Thank you for choosing Alpha Home &Commercial Building Inspection

This Inspection Report is supplemental to the Property Disclosure Statement. It is the responsibility of the Client to obtain any and all disclosure forms relative to this real estate transaction. This inspection does not include testing for radon in air, pest, private septic systems, lawn irrigation, portable hot tubs, swimming pools, fire suppression, low voltage systems, alarm systems or home automation, central vacuum systems, laundry equipment, water quality, mold or other hazardous materials unless specifically requested. The client may wish to have additional testing or inspections performed by a qualified professional on these or other items that are not covered by this inspection as outlined by the State of NH Standards of Practice. This report supercedes any alleged verbal comments.

The recommendations in this report should be completed DURING YOUR INSPECTION CONTINGENCY PERIOD AND PRIOR TO CLOSING by qualified, licensed specialists, who may identify additional defects or recommend some upgrades that could affect your evaluation of the property.

This report is based on the State of NH Home Inspection Standards of Practice. Click below to view https://alphabuildinginspections.com/blog/chapter-home-600-standards-of-practice/

Per our standards of practice we will report those systems and components inspected that in the professional opinion of the inspector are not functioning properly, significantly defficient , unsafe or near the end of service life.

A home inspection is intended to assist in evaluation of the overall condition of the dwelling. The inspection is based on observation of the visible and apparent condition of the structure and its components on the date of the inspection and not the prediction of future conditions. Material defects that are hidden or located at inaccessible areas or non observable areas are excluded. A home inspection will not reveal every concern that exists or ever could exist, but only those material defects observed on the day of the inspection. Conditions in the home can change from the time of inspection to the time of closing.

A material defect is a condition with a residential real property or any portion of it that would have a significant adverse impact on the value of the real property or that involves an unreasonable risk to people on the property. The fact that a structural element, system or subsystem is near, at or beyond the end of the normal useful life of such a structural element, system or subsystem is not by itself a material defect

Comments in BLUE below, indicate a condition that should either be monitored closely, assessed or be repaired by a qualified contractor .

USE OF PHOTOS AND VIDEO:

Your report includes many photographs which help to clarify where the inspector went, what was looked at, and the condition of a system or component at the time of the inspection. Some of the pictures may be of deficiencies or problem areas, these are to help you better understand what is documented in this report and may allow you to see areas or items that you normally would not see. A pictured issue does not necessarily mean that the issue was limited to that area only,but may be a representation of a condition that is in multiple places. Not all areas of deficiencies or conditions will be supported with photos. To view videos in the report the PDF needs to be downloaded and viewed with a full PDF reader such as Adobe.

A home inspection is not an insurance policy protecting against all present or future deficiencies that may or may not have been observable at the time of inspection. The client may wish to buy a home warranty.

See link for warranty providers https://alphabuildinginspections.com/blog/home-warranty-companies/

Although a home inspection cannot determine how long any particular system will last we have provided information regarding the Estimated Life Expectancies of Home Systems at: https://alphabuildinginspections.com/blog/life-expectancy-of-home-components/

Report Summary

Report Summary

The summary below consists of potentially significant findings. These findings can be a safety hazard, a deficiency requiring further assesment and repairs or items I would like to draw extra attention to.

All of the summary items should be addressed prior to closing on the property. The summary is not a complete listing of all the findings in the report, and reflects the opinion of the inspector. Please review all of the pages of the report as the summary alone does not explain all the issues. All repairs should be done by a licensed &bonded tradesman or professional. I recommend obtaining a copy of all receipts, warranties and permits for the work done. See photo sections for location and details of report comments.

Exterior Areas

Page 14 Item: 3 Window Condition

Page 15 Item: 5 Deck / Porch

3.2. Deterioration to window, frame and or trim. Recommend full assessment of windows and repairs by a qualified contractor as needed.

5.4. Broken or missing balusters at guard rails. Recommend repairs by a qualified tradesman.

5.5. One or more support joists are missing properly installed mechanical hangers. Recommend installation and proper nailing of joist hangers by a qualified contractor.

5.6. Guardrails are loose and/or damaged. This is a safety hazard. Recommend assessment by a qualified contractor.

Garage

Page 24 Item: 1 Walls / Ceilings

Page 26 Item: 4 Garage Door's Reverse Status

1.4. Stains at one or more area of the garage ceilings and or walls. This is evidence of past or present leaks. They tested dry at the time of the inspection. Recommend monitoring for further water intrusion, taking measures to divert water as needed, asking current home-owner for the source and history of any leaks or water intrusion and assessment and repairs of any stained area by a qualified tradesman.

4.2. No eye beam system present at one or more over head door. This is an important safety device to prevent injury to children. Under Writers laboratory now requires all UL Rated overhead doors to have an auto reverse device for safety. Recommend assessment by a qualified over head door contractor.

Page 27 Item: 5 Floor Condition

Page 28 Item: 2 Structure

5.2. Rodent activity observed in the garage. Vermin can damage insulation & electrical wiring. Recommend a professional pest contractor evaluate for treatment.

2.2. Stains were found in one or more surfaces that tested or appeared to be dry. The stain(s) may be due to past or present roof and/or plumbing leaks. Recommend asking the property owner(s) about this, and monitoring the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, a qualified contractor should evaluate and repair areas as necessary.

