EMERGENCY LIGHTING SYSTEMS VER 18.1
Awex brand has been existing in the emergency lighting sector since 2002, invariably fulfilling its clearly defined mission: top-quality state-of-the-art products and customer satisfaction. We offer the full range of emergency lighting devices in compliance with all the European standards. Within 15 years of our market presence, we gained the leading position in the industry thanks to the involvement of knowledge, means, cooperation with best specialists, including research facilities, and investments in innovative projects. Awex means the latest technologies, experienced team of designers and engineers, top quality, reliable equipment, diversity of offer, unique design, unlimited productivity and unblemished reputation supported by references. The biggest award is satisfied and trusted customers. We also enjoy the recognition of independent experts. We were awarded the title of the “Export Leader 2006” for our business volume, and the Puls Biznesu awarded us twice with the “Business Gazelles” prize as one of the most dynamically developing companies in Poland. PROFESSIONAL PERSONNEL We employ the best specialists in many different fields for whom we ensure constant improvement in qualifications by specialist trainings. The company’s design department provides flexible design of individual orders and the team of highly qualified engineers ensures continuous technological progress of offered equipment. The use of modern information flow methods within the company ensures that the offer and functionality of products is updated on an ongoing basis. The effcient project management allows building permanent and trust-based relationships with customers. INVESTMENTS We use the latest world technologies to guarantee quality, precise workmanship, optimised technological process, and work ergonomics. We invest time and means so that every stage of manufacturing our products contributes to meeting any expectations of our customers.
TESTS The research and development works ensure that our offer is constantly updated according to development trends in the industry, and thus we can supply the most modern, multifunctional and technologically advanced products. WE TAKE CARE OF THE ENVIRONMENT We offer the environment-friendly products and the manufacturing process meets strict EU standards. QUALITY WARRANTY Due to the purpose of the company’s mission realization, we have initiated the Quality Control System according to the EN ISO 9001:2008, and the received TÜV NORD certificate guarantees the highest projects quality as well as the production, assemble and service of the emergency lighting devices. In 2016 the company Awex received, for the new products in scope of the fittings and systems of the emergency lighting, a prestige and recognized all over the world the BSI certificate. The certificate’s receipt is related to a long procedure and very restricted tests which we had to do. It proves the highest technical quality of the offered products.
TABLE OF CONTENTS SMART VISIO PLATFORM
5
OFFLINE TECHNOLOGY – IF NEEDED
66
CONTROL UNIT
67
8
COMPARISON OF SPS SYSTEMS
70
LOCATION OF LUMINAIRES
9
ACCESSORIES
73
SMART VISIO ICONS
11
CBS CENTRAL BATTERY SYSTEMS
75
SYSTEM OVERVIEW SMART – SWITCHING METHOD
76
AND REVISION TECHNOLOGY LPS SYSTEM DESCRIPTION
77 78
CM-NET CONTROL MOdULE
79
CCM CHARGING CONTROL MODULE
81
BST 430 - BOOSTER
81
24
ML-E 2X6A CIRCUIT MODULE
82
25
ML-E 4X3A CIRCUIT MODULE
82
26 27
ML-E 8X1,5A CIRCUIT MODULE
83
HUB MODULE
83
28
LS-24 SENSOR MODULE
84
LS-230 SENSOR MODULE
84
ELS-230 EXTERNAL MODULE
85
SOFTWARE OVERVIEW
DES DYNAMIC ESCAPE SYSTEM
13
SYSTEM OVERVIEW
15
SYSTEM TOPOLOGY
16
SYSTEM COMPONENTS
18
DYNAMIC ESCAPE LUMINAIRES WALL E FLAT EYE EXIT DES INFINITY DES WALL LINE
RUBIC UNA SYSTEMS
23
31
RUBIC MINI UNA
32
RUBIC UNA
34
RUBIC UNA WIRELESS
36
ACCESSORIES
38
EMERGENCY CONVERSION KITS
39
EMERGENCY ESCAPE LUMINAIRES
42
ESCAPE ROUTE LUMINAIRES
44
FZLV CENTRAL BATTERY SYSTEM 47
CZF LON EXTERNAL MODULE
85
CZF-01 PHASE LOSS SENSOR
86
ETA 2 SWITCHING MODULE
86
ADN ADDRESS MODULE
87
MP 500 SWITCHING MODULE
88
MP 4A SWITCHING MODULE
89
PZS LON MODULE
90
PZS MODULE
91
SD MEMORY CARD
91
SYSTEM STRUCTURE
92
SAMPLE SYSTEM DIAGRAM
93
COMPARISON OF CBS SYSTEMS
94
EMERGENCY ESCAPE LUMINAIRES
96
ESCAPE ROUTE LUMINAIRES
98
SYSTEM OVERVIEW
48
SMART – SWITCHING METHOD AND REVISION TECHNOLOGY
50
CONTROL MODULE
51
SMART TOUCH CONTROLLER
52
COMPARISON OF FZLV SYSTEMS
54
ACCESSORIES
57
PICTOGRAMS
100
EMERGENCY ESCAPE LUMINAIRES
58
SYMBOLS USED
101
ESCAPE ROUTE LUMINAIRES
60
STANDARDS AND REGULATIONS
102
SPS CENTRAL BATTERY SYSTEMS 63 SYSTEM OVERVIEW
64
USER INFORMATION
100
SMART VISIO PLATFORM SOFTWARE OVERVIEW
8
LOCATION OF LUMINAIRES
9
SMART VISIO ICONS
11
EMERGENCY LIGHTING SYSTEMS
SMART VISIO PLATFORM
LAN line for communication between single system devices Smart Visio platform communication line communication line for control units to PZS communication bus RUBIC UNA PH90 (E90) power supply cable for FZLV and CBS communication for control units RUBIC UNA WIRELESS
CBS SYSTEM
6
EMERGENCY LIGHTING SYSTEMS
SMART VISIO PLATFORM
FZLV SYSTEM
RUBIC UNA/ RUBIC UNA WIRELESS
7
EMERGENCY LIGHTING SYSTEMS
SMART VISIO PLATFORM SOFTWARE OVERVIEW SMART VISO is an advanced control and monitoring application for the latest emergency lighting systems manufactured by AWEX. Irrespective of the chosen solution (FZLV, SPS, LPS, CBS, or RUBIC UNA), SMART VISIO enables connection, integration and visualization of each system at the same time in any configuration and at a single control desk. Thanks to the application of the common BACnet protocol for system communication, the software can be implemented virtually in any building. SMART VISIO
is inexpensive to install and offers the possibility of complete system visualization, which saves time and costs of everyday supervision. The software is recommended for use in shopping centres, medium and large office buildings, hospitals, stadiums, airport terminals, manufacturing plants and special purpose facilities. The system reporting complies with PN-EN 50172.
Features: • Possibility of installation on any Windows-based PC connected to a common LAN • Instant verification of any faults and system errors • Quick identification of faulty devices • Simple diagnostics of primary system parameters visualized in a block diagram • Possibility of system expansion by any number of connected components • Possibility of remote management of integrated systems
• Compatibility with all other AWEX emergency lighting systems • Intuitive menu • Possibility to upload floor plans and luminaire layouts • Automatic control of emergency lighting • Unlimited configuration possibilities for individual luminaires and the whole system from one place • Luminaire and system status monitoring
SMART VISIO APPLICATION
PC
LAN
LAN
max. 100m
max. 100m
ROUTER
CBS
8
LPS
SPS
FZLV
RUBIC UNA/RUBIC UNA WIRELESS
EMERGENCY LIGHTING SYSTEMS
SMART VISIO PLATFORM LOCATION OF LUMINAIRES A drop-down list in the left section of the window enables easy selection of individual luminaires installed in different systems in the building or facility. When a specific luminaire is selected it can be set up or its real-time status can be viewed. The most important information, such as: luminaire name (editable), assigned address and technical parameters are displayed in a clear and user-friendly manner. The actual location of the selected luminaire in the building or facility can be identified by a single mouse click.
The SMART VISIO platform includes a SMART PANEL module, where the user can view – besides the current status of the luminaires – information about the inputs and outputs handled by the controlled devices.
The SMART VISIO enables status verification and luminaire configuration in a clear and easy way, even in the most complex systems. Intuitive menu and the visualization of uploaded floor plans/blueprints enables quick location of luminaires in the building/facility.
When a specific system is selected from the list of available equipment, a clear interface with advanced functions is displayed. One of key features of SMART VISIO is the access it provides to the system status in real time, which enables an immediate response in case of a fault or failure.
9
EMERGENCY LIGHTING SYSTEMS
SMART VISIO PLATFORM The layout of a building/facility comprises e.g. a floor plan where the user can place icons representing actual system components. The icons change the colour according to their current status, so the operation of the devices (e.g. luminaires) can be easily monitored. This kind of visualization is an essential tool in the process of dynamic system status control in a building or facility.
The SMART VISIO platform also includes a panel level, from which the user can view – besides the current status of the luminaires – information about the inputs and outputs handled by the controlled devices.
10
EMERGENCY LIGHTING SYSTEMS
SMART VISIO PLATFORM SMART VISIO ICONS UNKNOWN
CBS control unit
FZLV control unit
RUBIC control unit
SPS
Module
Group
Luminaire
Exit Sign
Luminaire
Output
Sensor
Lock
Switch
11
ACTIVE
EMG
ERR
OFF
ON
DES - DYNAMIC ESCAPE SYSTEM SYSTEM OVERVIEW
15
SYSTEM TOPOLOGY
16
SYSTEM COMPONENTS
18
SYSTEMY OŚWIETLENIA AWARYJNEGO
SYSTEM OŚWIETLENIA DYNAMICZNEGO DES
14
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE SYSTEM
WHAT IS DYNAMIC ESCAPE SYSTEM? GENERAL INFORMATION Dynamic illumination is an innovative system controlling escape route depanding on situation present on facility. Due to connection with fire alarm systems, marking allows to fast recognition of safe escape route. Rapidally changing conditions such as smoke or fire require system which allows fast and dynamic change of the safest escape route.
DES – DYNAMIC ESCAPE SYSTEM DES is a dynamic illumination system which consists of escape route luminaires, control panel and central power system. Dynamic luminaires may display up to ten various characters depanding on programmed scenario. Due to application of DES system it is possible to show proper escape route in case of hazards, eg. fire hazard.
DES LUMINAIRES Each luminaire may display one of ten characters programmed according to scenario. The luminaire is capable of connecting power from the CBS and the control signal from the DES control panel.
DES INSTALLATION The DES touch panel module controls scenarios initiated by fire alarms. The communication line controls characters displayed on DES luminaires. Central battery system provides power supply to the DES luminaires during malfunction due to the use of battery sets. The central battery system has an internal charger which controls charging process and switching of operation mode.
15
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE SYSTEM
system topology The DES system cooperates with the CBS central battery system. Due to such solution dynamic luminaires are also powered during malfunction. Circuits which power dynamic luminaires should be led with fire resistant 3 core cable. Comunication between the dynamic luminaires and the control panel is done with the 3 core comunication cable. The DES panel sends information about active scenario to particular luminaires. There is also possibility to check automatically and completely if the installed luminaires work properly. The test result is registered in a log file which is saved in non-volatile memory.
MWB module
together with luminaries
RS485 SMART VISIO
max. 1200m
POTENTIAL FREE FIRE ALARM SYSTEM SIGNAL
DES PANEL
VIZUALIZATION
LAN max. 100m
RS485
max. 1200m
CENTRAL BATTERY SYSTEM CBS
LAN max. 100m
POTENTIAL FREE TEST SIGNAL
COMMUNICATION
HDGS 3x2,5mm2
POWER SUPPLY 230 VAC/216 VDC
16
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE SYSTEM
Dynamic luminaires may display up to 10 characters depanding on accepted scenerio. Additional function is running light mode. Scenarios are initiated from panel on DES control unit and potential-free MWB input module which gathers signals from detection devices. Any time scenario changes can be done without any additional software.
MP 4
Max 250 luminaires
MP 16
MPU 250 power Max 13
Max 250 luminaires
Max 250 luminaires
Max 250 luminaires
Max 750 luminaires
17
Max 250 luminaires
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE SYSTEM
System components DES PANEL
Features: • Touch screen control unit • Unique addresses of luminaires • Factory-assigned module addresses • No need for an addressing unit • Intuitive graphical user interface • No need to keep the polarity of communication cables connection • Remote access via website • Monitoring of up to 750 luminaires per control unit (3 logical buses: 01, 02 and 03 - each one with 2 physical channels) • Inbuilt four potential-free inputs and outputs • System status indication • Internal battery for uninterruptible control unit operation • Automatic execution of programmed tests from the calendar • Event log • Mains supply mode for selected luminaires/groups • System management and visualization by using dedicated SMART VISIO software • BACnet standard for Building managment system (BMS)
18
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE SYSTEM MPU250 POWER – SUBMODULE Features: • Monitoring of up to 250 DES luminaires • Two separate channels for bus with up to 1200m each • TH35 (DIN-3) rail mounted • Internal battery for uninterruptible sub module operation • RJ45 connector for DES panel • Individually programmable IP address
MWB – INPUT MODULE Features: • designed for operation with DES panel and DES luminaires • comunication with central unit via RS 485 protocol • up to 6 MWB modules can be connected to the submodule • 8-32V DC supply, require to use additional uninterruptible power suplply unit • up to 12 potential-free inputs • possibile to change single input modes: 1k; 4,7k; 22k; 47k; NC, NO • indicated status of each single input on central unit • assembly on DIN rail (TH-35)
ZMP- U – POWER SUPPLY Features: • designed to operate with MWB modules • 230 V AC power suplly • Internal battery for uninterruptible operation • possibility to supply up to 2 MWB • assembly on DIN rail (TH-35) • 10 - 14,6 V DC output voltage
BM DES – ADDRESSABLE MODULE Features: • designed to operate with DES panel and DES luminaires • comunication with central unit via RS 485 protocol • displays up to 10 signs • LED indicator included for any comunication and operation malfunction • preset scenario activation by 230V control input • automatic detection of connected light source • compact housing • posibility to connect up to 250 modules to the sub-module
19
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE SYSTEM The following scenarios show situations in which fire occurs in two buildings of different purposes. Building plan 1 shows open space and a number of office rooms with conference rooms and sanitary rooms. Building plan 2 shows a hotel building with catering area, technical facility and a lobby with reception. In each of the buildings escape routes have been defined due to dynamic lighting system and INFINITY II and flat eye luminaires. Due to this application, leaving the building takes place on safe roads, ie free from smoke. Dynamic lightning system increase a escape comfort and safety level of people in case of emergency situation.
