphone and optimised use of

SAUTER Mobile Building Services (Mobile Room Control app) • Simple integration into the SAUTER automation system with viaSens196 • For up to 16 sensors for an ecos504/505 room controller • Complete commissioning with CASE Suite and Bluetooth smartphone app • Meshing of up to 15 viaSens116 sensors via Bluetooth mesh technology to the viaSens196 sensor

gateway • IoT ready thanks to encrypted MQTT communication in the viaSens196 as an MQTT client

N

FMS1*6F121A

Technical data Power supply

Power supply Current consumption Power consumption

12...34 VDC, typ. 24 VDC Max. 80 mA at 24 VDC Typ. 2 W

Method of measurement Measuring range Resolution Time constant Method of measurement Measuring range Resolution Measuring accuracy6) Emissivity Field of view (FOV) Method of measurement Measuring range Resolution Measuring accuracy Time constant Method of measurement Measuring range Resolution Time constant

CMOS technology (SHT40) 0…40 °C 0.1 K Approx. 8 s (dew 63%) Far infrared (MLX) 15…40 °C 0.1 K ±1 K 0...100%, parameterisable 50° CMOS technology (SHT40) 0...100%, typ. 20...80% rh 1% ±2% in 10…90% range at 25 °C. Approx. 8 s (dew 63%) CMOS technology (SGP40) 1…500 VOC index 1 VOC index < 10 s (dew 63%)

Parameters5)

Temperature (TDIG)

Temperature (TFIR)

Relative humidity (HUM)

Volatile compound gases (VOC)

1) 2) 3) 4) 5) 6)

426

IAQ: indoor air quality VOC: volatile organic compounds IEQ: indoor environment quality The Bluetooth® word mark and logos are registered trademarks of Bluetooth SIG, Inc. For explanations, see the “Abbreviations (sensor types and functions)” list Thermal objects can affect the measuring accuracy

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Motion, presence (PIR)

Brightness (LUX)

Sound pressure level (SPL)

Technology

Method of measurement Detection range7)

Field of view (FOV) Fresnel lens Method of measurement Measuring range Resolution Field of view (FOV) Measuring range Frequency spectrum Filter type Sensitivity Processor

Four-element IR detector (PYQ) Ø 9 m and approx. 8 × 8 m area at 2.5 m fitting height, 360° tangential and radial 120° 34 zones Digital light sensor (APDS) 0…16 000 lux 1 lux 140° 0...120 dB(A) 60…20 000 Hz A weighting −26 dB on the measuring range, ±1 dB tolerance Dual-Core ARM Cortex, 32-bit, 240 MHz

Ambient conditions

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −25…70 °C 10…80% rh, no condensation

Indicator/display8)

LED ring with 12 LEDs, RGB colours (red, green, blue; 24 bit) Configurable animation profiles with 16 predefined colours Identification, service menu, restart, factory reset (front)

Display and operation

Push-button, capacitive

N

Interfaces, communication

Bluetooth mesh

Network Radio frequency Range9) Bluetooth mesh profile

Localisation Ethernet (FMS 196)

Ethernet network 10/100 BASE-T(X) Communication protocol NFC (near field communication) Slide switch10) Serial port WiFi (802.11 a/b/g/n)

Bluetooth mesh node (2.4 GHz), up to 8 TTL hops 2.4 GHz (5 dBm) Up to 10 m FMS 116: Bluetooth mesh relay node, sensor-node (sensor server model, V1.0) FMS 196: Bluetooth mesh, sensor gateway (sensor server + client model, V1.0) Bluetooth beacon (iBeacon), indoor position determination 1 × RJ-45 connector 10/100 Mbit/s MQTT client V3.1.1/V5, MQTT(S), TLS V1.2, WS(S) (ISO/IEC 20922) Product data and configuration parameters (De)activation of sound pressure level (rear) UART for firmware update (point to point), 3.3 V TTL WLAN client deactivated, can be temporarily activated for firmware update with app

7)

As per IEC 63180:2020 Example application: Presence: LED ring off/blue, room climate / air quality: LED ring green/red 9) Depending on building and room structure; planning recommendation: max. 10 m between two Bluetooth mesh nodes 10) Switching only takes effect when the power is off 8)

Right of amendment reserved © 2024 Fr. Sauter AG

427


Room automation | Room automation Construction

Surface Ø × D: 103 × 30 mm Recessed Ø × D: min. 50 × 35 mm Thermoplastic (PC, PC-ABS) Recessed, surface and hollow ceiling mounting 2.5…3.5 m (ceiling)

Dimensions11) Housing material Fitting12) Fitting height Standards, directives

CE/UKCA conformity13)

Type of protection Protection class Environment class Plastic fire classification EMC-D 2014/30/EU (CE)

IP20 (EN 60730) III 3K3 (IEC 60721) UL94 EN 301489 (EMC for radio equipment) EN 60730-1 (residential premises) See EMC Directive EN 60730-1, EN 62311 EN 60730-1, EN 62311 ETSI EN 300 328 (V2.2.2), 2.4 GHz band ETSI EN 300 328 (V2.2.2), 2.4 GHz band EN IEC 63000

EMC-2016 (UKCA) LV-D 2014/35/EU (CE) EESR-2016 (UKCA) RED 2014/53/EU (CE) RER-2017 (UKCA) RoHS-D 2011/65/EU & 2015/863/EU (CE) RoHS-2012 (UKCA)

N

EN IEC 63000

Overview of types Type

Description

Weight

Housing

FMS116F121

Smart sensor, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL

0.2 kg

Traffic white (ws)

FMS116F121A

Smart sensor, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL

0.2 kg

Jet black (sw)

FMS196F121

Smart sensor, MQTT/ETH, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL

0.3 kg

Traffic white (ws)

FMS196F121A

Smart sensor, MQTT/ETH, Bluetooth mesh, TDIG, TFIR, HUM, VOC, PIR, LUX, SPL

0.3 kg

Jet black (sw)

A

FMS196F121(A) has the same sensor characteristics as FMS116F121(A). The additional Ethernet interface is used as a sensor gateway for the Bluetooth mesh network and for integrating the sensor network in the automation system with MQTT via TCP/TCP+TLS (MQTT/MQTTS) or via web socket (WS/WSS)

A

Housing: matt, traffic white similar to RAL 9016, jet black similar to RAL 9005

Abbreviations (sensor types and functions) FOV HUM LUX MQTT/ETH PIR SPL TDIG TFIR VOC

Field of view Measurement of relative humidity with digital measuring element Measurement of illuminance Ethernet interface for MQTT Motion and presence detection with passive infrared sensor Measurement of sound pressure level Temperature measurement with digital measuring element Temperature measurement with far infrared temperature element Measurement of volatile organic compounds

11)

For dimensions of accessories, see fitting instructions Recessed mounting with box at least 45 mm deep for FMS 116 and at least 61 mm deep for FMS 196 (Ethernet cable bending radius). Mounting in hollow ceiling with spring clamps, at ceiling thickness 2…20 mm hole diameter 68 mm; at 20…25 mm hole diameter 75 mm. Surface mounting with box 28 mm deep for FMS 116 and 53 mm deep for FMS 196 13) Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in the appendix to SAUTER product catalogues 12)

428

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Accessories Type

Delivery quantity

Description

0940241101

1 pcs.

Mounting plate, recessed, white

0940241101A

1 pcs.

Mounting plate, recessed, black

0940241110

Set of 10

Mounting plate, recessed, white

0940241110A

Set of 10

Mounting plate, recessed, black

0940241201

1 pcs.

Mounting plate, surface, 53 mm, white

0940241201A

1 pcs.

Mounting plate, surface, 53 mm, black

0940241210

Set of 10

Mounting plate, surface, 53 mm, white

0940241210A

Set of 10

Mounting plate, surface, 53 mm, black

0940241301

1 pcs.