Page 32 Item: 3 Insulation Condition

Foundation

Page 35 Item: 2 Under Floor Framing

Electrical

Page 38 Item: 3 Electric Panel Condition

3.2. Animal droppings or activity observed in the attic. Vermin can damage insulation & electrical wiring. We do not identify the droppings. If squirrels or bats are present it can be more difficult and costly to treat. When animal droppings are observed a qualified pest company should always assess. Recommend a professional pest contractor evaluate for treatment.

2.2. Water staining on framing at one or more area, tested dry at time of inspection. Recommend monitor for further water intrusion and repairs as needed by a qualified contractor.

3.2. There are open knock outs present in main panel enclosure. This is a potential safety hazard and can allow mice or insects into panel.

3.3. Corrosion inside panel and or electric connections. Recommend further investigation and repairs by a licensed electrician.

Kitchen

Page 46 Item: 1 Cabinets

Page 47 Item: 5 Vent Condition

Interior Areas

Page 50 Item: 2 Windows

Page 50 Item: 3 Walls

Page 53 Item: 6 Electrical Finish

1.2. Water staining at base of sink cabinet. Recommend monitor condition and repairs as needed.

5.2. The kitchen vent termination was not located. If kitchen vent hood is not the recirculating type, termination of kitchen venting system should be to the exterior with a proper hood or roof cap equipped with a back draft damper. Recommend assessment by a qualified tradesman.

2.2. Window has staining on sill or frame was dry at time of inspection. Recommend monitor condition and further assessment and repairs if needed.

3.3. Staining on wall dry at time of inspection. Recommend asking current homeowner for the source and history of any leaks or water intrusion and assessment and repairs of any affected areas by a qualified tradesman.

6.2. Outlet or switch cover plates missing. Recommend repairs for safety.

6.3. Electrical outlet at wet location is not GFCI protected. Current building practices require GFI protection at all wet locations; kitchen and bath counters, outdoor and garage outlets, unfinished basement outlets, any outlet providing power to a wet appliance such as hot tub or pool and any outlet within 6' of the rim of a sink. Recommend assessment and installation of GFI outlets where needed by a licensed electrician for safety.

6.4. GFCI outlet will not trip when tested. Recommend repair by a licensed electrician.

Page 54 Item: 7 Electrical Wiring

Bathroom

Page 60 Item: 1 Cabinets

Page 62 Item: 2 Exhaust Fan

Page 65 Item: 4 Sinks

Page 66 Item: 5 Toilets

Heat AC

Page 69 Item: 1 Heater Condition

7.1. Open junction boxes. Recommend installing proper covers, as needed, for safety.

1.2. There is staining in cabinets under sink, tested dry. Recommend monitor for any further intrusion and repairs as needed.

2.3. Termination of bath fan vents could not be determined. Exhaust fans should be terminated to outside of house. Recommend assessment by a qualified contractor.

4.2. Sink water supply has corrosion on pipes and line leaks. Recommend further investigation and repair by a qualified plumber.

5.2. The toilet is loose at the floor anchor bolts. Potential for leaking and sub floor damage, which may not be visible during inspection. Recommend assessment and repair by a licensed plumber.

5.3. Elevated moisture observed at the base of toilet or at water supply line. Recommend assessment by a licensed plumber.

1.3. Furnace, boiler or air handler is beyond its design life. The system was operating and providing heat and or AC at the time of inspection. Due to the age there could be issues that are not detected in our visual inspection. Recommend assessment by a qualified heating contractor prior to closing.

1.4. Oil boilers and furnaces require annual maintenance. Last maintenance is not recorded. Recommend inspection maintenance and cleaning by a certified oil heating company. Recommend inspection of oil tank during each annual boiler service.

Page 73 Item: 4 Heater 2 Condition

Water Heater.

Page 74 Item: 1 Water Heater Condition

4.1. Furnace / boiler would not start using normal controls, recommend full inspection and repairs if needed by a qualified HVAC contractor.

4.2. Furnace, boiler or air handler is beyond its design life. The system was operating and providing heat and or AC at the time of inspection. Due to the age there could be issues that are not detected in our visual inspection. Recommend assessment by a qualified heating contractor prior to closing.

1.1. Water temperature is above 125 degrees, should be set minimum 110 degrees for comfort and maximum 125 degrees to prevent scalding particularly for very young and very old persons.

Grounds

1. Driveway and Walkway Condition

Observations: Asphalt driveway

Observations:

1.1. The driveway is improperly sloped towards the foundation. Water can infiltrate into the interior. Recommend taking measures to divert water away from this area or repairing or replacing the drive to properly slope away from the foundation.

1.2. Typical cracking was observed at the driveway and or walk way surfaces. Further deterioration will occur as water expands and contracts from freeze and thaw cycles. Regular maintenance of driveways and or walk ways will extend the life of these surfaces.

2. Grading Observations:

2.1. Lot grading and drainage have a significant impact on the building, simply because of the direct and indirect damage that moisture can have on the foundation. It is very important, therefore, that surface runoff water be adequately diverted away from the home. Lot grading should slope away and fall a minimum of 5% or 6 inches for a distance of 10 feet around the perimeter of the building.

2.2. Grading at front side of house has improper slope towards foundation. Recommend monitoring condition and take measures to divert water away from this area as needed.

Driveway slopes towards house Cracks in driveway

3. Vegetation Observations Observations:

3.1. Recommend always pruning or remove any plants that are in contact or proximity to home to eliminate pathways of wood destroying insects, water intrusion and fungal growth.