SCENARIO I
SCENARIO III
20
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE SYSTEM Legend: fixture EYE FLAT with arrow "right" direction
fixture INFINITY II with arrow "down" direction
fixture EYE FLAT with arrow "left" direction
fixture INFINITY II with „STOP’ sign
fixture EYE FLAT with arrow "up" direction
place of fire
fixture EYE FLAT with arrow "down" direction
people inside the building
fixture EYE FLAT with "STOP" sign
SCENARIO II
21
DYNAMIC ESCAPE LUMINAIRES 24
WALL E FLAT EYE
25
EXIT DES INFINITY DES
26 27
WALL LINE
28
WALL E
FLAT EYE
INFINITY II DES
WALL LINE
EXIT DES
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE LUMINAIRES WALL E
DIMENSIONS (mm):
126
MATERIALS: Stainless steel 316L Tempered glass window 5mm MOUNTING: Surface (wall) POWER SUPPLY: Self contained – 220÷240VAC/50÷60Hz Central battery – 220÷240VAC/50÷60Hz; 216VDC LIGHT SOURCE: max. 2W – high intensity led INSULATION CLASS: I IP RATING: IP65 AMBIENT TEMPERATURE: ta : 0°C ÷ 40°C OPTIONS: DES – dynamic escape system ADDITIONAL INFORMATION: Luminaire cooperates only with the dynamic escape sign system DES Luminaire indicate escape route direction according to scenarios from DES.
288
87
DES SYSTEM CONFIGURATION CODE
POWER
SYSTEM
OPTION
WLE
2W
CB
DES
Legend: DES – dynamic escape system CB – central battery WLE – fixture Wall E
24
220-240V AC 50-60Hz
176-275V DC
DES
LED
IP65
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE LUMINAIRES FLAT EYE
DIMENSIONS (mm):
141
MATERIALS: Stainless steel 316L Tempered glass window 5mm MOUNTING: Surface (wall) POWER SUPPLY: Self contained – 220÷240VAC/50÷60Hz Central battery – 220÷240VAC/50÷60Hz; 216VDC LIGHT SOURCE: max. 2W – high intensity led INSULATION CLASS: I IP RATING: IP65 AMBIENT TEMPERATURE: ta : 0°C ÷ 40°C OPTIONS: DES – dynamic escape system ADDITIONAL INFORMATION: Luminaire cooperates only with the dynamic escape sign system DES Luminaire indicate escape route direction according to scenarios from DES.
128
84
DES SYSTEM CONFIGURATION CODE
POWER
SYSTEM
OPTION
FLE
2W
CB
DES 220-240V AC 50-60Hz
176-275V DC
DES
Legend: DES – dynamic escape system CB – central battery FLE – fixture FLAT EYE
25
LED
IP65
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE LUMINAIRES EXIT DES
178
DIMENSIONS (mm):
52
MATERIALS: White polycarbonate body Opal polycarbonate cover MOUNTING: Surface (wall) Optionally recessed* (wall) POWER SUPPLY: Self contained – 220÷240VAC/50÷60Hz Central battery – 220÷240VAC/50÷60Hz; 216VDC LIGHT SOURCE: max. 3W INSULATION CLASS: II IP RATING: IP65 AMBIENT TEMPERATURE: ta : 0°C ÷ 40°C OPTIONS: DES – dynamic escape system ADDITIONAL INFORMATION: Luminaire cooperates only with the dynamic escape sign system DES Luminaire indicate escape route direction according to scenarios from DES. *requires an accessory for recessed mounting
332
52
DES SYSTEM CONFIGURATION CODE
POWER
SYSTEM
OPTION
ETL
3W
CB
DES
RECESSING CUT (mm): • wall
160 x 314
220-240V AC 50-60Hz
176-275V DC
LED
IP65
DES
Legend: DES – dynamic escape system CB – central battery ETL – fixture EXIT L DES
26
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE LUMINAIRES INFINITY II DES
DIMENSIONS (mm):
189
37
72
MATERIALS: White polycarbonate body Opal polycarbonate cover MOUNTING: Surface (wall) Optionally recessed* (wall) POWER SUPPLY: Self contained – 220÷240VAC/50÷60Hz Central battery – 220÷240VAC/50÷60Hz; 216VDC LIGHT SOURCE: max. 3W INSULATION CLASS: II IP RATING: IP40 AMBIENT TEMPERATURE: ta : 0°C ÷ 40°C OPTIONS: DES – dynamic escape system ADDITIONAL INFORMATION: Luminaire cooperates only with the dynamic escape sign system DES Luminaire indicate escape route direction according to scenarios from DES. *requires an accessory for recessed mounting
337
220-240V AC 50-60Hz
57
176-275V DC
LED
DES SYSTEM CONFIGURATION CODE
POWER
SYSTEM
OPTION
IF2B
3W
CB
DES
Legend: DES – dynamic escape system CB – central battery IF2B – fixture INFINITY II DES
27
DES
IP40
EMERGENCY LIGHTING SYSTEMS
DYNAMIC ESCAPE LUMINAIRES WALL LINE MATERIALS: Stainless steel body Plexi glass MOUNTING: Surface (wall) POWER SUPPLY: Self contained – 220÷240VAC/50÷60Hz Central battery – 220÷240VAC/50÷60Hz; 216VDC LIGHT SOURCE: max. 2W – high intensity led INSULATION CLASS: I IP RATING: IP65 AMBIENT TEMPERATURE: ta : 0°C ÷ 40°C OPTIONS: DES – dynamic escape system ADDITIONAL INFORMATION: Luminaire cooperates only with the dynamic escape sign system DES Luminaire indicate escape route direction according to scenarios from DES Possibility to connect several segments together
220-240V AC 50-60Hz
176-275V DC
LED
IP65
DES
DES SYSTEM CONFIGURATION CODE
POWER
SYSTEM
OPTION
WLL
2W
CB
DES
112
DIMENSIONS (mm):
820
Legend: DES – dynamic escape system CB – central battery WLL – fixture WALL LINE
28
140
SYSTEMY OŚWIETLENIA AWARYJNEGO
OPRAWY DYNAMICZNE
29
RUBIC UNA SYSTEMS RUBIC MINI UNA
32
RUBIC UNA
34
RUBIC UNA WIRELESS
36
ACCESSORIES
38
EMERGENCY CONVERSION KITS
39
EMERGENCY ESCAPE LUMINAIRES
42
ESCAPE ROUTE LUMINAIRES
44
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM RUBIC MINI UNA The RUBIC MINI UNA system is a modern, compact solution designed for the monitoring of emergency luminaires with unique addresses installed in small-size buildings and facilities. The system offers the possibility to supervise up to 500 emergency luminaires equipped with RU-type power supply sources. The main advantages of the MINI UNA control unit are its compact size and the possibility to mount it on a DIN-3 standard rail (TH35). The system is simplified but not deprived of the most important functionalities from the user’s point of view. Each control unit is equipped with an RS485 connection for the communication bus, an RJ45 connector, four LEDs indicating the current status of the system, three function keys which can be programmed in the control unit, a reset button and a service pin to assign a unique IP address to the unit. Additionally, the control unit has two potential-free input contacts and two outputs. Communication with RU emergency luminaires is provided by means of an RS485 standard communication bus. A single bus may not exceed 1200 m when linear topology is used. The communication with luminaires is continuous.
Features: • Monitoring of up to 500 emergency luminaires • Maximum lenght of each single bus line 1200m • System status indicatiors • TH35 (DIN-3) rail mounted • Three programmable function keys • Two potential-free inputs (current loops) • Two outputs (to control external relays) • Internal memory to store emergency lighting system reports, compliant with PN-EN 50172 • Mains mode, configured from the control unit • Testing of individual luminaires or groups of luminaires • Internal battery for uninterruptible operation • RJ45 connector for direct communication with any computer via Ethernet • Individually programmable IP address • System status preview using any web browser • Continuous communication with luminaires installed in the system • System management and visualization by using dedicated SMART VISIO software For safety reasons, the control unit communicates with luminaires continuously and has a built-in powers supply source. All AWEX systems are manufactured in compliance with applicable European standards.
32
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM SYSTEM TOPOLOGY
RS485 max. 1200m
01.001
01.002
01.003
01.099
01.100
00–0A–139A–F001
00–0B–C21A–0020
00–01–1A1F–F001
00–00–1C2C–F001
00–01–1A0D–F0FF
RS485 max. 1200m
RUBIC MINI UNA
02.001
02.033
02.123
02.240
00–0A–132A–F091
00–0A–141A–9000
00–00–122C–F901
00–00–122C–F001
LAN max. 100m
SWITCH INTERNET
PC
LAN max. 100m
PC
SYSTEM COMPONENTS
ADDRESS MODULE Features: • Compatible with LED light sources • Switching to emergency mode • LiFePO4 battery • Battery charge indicator • Luminaire status indicator
SMART VISIO PLATFORM Features: • System status monitoring • System programming • Event log viewing • Test function • Possibility to upload floor plans of the building/facility
33
WWW
max. 500 units
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM RUBIC UNA The RUBIC UNA is the latest and the most advanced monitoring system designed to control independent luminaires of emergency and escape route lighting systems. It is designed to be used in medium-to-large facilities and buildings. Each control unit can handle up to 4,000 luminaires using MPU250 Power submodules. The submodules communicate with the RUBIC UNA control unit via LAN. The use of LAN also enables communication between individual submodules. The RUBIC UNA system is equipped with a touch panel and an intuitive graphic menu to enable quick and easy system configuration without the need for using SMART VISIO. Thanks to introduced technical solutions polarity does not need to be observed any more while connecting a communication bus to the following system components: • RUBIC UNA control unit • MPU250 Power submodules • RU address modules Each RU address module is assigned an individual number/address. The addresses are factory-assigned, so an addressing unit is not required for installation, setting up or maintenance work. Communication with RU emergency luminaires is provided by means of an RS485 standard communication bus. A single bus may not exceed 1200 m when linear topology is used. The communication with luminaires is continuous.
34
Features: • Touch screen control unit • Unique addresses of luminaires • Factory-assigned module addresses • No need for an addressing unit • Intuitive graphical user interface • No need to keep the polarity of communication cables connection • Inbuilt four potential-free inputs and outputs • Remote access via web browser • Monitoring of up to 750 luminaires per control unit (3 logical buses: 01, 02 and 03 - each one with 2 physical channels) • Possibility to expand the control system up to 4,000 luminaires by using additional external submodules • System status indication • Compatibility LED light sources • Internal battery for uninterruptible operation • Automatic performance of tests • Event log • Posibility to divide the luminaires for logic groups • Mains mode for selected luminaires/groups • System management and visualization using of dedicated SMART VISIO software • BACnet standard, enabling compatibility of the RUBIC UNA with Building Management Systems (BMS)
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM SYSTEM TOPOLOGY
RS485 max. 1200m
RS485
05.004
05.005
05.003
05.091
00–0A–2A3A–F001
00–1A–1F1A–0001
00–00–1F1D–F001
00–10–1F2C–F021
max. 1200m
MPU250 - POWER
05.001
05.002
05.007
05.211
00–0A–214C–F001
00–1A–141C–0120
00–00–113F–C201
00–10–12CC–F321
Max. 250 units
RS485 max. 1200m
MPU250 - POWER LAN max. 100m
LAN
RUBIC UNA
max. 100m
04.001
04.043
04.123
04.240
00–2A–231A–F022
00–1A–131A–0143
00–00–311D–F029
00–10–322C–F028
Max. 250 units
RS485 max. 1200m
SWITCH
03.001
03.003
03.031
00–1A–145A–0143
00–00–115D–F029
00–10–126C–F027
RS485 Max. 750 units
max. 1200m
RS485
02.001
02.033
02.123
00–1A–144A–0143
00–00–141D–F029
00–10–142C–F023
max. 1200m
INTERNET
PC
01.001
01.010
01.123
00–1A–121A–0143
00–00–121D–F029
00–10–132C–F023
WWW
SYSTEM COMPONENTS MPU250 Power module Features: • Submodules mounted on a DIN-3 rail (TH35) • Monitoring of up to 250 luminaires • Ethernet connection for LAN communication • Service pin and Reset button • Freely programmable IP address • Built-in uninterruptible power supply unit • LED indicator of battery charging
ADDRESS MODULE Features: • Compatible with LED light sources • Switching to emergency mode • Operating on Ni-Cd, Ni-MH or LiFePO4 batteries • LED status indicator included
SMART VISIO PLATFORM Features: • System status monitoring • System programming • Event log viewing • Test function • Possibility to upload floor plans of the building/facility
35
Max. 4000 units
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM RUBIC UNA WIRELESS RUBIC UNA Wireless system is the latest and most advanced version of the monitoring system intended for emergency and evacuation luminaires. It is d e d i c a t e d f o r a l l t y p e s o f b u i l d i n g s . E a c h c e n t ra l u n i t c a n control up to 4000 luminaires with the use of submodules MPW250 – Power. submodules communicate with RUBIC UNA RW central unit via LAN network. Communication between luminaires and central unit is wireless. By Mesh network and innovative data sending algorithms was allowed to have a reach up to of 200m in open space area. The system operates in the band ISM 868 MHz which allows overcoming such obstacles as a concrete ceiling and walls. Thanks to this it is possible to increase four times the range in coparison of divices which are oprate with 2,4GHz band, e.g. Wi-Fi standard access points
The Central Unit UNA Wireless has a built in additional submodule with an aerial to communicate with the wireless fittings. To communicate in a wireless mode, each emergency fitting must have a built in aerial. The aerial is assembled in each fitting in a way to avoid or decrease any additional interferences which can may appear during the operation of the electronics. RUBIC UNA Wireless has a touch panel as well as the graphical and intuitive menu, which causes that in an easy way the system can be configured without using the smartvisio software. Each addressable RW module has its own individual number/address. The addresses are added during the production process therefore it is pointless to have the additional device such as programmer during the installation or maintenance works.