Mounting plate, surface, 28 mm, white

0940241301A

1 pcs.

Mounting plate, surface, 28 mm, black

0940241310

Set of 10

Mounting plate, surface, 28 mm, white

0940241310A

Set of 10

Mounting plate, surface, 28 mm, black

0940241420

2 sets of 10

Mounting spring, false ceiling

0940241510

Set of 10

PIR orifice plate, 180° angle (half), white

0940241510A

Set of 10

PIR orifice plate, 180° angle (half), black

0949360014

Set of 10

Terminal, 2-pin, push-in, @2×2P (green)

A

The sensors are supplied without mounting accessories. Accessory 0949360014 for power supply connection is supplied

N

Right of amendment reserved © 2024 Fr. Sauter AG

429


SAUTER ecos remote I/O modules The SAUTER ecoLink modules are remote modules for flexibly expanding the I/O mix of the ecos504/505 and modulo 6 automation stations. The modules are used to capture digital and analogue signals from sensors and HVAC installations. They control valve actuators, dampers, fans, dimmable lamps or sunshade actuators. The remote fitting reduces the wiring needed for the sensors and actuators.

Overview of remote I/O modules

Type designation Product name Power supply Inputs/outputs Universal inputs 0-10 V / digital inputs Ni1000/Pt1000 inputs DIM-10 V outputs Normally-open relay contacts Changeover relay contacts Triac Analogue outputs Further information

430

EY-EM510F001 ecoLink510 24 VAC

EY-EM511F001 ecoLink511 24 VAC

EY-EM512F001 ecoLink512 24 VAC

− 4 2 − 3 − 3 3 Page 432

− 4 2 − − − 3 3 Page 432

− 4 − − − − 2 3 Page 432

Right of amendment reserved © 2024 Fr. Sauter AG


Type designation Product name Power supply Inputs/outputs Universal inputs 0-10 V/digital inputs Ni1000/Pt1000 inputs DIM-10 V outputs Normally-open relay contacts Changeover relay contacts Triac 24 VDC MOS-FET 24 VAC/DC Analogue outputs Further information

Type designation Product name Power supply Inputs/outputs Universal inputs 0-10 V/digital inputs Ni1000/Pt1000 inputs Digital/meter inputs DIM-10 V outputs Normally-open relay contacts Changeover relay contacts Triac Analogue outputs Further information

EY-EM514F001 ecoLink514 24 VAC/DC

EY-EM515F001 ecoLink515 24 VAC/DC

4 − − − 4 − − 6 4 Page 434

4 − − − − − − 6 4 Page 434

EY-EM522F001 ecoLink522 230 VAC

EY-EM523F001 ecoLink523 230 VAC

EY-EM527F001 ecoLink527 230 VAC

4 − − − 4 4 − − 4 Page 436

4 − − − 4 − − − 4 Page 436

4 − − 4 − 4 − − − Page 438

Right of amendment reserved © 2024 Fr. Sauter AG

431


Room automation | Room automation

EY-EM 510...512: Remote I/O module, ecoLink510...512 Features • Part of the SAUTER modulo 5 system family • Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

engineering • Remote I/O module for ecos504/505 • Communicative connection of actuators to automation stations

EY-EM510F001

• Can be located up to 500 m from automation stations

Technical data Power supply

Power supply Current consumption

Dissipated power

24 VAC, ±20%, 50...60 Hz ≤ 0.2 A, without load current from Triac and relay outputs ≤ 6.6 VA Triac outputs not under load, ≤ 48 VA Triac outputs with rated load ≤ 5 W (typically approx. 0.5 W)

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C –25...70 °C 10...85% rh, no condensation

Analogue/digital inputs Ni1000/Pt1000-Eingänge Relay outputs

Type Type Type Load1)

0...10 V/O-I -20...100 °C 0-I, normally-open contacts 230 VAC, 5 A (total max. 10 A)

Switching frequency Triac outputs Analogue outputs

Type Type

> 3 × 105 cycles 0-I, 24 V~/0.5 A 0...10 V, 2 mA

Activation Interface Protocol Line Line length2)

From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination

Dimensions W × H × D Weight

105 × 95 × 60 mm 0.22 kg

Type of protection3) Protection class

IP00 (EN 60529) II (EN 60730-1) for EY-EM 510, III (EN 60730-1) for EY-EM 511, EY-EM 512 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1

Power consumption

Ambient conditions

N Inputs/outputs

Interfaces and communication

Construction

Standards and directives

CE conformity according to

Environment class EMC Directive 2014/30/EU4) Low-Voltage Directive 2014/35/EU

1) 2) 3) 4)

432

See the section “Digital outputs (relays)” See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted EN 61000-6-2: In order to meet the European Standard, the power cables for the inputs and outputs must not exceed 30 metres in length

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Overview of types Type

Description

EY-EM510F001

Remote I/O module, 24 V~, 3 relays, 3 Triacs

EY-EM511F001

Remote I/O module, 24 V~, 3 Triacs

EY-EM512F001

Remote I/O module, 24 V~, 2 Triacs

Overview of I/O mix Relay Triac 0...10 V Out Ni1000/Pt1000 0...10 V In, Digital In

EY-EM 510 3 3 3 2 4

EY-EM 511 0 3 3 2 4

EY-EM 512 0 2 2 0 4

Accessories Type

Description

0949360003

Plug-in connector for ecoLink RS-485, 10 pcs.

0900240020

Terminal cover

0450573001

Transformer 230 VAC / 24 VAC, 42 VA; for DIN rail 35 mm, dimensions: 78 × 74 × 52 mm (W×H×D)

N

Right of amendment reserved © 2024 Fr. Sauter AG

433


Room automation | Room automation

EY-EM 514, 515: Remote I/O module, ecoLink514, 515 Features • Part of the SAUTER modulo 5 system family • Remote I/O module for ecos504/505 • Communicative, digital connection of actuators and sensors to automation stations • Activation of actuators for heated/chilled ceilings, recirculated air and fan coil units, and window blinds

EY-EM514F001

• Inputs for presence detectors, temperature sensors, analogue sensors and window contacts • Can be located up to 500 m from automation stations

Technical data Power supply

Power supply

Dissipated power

24 VAC, ±20%, 50...60 Hz 24 VDC, ±10% Max. 150 mA Without load current of DO (relay, FET) Plus up to 0.5 A / FET Max. 2 W (typically 1.2 W)

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C –25...70 °C 10...85% rh, no condensation

Type Load

0-I relay, normally-open contacts 24...250 V 5 A resistive load Total max. 10 A

Switching frequency

Current consumption

EY-EM515F001 Ambient conditions

N Inputs/outputs

Relay outputs

Semiconductor outputs (FET)

Type

Analogue outputs Universal inputs

Type Analogue Digital Resistance Potentiometer Ni1000/Pt1000

> 3 × 105 cycles 0-I, 24 VAC/DC, 0.5 A, connected to ground max. peak current 1 A at 20 ms 0...10 V/2 mA 0...10 V / 0...1 V 0-I 100...2500 Ω 1...10 kΩ -20...100 °C

Activation Interface Protocol Line Line length1)

From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination

Dimensions W × H × D

105 × 95 × 60 mm

Type of protection2) Protection class

IP00 (EN 60529) II (EN 60730-1) for EY-EM 514 III (EN 60730-1) for EY-EM 515 3K3 (IEC 60721)

Interfaces, communication

Connection to automation station

Construction

Standards, directives

Environment class

1) 2)

434

See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1 (EY-EM 514 only)

Overview of types Type

Description

Weight

EY-EM514F001

Remote I/O module, 24 V~/=, 4 relays, 6 DO FET, 4 AO, 4 UI

270 g

EY-EM515F001

Remote I/O module, 24 V~/=, 6 DO FET, 4 AO, 4 UI

220 g

Overview of I/O mix Normally-open relay contacts Semiconductor FET switch (connected to ground) Analogue outputs Universal inputs

EY-EM 514 4 6 4 4

EY-EM 515 – 6 4 4

Accessories Type

Description

0949360003

Plug-in connector for ecoLink RS-485, 10 pcs.