3.2. Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structures exterior. Vegetation can serve as a conduit for wood destroying insects and fungal growth and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structures exterior.

What a view!
Negative grading at front towards house
Shed not inspected

4. Retaining Wall / Fence Condition

DescriptionObservations: Block Wall

Stone Wall

Retaining walls should be monitored for movement and integrity on a regular basis. Spring is the best time to monitor for movement from winter conditions and spring rains.

Observations:

4.1. There are cracks, damage or evidence of movement in retaining walls. Recommend further investigation and repair as needed by a qualified masonry contractor.

Vegetation in contact with house
Vegetation in contact with house
Monitor block wall for movement
Monitor block wall for movement
Monitor stone walls, movement
Damaged to block wall at front left of home

Exterior Areas

Fashings around doors and windows is critical to water proofing the exterior walls. Missing,damaged or improperly installed flashings are the most common cause of moisture intrusion. Because they are concealed we disclaim any evaluation of these flashings, Leaks may become evident only during heavy, prolonged or wind driven rainfall. The window screens are not evaluated, Home Inspectors cannot always determine the integrity of the thermal seal in double glazed windows. Evidence of failed seals may be more or less visible from one day to the next depending on the weather and inside conditions.

1. Doors

Observations:

1.1. Exterior doors were checked on a random basis for proper operation and significant damage.

2. Siding Condition

A visual inspection of exterior surfaces is performed, checking for evidence of significant deterioration, damage, excessive staining, or improper installation.

Vinyl siding, wood frame construction

Observations:

2.1. Areas of lifting or deterioration to siding and or trim. Recommend assessment and repair by a qualified tradesman.

Monitor animal entrance for pest intrusion Lifting siding at rear right of home

Rear right of home
Rear of home
Rear left of home
Front left of home

3. Window Condition

Description A visual inspection of exterior window surfaces is performed, checking for evidence of deterioration or damage.

Vinyl Insulated Pane

• Inspectors cannot always determine the integrity of the thermal seal in double-glazed windows. Evidence of failed seals may be more or less visible from one day to the next depending on the weather and inside conditions (temperature,humidity, sunlight, etc.).

Observations:

3.1. Window has broken seals (fogged) this condition can diminish the energy efficiency of the window and cause permanent hazing to the glass. Recommend further assessment of windows and repairs by a qualified window contractor as needed.

3.2. Deterioration to window, frame and or trim. Recommend full assessment of windows and repairs by a qualified contractor as needed.

Fogged windows at right side of garage
Frame rot at rear of garage windows Fogged window

4. Stairs

Observations:

4.1. Exterior stairs were inspected for any areas of damage, missing or improper hand rails or guard rails and for any areas of improper installation.

4.2. Hand rails on stairs are non-graspable, this is a potential safety hazard. An easily graspable hand rail should be installed by a qualified tradesman.

4.3. Damaged stair tread. Recommend repair by a qualified tradesman.

5. Deck / Porch

Observations:

5.1. Outside decks, porches or landings were inspected for any areas of damage, missing or improper hand rails or guard rails and for any areas of improper installation.

5.2. Limited visibility under deck due to skirting or low clearance. Unable to fully inspect all deck components.

5.3. There is framing to deck / balcony that appears to have cantilevered support members. A cantilever deck is one where the joists project beyond the support beam. Most of the framing connections are not visible and cannot be inspected. The safety and structural integrity of this type of framing cannot be confirmed by this visual inspection.

5.4. Broken or missing balusters at guard rails. Recommend repairs by a qualified tradesman.

5.5. One or more support joists are missing properly installed mechanical hangers. Recommend installation and proper nailing of joist hangers by a qualified contractor.

5.6. Guardrails are loose and/or damaged. This is a safety hazard. Recommend assessment by a qualified contractor.

Framing appears to be canitlevered

Steve Powers 30 Stillwater Way, Barrington, NH
Missing Joist hangers
Limited visibility to rear deck framing
Limited visibility to rear deck framing
Rear left deck framing
Missing Joist hangers
Steve Powers 30 Stillwater Way, Barrington, NH
Missing Joist hangers
Rear railing is loose
Several damage/loose balusters
Damaged deck boards
Damaged / deteriorated deck boards at primary bedroom porch
Left Side second floor porch

6. Exterior Faucet

Observations:

6.1. The water is shut off or not working to exterior faucet, not tested. Recommend contacting home owner for confirmation of proper operation or assessment by a qualified plumber if needed.

No water to exterior faucet at front of home

Roof

Roofs may leak at any time.This inspection may not reveal future leaks, they often appear at roof penetrations, flashings, changes in direction or changes in material. A roof leak should be addressed promptly to avoid damage to the home. Ice dam leaks are common in winter .A roof leak does not necessarily mean the roof has to be replaced. It is not always possible to inspect the total underside surface of the roof sheathing for evidence of leaks or ice damming. Evidence of prior leaks may be covered by interior finishes. Chimney flue is not included in this inspection, recommend having the interior of all chimneys and flues inspected by a qualified masonry contractor.

1. Roof Condition

Approximate estimated age of Roof:10-15 Years

Inspected using pole camera

Materials: Asphalt shingles, design life 20-25 years

Observations:

1.1. There are trees and branches over hanging or in contact with roof, this condition is detrimental to life of roof and can cause damage, fungal growth, water, insect and animal intrusion. Keep trees and branches trimmed to help prolong life of roof covering.