36
Features: • Touch screen control unit • Unique addresses of luminaires • Factory-assigned module addresses • No need for an addressing unit • Intuitive graphical user interface • Communication band ISM 868MHz • Range up to 200m in open space • Possible to use signal booster • 4 potential-free inputs and outputs built in the central unit • Remote access via web browser • The central unit monitors up to 250 wireless luminaires • Possible to extend to have 4000 luminaires thanks to use external submodules • Possible to connect Wireless luminaires and and standard cable connection • System status indication • Wireless option for LED luminaires only • Internal battery for uninterruptible operation • Automatic performance of tests • Event log • Posibility to divide the luminaires for logic groups • Mains mode for selected luminaires/groups • System management and presentation by using dedicated SmartVISIO software • BACnet system
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM SYSTEM TOPOLOGY
MPW250 POWER RS485
05.009
05.023
05.090
05.105
05.135
05.198
00-0A-139A-F001
00-0B-C21A-0020
00-01-1A1F-F050
00-00-2C2F-F001
00-0A-1A0D-F000
00-00-122C-F901
max. 1200m
MPU250 POWER
04.016
04.070
04.166
04.235
04.240
00-0C-234F-H001
00-0B-C45B-0550
00-01-2A3F-8987
00-0A-123V-F908
00-01-C21A-F0FF
LAN max. 100m
RS485
02.002
02.050
02.104
02.205
02.244
00-0A-139A-F001
00-0B-C21A-0020
00-01-1A1F-8000
00-0A-1C2C-F908
00-01-1A0D-F0FF
max. 1200m
LAN max. 100m
RUBIC UNA WIRELESS
01.002
01.003
01.004
01.005
01.006
00-0A-179A-F006
00-0A-139A-F001
00-0A-141A-9000
00-0A-122C-F901
00-0A-122C-F001
ROUTER
INTERNET
PC
WWW
ELEMENTY SYSTEMU MODULE MPW250 – POWER Features: • Assembly of subordinate module on bus DIN-3 (TH35) • Monitoring up to 250 wireless luminaires • RJ45 connector • Service pin and reset button • Freely programable IP address • Builtin wireless feeder • Internal battery for uninterruptible operation with battery indicator
UNILED BM RW WIRELESS ADDRESS MODULE Features: • Cooperation with LED light source only • Emergency mode switch • Compatible with NiCD and LIFEPO4 batteries • Storage battery charging signal • LED indicator included • Compatible with specific Wireless luminaires
SMART VISIO APPLICATION Features: • System status control • System programming • Event log readout and printout • Calling test function • Possible to read in plans
37
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM ACCESSORIES MPU250 – Power Name
RUBIC UNA submodule with a built-in power supply unit
Max. numberof luminaires
250
Communication
RUBIC UNA – LAN/luminaires – RS485
Mounting
DIN-3 (TH35)
Supply voltage
230VAC
Dimensions
210 x 90 x 58 mm
Output Voltage
12VDC
MPW250 – Power Name
RUBIC UNA WIRELESS submodule with a built-in power supply unit
Max. numberof luminaires
250
Communication
RUBIC UNA – LAN/luminaires – Wireless
Mounting
DIN-3 (TH35)
Supply voltage
230VAC
Dimensions
210 x 90 x 58 mm
Output Voltage
12VDC
SIGNAL BOOSTER Name
Wireless signal amplifier
Max. number of booster
10
Communication
Wireless
Mounting
Surface
Supply voltage
230VAC
Dimensions
230 x 70 x 37
ZMP-U Name
Uninterruptible power supply unit (UPS)
Number of modules
1
Supply voltage
230V AC 50/60 Hz
Output voltage
12V DC
Mounting
DIN-3 (TH35)
Dimensions
105 x 90 x 58 mm
SWITCH RU Name
Network switch
Number of channels
5 or 8
Supply voltage
12V DC
Output voltage
12V DC
Mounting
DIN-3 (TH35)
Dimensions
33 x 78 x 107 or 64 x 98 x 118 mm
38
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM UNILED BM
38
22
MATERIALS: Polycarbonate body MOUNTING: Inside the primary lighting luminaire or separately POWER SUPPLY: 220÷240VAC/50÷60Hz LIGHT SOURCE: 1W, 3W or 6W*, dedicated 3.3V light sources CHARGING: Max. 12 h; energy-effcient electronic pulse charger AUTONOMY AND BATTERIES: 1h, 2h, 3h or 8h; LiFePO4 batteries INSULATION CLASS: II IP RATING: IP20 AMBIENT TEMPERATURE: ta: 0°C÷40°C Option: low-temperature version (to -25°C) equipped with an HTR25 heater unit ADDITIONAL INFORMATION: LED indicator of mains power supply and battery charging Deep discharge protection Automatic detection of battery capacity and setting up test parametres *6W LED output available only in emergency mode (SE)
134
UNILED BM MODULE CONFIGURATION CODE
POWER [W]
BM/1/1/RU BM/1/3/RU
1
AUTONOMY [h]
OPTION
BATTERY
1
RU
LiFePO4 6,4V 1,0Ah
3
RU
LiFePO4 6,4V 1,0Ah
BM/1/8/RU
8
RU
LiFePO4 6,4V 3,0Ah
BM/2/1/RU
1
RU
LiFePO4 6,4V 1,0Ah
3
RU
LiFePO4 6,4V 2,0Ah
1
RU
LiFePO4 6,4V 1,5Ah
3
RU
LiFePO4 6,4V 3,0Ah
1
RU
LiFePO4 6,4V 3,0Ah
3
RU
LiFePO4 6,4V 6,0Ah
BM/2/3/RU BM/3/1/RU BM/3/3/RU BM/6/1/RU BM/6/6/RU
2
3
6
*Battery pack included.
LEGEND: RU – Rubic UNA central monitoring BM – UNILED BM emergency module
39
220-240V AC 50-60Hz
IP20
LiFePO4
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM
42
MATERIALS: Polycarbonate body MOUNTING: Inside the primary lighting luminaire or separately POWER SUPPLY: 220÷240VAC/50÷60Hz; LIGHT SOURCE: Power output mode: max. 80W Compatible with LED light sources operating at 12V – 90V DC (up to 80W) OUTPUT POWER: 1W – 9W (100mA – 750mA) CHARGING: Max. 12h or 24h, depending on the battery capacity AUTONOMY AND BATTERIES: 1h, 3h or 8h; LiFePO4 batteries INSULATION CLASS: II IP RATING: IP20 AMBIENT TEMPERATURE: ta: 0°C÷50°C Option: low-temperature version (to -25°C) equipped with an HTR25 heater unit ADDITIONAL INFORMATION: Deep-discharge protection Automatic detection of battery capacity and setting up test parametres Automatic detection of the voltage of the installed light source In emergency mode, an LED indicates incorrect configuration
35
UNILED UM
157
220-240V AC 50-60Hz
POWER OUTPUT MODE LED power supply max. 80W
LiFePO4
Settings Power output mode. Output power selection range: 1W to 9W
UNILED UM
Battery type
LiFePO4
IP20
AUTONOMY [H] 1h
3h
8h
9,6V 1500mAh
9W
3W
1W
9,6V 3000mAh
9W
5W
2W
9,6V 6000mAh
9W
9W
4W
OFF
Light source power in emergency mode luminous flux in emergency mode luminous flux in mains supply mode
luminous flux in emergency mode [lm]
40
= =
LED l. s. power in emergency mode LED l. s. power in mains supply mode
LED l. s. power in emergency mode ] [W] LED l. s. power in mains supply mode [W]
x
luminous flux in mains supply mode [lm]
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM UNILED UM PREMIUM CONFIGURATION CODE
BATTERY
OPTION
CAPACITY
TYPE
UM
15
Li
B1
B2
B13
RU
UM
30
Li
B1
B2
B13
RU
UM
60
Li
B1
B2
B4
RU
*Battery pack included.
BATTERY PACK CONFIGURATION DIAGRAM
B4
B13
LEGEND: RU – Rubic UNA central monitoring UM – UNILED UM emergency module 15 – 1500 mAh battery capacity 30 – battery capacity 3000 mAh 60 – battery capacity 6000 mAh Li – battery type LiFePO4 B1, B2, B4, B13 – battery pack configuration types
41
PACKAGES
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM EMERGENCY ESCAPE LUMINAIRES AXN RU/RW series Luminaire type
Surface-mounted, ceiling, wall, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W or 6W (SE)
IP Rating
IP42 or IP65
Operating modes
Programmable SA/SE
RW mode
YES
AXNC, AXNR, AXNO, AXNU, AXNA 220-240V AC 50-60Hz
LED
IP65
AXP RU series Luminaire type
Recessed-mounted, ceiling, wall, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W or 6W (SE)
IP Rating
IP20 or IP65/20
Operating modes
Programmable SA/SE
AXPC, AXPR, AXPO, AXPU, AXPA 220-240V AC 50-60Hz
LED
IP20
IP65/20
LOVATO II RU/RW series Luminaire type
Surface-mounted, ceiling, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP41
Operating modes
Programmable SA/SE
RW mode
YES
LV2C, LV2R, LV2O, LV2U, LV2A 220-240V AC 50-60Hz
LED
IP41
LOVATO P RU series Luminaire type
Recessed-mounted, ceiling, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
Operating modes
Programmable SA/SE
LVPC, LVPR, LVPO, LVPU, LVPA 220-240V AC 50-60Hz
LED
IP20
EYE LED RU series Luminaire type
Recessed-mounted, ceiling, R or U optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
Operating modes
Programmable SA/SE
EY, EYR, EYU, EYK, EYKR, EYKU 220-240V AC 50-60Hz
LED
IP20
220-240V AC 50-60Hz
LED
IP20
220-240V AC 50-60Hz
LED
IP20
220-240V AC 50-60Hz
LED
SPY II RU series Luminaire type
Inside primary luminaire
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
Operating modes
Programmable SA/SE
SP2
MICRO SPOT RU series Luminaire type
Inside primary luminaire, R or U optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
Operating modes
Programmable SA/SE
MSU, MSR
OUTDOOR LED RU series Luminaire type
Surface-mounted, wall
Light source
LED 3x1W
IP Rating
IP66
Operating modes
Programmable SA/SE
ODB
EXIT RU/RW series Luminaire type
Surface/Recessed*-mounted, wall, ceiling
Light source
LED 1W, 2W, 3W, 6W
IP Rating
IP65
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
ETS, ETE, ETL 220-240V AC 50-60Hz
IP65
HELIOS RU/RW series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 3W, 3x1W, 6x1W
IP Rating
IP42/IP65
Operating modes
Programmable SA/SE (*only LED version)
RW mode
YES
H, HL, HHP, HW 220-240V AC 50-60Hz
TIGER RU series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 3W
IP Rating
IP22
Operating modes
Programmable SA/SE (*only LED version)
42
TL 220-240V AC 50-60Hz
IP65
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM SK–8 RU/RW series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 3W
IP Rating
IP44
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
SK–8 220-240V AC 50-60Hz
LED
IP44
220-240V AC 50-60Hz
LED
IP40
INFINITY II RU/RW series Luminaire type
Surface-mounted, wall
Light source
LED 3W
IP Rating
IP40
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
IF2BWD
ARROW N RU series Luminaire type
Surface-mounted, wall, ceiling with O or C optics
Light source
LED 1W, 2W, 3x1W
IP Rating
IP40
Operating modes
Programmable SA/SE
ARNO, ARNC, ARNS 220-240V AC 50-60Hz
LED
IP40
220-240V AC 50-60Hz
LED
IP40
220-240V AC 50-60Hz
LED
IP54
220-240V AC 50-60Hz
LED
IP54
ARROW P RU series Luminaire type
Recessed, ceiling with O or C optics
Light source
LED 1W, 2W, 3x1W
IP Rating
IP40
Operating modes
Programmable SA/SE
ARPO, ARPC, ARPS
EDGE R RU/RW series Luminaire type
Surface-mounted, wall, ceiling
Light source mains mode
LED 12W, 18W, 24W
EDRE
Light source emergency mode LED 1W, 3W IP Rating
IP54
Operating modes
Programmable SA/SE
RW mode
YES
EDGE S RU/RW series Luminaire type
Surface-mounted, wall, ceiling
Light source mains mode
LED 12W, 18W, 24W
Light source emergency mode LED 1W, 3W IP Rating
IP54
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
*current list of CNBOP fire protection approvals is available at www.awex.eu **current list of products with Kitemark and ENEC is available at www.awex.eu
43
EDSE
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM ESCAPE ROUTE LUMINAIRES SK-8 RU/RW series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W, 2W
IP Rating
IP44
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
SK–8 220-240V AC 50-60Hz
LED
IP44
220-240V AC 50-60Hz
LED
IP40
220-240V AC 50-60Hz
LED
IP40
220-240V AC 50-60Hz
LED
IP41
220-240V AC 50-60Hz
LED
IP20
220-240V AC 50-60Hz
LED
IP20
220-240V AC 50-60Hz
LED
IP22
220-240V AC 50-60Hz
LED
IP22
LED
IP40
ARROW N RU series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
Operating modes
Programmable SA/SE
ARN
ARROW P RU series Luminaire type
Recessed-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
Operating modes
Programmable SA/SE
ARP
TWINS RU series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W, 2W
IP Rating
IP41
Operating modes
Programmable SA/SE
TW
PLEXI LED RU series Luminaire type
Recessed-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP20
Operating modes
Programmable SA/SE
PL
ESCAPE RU series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP20
Operating modes
Programmable SA/SE
EL
TIGER RU series Luminaire type
Surface/Recessed-mounted, wall
Light source
LED 1W, 2W
IP Rating
IP22
Operating modes
Programmable SA/SE
TL
TIGER DS RU series Luminaire type
Surface/Recessed-mounted, ceiling
Light source
LED 1W
IP Rating
IP22
Operating modes
Programmable SA/SE
TSL
SCREEN RU series Luminaire type
Surface-mounted, wall
Light source
LED 3x1W, 3W, 2x3W
IP Rating
IP40
Operating modes
Programmable SA/SE
SC30, SC40, SC60 220-240V AC 50-60Hz
SCREEN DS RU series Luminaire type
Surface-mounted, ceiling
Light source
LED 3x1W, 3W, 2x3W
IP Rating
IP40
Operating modes
Programmable SA/SE
44
SCS30, SCS40, SCS60 220-240V AC 50-60Hz
LED
IP40
EMERGENCY LIGHTING SYSTEMS
RUBIC UNA SYSTEM HELIOS RU series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W
IP Rating
IP42/IP65
Operating modes
Programmable SA/SE
HL 220-240V AC 50-60Hz
LED
IP42
IP65
220-240V AC 50-60Hz
LED
IP42
IP65
HELIOS DS RU series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W
IP Rating
IP42/IP65
Operating modes
Programmable SA/SE
HDL
EXIT RU/RW series Luminaire type
Surface/Recessed-mounted*, wall, ceiling**
Light source
LED 1W, 2W
IP Rating
IP65
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
ETS+ETS/PLX, ETE+ETE/PLX, ETL+ETL/PLX 220-240V AC 50-60Hz
