SERVICE HOLE LOCATION <TITLE GUIDE 1> SJI<TITLE 400x90 2>
SPECJO ST DO NOT CUT / DRILL HOLES IN THESE LOCATIONS
150mm
150mm
150mm 150mm
150mm
150mm
End Support
150mm
150mm
Intermediate Support
Exclusion Zone
Cantilever Support
x = Larger of Joist Height / 2 or 150mm
do not cut holes too close to supports
do not over cut holes
do not punch holes with hammer
do not cut or drill holes in flanges
ACCEPTABLE HOLE LOCATIONS 50mm or less holes in any location outside exclusion zones minimum of 300mm from supports 100mm from any other hole
100mm
A
h
B
h
B
Consider clusters of holes as a single larger hole
h
B
h
A
A = Distance from a support to a Hole B = Distance from a hole to another hole Distance
Minimum distance to the hole is the greater of
A
Length Shown on Table for the hole size required
B
Length Shown on Table for largest of the 2 adjacent holes
210mm 270mm
Joist Span (m) 3.0
3.6
4.2
4.8
5.4
6.0
6.6
2.
300 300
300 300
300 300
300 400
300 800
300 1200
300 1500
There is no maximum number of holes that can be cut into the joists provided they meet the above requirements
3.
Contact ITI for further design assistance is required
4.
Cut holes carefully. Do not over cut holes
5.
Do not cut the flanges of the I-Joists
6.
Holes may be located within the full depth of the web provided there is a minimum of a 5mm gap from the bottom of the hole to the flange
7.
No holes are to be cut into a cantilever
Rectangular Holes Hole Size (mm) Height 225
Joist Span (m)
Width
3.0
3.6
4.2
4.8
5.4
6.0
6.6
225
300 400
300 800
300 1200
600 1500
1000 1900
1400 2300
1700 2700
250
Biggest Hole Width / Diameter x2
Notes: 1. Tables shown are for Residential Live Load (1.5 kPa) + 110kg/m2 Dead Load
Circular Holes Hole Diameter (mm)
or
More Information: ITI Spec Joist (SJI) I-Joist Product Specification Guide
itiaustralia.com.au