Front roof surface
Front roof surface
Front roof surface
Front roof surface
Rear roof surface
Rear roof surface
Rear roof surface
Rear roof surface
Upper roof surface Trees overhanging roof should be cut back or removed.

2. Chimney

Description Masonry Chimney

Flue is not included in this inspection, recommend having flue inspected by a qualified masonry / chimney contractor.

Limited visibility to some upper areas chimney and or flashing due to height and pitch of roof.

Observations:

2.1. Chimney cap has cracked and damaged mortar. Recommend monitor condition and further investigation and repair by a qualified chimney contractor if needed.

3. Spark Arrestor

Observations:

3.1. No chimney rain cap observed. Recommend installing a chimney rain cap to prevent the entrance of the elements and local wildlife and to preserve the life of the chimney as well as minimize maintenance.

Masonry chimney
Masonry chimney, cracks in chimney cap Cracks in chimney cap, missing spark arrestor

4. Sky Lights

Observations:

4.1. Sky lights are not opened or operated during inspection

4.2. Stains noted inside and around skylights, dry at time of inspection. Recommend checking with homeowner for history of water intrusion and repairs and assessment of skylights, repair of any affected surfaces by a qualified contractor and monitor for further staining.

Missing chimney cap
Rear right skylight
Rear right skylight
Rear middle skylight
Rear middle skylight, stains
Rear left skylight
Rear left skylight, staining on framing

Garage

1. Walls / Ceilings

Observations:

1.1. Interior ceiling and wall surfaces were checked for visible evidence of staining, damage, settlement cracks and improper installation.

1.2. Limited visibility due to stored items.

1.3. There is cracking or damage to ceiling and or wall surfaces. Recommend further assessment and repairs by a qualified contractor.

1.4. Stains at one or more area of the garage ceilings and or walls. This is evidence of past or present leaks. They tested dry at the time of the inspection. Recommend monitoring for further water intrusion, taking measures to divert water as needed, asking current home-owner for the source and history of any leaks or water intrusion and assessment and repairs of any stained area by a qualified tradesman.

Water staining
Limited visibility due to stored items.
Limited visibility due to stored items. Water staining

2. Garage Vehicle Door

Observations:

2.1. Garage doors function normally.

2.2. Exterior door trim along lower surface has damaged or deteriorated areas. Recommend monitor and repairs as needed.

2.3. Over head door has areas of impact damage. Recommend repairs by a qualified tradesman.

Damage to wall
Impact damage to middle and right garage doors Damaged lower trim

Damaged lower trim

3. Garage Opener Status

Observations:

3.1. Tested and operated normally.

4. Garage Door's Reverse Status

Observations:

4.1. Eye beam present operated normally.

4.2. No eye beam system present at one or more over head door. This is an important safety device to prevent injury to children. Under Writers laboratory now requires all UL Rated overhead doors to have an auto reverse device for safety. Recommend assessment by a qualified over head door contractor.

No eye beam present at Left and middle door Right garage door eye beam

5. Floor Condition

Materials: Concrete floor Observations:

5.1. Typical settlement cracks.Recommend monitor condition for further cracking and water intrusion and repairs as needed by a qualified contractor.

5.2. Rodent activity observed in the garage. Vermin can damage insulation & electrical wiring. Recommend a professional pest contractor evaluate for treatment.

Powers
Typical cracks
Rodent activity

Attic

•Present or possibility of future water leaks is not alway observable.

•Access to all areas of attic space is often limited due to lack of permanently installed walkways, the possibility of damage to insulation, low height and/or stored items. These areas are excluded from this inspection.

•Insulation/ventilation type and levels in concealed areas, like exterior walls, are not inspected.

•Potentially hazardous materials such as Asbestos and Urea Formaldehyde Foam Insulation (UFFI) cannot be positively identified without laboratory analysis. This is beyond the scope of the inspection.

•Any estimates of insulation R values or depths are rough average values.

1. Access

Observations:

1.1. Walk up stairs

1.2. Door at second floor wall

2. Structure

Materials: Rafters

Plywood

Dimensional lumber wood ceiling Joists

Observations:

2.1. Water staining along drip edge area, dry at time of inspection, this staining is consistent with a prior ice damming event. This condition can occur occasionally after specific weather conditions. Recommend monitor for water intrusion during winter months and further investigation and repair by a qualified roofing contractor if needed.

2.2. Stains were found in one or more surfaces that tested or appeared to be dry. The stain(s) may be due to past or present roof and/or plumbing leaks. Recommend asking the property owner(s) about this, and monitoring the stained area(s) in the future, especially after heavy or prolonged rain. If elevated moisture is found in the future, a qualified contractor should evaluate and repair areas as necessary.

Door at second floor wall

Staining consistent with ice damming at room above garage

Room above garage

Room above garage

Room above garage

Staining throughout

Room above garage

Steve Powers 30 Stillwater Way, Barrington, NH
Upper attic Stains tested dry
Stains around chimney Stains tested dry
Stains tested dry
Upper attic
Steve Powers 30 Stillwater Way, Barrington, NH

3. Insulation Condition

Materials: Unfinished fiberglass batts

Insulation Depth Insulation averages about 8-10 inches in depth

Current building standards would require approximately 16-18 inches of insulation or R-49 in attic floor area. Client may wish to add insulation to enhance energy efficiency.