LED
IP65
220-240V AC 50-60Hz
LED
IP40
220-240V AC 50-60Hz
LED
IP40
220-240V AC 50-60Hz
LED
IP40
220-240V AC 50-60Hz
LED
IP40
*requires an accessory for Recessed mounting **requires an accessory – plexi glass INFINITY II A RU/RW series Luminaire type
Surface/Recessed-mounted*, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
IF2ACS
*requires an accessory for Recessed mounting INFINITY II A RU/RW series
IF2AWS
Luminaire type
Surface/Recessed-mounted*, wall
Light source
LED 1W, 2W
IP Rating
IP40
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
*requires an accessory for Recessed mounting INFINITY II A RU/RW series
IF2ALS
Luminaire type
Surface/Recessed-mounted*, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
*requires an accessory for Recessed mounting INFINITY II B RU/RW series Luminaire type
Surface/Recessed-mounted*, wall
Light source
LED 1W, 2W
IP Rating
IP40
Operating modes
Programmable SA/SE
RW mode
YES, only surface mounting
*requires an accessory for Recessed mounting
*current list of CNBOP fire protection approvals is available at www.awex.eu **current list of products with Kitemark and ENEC is available at www.awex.eu
45
IF2BWS
FZLV CENTRAL BATTERY SYSTEM SYSTEM OVERVIEW
48
SMART – SWITCHING METHOD AND REVISION TECHNOLOGY
50
CONTROL MODULE
51
SMART TOUCH CONTROLLER
52
COMPARISON OF FZLV SYSTEMS
54
ACCESSORIES
57
EMERGENCY ESCAPE LUMINAIRES
58
ESCAPE ROUTE LUMINAIRES
60
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM SYSTEM OVERVIEW The emergency luminaire market has recently undergone a significant transformation, in particular as regards light sources. Luminaires with LED lamps are now more and more common in emergency lighting systems due to their longer durability, a better energy efficiency and lower operating temperatures. Moreover, increasingly restrictive requirements concerning safety, reliability and autonomy of such systems, as well as a reduction of their installation costs, inspired AWEX to design a new central battery system (FZLV) that would satisfy all those needs. The FZL V system supplies loads via SELV (Safety Extra-Low Voltage) circuits operating at 24V DC, according to protection class III. The use of SELV ensures a very high level of the safety of operation of the whole system and its components and complies with applicable regulations. The system also provides a good protection against electric shock in case of a firefighting action, even if voltage is present in the circuits. The FZLV combines advantages of decentralized autonomous systems with the convenience of using central battery systems.
FZLV
48
The system incorporates own batteries whose capacity depends on the rated load and required duration of emergency lighting. The system is especially useful within a single fire zone. The use of a low power supply voltage does not only enhance the fire safety of the system, but also enables the use of smaller-sized batteries and consequently the cabinet is also smaller. A more compact size of the cabinet can be located in places where bulky central battery systems cannot be fitted.
FZLV – MAX
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM An FZLV unit can be supplied from a 230V AC or a 216V DC power source. As a result, the unit can be connected to a central battery system (CBS) as a substation without installing internal batteries. This functionality enables the system to be used in facilities where a CBS is required, but a safe voltage must also be ensured in areas where there is a risk of electric shock. Comparison of two different power supply concepts: conventional and decentralised
CONVENTIONAL CENTRAL BATTERY SYSTEM
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE 1....20 1....20 1....20 1....20 PH90*
PH90*
STAIRCASE FIRE ZONE
FIRE ZONE
Conventional system Main station failure
Damaged insulation of the branch circuit
Cable failure: main station – substation
Total substation failure
Damaged insulation of the branch circuit
Risk of electric shock
FZLV CENTRAL BATTERY SYSTEM
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20 PH90*
STAIRCASE FIRE ZONE
FIRE ZONE
Decentralized system Main station failure
No central system
Cable failure: main station – substation
Each system is independent; the failure is limited to one fire zone
Damaged insulation of the branch circuit
Negligible fire hazard (SELV)
*national regulations apply
49
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM SMART – SWITCHING METHOD AND REVISION TECHNOLOGY A conventional installation requires that the operating mode of each circuit is specified at the design stage. Subsequent modifications or errors may cause extra costs. In order to eliminate such drawbacks, AWEX has introduced a new technology with automatic monitoring and individual control of each luminaire in a system. Switching Method And Revision Technology or SMART for short. This technology enables installation of luminaires - in a common circuit – operating in four modes: continuous, intermittent, switched and dimmed. Programming and monitoring of the luminaires are provided via power supply cables. The applied technology does not require the use of special communication cables. It can be implemented if appropriate address modules are installed in the luminaires. The modules are fitted as standard in all luminaires designed to work within an FZLV central battery system. Each address module is assigned a unique address which enables its accurate identification in the system.
A SMART TECHNOLOGY SYSTEM LAYOUT MAINTAINED
SMART advantages:
OPERATION
NON-MAINTAINED OPERATION
• Luminaires operating in different modes can be installed within a single circuit • Less cable is required • Smaller number of circuits • Lower installation costs • Operating modes of the luminaires can be changed at any time
SWITCHED MODE
*DIMMED MODE
A CONVENTIONAL SYSTEM LAYOUT MAINTAINED OPERATION
Conventional limitations: As compared with the SMART system, a conventional system has the following limitations:
NON-MAINTAINED OPERATION
SWITCHED MODE
* FZLV systems only
50
• Only one operating mode is available in the branch circuit • Higher installation costs • Higher costs of subsequent changes • Changing operating modes is more difficult
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM CONTROL MODULE The system control module is equipped with a large touch screen panel which displays information on the current operating status of the system and luminaire circuits and enables setting up and modifying all system parameters via a graphic user interface. The statuses are displayed using text and graphics. Each luminaire integrated within the system can be assigned a name to facilitate its identification.
51
Signal out 4
Signal out 3
potential-free input IN4
Signal out 2
potential-free input IN3
Signal out 1
potential-free input IN2
potential-free input IN1
ModBus
Line 4: 1-20 luminaires
Line 3: 1-20 luminaires
Line 2: 1-20 luminaires
Line 1: 1-20 luminaires
230V AC input SW4
230V AC input SW3
230V AC input SW2
230V AC input SW1
Supply
Features: • Non-volatile memory to store all events and tests results for at least 2 years • Control menu with language selection • Registration of system configuration parameters and events on an SD card • Standard Ethernet interface for remote control and monitoring via a web browser • Integrated ModBUS protocol to communicate with a BMS • System status display • Automatic detection and integration of new luminaires in the system • Automatic or manual activation of short or long tests of the whole system • Operating mode and control configuration for each luminaire • Setting brightness and emergency duration for each luminaire separately • Assigning names to luminaires • Assigning design addresses to luminaires • Adjustable daytime/nighttime operation timer • Connection of up to 8 phase loss sensors • Built-in clock and calendar with DST adjustment and synchronization with a time server • Remote luminaire diagnostics • Remote notification of the system status by e-mail
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM SMART TOUCH CONTROLLER The SMART TOUCH controller enables remote control and monitoring of any number of units from a single location. The controller provides remote monitoring, configuration and reading of events for each connected FLZV unit.
SMART TOUCH control panel – sample menu
Features: • Functional test/Battery test activation for each device • Global system locking/unlocking • Password-protected access to the controller • Checking the status of individual systems • Full remote configuration of all systems • Active list of systems enabling quick status checks • Four globally configured inputs and outputs • Standard fitted Ethernet interface to enable remote control and visualization of the system via a web browser
SWITCH
MAX 100m MAX 100m
MAX 100m
1....20
MAX 100m MAX 100m MAX 100m
MAX 100m
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20 PH90*
STAIRCASE FIRE ZONE
52
FIRE ZONE
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM The FZLV system is equipped with an Ethernet port as standard. The connection enables remote checking of the status and setting up of the system via a dedicated website. This solution provides the user with the ability to control and monitor the system from a computer with a web browser installed. To check the system status using a computer, the user only needs to log in to the structural network of the facility or building where the CBS is installed. Each unit, circuit and luminaire can be monitored via the Internet. The access to the dedicated website is password protected.
Remote control – example menu screens
ACCES POINT
ROUTER INTERNET
MAX 100m MAX 100m
MAX 100m
1....20
MAX 100m MAX 100m MAX 100m
MAX 100m
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20 PH90*
STAIRCASE FIRE ZONE
53
FIRE ZONE
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM COMPARISON OF FZLV SYSTEMS Technical specifications - FZLV Technical specifications Supply voltage Protection class Ingress protection Output voltage Operating temperature range Battery capacity Number of circuits Max. circuit load Cable glands
Part No.
24V DC ±30%
24V DC ±30%
-5oC to 30oC
-5oC to 30oC
12Ah
24Ah
4
4
76W
76W
9 x M20
9 x M20 6 x M16 WCB 0000021
2h
WCB 0000012
WCB 0000022
3h
WCB 0000013
WCB 0000023
8h
WCB 0000014
WCB 0000024
140 472 140 639 54
I IP20
WCB 0000011
140
140
I IP20
1h
Cabinet dimensions [mm]: FZLV – 24Ah
266
FZLV – 24 Ah AC: 1-phase 230V ± 10%, 50/60Hz or DC: 216V ± 20%
6 x M16
Cabinet dimensions [mm]: FZLV – 12Ah
266
FZLV – 12 Ah AC: 1-phase 230V ± 10%, 50/60Hz or DC: 216V ± 20%
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM
Technical specifications – FZLV MAX Technical specifications Supply voltage Protection class Ingress protection Output voltage Operating temperature range Battery capacity Number of circuits Max. circuit load Cable glands
Part No.
I
I
IP20
IP20
24V DC ±30%
24V DC ±30%
-5oC to 30oC
-5oC to 30oC
33Ah
52Ah
4
4
76W
76W
1 x M25
1 x M25
9 x M20
9 x M20 6 x M16
1h
WCB 0000031
WCB 0000041
2h
WCB 0000032
WCB 0000042
3h
WCB 0000033
WCB 0000043
8h
WCB 0000034
WCB 0000044
800 55
FZLV MAX – 52 Ah AC: 1-phase 230V ± 10%,50/60Hz or DC: 216 V ± 20%
6 x M16
Cabinet dimensions [mm]: FZLV MAX – 33/52Ah
400
FZLV MAX – 33 Ah AC: 1-phase 230V ± 10%,50/60Hz or DC: 216 V ± 20%
170
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM TECHNICAL SPECIFICATIONS – FZLV Technical specifications
FZLV – 12 Ah
FZLV – 24 Ah
FZLV MAX – 33 Ah
FZLV MAX – 52 Ah
AC: 1-phase 230V ± 10%, 50/60Hz or DC: 216V ± 20%
AC: 1-phase 230V ± 10%, 50/60Hz or DC: 216V ± 20%
AC: 1-phase 230V ± 10%, 50/60Hz or DC: 216V ± 20%
AC: 1-phase 230V ± 10%, 50/60Hz or DC: 216V ± 20%
Protection class: I Ingress protection: IP20 DC Voltage: 24 V ± 30% Operating temperature range: -5°C to 30°C
Supply voltage
Battery capacity
12Ah
24Ah
33Ah
52Ah
1h
123W
219W
304W
304W
2h
70W
142W
195W
301W
3h
49W
102W
140W
219W
8h
21W
47W
66W
106W
4
4
4
4
76W
76W
76W
76W
Power supply
2,5
2,5
2,5
2,5
Circuit
2,5
2,5
2,5
2,5
RS485 bus
2,5
2,5
2,5
2,5
24V power out
2,5
2,5
2,5
2,5
Switch monitoring
2,5
2,5
2,5
2,5
Potential free input
2,5
2,5
2,5
2,5
Signal out
2,5
2,5
2,5
2,5
9 x M20
9 x M20
1 x M25
1 x M25
6 x M16
6 x M16
9 x M20
9 x M20
6 x M16
6 x M16
Max. power output
Number of circuits Maximum circuit load Cable connection – max wire size [mm2]
Cable glands Weight [kg] Dimensions [mm]
* loss of power in luminaire supply cables is not considered
56
15,5 kg
24,3 kg
39,2 kg
48,3 kg
472x266x140
639x266x140
800x400x170
800x400x170
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM ACCESSORIES REMOTE STATUS INDICATION PANEL: PZS This panel enables remote checking of some basic operating statuses of the system, such as: stand-by, battery operation or fault. Continuous operation can be locked using a built-in key. This prevents the system from unauthorized tampering.