0900240020

Terminal cover

0450573001

Transformer 230 VAC / 24 VAC, 42 VA; for DIN rail 35 mm, dimensions: 78 × 74 × 52 mm (W×H×D)

Right of amendment reserved © 2024 Fr. Sauter AG

N

435


Room automation | Room automation

EY-EM 522, 523: Remote I/O module, ecoLink522, 523 Features • Part of the SAUTER modulo 5 system family • Remote I/O module for ecos504/505 • Switching and dimming of up to four lamps • Can be located up to 500 m from the automation station

EY-EM522F001

Technical data Power supply

Power supply Current consumption Dissipated power

230 VAC ±10%, 50...60 Hz Max. 20 mA (typically 14 mA) Without load current of relays Max. 2.5 W (typically 1.5 W)

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C –25...70 °C 10...85% rh, no condensation

Type

0-I relay, NO contacts 230 VAC with voltage applied 230 VAC / 5 A resistive load Total max. 10 A

Ambient conditions

EY-EM523F001 Inputs/outputs

N

Relay outputs

Load Switching frequency DIM-10V outputs

Type

Analogue outputs Universal inputs

Type Analogue Digital Resistance Potentiometer Ni1000/Pt1000

> 3 × 105 cycles 1...10 V passive output for electronic ballasts as per EN 60929 Electrically isolated 0...10 V / 2 mA 0...10 V / 0...1 V O-I 100…2500 Ω 1...10 kΩ -20...100 °C

Activation Interface Protocol Line Line length1)

From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination

Dimensions W × H × D Weight

105 × 95 × 60 mm 0.32 kg

Type of protection2) Protection class Environment class EMC Directive 2014/30/EU3)

IP00 (EN 60529) II (EN 60730-1) 3K3 (IEC 60721) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1

Interfaces and communication

Connection to automation station

Construction

Standards and directives

CE conformity according to

Low-Voltage Directive 2014/35/EU 1) 2) 3)

436

See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted EN 61000-6-2: In order to meet the European Standard, the power cables for the inputs and outputs must not exceed 30 m in length

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation Overview of types Type

Description

EY-EM522F001

Remote I/O module, 230 V~, 4 normally-open relay contacts, 4 DIM outputs

EY-EM523F001

Remote I/O module, 230 V~, 4 DIM outputs

Overview of I/O mix Normally-open relay contacts (with voltage applied) DIM-10V Analogue outputs Universal inputs

EY-EM 522 4 4 4 4

EY-EM 523 4 4 4

Accessories Type

Description

0949360003

Plug-in connector for ecoLink RS-485, 10 pcs.

0900240020

Terminal cover

N

Right of amendment reserved © 2024 Fr. Sauter AG

437


Room automation | Room automation

EY-EM 527: Remote I/O module, ecoLink527 Features • Part of the SAUTER modulo 5 system family • Remote I/O module for ecos504/505 • Communicative, digital connection of actuators and sensors to automation stations • Controlling ventilation dampers, motorised windows and blinds

EY-EM527F001

• Inputs for positional feedback, presence detectors, window contacts • Universal inputs for temperature measurement, 0-10 V signals, potentiometer • Meter inputs for recording energy pulses up to 10 Hz • Can be located up to 500 m from automation stations

Technical data Power supply

Power supply Current consumption Dissipated power

230 VAC ±10%, 50...60 Hz Max. 15 mA Without load current of relays Max. 2.5 W (typically 1.5 W)

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C –25...70 °C 10...85% rh, no condensation

Type Load

0-I relay, normally-open contacts 24...250 VAC 5 A resistive load Total max. 10 A

Switching frequency Analogue Digital Resistance Potentiometer Ni1000/Pt1000 Digital Meter

> 3 × 105 cycles 0...10 V / 0...1 V 0-I 100...2500 Ω 1...10 kΩ -20...100 °C 0-I 10 Hz (pulse duration 50 ms)

Activation Interface Protocol Line Line length1)

From ecos504/505 RS-485 SLC 4-wire, twisted, shielded Up to 500 m with bus termination

Dimensions W × H × D Weight

105 × 95 × 60 mm 0.35 kg

Type of protection2) Protection class Environment class

IP00 (EN 60529) II (EN 60730-1) 3K3 (IEC 60721)

Ambient conditions

N

Inputs/outputs

Relay outputs

Universal inputs

Digital inputs

Interfaces and communication

Connection to automation station

Construction

Standards and directives

1) 2)

438

See the section “Engineering notes” IP20 with terminal cover (accessory 0900240020); IP40 at front when fitted

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation CE conformity according to

EMC Directive 2014/30/EU Low-Voltage Directive 2014/35/EU

EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 EN 60730-1

Overview of types Type

Description

EY-EM527F001

Remote I/O module, 230 V~, 4 normally-open relay contacts, 4 universal and 4 digital inputs

Overview of I/O mix Normally-open relay contacts Universal inputs Digital inputs / meter inputs (10 Hz)

EY-EM 527 4 4 4

Accessories Type

Description

0949360003

Plug-in connector for ecoLink RS-485, 10 pcs.

0900240020

Terminal cover

N

Right of amendment reserved © 2024 Fr. Sauter AG

439


SAUTER modulo power supply units Efficient switched-mode power supply units for supplying power to automation stations, I/O modules and field devices in building automation. Optimal for use with the SAUTER ecos and modulo 6 system families. • Variable input voltage • Output protected against short circuit • Flat DIN-rail housing for small distribution box

Overview of power supply units

Type designation Nominal rating Nominal current Efficiency Dimensions W × H × D Weight Further information

440

EY-PS031F011 30 W 1.25 A Typ. 86.5% 36 × 94 × 68 mm 0.13 kg Page 441

EY-PS031F021 60 W 2.5 A Typ. 91.7% 52.5 × 95 × 68 mm 0.21 kg Page 441

EY-PS031F041 100 W 4.16 A Typ. 92.1% 72 × 93 × 68 mm 0.24 kg Page 441

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | Room automation

EY-PS 031: Power supply, DIN rail, 230 V / 24 VDC Features • Optimum power supply for the SAUTER modulo and ecos system families and the SAUTER field devices • Modern, efficient switching power supply with quasi-resonant flyback converter principle • High efficiency and minimum idle power (standby) • Variable input voltage • Controlled output voltage with tolerance of ± 3% with mains voltage fluctuations of ± 10% • Output short-circuit proof with HICCUP mode, without overshoot when switching on

EY-PS031F011

• Compact DIN rail housing ideal for DIN rail mounting in standard small distribution boxes or cabinets • High reliability

Technical data Power supply

Input voltage (SELV)

110…240 VAC, 45…65 Hz

Operating temperature Storage and transport temperature Ambient humidity

−10…50 °C −40…85 °C 0…95% rh, no condensation

Output voltage Setting range Overload behaviour1) LED indicator

24 VDC ± 3% 24…28 VDC HICCUP mode Green (device ready for operation)

Connection terminals

Screw terminals 0.5...2.5 mm2 rigid/flexible DIN rail as per EN 60715 Type TH 35 × 7.5/15 DIN rail housing DIN 43880

Ambient conditions

EY-PS031F021

N

Output

Construction

Fitting

EY-PS031F041

Standards, directives

CE conformity according to

Type of protection Protection class EMC Directive 2014/30/EU

Low-Voltage Directive 2014/35/EU RoHS-D 2011/65/EU & 2015/863/EU (CE)

1)