Observations:

3.1. Limited visibility due to finished flooring in attic.

3.2. Animal droppings or activity observed in the attic. Vermin can damage insulation & electrical wiring. We do not identify the droppings. If squirrels or bats are present it can be more difficult and costly to treat. When animal droppings are observed a qualified pest company should always assess. Recommend a professional pest contractor evaluate for treatment.

Insulation above garage
Rodent or animal droppings
Limited visibility due to finish flooring
4. Ventilation
Ridge exhaust venting
Soffit inlet vents
Ridge Vent
Soffit vents
Ridge Vent above garage
Soffit vents above garage
Soffit vents with propa vents
Ridge Vent

Foundation

Despite all efforts, it is impossible for a home inspection to provide a guaranty that the foundation, and the overall structure and structural elements of the building is sound. Alpha Building Inspections suggests that if the client is at all uncomfortable with this condition or our assessment, a structural engineer be consulted to independently evaluate any specific concern or condition, prior to making a final purchase decision.

Limitations of Structure Inspection

•Full inspection of all structural components (posts/girders, foundation walls, sub flooring, and/or framing) is not possible in areas/rooms where there is insulation, stored items, shelves, appliances or are finished walls, ceilings and floors. A representative sample of the visible structural components was inspected.

•No representation can be made to future leaking of foundation walls.

1. Foundation Walls

Materials: Concrete

Limited visibility due to finished basement space and or stored items or cluttered conditions.

Observations:

1.1. Vertical cracks on foundation wall , recommend monitor for further movement and or water intrusion and sealing / repairs as needed.

Vertical crack on rear wall
Vertical crack on rear wall
Vertical crack on rear wall

2. Under Floor Framing

Limited visibility due to finish basement, insulation or cluttered conditions.

Beam Material: Wood

Steel lally columns

Dimensional lumber wood Joists

Plywood sheathing sub floor.

Observations:

2.1. Damaged or disturbed insulation along floor framing. Recommend assessment and repairs as needed by a qualified contractor.

2.2. Water staining on framing at one or more area, tested dry at time of inspection. Recommend monitor for further water intrusion and repairs as needed by a qualified contractor.

Basement framing
Basement framing
Basement framing
Basement framing

3.

Description Limited visibility due to finished basement space and or stored items or cluttered conditions.

Concrete Floor Slab

Observations:

3.1. A radon mitigation system is present. A vent pipe is run from floor slab outside with a vent fan. There is a blue water column, when water lines are uneven fan is operating creating vacuum in vent pipe. although proper operation of the system does diminish radon levels in the home, acceptable levels of radon in the air can only be determined by conducting a radon in air test.

3.2. Damage or significant cracks. Recommend assessment and repairs by a qualified contractor as needed.

Staining on framing
Areas of damage insulation on Lakeside wall
Staining on framing
Floor Slab
Powers
significant cracks
Radon Pipe
Water line gauge
Radon Pipe

1. Electric Service Entrance

Electrical

Description: Main service entrance cable is over head. Driven Ground Rods Present

Main service cable is overhead Electric meter and main service entrance

2. Main Panel

Description Panel box located in basement

Main electric disconnect located in main electric panel.

120/240 volt

Circuit Breakers

Copper Romex Wiring

200 amp

3. Electric Panel Condition

Observations:

3.1. Electric panel was inspected for any areas of damage, deterioration, improper installation and any safety hazards.

3.2. There are open knock outs present in main panel enclosure. This is a potential safety hazard and can allow mice or insects into panel.

3.3. Corrosion inside panel and or electric connections. Recommend further investigation and repairs by a licensed electrician.

Observations:

4.1. The main service contains wiring related to the use of an on demand propane or natural gas generator providing power to the home during general power failures. Inspection of the generator wiring lies beyond the scope of the general home inspection. This back up power system requires regular maintenance from a qualified contractor. Recommend obtaining service records and or having the generator wiring and generator evaluated by a qualified electrical contractor.

Corrosion on main panel main panel
Corrosion inside panel, open knock outs
Corrosion inside panel
4. Generator
Generator transfer switch
Generator lid was locked, unable to test

Plumbing

1. Plumbing

Description: Some plumbing lines are not visible due to finished space. insulation or stored items.

Main water shut off valve is located in basement

Copper water supply lines

"PVC" waste and vent pipes

Pex water supply lines

Septic inspection was performed by Kent Septic their report will be sent as a separate document.

Observations:

1.1. There is corrosion on one or more water supply and or drain line fittings. Recommend monitor for any further corrosion and leaking and have repairs by a licensed plumber as needed.

Main water shut off valve is located at well tank
Main drain line termination
Corrosion on basement plumbing lines

2. Well System

Observations:

2.1. A visual assessment of the well equipment and operation of the well was conducted, no gauges or special testing equipment were used. This report makes no comment or prediction as to the future production or operation of the well system. Operation of multiple plumbing fixtures at the same time may not be advisable to help prevent over loading the well system. The client may wish to have additional testing done by a qualified well company. The system is a drilled well with submerged pump and well tank located in the basement. The well-head was not located. The state of NH requires a minimum radius of 75' from the septic system and minimum set backs from structures and lot lines, recommend client confirm location of well by home-owner or qualified well company. Water flow was observed after running tub system for a minimum of 10 minutes and was providing a minimum of 3 gallons per minute. Pump had an acceptable pressure of 35 psi to 55 psi. Pump had an acceptable operating cycle of approximately three minutes, Water quality test report will be delivered in a separate email.