Technical specifications Connection (max wire size)
PZS 1,5mm2 80x80x55mm Wall-mounted
Part No.
WCB 0000006C
80
Max. dimensions (HxWxD) Mounting
80
PHASE LOSS SENSOR: CZF-01 The quick-acting phase loss sensor is used to monitor the voltage in primary lighting switchboards to ensure that specific circuits or the whole system are energized for emergency operation. The voltage changeover threshold is as per PN-EN 60598-2-22. Technical specifications Supply voltage Switchover threshold
CZF 230/400V 50Hz as per PN-EN 60598-2-22
Mounting
DIN-3 (TH35)
Delay time
< 200 ms
Connection (wire size) Contact Dimensions (HxWxD)
98,0 x 17,5 x 56,4 WCB 0000007
56,4
Part No.
2,5 mm2 230V/50Hz 0.5A
98,00
57
17,50
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM EMERGENCY ESCAPE LUMINAIRES AXN FZLV series Luminaire type
Surface-mounted, ceiling, wall, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W or 6W (SE)
IP Rating
IP42 or IP65
AXNC, AXNR, AXNO, AXNU, AXNA 24V DC
LED
IP65
AXP FZLV series Luminaire type
Recessed-mounted, ceiling, wall, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20 or IP65/20
AXPC, AXPR, AXPO, AXPU, AXPA 24V DC
LED
IP20
IP65/20
LOVATO II FZLV series Luminaire type
Surface-mounted, ceiling, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP41
LV2C, LV2R, LV2O, LV2U, LV2A 24V DC
LED
IP41
LOVATO P FZLV series Luminaire type
Recessed-mounted, ceiling, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
LVPC, LVPR, LVPO, LVPU, LVPA 24V DC
LED
IP20
EYE LED FZLV series Luminaire type
Recessed-mounted, ceiling, R and U optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
EY, EYR, EYU, EYK, EYKR, EYKU 24V DC
LED
IP20
24V DC
LED
IP20
24V DC
LED
IP20
24V DC
LED
IP66
LED
IP65
24V DC
LED
IP42
24V DC
LED
24V DC
LED
IP44
24V DC
LED
IP40
SPY FZLV series Luminaire type
Inside the primary luminaire
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
SP2
MICRO SPOT FZLV series Luminaire type
Inside the primary luminaire
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
SP2
OUTDOOR LED FZLV series Luminaire type
Surface-mounted, wall
Light source
LED 3x1W
IP Rating
IP66
ODB
EXIT FZLV series Luminaire type
Surface/Recessed-mounted, ceiling, wall
Light source
LED 1W, 2W, 3W
IP Rating
IP65
ETS, ETE, ETL 24V DC
HELIOS FZLV series Luminaire type
Surface-mounted, ceiling, wall
Light source
LED 3W, 3x1W, 6x1W
IP Rating
IP42/IP65
HL, HHP, HW
TIGER FZLV series Luminaire type
Surface/Recessed-mounted, ceiling, wall
Light source
LED 3W
IP Rating
IP22
TL
SK–8 FZLV series Luminaire type
Surface-mounted,ceiling, wall
Light source
LED 1W, 2W, 3W
IP Rating
IP44
SK–8
INFINITY II FZLV series Luminaire type
Surface-mounted, wall
Light source
LED 3W
IP Rating
IP40
58
IF2BWD
IP65
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM ARROW N FZLV series Luminaire type
Surface-mounted, ceiling, O or C optics
Light source
LED 1W, 2W, 3x1W
IP Rating
IP40
ARNO, ARNC, ARNS 24V DC
LED
IP40
LED
IP40
ARROW P FZLV series Luminaire type
Recessed-mounted,ceiling, O or C optics
Light source
LED 1W, 2W, 3x1W
IP Rating
IP40
*current list of CNBOP ďŹ re protection approvals is available at www.awex.eu **current list of products with Kitemark and ENEC is available at www.awex.eu
59
ARPO, ARPC, ARPS 24V DC
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM ESCAPE ROUTE LUMINAIRES SK–8 FZLV series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP44
SK–8 24V DC
LED
IP44
24V DC
LED
IP40
24V DC
LED
IP40
24V DC
LED
IP41
24V DC
LED
IP20
24V DC
LED
IP20
24V DC
LED
IP22
24V DC
LED
IP22
24V DC
LED
IP22
24V DC
LED
IP42
IP65
24V DC
LED
IP42
IP65
24V DC
LED
IP42
IP65
24V DC
LED
IP65
ARROW N FZLV series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
ARN
ARROW P FZLV series Luminaire type
Recessed-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
ARP
TWINS FZLV series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W
IP Rating
IP41
TW
PLEXI LED FZLV series Luminaire type
Recessed-mounted, ceiling
Light source
LED 1W
IP Rating
IP20
PL
ESCAPE FZLV series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W
IP Rating
IP20
E
TIGER FZLV series Luminaire type
Surface/Recessed-mounted, ceiling
Light source
LED 1W
IP Rating
IP22
TL
TIGER P FZLV series Luminaire type
Surface/Recessed-mounted, ceiling
Light source
LED 1W
IP Rating
IP22
TPL
TIGER DS FZLV series Luminaire type
Surface/Recessed-mounted, ceiling
Light source
LED 1W
IP Rating
IP22
TSL
HELIOS FZLV series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W
IP Rating
IP42/IP65
HL
HELIOS P FZLV series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W
IP Rating
IP42/IP65
HPL
HELIOS DS FZLV series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W
IP Rating
IP42/IP65
HDL
EXIT FZLV series Luminaire type
Surface/Recessed-mounted*, wall, ceiling**
Light source
LED 1W, 2W
IP Rating
IP65
*requires an accessory for recessed mounting **requires an accessory – plexi glass
60
ETE
EMERGENCY LIGHTING SYSTEMS
FZLV CENTRAL BATTERY SYSTEM SCREEN FZLV series Luminaire type
Surface-mounted, wall
Light source
LED 3x1W, 3.2W, 2x3.2W
IP Rating
IP40
SC30, SC40, SC60 24V DC
LED
IP40
SCREEN DS FZLV series Luminaire type
Surface-mounted, ceiling
Light source
LED 3x1W,3.2W, 2x3.2W
IP Rating
IP40
SCS30, SCS40, SCS60 24V DC
LED
IP40
24V DC
LED
IP40
24V DC
LED
IP40
24V DC
LED
IP40
24V DC
LED
IP40
INFINITY II A FZLV series Luminaire type
Surface/Recessed-mounted*, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
IF2ACS
*requires an accessory for recessed mounting INFINITY II A FZLV series Luminaire type
Surface/Recessed-mounted*, wall
Light source
LED 1W, 2W
IP Rating
IP40
IF2AWS
*requires an accessory for recessed mounting INFINITY II A FZLV series Luminaire type
Surface/Recessed-mounted*, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
IF2ALS
*requires an accessory for recessed mounting INFINITY II B FZLV series Luminaire type
Surface/Recessed-mounted*, wall
Light source
LED 1W, 2W
IP Rating
IP40
*requires an accessory for recessed mounting
*current list of CNBOP ďŹ re protection approvals is available at www.awex.eu **current list of products with Kitemark and ENEC is available at www.awex.eu
61
IF2BWS
SPS CENTRAL BATTERY SYSTEMS SYSTEM OVERVIEW
64
OFFLINE TECHNOLOGY – IF NEEDED
66
CONTROL UNIT
67
COMPARISON OF SPS SYSTEMS
70
ACCESSORIES
73
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS SYSTEM OVERVIEW The Central Battery System SPS provides emergency power supply when the mains power is lost or its parameters are inappropriate. The main purpose of the system is to supply power to emergency lighting luminaires and assure 100% of the power for at least 1 hour. The lighting which uses LED luminaires, fluorescent luminaires or compact fluorescent luminaires can combine them in the same system. It is possible to connect any type of luminaire and it is not necessary to install any additional internal module. When designing the device, all applicable standards were followed. The device is composed of an inverter which serves to maintain the voltage of 230 VAC ± 3 % 50 Hz on output circuits. The system is equipped with batteries whose capacity is dependent upon load and emergency luminaire supply period.
SPS 300
64
SPS 600
SPS 1000
The batteries are self-operating accumulators with a 10-year operation life. SPS is based on the Offline technology, connected devices are supplied directly from the mains. The supply voltage is regularly monitored and in the event of a loss, the control system (after ca. 150 ms) disconnects the mains power and switches into accumulator mode. The device is secured against extensive load and short circuit. The circuit safety devices are continuously monitored and the damage notification is displayed on the front signaling panel. In spite of the simple structure, SPS has been provided with a set of modern functions. The unit can be configured and operated by means of the built-in www server and SmartVisio app (optional). The use of all-purpose Modbus and BACnet protocols allows integrating system from BMS. A small size of the cabinet allows installing the system in places where large-size central battery systems do not fit.
SPS 1500
SPS 2000
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS COMPARING VARIOUS SUPPLY VARIANTS: CONVENTIONAL, DECENTRALIZED CBS – CONVENTIONAL CENTRAL BATTERY SYSTEM
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE
1....20
1....20
1....20
1....20
FIRE ZONE
FIRE ZONE 1....20 1....20 1....20 1....20 PH90*
PH90*
STAIRCASE FIRE ZONE
FIRE ZONE
Conventional system Main station failure
Failure of the entire facility
Wiring failure, main station – substation
Failure of the entire substation
Damage to final circuit insulation
Possible fire hazard
SPS – GROUP BATTERY SYSTEM
max 250 W
max 250 W
max 250 W
max 250 W
max 250 W
max 250 W
FIRE ZONE
FIRE ZONE
max 250 W
max 250 W
max 250 W
max 250 W
FIRE ZONE
FIRE ZONE
max 250 W
max 250 W
max 250 W
max 250 W
STAIRCASE
PH90* FIRE ZONE
FIRE ZONE
Decentralized system Main station failure
No central system
Wiring failure, main station – substation
Each system is independent, failure in one fire zone only
Damage to final circuit insulation
Possible fire hazard
* national regulations apply
65
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS OFFLINE TECHNOLOGY - IF NEEDED The Central Battery System SPS is based on the Offline technology. Thanks to this technology, it is possible to minimize energy losses during mains operation and thus increase durability and reduce operation costs. In practice, it is possible to supply devices connected to SPS directly from the mains. During a normal mains operation, the system control unit and a unit responsible for monitoring accumulator parameters are supplied with power. The supply voltage is monitored on a regular basis and in case of its loss (after about 160ms) the converter starts operating and converts the constant voltage of 24 VDC from accumulators into alternating voltage for output (230 VAC 50 Hz sinus). Advantages OFFLINE: • Inconsiderable energy losses during mains power operation • low working temperature • increased system component durability • low operation costs due to low damage rate • low noise emission during mains operation SPS block diagram:
The block diagram of the emergency supply central system SPS.
66
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS CONTROL UNIT – GENERAL DESCRIPTION The system control unit has a clear signaling panel serving to display the most important system statuses, i.e. mains operation, batterybased operation, inverter failure, charger failure, etc. The statuses are displayed via colored diodes. Additionally, the panel is equipped with two buttons intended for testing and resetting protection against serious discharge. All indicators and buttons were designed in accordance with requirements of PN-EN 50171 standard. To configure inputs/outputs, circuit operation modes, test parameters and to operate them, a complex www server interface is used or Smart Visio application is applied.
Features: • Compliance with the following standards: EN 50171, EN 50272-1, EN 50272-2, EN 60950-1 • Measuring voltage and current of battery charging/discharging • Monitoring circuit safety devices • Built-in internal power supply loss sensor with a switch point in compliance with EN 60950-2-22 • 4 potential-free inputs configurable as a switch, phase cancellation sensor, interlock • 4 voltage inputs configurable as a switch, phase cancellation sensor, interlock • 4 potential-free outputs configurable as the mains operation indicator, battery-based operation, defects, emergency operation, interlock, test, etc. • Protection against battery deep discharge • Configuration and operation through the built-in www Server and SmartVisio app • MODBUS and BACNET protocol included • Configuration of non-maintained operation, maintained operation, switchable operation • Possible to set any work modes, phase loss sensors and duration time • Remote configuration, data import/export, access to log book and firmware updates • Possible to send e-mails automatically • Functional test (short) and duration test (long) automatically or manually activated • Supporting many languages • Programmable late switch into emergency mode recovery time • Status indicators: mains operation, battery operation, emergency operation, device blocked, test, charger failure, battery failure, inverter failure, circuit failure, protection against deep discharge
67
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS CONTROL UNIT – CONNECTING WIRES
Supply
potential-free IN1 potential-free IN2 potential-free IN3 potential-free IN4
230V AC input SW1
230V AC input SW2
230V AC input SW3
230V AC input SW4
potential free OUT4
potential free OUT3
68
potential free OUT2
potential free OUT1
SPS main board and connection method
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS CONTROL UNIT – REMOTE CONTROL SPS system is equipped in standard with RJ45 socket and freely programmable IP address. Thanks to this, it`s possible to control and configure the system remotely via standard web browser. An access to the web interface is protected by password.