IP20 (EN 60529) II (EN 60730-1) EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 61000-6-3, EN 55032 Class B, EN 55035 EN 62368-1, EN 60335 EN IEC 63000

HICCUP: Halt or inhibit on overcurrent and overvoltage protection

Right of amendment reserved © 2024 Fr. Sauter AG

441


Room automation | Room automation Overview of types Type

Nominal rating Nominal cur- Efficiency rent

Dimensions W × H × D

Weight

EY-PS031F011

30 W

36 (2 HP) × 94 × 68 mm

130 g

EY-PS031F021 EY-PS031F041

A

86.5%

60 W

2.5 A

91.7%

52.5 (3 HP) × 95 × 68 mm

210 g

100 W

4.16 A

92.1%

72 (4 HP) × 93 × 68 mm

240 g

1 HP = one horizontal pitch with 17.5 mm

Type EY-PS031F011 EY-PS031F021 EY-PS031F041

A

1.25 A

Manufacturer/supplier's original type designation: Comatec® PSH series PSH02P03024AGEB PSH03C06024AGEB PSH04P10024AGEB

The original data sheets from Comatec Hi-Tech S.r.l., www.comatec-hitech.com, are legally binding

N

442

Right of amendment reserved © 2024 Fr. Sauter AG


SAUTER communication modules The devices of the SAUTER moduNet series enable the novaNet bus system to be integrated into parent IT networks. A direct Ethernet interface and an RS-232 serial port are provided for this purpose.

Overview of communication modules

Type designation Product name Property Fitting Further information

EY-BU292F001 moduNet292 Connection of novaNet to Ethernet/IP Cabinet model Page 444

Right of amendment reserved © 2024 Fr. Sauter AG

EYZ291F001 novaNet291 Router Cabinet model Page 446

443


Room automation | HVAC automation

EY-BU 292: novaNet-Ethernet interface, moduNet292 Features • Part of the SAUTER EY-modulo 2 system family • Bus access device for novaNet system bus with Ethernet interface • To integrate novaNet stations (EY3600, EY-modulo 2) into IP networks based on Ethernet (LAN/WAN) • For SAUTER CASE Suite applications • To download programmes onto the stations

EY-BU292F001

• For SAUTER novaPro visualisations • For remote monitoring via the internet • TCP/IP communication • Communication with two-wire novaNet system bus • RJ-45 plug for Ethernet 10 Base-T (10 Mbit/s) • Fixed IP addressing • RS-232 interface for parameterisation and updating • Five LEDs for Error, novaNet Send, Power, Activity, Link

Technical data

N

Power supply

Power supply Power consumption

230 V~, +10%, –15% 115 V~, +10%, –15% (50...60 Hz) 6 VA, < 7 W

Operating temperature Storage and transport temperature Ambient humidity

0...45 °C (32...113 °F) –25...70 °C (–13...158 °F) 10...85% rh, no condensation

Ethernet

TCP/IP address Subnet mask TCP port (App 1) TCP port (App 2)

1 × RJ-45 socket 10 Mbit/s (10 Base-T) 1 × DB-9 (male) as per DTE (57k6, 8n1) 192.168.10.20 255.255.255.0 51806 (nova292-Server) 51807 (nova291-Emulation)

Fitting

DIN rail mounting

Type of protection Protection class Software class EMC Directive 2014/30/EU

IP00 (EN 60529); IP20 (EN 60529) I (EN 60730-1) EN 60730-1 Appendix H EN 61000-6-1, EN61000-6-2, EN 61000-6-4 EN 60950-1

Ambient conditions

Interfaces, communication

RS-232 serial port Standard settings

Construction

Standards, directives

CE conformity according to

Low-Voltage Directive 2014/35/EU

Overview of types

444

Type

Description

Dimensions W × H × D novaNet

Weight

EY-BU292F001

panel-fitted model

193 × 131 × 41 mm

650 g

1 × a/b terminal

Right of amendment reserved © 2024 Fr. Sauter AG


Room automation | HVAC automation Accessories Software Type

Description

GZS100F599

CASE Tools CD, latest version (CASE TPC, CASE HWC, CASE Sun, novaNet292 SW etc.)

Connecting cables Type

Description

0367862001

novaNet RJ-11 to RJ-11: 1.5 m

0367862002

novaNet RJ-11 to RJ-11: 2.9 m

0367862003

novaNet RJ-11 to RJ-11: 6.0 m

0367842002

Ethernet RJ-45 to RJ-45: 1.5 m

0367842003

Ethernet RJ-45 to RJ-45: 2.9 m

0367842004

Ethernet RJ-45 to RJ-45: 6.0 m

0386507001

Ethernet crossover RJ-45 to RJ-45: 3.0 m

General Type

Description

0374509001

Connector, 3-pin, packaged

0010240105

Cable housing for 0374509 001, cable cord grip

0374677001

Installation kit for 2-DIN rail mounting

N

Right of amendment reserved © 2024 Fr. Sauter AG

445


Room automation | HVAC automation

EYZ 291: Router, novaNet291 Features • Part of the EY-modulo 2 and EY3600 system family • Bus access device for novaNet system bus with RS-232 interface • For configuring EY-modulo 2 and EY3600 stations with SAUTER CASE applications • For management-level software and all SAUTER novaPro visualisations and novaNet OPC servers • Direct communication from novaNet stations to PC with a serial connection

EYZ291F001

• Remote access with router function via RS-232 modem • Remote monitoring in routel mode via RS-232 modem (i.e. automatic uploading of events) • Communication using two-wire novaNet system bus • Communication with RS-232-compatible pairs of devices (dial-up modem, ISDN adapter, electronic surge

protector, OWG converter, wireless modem etc.) • 1 MB buffer for separating the time characteristics of novaNet and RS-232 interface Technical data Power supply

N

Power supply Max. current consumption

230 V~, 50/60 Hz 10 VA

Operating temperature Storage and transport temperature Humidity

0...45 °C (32...113 °F) –25...70 °C (–13...158 °F) 10…90% rh, no condensation

COM port (DTE) novaNet DIP switch

DB9 plug 1 × a/b terminal, 1 × RJ-11 socket 4 (baud rate, router/routel function)

Weight

0.99 kg (2.2 lb)

Ambient conditions

Interfaces and communication

Construction

Standards and directives

CE conformity according to

Type of protection EMC Directive 2014/30/EU

EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4

Overview of types Type

Description

EYZ291F001

novaNet router

Accessories

446

Type

Description

0367862001

Connecting cable to novaNet291 or moduNet292 automation station 1.5 m (4.9 ft)

0367862002

Connecting cable to novaNet291 or moduNet292 automation station 2.9 m (9.5 ft)

0367862003

Connecting cable to novaNet291 or moduNet292 automation station 6.0 m (19.7 ft)

Right of amendment reserved © 2024 Fr. Sauter AG


Right of amendment reserved © 2024 Fr. Sauter AG

447


Management level

Building and energy management at any time, from anywhere. SAUTER Vision Center ensures optimum system monitoring and continuous operation. Energy management and maintenance modules offer additional benefits for facility management to ensure energy-efficient operation. SAUTER Mobile Building Services (MBS) is a SAUTER Cloud solution which is used in numerous applications for buildings and premises. Room conditions can be controlled in combination with the Mobile Room Control (MRC) app. SAUTER Digital Services allow secure remote access to plants, continuous analysis of buildings and access to key data. 448

Right of amendment reserved © 2024 Fr. Sauter AG


Management level Software YZP 480...495: SAUTER Vision Center

450

YCS 200...210: Mobile Building Services (MBS)