2.2. Water conditioning equipment is not inspected. Recommend contacting a qualified water treatment company for information on operation and maintenance of equipment.

2.3. There is a sediment filter that should be monitored and changed on a regular basis. A dirty sediment filter can significantly diminish water flow and pressure.

Sediment Filter, recommend changing to clear cover to observe when filter needs changing.

Well Tank Water treatment equipment.

3. Lawn irrigation

Observations:

3.1. The lawn irrigation system was not operated or inspected, system may not be in operation. System will need to be assessed and shut down by a qualified contractor prior to winter and start up in spring by a qualified lawn irrigation company. Recommend asking home-owner for service history to confirm system is in operational condition. It is important that sprinkler heads are not spraying onto house, deck or stairs.

Steve Powers
Control for lawn Irrigation
Plumbing for lawn Irrigation

Laundry

Our inspection of the laundry area is visual only we do not operate washer and dryer during the inspection. Laundry connections or areas of dryer venting obscured behind walls or obstacles are not inspected. Issues with improper laundry venting can be a potential fire hazard. We recommend regular inspection and cleaning of dryer vent to help reduce potential fire hazards.

1. Plumbing

Steel mesh burst proof laundry hoses.

2. Dryer Vent

Observations:

2.1. Recommend regular inspection and cleaning of dryer vent to help prevent fire hazard.

Dryer vent termination

3. Gas Valves

Observations:

3.1. Fuel for dryer is propane gas

Semi rigid dryer vent hose is an approved material.

Fuel for dryer is propane gas

1. Cabinets

Observations:

1.1. Kitchen cabinets are inspected for functionality and evidence of significant damage, usual wear and tear may not be noted in this report.

1.2. Water staining at base of sink cabinet. Recommend monitor condition and repairs as needed.

Staining below sink

2. Dishwasher

Observations:

2.1. Dishwasher was operated and inspected for areas of damage.

2.2. Dishwasher is missing high loop on drain, this is needed to prevent back flow from sink to dishwasher. Recommend repair by a qualified tradesman.

No high loop in drain line.

3. Oven & Range

Observations:

3.1. Ovens were inspected for damage and tested for proper operation.

4. Microwave Observations:

4.1. Microwave is inspected for damage and tested for proper operation.

5. Vent Condition

Description Recirculating Observations:

5.1. Kitchen exhaust vent / filter fan operated normally.

5.2. The kitchen vent termination was not located. If kitchen vent hood is not the recirculating type, termination of kitchen venting system should be to the exterior with a proper hood or roof cap equipped with a back draft damper. Recommend assessment by a qualified tradesman.

Kitchen vent termination, not located

6. Refrigerator

Observations:

6.1. Refrigerator was inspected for damage and proper operation.

7. Sinks

Observations:

7.1. Sinks are operated, as well as visually inspected for evidence of leaks, damage or improper operation.

8. Range Top

Observations:

8.1. Range top was inspected for damage and tested for proper operation.

8.2. One or more burner knobs did not operate properly. Recommend repair by a qualified appliance technician.

Range top knob does not operate properly

Interior Areas

Stored items, fit up and fixtures may prevent the inspector from viewing all areas. We do not test for mold or other hazardous materials. A qualified expert should be consulted if you would like further testing.

1. Doors

Observations:

1.1. Interior doors were checked on a random basis for proper operation and significant damage.

2. Windows

Observations:

2.1. Interior windows were checked on a random basis for damage, staining and proper operation.

2.2. Window has staining on sill or frame was dry at time of inspection. Recommend monitor condition and further assessment and repairs if needed.

Observations:

3.1. Interior finish space wall surfaces were checked for visible evidence of staining, damage, settlement cracks and improper installation.

3.2. Damage to surface of wall. Recommend assessment of wall surfaces and repairs by a qualified tradesman as needed.

3.3. Staining on wall dry at time of inspection. Recommend asking current homeowner for the source and history of any leaks or water intrusion and assessment and repairs of any affected areas by a qualified tradesman.

Stains on sill at primary bedroom
Stains on sill at left rear bedroom
3. Walls

4. Ceilings Observations:

4.1. Interior finish space ceilings were checked for visible evidence of staining, damage, settlement cracks and improper installation.

4.2. Typical settlement cracks on surface of ceilings. Recommend assessment of ceiling surfaces and repairs as needed by a qualified contractor.

Damage to wall at first floor full bathroom Stains on wall tested dry at first floor closet
Settlement cracks at right side bathroom

5. Floors Observations:

5.1. Interior finish floor surfaces were checked for visible evidence of damage, settlement cracks and improper installation.

5.2. Cracked or loose tiles. Recommend assessment and repairs by a qualified contractor.

Damage to ceiling at primary bedroom
Settlement cracks at primary bedroom
Settlement cracks at primary bathroom

6. Electrical Finish Observations:

6.1. A random sampling of outlets, GFI outlets, switches and light fixtures were observed and tested as well as visual inspection of all accessible / visible interior wiring. Outlets that are in use or not accessible usually due to furniture or stored items are not tested.