Remote control – example of menu
ACCES POINT
ROUTER INTERNET
MAX 100m MAX 100m
MAX 100m
MAX 100m MAX 100m MAX 100m
MAX 100m
max 250 W
max 250 W
max 250 W
max 250 W
FIRE ZONE
FIRE ZONE
max 250 W
max 250 W
max 250 W
max 250 W
max 250 W
max 250 W
FIRE ZONE
STAIRCASE
max 250 W
max 250 W
max 250 W
max 250 W PH90*
FIRE ZONE
* national regulations apply
69
FIRE ZONE
FIRE ZONE
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS SPS TECHNICAL DATA – COMPARING SPS Technical data
SPS 300
SPS 600
SPS 1000
SPS 1500
SPS 2000
AC: 1-phase 230V ± 10%, 50/60Hz
AC: 1-phase 230V ± 10%, 50/60Hz
AC: 1-phase 230V ± 10%, 50/60Hz
AC: 1-phase 230V ± 10%, 50/60Hz
AC: 1-phase 230V ± 10%, 50/60Hz
Protection class: I IP rating : IP20 Output voltage 230V AC 50Hz Working temperature: -5°C to 30°C
Supply voltage
Battery capacity
26Ah
55Ah
80Ah
120Ah
150Ah
1h
238W
475W
725W
1090W
1365W
3h
99W
209W
303W
458W
574W
8h
42W
92W
133W
203W
256W
6
6
12
12
12
250W
250W
250W
250W
250W
Power connector
2,5
2,5
2,5
2,5
2,5
Circuit connector
2,5
2,5
2,5
2,5
2,5
Power connector 24V out
2,5
2,5
2,5
2,5
2,5
24V power out
2,5
2,5
2,5
2,5
2,5
Switch monitoring connector
2,5
2,5
2,5
2,5
2,5
Potential-free input connector
2,5
2,5
2,5
2,5
2,5
Signaling output connector
2,5
2,5
2,5
2,5
2,5
17xM20
17xM20
17xM20
25xM20
25xM20
Max. power
Number of circuits Max. circuit load Terminal connection [mm2]
Cable penetrators Max. length of circuits
1,5
200
2,5 Weight [kg] Dimensions [mm]
70
300 25,4 kg
51,5 kg
59,6 kg
114,3 kg
142,5 kg
660x355x180
660x355x230
730x400x260
880x450x240
1000x530x280
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS SPS TECHNICAL DATA – COMPARING MECHANICS SPS 300
220
660
360
SPS 600
260
800
400
SPS 1000
240
940
450
71
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS
SPS 1500
280
1100
490
SPS 2000
280
1200
490
72
EMERGENCY LIGHTING SYSTEMS
SPS CENTRAL BATTERY SYSTEMS ACCESSORIES REMOTE SIGNALING PANEL – PZS The panel is intended for remote control of basic system statuses, such as: readiness for work, battery-based operation, defect. To lock the continuous operation, the built-in key must be used. This solution secures the system against access of unauthorized persons.
Technical specifications Connection (wire size)
PZS 1,5mm2 80x80x55mm Wall-mounted
Part No.
WCB 0000006C
80
Max. dimensions (HxWxD) Mounting
80
PHASE LOSS SENSOR: CZF-01 The quick-acting phase loss sensor is used to monitor the voltage in primary lighting switchboards to ensure that specific circuits or the whole system are energized for emergency operation. The voltage changeover threshold is as per PN-EN 60598-2-22. Technical specifications Supply voltage Switchover threshold
CZF 230/400V 50Hz as per PN-EN 60598-2-22
Mounting
DIN-3 (TH35)
Delay time
< 200 ms
Connection (wire size) Contact Dimensions (HxWxD)
129x17,5x170 mm WCB 0000007
56,4
Part No.
2,5 mm2 230V/50Hz 0.5A
98,00
73
17,50
CBS CENTRAL BATTERY SYSTEMS SYSTEM OVERVIEW SMART – SWITCHING METHOD
76
AND REVISION TECHNOLOGY LPS SYSTEM DESCRIPTION
77 78
CM-NET CONTROL MOdULE
79
CCM CHARGING CONTROL MODULE
81
BST 430 - BOOSTER
81
ML-E 2X6A CIRCUIT MODULE
82
ML-E 4X3A CIRCUIT MODULE
82
ML-E 8X1,5A CIRCUIT MODULE
83
HUB MODULE
83
LS-24 SENSOR MODULE
84
LS-230 SENSOR MODULE
84
ELS-230 EXTERNAL MODULE
85
CZF LON EXTERNAL MODULE
85
CZF-01 PHASE LOSS SENSOR
86
ETA 2 SWITCHING MODULE
86
ADN ADDRESS MODULE
87
MP 500 SWITCHING MODULE
88
MP 4A SWITCHING MODULE
89
PZS LON MODULE
90
PZS MODULE
91
SD MEMORY CARD
91
SYSTEM STRUCTURE
92
SAMPLE SYSTEM DIAGRAM
93
COMPARISON OF CBS SYSTEMS
94
EMERGENCY ESCAPE LUMINAIRES
96
ESCAPE ROUTE LUMINAIRES
98
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM SYSTEM OVERVIEW The CBS central power supply system is a an advanced, reliable and user-friendly central battery system, designed in compliance with the requirements of VDE 0108, PN-EN 50171 and PN-EN 50172 standards. The system provides the possibility of monitoring circuits, luminaires or both. A CBS unit is equipped with a controller to supervise the operation and status of the entire system, and to register all events according to the requirements specified in PN-EN 50172. A wide range of luminaire control options enables easy modification of functions as and when required by the user. The operating mode of a luminaire is set at the controller or via SMART VISIO software application and in either case the required mode can be configured at any time. A built-in timer can also be used to activate, for example, the nighttime mode of a luminaire.
The CBS can be flexibly adapted to any building or facility by diversifying the power supply plan of fire zones or the routing of emergency lighting circuits by implementing CBS LPS or CBS PBS substation systems, respectively. The whole system will not fail if the central control unit is damaged, because its substations will take over the control of branch circuits and luminaires, which considerably increases the safety level in the building or facility. Routine periodic tests, the event log and system configuration data can be stored on an SD memory card provided with the unit. Additionally, all that data is stored in the non-volatile memory of the control unit. With the safety of firefighting and rescue teams in mind, in all CBS units the IT earthing system
The system comprises an intelligent charger which controls the charging process and protects the batteries from damage, and thanks to the use of an active PFC function, fixed costs of operation are considerably reduced.
Features: • Modular design for quick assembly • Freely-programmable operating modes for each circuit (circuit monitoring) • Freely-programmable operating mode for each luminaire, irrespective of the circuit settings • Monitoring of each luminaire and circuits • Possibility to adapt the system to the layout of fire zones • Possibility to assign a text description to each luminaire, circuit and control modes • Four fully-programmable function keys • Four keys with preset functions • Temperature and voltage monitoring of single accumulator
76
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM SMART TECHNOLOGY SWITCHING METHOD AND REVISION TECHNOLOGY A conventional installation requires that the operating mode of each circuit is specified as early as at the design stage. Any possible changes or errors may incur extra costs or even make necessary corrections impossible. In order to eliminate such inconveniences, AWEX has introduced a new fully automatic technology to monitor and control each luminaire in a circuit: Switching Method And Revision Technology The SMART enables installation of luminaires operating in three different modes: continuous, intermittent and switched, in a single circuit. Programming and control of the luminaires is provided by means of power supply cables and therefore no extra communication cables are required. The SMART functionality is available for luminaires fitted with appropriate ADS address modules. The operating modes are set up from the main controller and no adjustments have to be made at the luminaires.
SMART ADVANTAGES: • Installation of luminaires operating in different modes within a single circuit • Flexible design and installation • Smaller number of circuits • Lower installation costs • Operating modes of the luminaires can be changed at any time
CONVENTIONAL LIMITATIONS: As compared with the SMART system, a conventional system has the following limitations: • Only one operating mode is available in the branch circuit • Higher installation costs • Higher costs of subsequent changes • Operating mode is difficult or impossible to change
77
MAINTAINED
NON-MAINTAINED
OPERATION
OPERATION
SWITCHED MODE
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM LPS SYSTEM DESCRIPTION The LPS is a state-of-the-art, reliable and user-friendly central battery system manufactured by AWEX. It has been designed to meet applicable standards and comprises the proprietary SMART technology. From the functional point of view, the LPS is equivalent to the CBS, however due to its compact size and reduced power output it is intended for smaller-sized locations or in places where the power sources of emergency luminaires must be diversified (as a group). The LPS can power luminaires with a total power output of 1500W for 1h or 500W for 3h. Thanks to four sensor
inputs provided in the control module, fire zones can be managed by means of phase loss sensors (CZF) which monitor the voltage of the power supplied to the zones, The system is upgradable with ELS230 modules with 9 potential control inputs. Line modules have separate protection for AC and DC mode, which considerably increases the safety of emergency lighting activation in the building/facility. In the DC mode, the system operates as an IT network (insulated).
Features: • Automatic performance of tests • Automatic detection and integration of new luminaires • Circuit monitoring • Luminaire monitoring • Luminaire programming and setting up from the system controller • Communication with luminaires via power supply cable • SMART technology (adjustable luminaire modes) • Separate AC and DC voltage for each output circiut in changeover module • Connection and an SD card to save, transfer and print emergency lighting system reports, according to PN-EN 50172 • Possibility to save system settings (back-up) on an SD memory card • Nighttime mode • Controlling of luminaires and system functions by means of 24V and 230V connections (internal and external) • Monitoring of the power supply at distribution switchboards and individual lighting circuits • USB port • RJ45 connector for direct communication with any computer via Ethernet • System status check by using any website browser • System management and visualization by using dedicated SMART VISIO software • Powering up luminaires with a total power output of 1500W for 1h or 500W for 3h
78
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM CM-NET CONTROL MODULE The CM-NET control module supervises and manages other modules included in the central battery system. The keys and LCD display on the front panel enable the user to set up and operate the system. System configuration is also possible through the RJ45 connector and the SMART VISIO installed on a PC. The LEDs on the front panel provide immediate visual information on the current status of the central battery system. The control module supervises the following functions: mains/battery power supply mode, battery charging, system current and voltage, insulation condition, and deep-discharge protection. Detection of a fault or error is immediately indicated and registered in the event log. The occurrence
of a short circuit or break in communication wires triggers automatic switchover of all circuits to the emergency mode. The module also offers the function of automatic searching and adding of all luminaires connected to the system. The controller enables making firmware upgrades of all internal system modules, as well as address modules. Thanks to a timer function, the operating mode of a luminaire can be changed according to its assigned, configurable program. The control module has programmable function keys which can be used to switch the system immediately into the service mode or the IT mode.
Features: Configuration: • Eight configuration keys • SD card • RJ45 connector for SMART VISIO
System control: • Four 24V potential-free inputs that can be programmed for: functional test, battery test, sensor input etc. • Four function keys: • Lock • Functional test activation • Battery test activation • Deep discharge error reset • Four programmable function keys: • Switching circuits for AC power supply • Switching circuits for DC power supply • Alarm reset: leakage fault • Alarm reset: emergency mode • Functional test without preheating • Three LON communication buses • 2 timers • 3PH phase loss sensor connector • Remote system lock input
External communication: • Current system status indication • LED indicators • LCD display • BMS – BACnet, LonWorks • Three potential-free outputs for PZS or BMS
79
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM CM-NET CONTROL MODULE Technical specifications
80
Display
Graphic LCD 128x4
Keypad
8 function keys and 8 control keys
LED indicators
4 LED indicators • mains supply mode • battery supply mode • fault • deep discharge
Interfaces
• • SD/MMC cards • • RJ45 – BACnet • • LON x 3 – Lonworks
Potential-free inputs
• locks • phase loss sensor • 4 programmable inputs
Outputs
• 3 programmable relay outputs 24V/0.5A
Acoustic signalling
programmable buzzer
Displayed information
• mains voltage • battery voltage • battery charge current (+) • battery discharge current (-) • date and time • type of test in progress • charging disturbance/error • deep discharge • manual reset • recovery delay • insulation failure • circuit failure • circuit overload • fuse failure • substation failure • circuit and control names • system and control parameters • communication errors • event log review (including substations) • switching substation failure • active critical groups • type of system lock
Event log
Registered on an SD card; reading and printing without dedicated software
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM CCM CHARGING CONTROL MODULE CCM module is responsible for accumulators charging process. Charging process is realized by BST - 430W booster. It's possible to
use larger accumulators by increasing quantity of BST - 430W booster, up to 16 pcs.
Features: • Supporting and controlling the BST-430 charge booster • Monitoring leakage conductance in branch circuits • Protection against deep discharge • The ability to control individual batteries in cooperation with BC battery control system • Fan control • Two connectors for the measurement of: • current • temperature • RS interface for communication with the BC system • Displaying the current status of the charger • Three programmable potential-free outputs • Status indicator LED Technical specifications
LED indicators
• Battery fault • Leakage fault • Stand by • Fault • Status
Protection against deep discharge
183,6V DC
Outputs
• 3 programmable relay
Max. Booster
16 pcs
BST 430 - BOOSTER The Booster module ensures battery charging on the basis of UI characteristic with temperature compensation according to PN-EN 50171. The charging algorithm of the charger is supervised by the control module. The charger is equipped with an internal active PFC module, which guarantees that the power factor is close to 1.0 (λ≈1).
The booster is used for charging batteries with the voltage rated at 216V. The maximum power of the charger is 430W.
Technical specifications Charging voltage
Boost charging Float charging
Max. power Booster
430W ± 5%
Max. current Booster
LED indicators
Protection against deep discharge
81
265V DC 246V DC
2A ± 5% • Charging • Redy • Fault • Status 183,6V DC
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM ML-E 2X6A CIRCUIT MODULE The 2x6A module supplies power to one branch circuit.
Features: • Controlling SMART luminaires • Monitoring up to 20 luminaires per circuit • Unique addresses programmed during production process • Freely programmable work mode • Independent control of each circuit • Independent control of each luminaire • Identification of each luminaire • Fault, module status and circuit status indicators • Service pin • Supplying luminaires with PN-EN 60347-2-7 ballasts and luminaires with LED and incandescent light sources • Adjustable AC/DC changeover time Technical specifications Number of circuits
2
Max. circuit length
up to 600m
Max. load Max. inrush current Switch-over time Fuse
6A 180A/ms 100 - 2500ms 2x10AT / 250V / 6,3x32
ML-E 4X3A CIRCUIT MODULE The 4x3A module supplies power to two branch circuits.
