Instruction Manual Supplement
DVC6000/DVC6200 Digital Valve Controllers
D103261X012
February 2011
Supplement to Fisherr FIELDVUEt DVC6000 or DVC6200 Digital Valve Controller Instruction Manuals Implementation of LockâinâLast Strategy Many applications require a valve assembly to remain in the position it was prior to a specific control system failure (lockâinâlast position). Functionality and safety can be designed into valve assemblies with FIELDVUE digital valve controllers by utilizing an array of accessories. The following paragraphs describe standard solutions for a number of generic lockâinâlast applications with DVC6000 or DVC6200 digital valve controllers.
Note This instruction manual supplement is for use with HARTr communicating FIELDVUE DVC6000 or DVC6200 digital valve controllers only.
LockâinâLast on Loss of Supply Pressure Once the supply pressure falls below a minimum value, the digital valve controller can no longer position a valve assembly; the valve will start to go to the actuator âat restâ position. The locking device senses this change and activates, preventing the remaining air from venting. The valve is âlockedâinâ this new position.
Note The lockedâin valve position depends on the exhausting speed of the actuator.
Assemblies with SingleâActing Actuators A Fisher 164A threeâway switching valve should be used for locking a singleâacting actuator in place on loss of supply pressure. Figure 1 is a schematic representing proper assembly layout. In normal operation, the digital valve controller output passes through the switching valve from port A to port B and on to the actuator.