452

YCS 320…325: Vision Services

454

YCS 451...453: Digital Services – Remote Management

455

YCS451F001: Remote Management connector

456

>

Right of amendment reserved © 2024 Fr. Sauter AG

449


Management level | Software

YZP 480...495: SAUTER Vision Center Central building management and visualisation of decentralised installations SAUTER Vision Center (SVC) is a web-based building management and integration platform in the HTML5 standard for running and visualising the building operation. SVC is suitable for both single buildings and entire real estate parks or distributed premises. Typical areas of use are office complexes, business parks, college and industrial campuses, airports, railway stations, hospitals or internationally distributed branch networks. The modular concept allows the software to be extended precisely to meet the customer requirements of every installation. Therefore, SVC gathers all of the data for the entire building and energy management and makes it available to the user from anywhere at all times. In the energy monitoring, meters and other information can be mapped, thus making daily, weekly, monthly and yearly consumption from the plants, buildings and properties automatically available. Specific energy widgets, KPIs and energy labels and other dashboard widgets are used to display the energy values and consumption. Since version 7, a powerful building analytics and energy management module (AEM) has been integrated in SVC, which already contained all the energy monitoring functions. In addition, with chart types such as scatter and carpet plots, but also SANKEY and histogram displays with calculations of the Gaussian distribution, analytic tools are available to carry out energy inspections, to optimise systems in transition phases such as spring and autumn, for example, and thus to meet energy and CO2 reduction requirements, as demanded for companies in the context of certifications in accordance with ISO 50001. The additional online analytics integrated in the AEM enables immediate information in dashboards as KPIs (traffic lights, circular or linear gauge etc.) or alarm messages in the event of abnormal plant operation. In this way, deviations from operating patterns and setpoints, as well as oscillations, are detected automatically and in real time. The maintenance module for SVC is used for optimum planning and efficient performance of servicing and facility management tasks. Here, support is also provided by plant asset management, the definition of maintenance intervals and the automatic triggering of maintenance cycles based on building management information. With energy monitoring, energy management and the building analytics and maintenance modules, SVC provides comprehensive information and tools to ensure continuous and constantly optimised and thus efficient and sustainable plant and building operation.

>

Thanks to SVC’s simple and intuitive operation, starting, planning and changing predefined building automation procedures is easy with the scenario manager. This allows users with PC skills to set rooms, for example, to Comfort or ECO mode at precise times, and to plan and log them via calendar views. For the integration of different equipment systems, SVC supports the manufacturer-independent BACnet standard, as well as connection to OPC UA servers, for integrating different protocols in the building automation. Thus, SVC is the first building and energy management system (BEMS) certified with a crossplatform profile B-XAWS 1.18. SVC supports device profiles B-AWS, B-ALWS, B-ACCWS and thus profile B-XAWS. As of SVC 7.1, the BACnet/SC protocol is also supported. It enables the encryption of the data traffic based on certificates. Ideally, this ensures a secure connection from local sites via BACnet/SC routers to Vision Services (SVC in the cloud) with full BACnet functionality. In addition to the OPC UA client, operation as an OPC UA server is also implemented. Furthermore, an IoT client is integrated that supports the connection of room controllers and automation stations via MQTT. TLS encryption ensures secure communication from decentralised automation stations, e.g. to connect SAUTER ecos or modulo 6 stations via the internet with an SVC located in the cloud. Direct connection of moduWeb Vision via web services and SAUTER novaNet plants via OPC is available for comprehensive support of the integration options. This makes it possible to connect existing systems when converting to the new generation of building management software without having to replace the existing automation level. SVC sends alarms directly via e-mail or SMS to mobile phones according to the responsibilities assigned. With its many user-defined settings and customisable dashboards, SVC guarantees maximum user convenience. SVC can be deployed in virtual IT environments and uses Microsoft SQL databases. These modern architectures and infrastructures enable topics such as high availability, redundancy via cluster systems and

450

Right of amendment reserved © 2024 Fr. Sauter AG


Management level | Software corresponding load assignments (load balancing) to be implemented and used.1) For optimum integration of the user structures of a company, it is possible to connect SVC to an existing LDAP server that additionally supports the latest communication types (LDAP signing & channel binding). Overview of types

/

SVC licences and options

Type

Description

YZP480F000

Provision of all codes in a single ticket

YZP480F098

Latest SVC version on a USB stick

YZP480F200

Basic licence for 500 addresses with maintenance

YZP481F200

Additional 100 objects with maintenance

YZP481F210

Additional 1000 objects with maintenance

YZP481F220

Additional 10000 objects with maintenance

YZP481F230

Additional 25000 objects with maintenance

YZP482F101

Termination of the software maintenance

YZP482F210

Resumption of the software maintenance

YZP483F300

novaNet connection (YZP487F201 is a prerequisite)

YZP484F200

Licence key for VM

YZP484F310

Migration Manager for SVC from nP32 and nPO

YZP484F400

Vision Center Studio

YZP485F201

Energy monitoring with maintenance

YZP485F203

Analytics and energy management with maintenance

YZP485F210

Maintenance module with software maintenance

YZP485F220

Scenario manager with software maintenance

YZP485F230

Touch panel server with 5 clients

YZP485F231

Additional 5 touch panel clients

YZP485F240

Reports and designer

YZP486F205

Upgrade from energy monitoring to analytics and energy management

YZP487F201

OPC UA client for SVC with maintenance

YZP487F203

OPC UA server with maintenance

YZP487F205

SVC MQTT client with maintenance (price per MQTT broker connection)

0900360001

Hardlock (dongle) for VM

1)

>

Scalable via MS SQL Express up to SQL Enterprise depending on the specified properties, virtual IT environments and high-availability VMware & SQL Enterprise.

Right of amendment reserved © 2024 Fr. Sauter AG

451


Management level | Software

YCS 200...210: Mobile Building Services (MBS) Features • Connects the local building management, including the integral room automation, with the room operation

via smartphone or tablet Control of lighting, temperature, window blinds and ventilation (depending on the building equipment) • • Direct access to information such as caretaker services, cafeteria schedule and other information • Direct notification from the MRC app of caretaker services and other services such as comfort notifications,

repair and cleaning requests, meeting room beverage orders, hotel and boarding house service requests • Reservations for meeting rooms, mobile workstations, parking spaces or equipment items (assets) • E-mail invitations including reservations directly from the MRC app • Guest invitations: Sending temporary access codes for the agreed meeting period • Integrated Indoor Navigation for employees and guests via MRC app • Access and rights management via unique access codes for each device based on user profiles and

dedicated room assignments • Room identification and user access via iBeacon badges for smartphones and tablets (iOS and Android) • Perfect for use in office buildings with meeting rooms and mobile workstations, hotels with business

facilities, suites and rooms, as well as upscale apartment buildings • High level of security and up-to-date functionality thanks to Microsoft Azure technology • MRC app available free of charge in the Google Play Store and the Apple App Store

Overview of types

>

452

Type

Description

YCS200F300

MRC app subscription per apartment (1-5 access codes per apartment), price per apartment per year, annual subscription based on monthly use of the master access code per apartment, invoice date 1 year after project activation by basic subscription, automatically renewed

YCS200F320

MRC app subscription (without indoor localisation), price per device (badge) per room, annual subscription based on monthly use of access codes (badges), invoice date 1 year after project activation by basic subscription, automatically renewed

YCS210F300

MRC app subscription (with indoor localisation via iBeacon), price per device (badge) including access profile for rooms, annual subscription based on monthly use of access codes (badges), invoice date 1 year after project activation by basic subscription, automatically renewed

YCS200F200

MBS Cloud Basic subscription for up to 50 rooms/apartments, annual subscription with automatic renewal

YCS200F210

MBS Cloud Basic subscription for up to 150 rooms/apartments, annual subscription with automatic renewal

YCS200F220

MBS Cloud Basic subscription for up to 300 rooms/apartments, annual subscription with automatic renewal

YCS200F230

MBS Cloud Basic subscription for up to 500 rooms/apartments, annual subscription with automatic renewal

YCS200F240

MBS Cloud Basic subscription for up to 1000 rooms/apartments, annual subscription with automatic renewal