Features: • Controlling SMART luminaires • Monitoring up to 20 luminaires per circuit • Unique addresses programmed during production process • Freely programmable work mode • Independent control of each circuit • Independent control of each luminaire • Identification of each luminaire • Fault, module status and circuit status indicators • Service pin • Supplying luminaires with PN-EN 60347-2-7 ballasts and luminaires with LED and incandescent light sources • Adjustable AC/DC changeover time • Adjustable emergency duration for each circuit Technical specifications Number of circuits
4
Max. circuit length
up to 600m
Max. load Max. inrush current Switch-over time Fuse
82
3A 180A/ms 100 - 2500ms 8x5AT / 250V / 6,3x32
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM ML-E 8X1,5A CIRCUIT MODULE The 8x1,5A module supplies power independently to four branch circuits. Features: • Controlling SMART luminaires • Monitoring up to 20 luminaires per circuit • Unique addresses programmed during production process • Freely programmable work mode • Independent control of each circuit • Independent control of each luminaire • Identification of each luminaire • Fault, module status and circuit status indicators • Service pin • Supplying luminaires with PN-EN 60347-2-7 ballasts and luminaires with LED and incandescent light sources • Adjustable AC/DC changeover time • Adjustable emergency duration for each circuit Technical specifications Number of circuits
8
Max. circuit length
up to 600m
Max. load Max. inrush current Switch-over time Fuse
1,5A 180A/ms 100 - 2500ms 16x2,5AT / 250V / 6,3x32
HUB MODULE The Lon Hub module is a component of the central battery system. It is installed in PBS-20/H substations. PBS-40/H. The module is designed to enable communication of the CM-NET control module with line modules
installed in substations (remote cabinets). The LON3 interface is used for communication with the main cabinet.
Features: • Communication with up to 5 modules: ML-S line modules and LS 24 or LS 230 sensor modules • Service pin • Address setting switch to set the HUB module address within the range of 1-10 • Power supply of up to 5 modules • Built-in termination of a communication line • Fault and module status indicators • Push-buttons to: add/remove, select and configure modules
Technical specifications Number of addresses Number of supported modules Connectors
83
1-10 5 • LON in – LON3 bus input • LON out – LON3 bus output • Term – for bus termination activation
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM LS-24 SENSOR MODULE This potential-free input module monitors up to 8 inputs in a 24V current loop. The inputs enable selective activation of luminaire control groups by assigning phase loss sensors to them. In the event of a voltage loss at the primary lighting switchboard, luminaires with control groups assigned to them are activated.
The inputs can also be used as potential-free inputs for building management systems (BMS) to activate individual control groups. The system can integrate up to 10 modules of the LS-24 and LS-230 type.
Features: • Monitoring of the phase loss sensor current loop • Monitoring of the 24V DC current loop • Possibility of joint control with a BMS via potential-free inputs • Programmable recovery delay • Service pin • Fault and module status indicators • Active input indicators • Possibility of sensor input negation
Technical specifications Number of inputs Recovery delay Connectors
Eight 24V current loop inputs from 1 s to 1 h 2,5mm2
LS-230 SENSOR MODULE The module has eight 230V AC potential-free inputs. It enables setting up emergency luminaire control groups with the power supply of primary lighting circuits. The logic of the inputs can be inverted, so that the input is in active state at 0V and inactive at 240V. This functionality enables monitoring of individual protections of the primary lighting system. The
inactive state recovery delay time is programmable within the range of 1 second to 1 hour. The system can integrate up to 10 modules of the LS-24 and LS-230 type.
Features: • Monitoring of primary lighting switches • Programmable inversion of input logic • Possibility of monitoring individual primary lighting protections • Programmable recovery delay time • Service pin • Fault and module status indicators • Input status and inversion indicators
Technical specifications Number of inputs Recovery delay Connectors
84
Eight 230V AC potential inputs from 1 s to 1 h 2,5mm2
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM ELS-230 EXTERNAL MODULE The ELS-230V sensor module is used for monitoring of 230V AC potential signals from primary lighting switches in order to activate an emergency luminaire control group along with the primary lighting. The module has 9 inputs. The inputs can be inverted to monitor individual circuit protections. The ELS-230 module can also serve as a phase loss sensor. The control inputs can be assigned the recovery delay function. The module has a
service pin, rotary address selector switches, a LON connector for data transmission (with a built-in terminating resistor) and a 24V power supply connection. The module is also equipped with LED indicators displaying the current logic settings and the status of individual inputs.
Features: • Monitoring of primary lighting switches • Function of a phase loss sensor • Programmable inversion of input logic • Possibility of monitoring individual primary lighting protections • Programmable recovery delay time • Service pin • Fault and module status indicators • Input status and inversion indicators
Technical specifications Power supply Protection class Ingress protection Operating temperature range Potential inputs Phase loss control Recovery delay Data transmission Number of addresses Switching threshold Dimensions (LxWxD) mm Connectors
24 V DC ± 5V I IP21 -10oC to + 40oC 9 isolated inputs Monitoring of up to 3 phases from 1 s to 1 h LON 1-32 as per 60598-2-22 105x85x60 2,5mm2
CZF LON EXTERNAL MODULE The CZF LON sensor module is used for monitoring of 230V AC potential signals from primary lighting switches in order to activate an emergency luminaire control group along with the primary lighting. The module has 3 inputs. The inputs can be inverted to monitor individual circuit protections. The CZF LON module can also serve as a phase loss sensor. The control inputs can be assigned the recovery delay function. The module has a
service pin, rotary address selector switches, a LON connector for data transmission (with a built-in terminating resistor) and a 24V power supply connection. The module is also equipped with LED indicators displaying the current logic settings and the status of individual inputs.
Features: • Monitoring of primary lighting switches or functioning asa phase loss sensor • Programmable inversion of the action logic of individual inputs • Possibility of monitoring individual primary lighting protections • Programmable recovery delay time • Service pin • Fault and module status indicators • Input status indicators
Technical specifications Power supply Protection class Ingress protection Operating temperature range Potential inputs Phase loss control Recovery delay Data transmission Number of addresses Switching threshold Dimensions (LxWxD) mm Connectors
85
24 V DC ± 5V I IP21 -10oC to + 40oC Three isolated inputs Monitoring of up to 3 phases from 1 s to 1 h LON 1-32 as per 60598-2-22 55x90x60 2,5mm2
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM CZF-01 PHASE LOSS SENSOR The quick-acting phase loss sensor is used for voltage monitoring in primary lighting switchboards to energise specific circuits or the whole system for emergency operation.
The switching threshold is as specified in PN-EN60598-2-22.
Features: • Phase loss detection • Switch activation detection • Switchover threshold as per PN-EN 60598-2-22 • Delay time <200 ms • Mounting in DIN-3 rail
Technical specifications Power supply
230V, 50Hz, 176V-275V DC
Switchover thresholds
As per PN-EN 60598-2-22
Mounting
DIN-3 rail (TH35)
Delay time
< 200ms
Connectors Contact
2,5mm2 230V/50Hz 0,5A NO
ETA 2 SWITCHING MODULE ETA-2 is an external module supplied from the central battery system (CBS). It is used for switching single luminaires or a group of luminaires connected to outputs OUT1 and OUT2. If a phase loss sensor and a 216V DC emergency lighting switch are triggered, the module always activates both outputs. In other circumstances, the activation of those outputs depends on the manually set up operating modes. In the case of a 230V AC power supply, OUT2 is activated depending on the settings of a CS or BUS mode. In the CS mode, OUT2 is activated by a switch. In the BUS mode, the output is always active to enable controlling external luminaires, for example by means of a DALI controller.
The OUT1 can be set up to work in three operating modes: always ON (maintained operation), always OFF (non-maintained operation) or depending on the status of the switch. Luminaires connected to OUT1 can also be controlled by an external controller operating in the BUS mode when the output is always active.
Features: • Phase loss detection • Switch activation detection • Emergency mode detection • Fault indication by relay closure • Multiple operating modes: relay outputs activated depending on switch settings
Technical specifications Power supply Ingress protection Protection class Max. power Potential outputs
IP20 I 920 VA 1x1A, 1x4A
Wire terminals
max. 2,5mm2
Temperature range
-10oC to +40oC
Mounting Dimensions (LxWxD) Weight
86
220 - 240V 50-60Hz, 216V DC ± 20%
DIN rail 88x90x58mm 0,1kg
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM ADN ADDRESS MODULE The ADN address module is used for monitoring and controlling (emergency) luminaires. The control is provided by a freely programmable control group. The module supports luminaires with LED, fluorescent or incandescent light sources. It is designed for use in circuits with luminaire
monitoring and a mixed mode of operation: continuous, intermittent and switched. The module is also equipped with a control input for the monitoring of a local switch.
38
22
Dimensions [mm]:
134
Technical specifications Power supply Ingress protection Max. power Light source Max. Ambient temperature range Mounting Weight
87
230V 50Hz , 216V DC ± 20% IP20 120W 1-120W -20oC to +50oC Inside the luminaire 0,1kg
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM MP 500 SWITCHING MODULE The MP500 is used for activating the mains supply mode of a luminaire of a group of luminaires by means of a primary lighting switch. The module
enables application of primary lighting luminaires as emergency luminaires.
Module dimensions in mm
18,5 5 18,5
157
15
7
21
44
18
157
Technical specifications Power supply
230V 50Hz, 216V DC ± 20%
Ingress protection
IP20
Max. power
500 VA 3x2,5mm2
Wire terminals
-10oC to +40oC
Max. Ambient temperature range Mounting
Inside the luminaire
Weight
PHASE LOSS
L(+) N(-) L N
POWER
ON OFF
TO
CB
0,1kg
NO
ON
~230V AC
0V
ON
ON
NO
OFF
~230V AC
0V
OFF
OFF
YES
ON
~0V
~230V DC
ON
OFF
YES
OFF
~0V
~230V DC
ON
OFF
TO
MP 500
L(+) N(-) emerency lighting fittings
OFF ON
L N
basic lighting fittings
CZF
CB – Central battery ML – Linear module input CZF – Phase loss sensor TO – Basic lighting switch board MP500 - switching module LS-24 – Potential free input module
88
CB ML
LS-24
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM MP 4A SWITCHING MODULE The MP 4A is used for activating the mains supply mode of a luminaire of a group of luminaires by means of a primary lighting switch. Thanks to the applied logic (see Fig. below) of the control input, when the
primary lighting fails all luminaires in this group are switched to the emergency mode.
Module dimensions in mm
18,5 5 18,5
157
15
7
21
44
18
157
Technical specifications Power supply
230V 50Hz, 216V DC ± 20%
Ingress protection
IP20
Max. load
4A 3x2,5mm2
Wire terminals
-10oC to +40oC
Max. Ambient temperature range Mounting
Inside the luminaire
Weight
PHASE LOSS NO
0,1kg
L N L(+) N(-)
CB POWER SUPPLY Pos. 1
230V AC
ON
MP 4A
L(+) N(-)
emerency lighting fittings
OFF
NO
Pos. 2
230V AC
OFF
ON
YES
Pos. 1
230V DC
ON
OFF
YES
Pos. 2
230V DC
ON
OFF
TO
W
L N basic lighting fittings
CB – Central battery ML – Linear module input CZF – Phase loss sensor TO – Basic lighting switch board MP 4A - switching module W - single-pole double-throw switch
89
CB ML
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM PZS LON MODULE The PZS LON module is used for monitoring of Central Battery Systems connected via LON buses. Thanks to the PZS LON module the user can check the name and the status of the connected system. Additionally, all faults and errors that have occurred in each of the connected systems can be viewed.
The module has an LCD display and LEDs indicating: AC operation, DC operation, Lock, Fault; the panel is equipped with 5 push-buttons and a key.
Features: • Reading and viewing the current status of all systems connected to the module • Plug & Play device – no configuration required • System monitoring within a single group (up to 10 systems); selection of 1-4 groups • Possibility of locking all connected system components by pushing the Block button • Configurable lock for selected systems (not all systems have tobe locked by the module; monitoring only possible) • Configuration is saved when the power supply is interrupted • Loss of communication is notified by the module (timeout) • Loss of communication with the system removes any previously applied locks • Acoustic signalling of system faults or errors (can be postponed for a specific time) • LED indicators on the front panel: AC supply mode, DC supply mode, Lock, Fault • LED status depends on all monitored systems
Technical specifications Power supply Protection class Ingress protection
-10oC to +40oC
Number of monitored systems
from 1 to 10
Connectors Max. dimensions (HxWxD)
Strip X1 Point
90
L11
L12
LON1 LON2
-24VDC
+24VDC
Mounting
LON1
I IP21
Operating temperature range
Data transmission
LON1
24 V DC ± 5V
LON 1,5mm2 130x100x40mm Wall-mounted
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM PZS MODULE This panel enables remote checking of some basic operating statuses of the system, such as: stand-by (mains operation), battery operation or fault.
A built-in key can be used to lock continuous and emergency operation. This prevents the system from unauthorized tampering.
Technical specifications 1,5mm2
Connectors Max. dimensions (HxWxD)
82x80x55mm
Mounting
Wall-mounted
Connection of the PZS module Switch ON
– lock applied
Switch OFF
– lock removed
Loop control
– lock is removed in case of a short or open circuit
SD MEMORY CARD An SD memory card enables saving the event log and subsequent opening and printing it on a PC with standard word processing software.
Using the card, the system configuration can also be stored and the firmware can be updated.