6.2. Outlet or switch cover plates missing. Recommend repairs for safety.

6.3. Electrical outlet at wet location is not GFCI protected. Current building practices require GFI protection at all wet locations; kitchen and bath counters, outdoor and garage outlets, unfinished basement outlets, any outlet providing power to a wet appliance such as hot tub or pool and any outlet within 6' of the rim of a sink. Recommend assessment and installation of GFI outlets where needed by a licensed electrician for safety.

6.4. GFCI outlet will not trip when tested. Recommend repair by a licensed electrician.

Missing outlet cover in room above garage

Kitchen counter outlet is not GFI protected.

Cracked floor tiles at first floor half bath

7. Electrical Wiring Observations:

7.1. Open junction boxes. Recommend installing proper covers, as needed, for safety.

GFI outlet will not trip at primary bathroom
Open Junction box in basement
Open Junction box in basement

8. Smoke Detectors

Observations:

8.1. A Visual inspection of smoke detectors is conducted. Today s safety standards recommends hard-wired interconnected smoke detectors, one on each floor hall and one in each bedroom and one CO detector on each floor. For battery powered smoke detectors it is recommended to test and change batteries twice a year when clocks are changed.

8.2. Smoke and or CO detectors are missing at one or more bedrooms, client may wish to have assessment and installation of smoke / CO detectors at the correct locations by a licensed electrician.

Missing smoke detector/open junction box in basement
Open Junction box in basement
Open Junction box in basement

Heat registers / base board heaters were spot tested and providing heat and or conditioned air at time of inspection.

Heat Distribution Method: Forced hot water baseboard heaters

Smoke detector missing at rear left bedroom
Smoke detector missing at front left bedroom
Smoke detector missing at primary bedroom
Smoke detector missing at front right bedroom
9. Heat Distribution

10. Stairs & Handrail Observations:

10.1. Interior stairs were inspected for any areas of damage, missing or improper hand rails or guard rails and for any areas of improper installation.

10.2. Rail opening on stairs is greater than 4 inches, this is a safety hazard particularly for young children. By todays construction and safety standards vertical ballusters should be installed no greater than 4" apart.

10.3. Stair landing has no guard rail, although not required by code if less than 30" high, recommend installation of guard rail for safety.

10.4. Stairs have horizontal baluster. Recommend installing vertical baluster no greater than 4" apart on inside of stairs to prevent children from climbing and getting injured.

11. Fire Place

Description Level II inspection—The National Fire Protection Association (www.nfpa.org) advises that each chimney receive a Level II inspection each time a residence is sold. Inspection levels are explained at www.csia.org/pressroom/press-inspection-levels-explained.htm. It is also advised that this inspection be conducted by a chimney sweep certified by the Chimney Safety Institute of America (www.csia.org)

Freestanding style wood burning stove

Observations:

11.1. Recommend having fireplace, flue and chimney cleaned and inspected by a qualified chimney contractor before using. Chimney flu inspections are not with in the scope of this inspection

11.2. Wood, pellet and gas stoves are not included in inspection. Recommend having stove, flue and chimney cleaned and inspected by a qualified contractor before using.

Rail opening exceeds 4 inches, missing guard rail at basement stairs
Horizontal balusters
Woodstove, not inspected
Woodstove, not inspected
Wood fireplace, not inspected
Wood fireplace, not inspected

Bathroom

1. Cabinets

Observations:

1.1. Bathroom cabinets are inspected for functionality and evidence of significant damage, usual wear and tear may not be noted in this report.

1.2. There is staining in cabinets under sink, tested dry. Recommend monitor for any further intrusion and repairs as needed.

First floor full bath
First floor full bath sink cabinet
First floor half bath
Limited visibility will first floor half bath sink
Left Side bathroom Left Side bathroom sink

2. Exhaust Fan

Observations:

2.1. Bath exhaust fans operated normally.

2.2. Bath fan is not properly terminated to exterior. Exhaust fans should be terminated to outside of house. Recommend repairs by a qualified contractor.

2.3. Termination of bath fan vents could not be determined. Exhaust fans should be terminated to outside of house. Recommend assessment by a qualified contractor.

First floor full bath vent terminates into storage room above garage
First floor full bath vent terminates into storage room above garage
First floor half bath vent Bath fan termination at exterior wall.
Left side bathroom vent
Left Side bathroom vent termination
Right side second floor bathroom vent, termination not located

3. Tub / Showers

Observations:

3.1. Tub and shower fixtures were operated as well as visually inspected for evidence of leaks, damage or improper operation. This inspection cannot predict or guarantee against future leaks.

3.2. Tub/shower diverter not functioning properly. Recommend further evaluation and repair by a qualified plumber/contactor.

3.3. Does not appear to be tempered safety glass. Recommend assessment by a qualified glass company.

First floor shower
Primary bathroom shower
Safety glass etching not located
Right side bathroom shower

4. Sinks

Observations:

4.1. Sink fixtures were operated as well as visually inspected for evidence of leaks, damage or improper operation.

4.2. Sink water supply has corrosion on pipes and line leaks. Recommend further investigation and repair by a qualified plumber.

Tub diverter does not operate properly at right side bathroom shower
Left Side bathroom shower
First floor full bathroom sink
Corrosion on plumbing line

Observations:

5.1. Toilets are operated, checked for proper attachment to floor, as well as visually inspected for evidence of leaks, damage or improper operation.