YCS210F200

MBS Cloud Basic subscription for office with indoor localisation for up to 50 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes

YCS210F210

MBS Cloud Basic subscription for office with indoor localisation for up to 150 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes

YCS210F220

MBS Cloud Basic subscription for office with indoor localisation for up to 300 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes

YCS210F230

MBS Cloud Basic subscription for office with indoor localisation for up to 500 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes

YCS210F240

MBS Cloud Basic subscription for office with indoor localisation for up to 1000 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes

YCS210F250

MBS Cloud Basic subscription for office with indoor localisation for over 1000 iBeacons, annual subscription with automatic renewal to use YCS210F300 access codes

YCS211F200

MBS Cloud Booking option, subscription per MS Exchange Online

YCS220F200

MBS Cloud Indoor Navigation option, subscription for up to 100 iBeacons

YCS220F210

MBS Cloud Indoor Navigation option subscription for up to 200 iBeacons

Right of amendment reserved © 2024 Fr. Sauter AG


Management level | Software Type

Description

YCS220F220

MBS Cloud Indoor Navigation option subscription for up to 300 iBeacons

YCS220F230

MBS Cloud Indoor Navigation option subscription for up to 500 iBeacons

YCS220F240

MBS Cloud Indoor Navigation option subscription for up to 1000 iBeacons

YCS221F000

RTLS engineering support for Indoor Navigation per day excl. expenses for on-site work

>

Right of amendment reserved © 2024 Fr. Sauter AG

453


Management level | Software

YCS 320…325: Vision Services Vision Services: Powerful, efficient energy and building management from the cloud SAUTER Vision Services are comprehensive, powerful modules from the SAUTER Cloud for energy monitoring, building management and energy management and analytics. The centralised approach of cloud operation means that the latest functions and extensions are always available for all building and energy management applications, without the need for time-consuming installations and migrations. Additionally, it saves the investment costs in hardware and software and shifts these investments and their support to the cloud. IoT clients are used to securely transfer local energy and automation data by means of the MQTT protocol with TLS encryption. Features • Vision Services Energy Monitoring with dashboards, diagrams, energy navigation, meter overview with

correction and offset functions for meter replacement, alarms, reports and data import and export management • Vision Services Building with dashboards, diagrams, alarms, object lists, scenario manager, reports and export function • Vision Services Energy Management & Analytics with additional diagrams for energy and plant analysis such as SANKEY, carpet & scatter plots. Histogram plots with Gaussian distribution function and analytics functions for automatic detection of operating pattern deviations, setpoint deviations and oscillations. All Vision Services Energy Monitoring functions are included. All Vision Services can be booked individually or in combination. For example, Vision Services Energy can be used to operate dedicated monitoring in the cloud that runs independently of the local building management. However, complete building and energy management with analytics from the cloud can also be booked as a subscription.

>

Overview of types

454

Type

Description

YCS320F200

Vision Services Building, subscription incl. 1 admin & 1 standard user, 1 MQTT client

YCS321F200

Vision Services Energy Monitoring, subscription incl. 1 admin & 1 standard user, 1 MQTT client

YCS321F210

Vision Services Energy Management & Analytics, subscription incl. 1 admin & 1 standard user, 1 MQTT client

YCS324F200

Object package 50 from 0...500

YCS324F201

Object package 100 from 500...1000

YCS324F202

Object package 100 from 1000

YCS324F220

Additional standard user

YCS325F010

Cloud Connection Service (project & user set-up) incl.1 MQTT connection

YCS325F020

Additional MQTT connection per device

YCS325F400

Cancellation of project subscription; no option of single item cancellation

Right of amendment reserved © 2024 Fr. Sauter AG


Management level | Software

YCS 451...453: Digital Services – Remote Management Features • Secure access to decentralised systems and applications • Two-factor authentication via e-mail or SMS • Fully transparent and secure network connection via browser and Windows client • Remote access: • To applications such as SAUTER Vision Center or moduWeb Unity (via http/https) • To PCs and servers and their applications (via RDP/VNC) • Via VPN tunnel (Layer 2):

The local PC appears in the remote network structure (use of all engineering and network tools from the local PC in the remote system) • Rights administration with user and group management for the assignment of rights for individual systems and buildings, right up to distributed properties Overview of types Type

Description

YCS451F010

G100 Remote Management connector with 2 Ethernet ports, incl. pre-installed OS and VPN licence

YCS451F002

3G/4G option for YCS451F001 (Huawei e3372 modem)

YCS452F200

Remote Management basic connector subscription incl. 5 secured connections

YCS452F210

Remote Management connector subscription, additional 5-pack of secured connections

YCS452F220

Remote Management connector subscription, 5-pack of time-limited, unauthenticated links

YCS453F200

End user subscription, access to all predefined connections via dashboard and Windows client

YCS453F203

End user + 1 VPN channel subscription, access to all pre-defined connections via dashboard and Windows client, incl. VPN tunnel (layer 2 and 3)

YCS453F210

Engineering user subscription with full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client

YCS453F220

Admin user subscription, full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client, incl. user & group management

A

The term of the connector subscription (YCS452F2**) is 12 months with automatic renewal. YCS452F200 must be ordered together with the universal gateway.

A

The user subscriptions (YCS453F2**) of the SAUTER Cloud for Remote Management are monthly subscriptions with automatic monthly renewal.

Right of amendment reserved © 2024 Fr. Sauter AG

>

455


Management level | Software

YCS451F001: Remote Management connector Features • VPN gateway for SAUTER Digital Services – Remote Management • Integrated web server for configuration and monitoring • MicroSD, USB, watchdog, LED indicator • Painted aluminium DIN rail housing as per DIN 43880

Technical data Power supply

Power supply

12...24 V=, 2 A

Connection Battery (buffer: RTC)

Screw terminals, plug-in terminal block CR2032, backup for up to 7 days

Operating temperature Storage and transport temperature Ambient humidity

0…45 °C −20…70 °C 10…80% rh, no condensation

Web server VPN/access point DHCP, DNS services

Yes (Node.js, V 7.8.x) Yes (Open SSL, L2TP) Yes, IPv4 and IPv6

Processor RAM (memory) Memory

H3 Quad-Core Cortex-A7 1 GB (Low Power DDR2) microSDHC, 64 GB included, includes OS and software USB up to 64 GB Embedded Linux (on SD card)

Parameters

Ambient conditions

Function

>

Architecture

Operating system Interfaces, communication

Ethernet/LAN

Ethernet network

Wireless

Transmission rate WLAN

1 × RJ45 connector, 10/100 BASET(X) 10/100 Mbit/s 3 × USB type C (for accessory YCS451F002)

Construction

Fitting

On metal DIN rail 35 × 7.5/15 as per EN 60715 71 (4 HP) × 102 × 62 mm 300 g

Dimensions W × H × D Weight

Overview of types Type

Description

YCS451F001

SAUTER Remote Management connector – universal gateway, incl. pre-installed OS and VPN licence

A

The device can only be ordered together with a connector subscription, see accessories.

Accessories

456

Type

Description

YCS451F002

3G/4G option for YCS451F001 (Huawei e3372 modem)

YCS452F200

Remote Management basic connector subscription incl. 5 secured connections

Right of amendment reserved © 2024 Fr. Sauter AG


Management level | Software Type

Description

YCS452F210

Remote Management connector subscription, additional 5-pack of secured connections

YCS452F220

Remote Management connector subscription, 5-pack of time-limited, unauthenticated links

YCS453F200

End user subscription, access to all predefined connections via dashboard and Windows client

YCS453F210

Engineering user subscription with full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client

YCS453F220

Admin user subscription, full access to all protocols incl. VPN tunnel connection (layer 2) and Windows client, incl. user & group management

A

The term of the connector subscription (YCS452F2**) is 12 months with automatic renewal. YCS452F200 must be ordered together with the universal gateway.

