Skip to main content

Elimination and Identification of Harmonic Pollution by Active Compensation Scheme in Radial Syste

Page 1

International Journal of Electrical and Electronics Research ISSN 2348-6988 (online) Vol. 8, Issue 2, pp: (14-22), Month: April - June 2020, Available at: www.researchpublish.com

Elimination and Identification of Harmonic Pollution by Active Compensation Scheme in Radial System Daniel Manoj Nethala1, Sunil Kumar.V2, Dr.P.Santosh Kumar Patra3 1,2

Assistant Professor, 3Principal & Professor in CSE

St.Martin’s Engineering College, Secunderabad, Telangana, India.

Abstract: This paper proposes an appropriated active compensation method for eliminating the harmonic pollution in a distribution network. The proposed distributive active compensation scheme covers a number of multi active component filter units that were started at the same area or various areas within the power systems. Optimum positioning of Active compensation stays on dragging in momentous observation, in view of the strong effect on power efficiency and advancement of semiconductor power devices by users. Active filter channel innovation is the most productive approach to repay and counteract the voltage distortions hailing from nonlinear loads and this Numerous Distributive Active Compensation (NDAC) worked as a shunt compensation scheme from the congregation of nonlinear loads, so the ensuring collective voltage drawn from the ac source is sinusoidal. Droop housing in between the harmonized conductance and the volt-ampere (VA) of the AFU is modified into the controller of each one unit, so diverse AFUs can communicate the workload of harmonic minimization without any correspondences. The compensation process is focused around idea of PQ theory. This proposed numerous distributive active compensation schemes is tested on 9-bus radial as well as non-radial distribution systems is verified and simulated through MATLAB-SIMULINK environment. Keywords: Distributive active compensation scheme, Active filter units, Power quality, Harmonic Pollution, Total Harmonic Distortion (THD).

I. INTRODUCTION Evolution of dispersed generation and deregulated electricity markets will force electric utilities to be more concerned about power-quality (PQ) problems, especially harmonics. There are various sources of harmonic pollution in the power network with nonlinear loads and dispersed generators that use power-conditioning units as the main sources. Identifying the source of harmonic pollution is the first step toward improving the PQ of the network. A great number of nonlinear loads like adjustable speed drives and static power switches including those of higher capacity ground the power quality strife. The Power Quality is the combination of voltage quality and current quality [1].One of the major power quality issue that affects the end user is harmonics. The total and individual voltage harmonic distortions are limited to 5% and 3% respectively as per the guideline given by IEEE 519-1992 standard [2]. Nonlinear loads are continuously increasing. Harmonics have become an important power quality problem because of the increased distortion levels in the power system as a result of an increasing number of harmonic producing loads [3, 4]. The main effects of harmonics in power systems are heating, overloading, aging of equipment, increased losses and system unbalancing. Harmonics may lead to malfunctioning of power system components and electronic devices. Relays and measurement equipment may function erroneously under non-sinusoidal voltage and currents. These harmonics can be mitigated by adopting various mitigation techniques including passive and active filtering techniques. Among these, passive filters are adopted often since it is easy to install and less cost. Various types of passive filters have been proposed to mitigate the harmonics along radial distribution system (RDS) [5]. Resonance is the major problem occurring due to the incorporation of passive filters along a radial distribution system. The recent manifestation

Page | 14 Research Publish Journals


Turn static files into dynamic content formats.

Create a flipbook
Elimination and Identification of Harmonic Pollution by Active Compensation Scheme in Radial Syste by Research Publish Journals - Issuu