5.2. The toilet is loose at the floor anchor bolts. Potential for leaking and sub floor damage, which may not be visible during inspection. Recommend assessment and repair by a licensed plumber.

5.3. Elevated moisture observed at the base of toilet or at water supply line. Recommend assessment by a licensed plumber.

First floor half bath sink
Primary bathroom sinks
Right side bathroom sink
Left Side bathroom sink
5. Toilets
Toilet is loose at first floor full bath
Elevated moisture at base of first floor toilet
Toilet is loose at hall bath
Elevated moisture at base of first floor half bath
Toilet is loose at primary bath

6. Jacuzzi Tub

Observations:

6.1. Whirlpool tub was filled to a level above the water jets and operated to check intake and jets. Tub performed normally. Pump and supply lines are not normally accessible and were not inspected unless otherwise noted.

Whirlpool tub operated properly

Heat AC

1. Heater Condition

Heater Brand: Smith

Approximate Heater Age:30+ years

Heater Type: Hydronic Boiler... design life 20-25 years

Observations:

1.1. There is corrosion inside cabinet, this is an indication of leaks, of age or improper combustion. Recommend full inspection and repairs if needed by a qualified heating contractor.

1.2. There is corrosion on plumbing fixtures and or outside cabinet surface, this is an indication of leaks, of age or improper combustion. Recommend full inspection and repairs if needed by a qualified heating contractor.

1.3. Furnace, boiler or air handler is beyond its design life. The system was operating and providing heat and or AC at the time of inspection. Due to the age there could be issues that are not detected in our visual inspection. Recommend assessment by a qualified heating contractor prior to closing.

1.4. Oil boilers and furnaces require annual maintenance. Last maintenance is not recorded. Recommend inspection maintenance and cleaning by a certified oil heating company. Recommend inspection of oil tank during each annual boiler service.

Boiler
Burner

Description Metal single wall chimney vent pipe terminating into masonry chimney, Metal single wall chimney vent pipe with power vent.

Data plate, 36 years old
TPR valve
Corrosion on fittings
Corrosion on cabinet.
2. Venting

3. Fuel Line

Fuel shut off located at furnace / boiler.

Heating fuel is:

Propane Gas:propane tanks are outside of our scope of inspection, depending on the municipality, size of the tank and other factors clearances from other home components can vary, client may wish to contact fuel provider

Oil (Buyer is advised that oil tanks are prone to corrosion, even from the inside, making leakage a possibility at any time. Inspector cannot warrant this tank from leakage, even between date of inspection and date of close. Many oil company's have their own acceptable standards based their liability insurance, including the type of flooring under the tank. Many oil providers will not fill a tank that is on a dirt surface. Recommend inspection of oil tank by a qualified oil company during each boiler/ furnace servicing and prior to buying home).

Black iron pipe is used for gas supply distribution throughout the subject property.

Observations:

3.1. Gas piping is not properly bonded. Recommend assessment by a licensed electrician.

3.2. There is copper fuel line to one or more gas fired appliance. Copper piping is generally only allowed for gas piping from propane supply tanks to house regulator. Copper gas lines are no longer allowed in most municipalities. Client may need to replace existing copper gas lines in the future.

3.3. Corrosion on cast iron fuel distribution lines in basement. Recommend monitor condition and repairs as needed by a qualified gas fitter.

3.4. Corrosion or staining on oil tank, recommend inspection by a qualified oil burner company. A leaking oil tank can create environmental hazardous conditions. Oil tank should be inspected for evidence of leaking by a qualified oil burner company and replaced or repaired as needed.

Furnace / boiler vent
Metal single wall vent with power vent at garage heater
Oil tank
Corrosion on oil tank
Underside of oil tank
Propane tank and copper gas line
Left side of home propane tank and copper gas line Gas shut off valve at garage heating unit.

4. Heater 2 Condition

Description Heater Brand: Dayton

Approximate Heater Age:28 Years

Heater Type

Gas fired wall heaters

Observations:

4.1. Furnace / boiler would not start using normal controls, recommend full inspection and repairs if needed by a qualified HVAC contractor.

4.2. Furnace, boiler or air handler is beyond its design life. The system was operating and providing heat and or AC at the time of inspection. Due to the age there could be issues that are not detected in our visual inspection. Recommend assessment by a qualified heating contractor prior to closing.

Corrosion on cast iron fuel lines
Garage heater
Garage heater data plate

Water Heater.

1. Water Heater Condition

Description Water heater brand : American

Approximate Age:5 years

Gallons:80

Water heater type:Electric, design life 10-15 years

Observations:

1.1. Water temperature is above 125 degrees, should be set minimum 110 degrees for comfort and maximum 125 degrees to prevent scalding particularly for very young and very old persons.

Water heater
Data plate
Water temperature

2. TPRV

Materials: A Temperature Pressure Relief Valve (TPR Valve) present. This safety valve releases water (and thus relieves pressure) if either the temp or pressure in the tank gets too high. The TPR valve discharge tube must be made of copper, iron, or CPVC (NOT regular PVC). It must terminate within 6" above the floor--the end cannot be threaded or have a fitting. The discharge piping should not be reduced either by fittings, kinks or in any other way. Watts® Regulator Company, a maker of numerous water safety devices, states that discharge piping in excess of 30 feet or the use of more than four 90° elbows will reduce the discharge capacity. Shorter is better.

Down pipe is CPVC