A

The user subscriptions (YCS453F2**) of the SAUTER Cloud for Remote Management are monthly subscriptions with automatic monthly renewal.

Related documents Document number D100471121 D100471122 D100471123

Type Datenblatt Data sheet Données techniques

Language de en fr

Title Remote Management Remote Management Remote Management

>

Right of amendment reserved © 2024 Fr. Sauter AG

457


Engineering tools

Project engineering made easy. SAUTER CASE Suite is used to carry out the technical project processing for both building management systems and conventional control systems. Energy-efficient strategies and methods are already incorporated in the extensive and proven library. CASE Suite is also highly flexible when it comes to adapting solutions to special circumstances, so that even very unusual customer installations can be efficiently operated in terms of energy. 458

Right of amendment reserved © 2024 Fr. Sauter AG


Engineering tools Engineering GZS 100, 150: CASE Suite

460

_

Right of amendment reserved © 2024 Fr. Sauter AG

459


Engineering tools | Engineering

GZS 100, 150: CASE Suite Features • Supports the whole process of a project, from the planning stage to the engineering, commissioning and

servicing phases • ‘Nerve centre’ for the project data and software programs GZS 100, 150

• Seamless integration of the solution libraries • Safeguards the workflow between the specialist sub-programs (CASE Builder, CASE Engine, CASE Vision) • Planning and documentation of the system technology • Commercial and technical project processing • Creates the regulation, control and optimisation functions • Puts the automation stations into service • Based on the Microsoft Windows operating system • Multi-lingual program (German, English and French) • Licence is required for full use of the program

Technical data System requirements

Hardware

Processor Clock rate RAM memory

Intel I7 (recommended) 2.4 GHz or higher Min. 8 GB RAM – recommended 16 GB RAM Min. 20 GB free memory space USB (operating the VM licence dongle, program installation from USB stick), network Windows 10 Pro (x64) or higher, web browser, MS IIS (Internet Information Services) installed MS Office 2010 (32-bit) or higher Graphics program [CorelDRAW Graphics Suite]

Storage capacity Connections

_

Operating system

Software1)

Additional software2)

Overview of types

/

All licences delivered without CASE Suite application software

Type

Description

Running time

GZS150F010

CASE Suite Enterprise licence with maintenance [annual fees]

Unlimited

GZS150F011

CASE Suite Enterprise licence, excluding maintenance

Unlimited

GZS150F020

CASE Suite Enterprise time licence

365 days from activation

GZS150F021

CASE Suite Partner time licence

365 days from activation

GZS150F022

CASE Suite Designer time licence

365 days from activation

GZS100F699

CASE Suite, current software version on data carrier

–

Accessories Type

Description

0900360001

Hardlock VM

1) 2)

460

Compatible versions on request. To be able to use all the functions of CASE Suite Enterprise, we recommend installing the following software.

Right of amendment reserved © 2024 Fr. Sauter AG


Abbreviations used The following abbreviations are used in the technical data under “Standards, directives”:

ATEX-D ATEX-2016 CAN/CSA CE PED EAC EESR-2016 EMC-D EMC-2016 Machinery-D LVD PESR-2016 RED RER-2017 RoHS-D RoHS-2012 SMSR-2008 TÜV UKCA UL WEEE-D WEEE-2013

Explosive Atmospheres Directive 2014/34/EU Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres Regulations 2016 (UK) Standards and norms of the Canadian CSA Group Manufacturer's Declaration of Conformity for the European Union (EU) Pressure Equipment Directive 2014/68/EU Eurasian Conformity (Customs Union of Russia, Belarus, Kazakhstan, Armenia and Kyrgyzstan) Electrical Equipment (Safety) Regulations 2016 (UK) Electromagnetic Compatibility Directive 2014/30/EU Electromagnetic Compatibility Regulations 2016 (UK) Machinery Directive 2006/42/EC Low Voltage Directive 2014/35/EU Pressure Equipment (Safety) Regulations 2016 (UK) Radio Equipment Directive 2014/53/EU Radio Equipment Regulations 2017 (UK) Restriction of Hazardous Substances in Electrical and Electronic Equipment Directives 2011/65/EU & 2015/863/EU Restriction of Hazardous Substances (RoHS) Regulations 2012 (UK) Supply of Machinery (Safety) Regulations 2008 (UK) Technical Inspection Association (technical safety inspection with certificate) Manufacturer’s Declaration of Conformity for the United Kingdom of Great Britain and Northern Ireland (UK) Underwriters Laboratories (organisation for testing products, components, materials) Waste Electrical and Electronic Equipment Directive 2012/19/EU Waste Electrical and Electronic Equipment Regulations 2013 (UK)

Right of amendment reserved © 2024 Fr. Sauter AG

1 461


Alphabetical list of contents Type

Description

Page

Thermowells

22

Thermowells

58

Power and connecting cables for Smart Actuator

142

ADM 322

Rotary actuator

329

ADM 322S

Rotary actuator

331

AKF 112, 113

Rotary actuator

317

AKF 113S

Rotary actuator

318

AKM 105, 115

Rotary actuator

311

AKM 115S F132

Rotary actuator

313

AKM 115S F152

High-speed rotary actuator

315

AKM 115SA

Smart Actuator for ball valve

131

ASF 112, 113

Damper actuator

346

ASF 113S

Damper actuator

348

ASF 122, 123

Damper actuator

350

ASF 123S

Damper actuator

352

ASM 105, 115

Damper actuator

334

ASM 105S, 115S F132

Damper actuator, SUT

336

Type

Description

Page

AXT 301, 311

Thermal actuator for unit valves with stroke indicator

163

B2KL

6-way ball valve with male thread, PN 16

307

B6R

3-way valve (el.), PN 16

186

BKLI

3-way changeover ball valve with female thread, PN 40

297

BKR

3-way regulating ball valve, PN 40

286

BKRA

3-way regulating ball valve with male thread, PN 40

289

BKTA

3-way changeover ball valve, PN 40

303

BKTI

3-way changeover ball valve, PN 40

300

BQD

3-way flanged valve, PN 6 (el.)

197

BQE

3-way flanged valve, PN 16 (el.)

209

BUD

3-way flanged valve, PN 6 (el.)

194

BUE

3-way flanged valve, PN 16/10 (el.)

205

BUG

3-way flanged valve, PN 25/16 (el.)

216

BUL

3-way unit valve, PN 16

149

BUN

3-way valve, PN 16

180

BUS

3-way flanged valve, PN 40 (el.)

225

BUT

3-way unit valve, PN 16 (el.)

156

ASM 105S, 115S F152

High-speed damper actuator, SUT

338

BXL

3-way unit valve, PN 16

159

ASM 115SA

Smart Actuator for ventilation dampers

137

DEF

Tight-sealing butterfly valve

324

ASM 124

Damper actuator

340

DFC 17B, 27B

Pressure switches

36

ASM 124S, 134S

Damper actuator, SUT

344

DSA

Pressure switches

30

ASM 134

Damper actuator

342

DSB, DSF

Pressure monitors and pressure switches

32

ASV 215BF152*

VAV compact controller for laboratory and pharmaceutical applications

121

DSD

Differential pressure switch

38

DSDU, DSDI

Differential pressure transmitter

86

ASV205BF132E, ASV215BF132E

VAV compact controller

118

DSL, DSH

Pressure limiters

34

AVF 124

Valve actuator

252

DSU, DSI:

Pressure transmitters

84

AVF 125S

SUT valve actuator

254

EGE 112

Duct transducer, enthalpy

76

AVF 234S

SUT valve actuator

256

EGH 103

Dew point monitor

78

AVM 105S, 115S

SUT valve actuator

232

EGH 102

Dew point monitor and transducer

77

AVM 215

Valve actuator

234

EGH 110...112

Duct transducer, relative humidity and temperature

75

AVM 322-R

Retrofit actuator

244

AVM 322S-R

Retrofit actuator

246

EGH 120, 130

Room transducer, relative humidity and temperature, surface-mounted

73

AVM 105, 115

Valve actuator

230

AVM 115SA

Smart Actuator for 2- and 3-way valves

134

EGH 681

Room transducer, relative humidity and temperature, recessed

74

AVM 215S

SUT valve actuator

236

EGP 100

Differential pressure transmitter

80

EGQ 110

Duct transducer, air quality (VOC), temperature

70

EGQ 120

Room transducer, air quality, surface-mounted

66

EGQ 212

Duct transducer, CO2 and temperature

68

EGQ 220, 222

Room transducer, CO2, surface-mounted

64

EGQ 281

Room transducer, CO2, recessed

67

EGS 100

Radiation temperature sensor

62

Cable temperature sensors

54

Room temperature sensor, surface-mounted

49

AVM 234S

SUT valve actuator

249

AVM 321, 322

Valve actuator

238

AVM 321S, 322S

SUT valve actuator

241

AVN 224S

SUT valve actuator

259

AXF 217S

Motorised actuator for unit valves with positioner

169

AXM 217

Motorised actuator for unit valves

171

AXM 217S

Motorised actuator for unit valves with positioner

172

EGT 353...356, 456, 554, 654

AXS 315S

Continuous thermal actuator for unit valves with stroke indicator

166

EGT 130, 330, 332, 335, 430

EGT 301, 401, 601 Outdoor temperature sensor

462

52

Right of amendment reserved © 2024 Fr. Sauter AG


Type

Description

Page

Type

Description

Page

EY-SU 358

Push-button unit for room operating unit, ecoUnit358

416

EYZ 291

Router, novaNet291

446

FCCP 200

Fume cupboard indicator and monitor

124

FMS 116, 196

Smart Sensor viaSens116/196

426

EGT 311, 411, 611 Clamp-on temperature sensors

60

EGT 346...348, 392, 446, 447, 646, 647

Duct temperature sensor

56

EGT 386, 388, 486, 686, 688

Room temperature sensors, recessed

51

Heating controller with digital user interface, equitherm

FXV 3***

Electrical distributor

101

EQJW 126

106

Electric distributor for control signals

103

EQJW 146

Heating and district heating controller, equitherm

FXV 33** EasySwitch

108

GZS 100, 150

CASE Suite

460

EQJW 246

Heating and district heating controller, equitherm

111

HBC

Duct-mounted humidistat

43

HSC 101

Panel-mounted humidistat

42

EY6AS60

modular BACnet automation station, modu660-AS

361

EY6AS80

modular BACnet automation station and web server, modu680-AS

EY6CM20

HSC 120

Room humidistat

41

M3R, M4R

Control valve

320

357

MH32F, MH42F

Control valve

322

Modbus/RTU (RS‑485) communication module, modu620‑CM

389

NRFC 413, 422… 424

Modbus fan coil thermostat

93

EY6CM30

M-Bus communication module, modu630‑CM

391

RDT 405, 410

115

EY6IO30

16 x DI/CI inputs I/O module, modu630-IO

373

Electronic controller for simple applications, flexotron400

8 x UI (DI/CI/AI) and 8 x DI/CI I/O module, modu631-IO

SAIO 100

I/O module for smart actuators

140

EY6IO31

375

SGU 100

Sash sensor

88

EY6IO50

6 x relay (2A) outputs I/O module, modu650-IO

377

SVU 100

Air-flow transducer

83

TFL 201

Frost monitor/limiter with capillary sensor

25

EY6IO70

8 x DI/CI/DO (OC) and 8 x DI/CI I/O module

379

TFL 611

Continuous frost monitor

27

EY6IO71

8 x AO and 8 x DI/CI I/O module, modu671-IO

381

TRA 410, 421

Electronic room thermostat for heating and heating/cooling with display

97

EY6IO72

4 × AO, 4 × DO(OC), 4 × UI (DI/CI/AI) I/O module, modu672-IO

383

TRT 317, 327

Electronic room thermostat for heating and heating/cooling

99

Module for separated I/O module supply, modu601-LC

TSHK 621...643

Fan-coil room temperature controller

13

EY6LC01

366

TSHK 670...672

Fan-coil room temperature controller

15

Coupling kit for I/O modules in cabinet, modu602-LC

TSHK 681, 682

Fan-coil room temperature controller

17

EY6LC02

368

TSO, TSH

Room thermostats

11

EY6LC12

IP coupler for I/O modules with web server, modu612‑LC

370

TUC

Universal thermostat

20

Operating and indicating unit for I/O modules, modu600-LO

UVC 106

264

EY6LO00

386

Dynamic flow control system with 6-way ball valve, eValveco

BACnet router and SC hub, B/IP <-> B/SC, modu630-RT

394

UVC102MF065… 100

Dynamic flow control system with 2-way valve and energy monitoring, eValveco

266

EY6RT30

V6R

2-way valve (el.), PN 16

183

EY-BU 292

novaNet-Ethernet interface, moduNet292

444

EY-CM 581

Wireless interface, EnOcean, ecosCom581

423

VDL 010…050

2-way regulating valve, PN 25, Valveco compact

269

EY-EM 510...512

Remote I/O module, ecoLink510...512

432

VDL 050...100

274

EY-EM 522, 523

Remote I/O module, ecoLink522, 523

436

2-way regulating valve, PN 16, Valveco flange

EY-EM 527

Remote I/O module, ecoLink527

438

VKAA

294

EY-EM 514, 515

Remote I/O module, ecoLink514, 515

434

2-way cut-off ball valve with female thread, PN 40

EY-PS 031

Power supply, DIN rail, 230 V / 24 VDC

441

VKAI

2-way cut-off ball valve with female thread, PN 40

292

EY-RC 311

Room controller, ecos311

404

VKR

2-way regulating ball valve, PN 40

278

EY-RC 504/505

Room automation station, ecos504/505

399

EY-RU 310...316

Room operating unit, ecoUnit310...316

408

VKRA

2-way regulating ball valve with male thread, PN 40

282

EY-RU 110

Room sensor, ecoUnit110

418

VQD

2-way flanged valve, PN 6 (el.)

192

EY-RU 146

Room operating unit, EnOcean, ecoUnit146

420

VQE

2-way flanged valve, PN 16 (el.)

203

2-way flanged valve (el.)

189

EY-RU 355

Room operating unit, ecoUnit355

413

VUD

EY-RU 365

Touch room operating unit

410

VUE

2-way flanged valve, PN 16/10 (el.)

199

VUG

2-way flanged valve, PN 25/16 (el.)

212

VUL

2-way valves, PN 16

146

VUN

2-way valve with male thread, PN 16

177

EY-SU 106

Push-button unit for EnOcean room operating unit, ecoUnit106

Right of amendment reserved © 2024 Fr. Sauter AG

422

463


Type

Description

Page

VUP

Pressure-relieved 2-way flanged valve, PN 25 (el.)

220

VUS

2-way flanged valve, PN 40 (el.)

222

VUT

2-way valve, PN 16

154

XAFP 100

Flow probe

82

YCS 200…210

Mobile Building Services (MBS)

452

YCS 320...325

Vision Services

454

YCS 451...453

Digital Services – Remote Management

455

YCS451F001

Remote Management connector

456

YZP 480…495

SAUTER Vision Center

450

464

Right of amendment reserved © 2024 Fr. Sauter AG


D100523338

2024

Systems Components Services Facility Services

SAUTER – your local partner. www.sauter-controls.com

Right of amendments reserved © 2024 Fr. Sauter AG

Catalogue Product and Systems Information


Turn static files into dynamic content formats.

Create a flipbook