Data saved on the card: • Text description of the system • Description of each circuit • Description of each luminaire • Description of each control mode • Description of each control group • Complete configuration of the system • Event log • Firmware
91
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM SYSTEM STRUCTURE Communication with ELS 230V external modules, substations with a controller and substations with a HUB module (remote cabinets) is based on the LonTalk communication protocol. Three LonTalk interfaces are implemented in the controller. The first – LON1 – is used for communication
between systems with a controller and BMS type systems. The LON2 interface is intended for communication with external sensor modules of the ELS 230 type, whereas LON3 is reserved for substations equipped with a HUB module.
Central battery system communication diagram
Maximum number of system groups: 4
GROUP 1
GROUP 2
GROUP 3
GROUP 4 UNADDRESSED SYSTEM
GROUP topology
Group 1
A group may comprise up to 10 systems. System 1 is the MASTER. The other systems are SLAVES. Total length of LON 1 bus in the linear topology is 900m (JY(ST)Y 2x2x0.8mm2 or YTSKYeq) Each system can be connected to the dedicated BMS application – Smart VISIO
SYSTEM topology
CZF LON NR2
The system can be upgraded with PBS.../H and PBS susbstations. Maximum number of components: – 10 HUB modules – 10 control units – 32 sensor modules
92
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM SAMPLE SYSTEM DIAGRAM
Central battery circuits CB/02 circuit control signal
Central battery substation circuits L=230V
CB/02 CIRCUIT MONITORING
CB/02 (n=MAX 20 or 6A)
CB/01/01
CB/01/02
CB/01/03
CB/01/n (n=MAX 20)
PBS/01/n (n=MAX 20)
PBS/01/03
PBS/01/02
PBS/01/01
PBS/02/n (n=MAX 20)
PBS/02/03
PBS/02/02
PBS/02/01
CB/01 LUMINAIRE monitoring (mixed mode) PBS/02 – LUMINAIRE monitoring
AC - 230V LON LON
PBS/01 – LUMINAIRE monitoring (mixed mode)
DC - 216V LAN
AC - 230V
230V MAINS
ELS-230 module
Phase loss sensor CZF LON
PBS
Phase loss sensor
BMS
MONITORING OF L1, L2, L3 230V
93
CBS
MONITORING OF L1, L2, L3 230V
Remote status panel PZS LON
SMART VISIO
MONITORING OF L1, L2, L3 230V
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM COMPARISON OF CBS SYSTEMS CABINETS
CBS/32L-E
CBS/80L-E
CBS/40C-E
CBS/48C-E
CBS/72R-E
CBS/48R-E
CBS/32C-E
400V/230V
400V/230V
400V/230V
400V/230V
400V/230V
400V/230V
230V
50Hz
50Hz
50Hz
50Hz
50Hz
50Hz
50Hz
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
2050x800x400
2050x800x400
2050x800x400
2050x800x400
1200x800x400
1200x800x400
1800x600x350
Steel
Steel
Steel
Steel
Steel
Steel
Steel
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
Right hand
Right hand
Right hand
Right hand
Right hand
Right hand
Right hand
NO*(1)
NO*(1)
NO*(1)
NO*(1)
NO
NO
NO*(1)
single-sided
single-sided
single-sided
single-sided
single-sided
single-sided
Single-sided
IP21
IP21
IP21
IP21
IP21
IP21
IP21
I
I
I
I
I
I
I
top & bottom
top & bottom
top
top
top
top
top
Power supply parameters Mains voltage (3PH or 1PH) Frequency Earthing system Technical parameters Dimensions (HxWxD) [mm] Material Colour Door type Cabinet base Door lock Electrical parameters Ingress protection Protection class Cable glands Max. number of substations*(3)
6/2
6/2
2/ -
2/ -
2/ -
2/ -
1/ -
Mains power connection size
35mm2
35mm2
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
Battery connection size
35mm2
35mm2
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2
2
2
2 (2)
2 (2)
2 (2)
2 (2)
Substation power supply connection size
16mm
Max. size of branch circuit connection
4mm2
16mm
4mm2
10mm *
10mm *
10mm *
10mm *
10mm2
4mm2
4mm2
4mm2
4mm2
4mm2
5,5kW
600m
Max. length of branch circuit Power parameters 20kW
20kW
5,5kW
5,5kW
5,5kW
5,5kW
Max. main protection [A]
Max. system power
100
100
25
25
25
25
25
Max. substation protection [A]
63
63
10
10
10
10
10
Max. battery protection [A]
100
100
50
50
50
50
50
Equipment System controller
1
1
1
1
1
1
1
Power supply system 24V DC
1
1
1
1
1
1
1
Charging controller
1
1
1
1
1
1
1
Booster 430 W
1
1
1
1
1
1
1
16
9
2
2
4
2
1
5
12
7
7
11
7
6
Max. number of booster modules Max. number of modules Max. Number of circuits
32
80
40
48
72
48
32
Compact size
NO
NO
YES
YES
NO
NO
YES
94
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM
PBS/80-E
PBS/56-E
400V/230V 50Hz
PBS/24-E
PBS/48H-E*(4)
PBS/32H-E
PBS/16H-E
LPS/24-E*(5)
PBS/32-E
PBS/40-E
400V/230V
230V
400V/230V
230V
230V
230V
230V
230V
50Hz
50Hz
50Hz
50Hz
50Hz
50Hz
50Hz
50Hz
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
TN-S-C/IT
2050x800x400
1200x800x400
1200x800x400
1000x600x350
700x570x300
1000x600x350
700x570x300
500x420x300
1200x600x350
Steel
Steel
Steel
Steel
Steel
Steel
Steel
Steel
Stal
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
RAL 7035
Right hand
Right hand
Right hand
Right hand
Right hand
Right hand
Right hand
Right hand
Right hand
NO*(1)
-
-
-
-
-
-
-
-
Single-sided
Single-sided
Single-sided
Single-sided
Single-sided
Single-sided
Single-sided
Single-sided
Single-sided
IP21
IP21
IP21
IP21
IP21
IP21
IP21
IP21
IP21
I
I
I
I
I
I
I
I
I
top & bottom
top
top
top
top
top
top
top
top
-
-
-
-
-
-
-
-
-
35mm2
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
35mm2
16mm2
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
16mm2*(2)
-
-
-
-
-
-
-
-
-
4mm2
4mm2
4mm2
4mm2
4mm2
4mm2
4mm2
4mm2
4mm2
600m
17kW
11kW
11kW
11kW
8kW
11kW
8kW
5,5kW
1,5kW
80
-
-
-
-
-
-
-
16
-
-
-
-
-
-
-
-
-
80
-
-
-
-
-
-
-
25
1
1
1
1
1
2xHUB
1xHUB
1xHUB
1
1
1
1
1
1
-
-
-
-
-
-
-
-
1
-
-
-
-
-
-
-
-
1
-
-
-
-
-
-
-
-
-
12
9
6
7
4
8
5
3
4
80
56
32
40
24
48
32
16
24
-
-
-
-
-
-
-
-
YES
1
(*1) Optionally, cabinets may be supplied with a 10 cm or 20 cm base (*2) Special execution of a cabinet enables larger diameter connections with a reduced number of substations (*3) Option; the number of substations depends on the type of power supply (1PH/3PH) (*4) Remote cabinet, without a controller, equipped with a Lon HUB module (*5) Optional execution of: LPS/4-E, LPS/8-E, LPS/16-E, LPS/24-E
95
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM EMERGENCY ESCAPE LUMINAIRES AXN CBS series Luminaire type
Surface-mounted, ceiling, wall, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W or 6W
IP Rating
IP42 lub IP65
Oprawa AXNC, AXNR, typu:AXNO, AXN AXNU, AXNA 220-240V AC 50-60Hz
175-275V DC
LED
IP65
AXP CBS series Luminaire type
Recessed-mounted, ceiling, wall, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W or 6W
IP Rating
IP20 or IP65/20
AXPC, AXPR, AXPO, AXPU, AXPA 220-240V AC 50-60Hz
175-275V DC
LED
IP20
LOVATO II CBS series Luminaire type
Surface-mounted, ceiling, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP41
LV2C, LV2R, LV2O, LV2U, LV2A Oprawa typu: LVPC, LVPO 220-240V AC 50-60Hz
175-275V DC
LED
IP41
LOVATO P CBS series Luminaire type
Recessed-mounted, ceiling, C, R, O, U, A optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
LVPC, LVPR, LVPO, LVPU, LVPA 220-240V AC 50-60Hz
175-275V DC
LED
IP20
EYE LED CBS series Luminaire type
Recessed-mounted,ceiling, R and U optics
Light source
PowerLED 1W, 2W, 3W
IP Rating
IP20
EY, EYR, EYU, EYK, EYKR, EYKU 220-240V AC 50-60Hz
175-275v DC
LED
IP20
220-240V AC 50-60Hz
175-275V DC
LED
IP20
220-240V AC 50-60Hz
175-275V DC
LED
IP20
220-240V AC 50-60Hz
175-275V DC
LED
IP66
175-275V DC
LED
IP65
220-240V AC 50-60Hz
175-275V DC
LED
T5 G5
220-240V AC 50-60Hz
175-275V DC
LED
T5 G5
SPY II CBS series Luminaire type
Inside primary luminaire
Light source
LED 1W, 2W, 3W
IP Rating
IP20
SP2
MICRO SPOT CBS series Luminaire type
Inside primary luminaire, R or U optics
Light source
LED 1W, 2W, 3W
IP Rating
IP20
MSU, MSR
OUTDOOR LED CBS series Luminaire type
Surface-mounted, wall
Light source
LED 3x1W
IP Rating
IP66
ODB
EXIT CBS series Luminaire type
Surface/Recessed-mounted,ceiling, wall
Light source
LED 1W, 2W, 3W, 6W
IP Rating
IP65
ETS, ETE, ETL 220-240V AC 50-60Hz
HELIOS CBS series Luminaire type
Surface-mounted,ceiling, wall
Light source
LED 3W, 3x1W, 6x1W, LFL 8W, 11W, 18W
IP Rating
IP42/IP65
H, HL, HHP, HW
IP65
TIGER CBS series Luminaire type
Surface/Recessed-mounted,ceiling, wall
Light source
LED 3W, LFL 8W
IP Rating
IP22
96
TG, TL
IP65/20
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM SK-8 CBS series Luminaire type
Surface-mounted,ceiling, wall
Light source
LED 3W
IP Rating
IP44
SK–8 220-240V AC 50-60Hz
175-275V DC
LED
IP44
220-240V AC 50-60Hz
175-275V DC
LED
IP40
LED
IP40
INFINITY II CBS series Luminaire type
Surface-mounted, wall
Light source
LED 3W
IP Rating
IP40
IF2BWD
ARROW N CBS series Luminaire type
Surface-mounted, ceiling, O or C optics
Light source
LED 1W, 2W, 3x1W
IP Rating
IP40
ARNO, ARNC, ARNS 220-240V AC 50-60Hz
175-275V DC
ARROW P CBS series Luminaire type
Recessed-mounted, ceiling, O or C optics
Light source
LED 1W, 2W, 3x1W
IP Rating
IP40
ARPO, ARPC, ARPS 220-240V AC 50-60Hz
175-275V DC
LED
IP40
220-240V AC 50-60Hz
175-275V DC
LED
IP54
220-240V AC 50-60Hz
175-275V DC
LED
IP54
EDGE R CBS series Luminaire type
Surface-mounted, wall, ceiling
Light source mains mode
LED 12W, 18W, 24W
EDRE
Light source emergency mode LED 1W, 3W IP Rating
IP54
EDGE S CBS series Luminaire type
Surface-mounted, wall, ceiling
Light source mains mode
LED 12W, 18W, 24W
Light source emergency mode LED 1W, 3W IP Rating
IP54
*current list of CNBOP fire protection approvals is available at www.awex.eu **current list of products with Kitemark and ENEC is available at www.awex.eu
97
EDSE
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM ESCAPE ROUTE LUMINAIRES SK–8 CBS series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W, 2W
IP Rating
IP44
SK–8 220-240V AC 50-60Hz
175-275V DC
LED
IP44
220-240V AC 50-60Hz
175-275V DC
LED
IP40
220-240V AC 50-60Hz
175-275V DC
LED
IP40
220-240V AC 50-60Hz
175-275V DC
LED
IP41
220-240V AC 50-60Hz
175-275V DC
LED
IP20
220-240V AC 50-60Hz
175-275V DC
LED
IP20
220-240V AC 50-60Hz
175-275V DC
LED
T5 G5
IP22
175-275V DC
LED
T5 G5
IP22
LED
IP40
LED
IP40
ARROW N CBS series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
ARN
ARROW P CBS series Luminaire type
Recessed-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
ARP
TWINS CBS series Luminaire type
Surface-mounted, wall, ceiling
Light source
LED 1W, 2W
IP Rating
IP41
TW
PLEXI LED CBS series Luminaire type
Recessed-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP20
PL
ESCAPE CBS series Luminaire type
Surface-mounted, ceiling
Light source
LED 1W, 2W
IP Rating
IP20
EL
TIGER CBS series Luminaire type
Surface/Recessed-mounted, wall
Light source
LED 1W, LFL 8W
IP Rating
IP22
TL, TG
TIGER DS CBS series Luminaire type
Surface/Recessed-mounted, ceiling
Light source
LED 1W, LFL 8W
IP Rating
IP22
TSL, TGS 220-240V AC 50-60Hz
SCREEN CBS series Luminaire type
Surface-mounted, wall
Light source
LED 3x1W, 3W, 2x3W
IP Rating
IP40
SC30, SC40, SC60 220-240V AC 50-60Hz
175-275V DC
SCREEN DS CBS series Luminaire type
Surface-mounted, ceiling
Light source
LED 3x1W, 3W, 2x3W
IP Rating
IP40
98
SCS30, SCS40, SCS60 220-240V AC 50-60Hz
175-275V DC
EMERGENCY LIGHTING SYSTEMS
CENTRAL BATTERY SYSTEM HELIOS CBS series Luminaire type
Surface-mounted, wall
Light source
LED 1W, LFL 8W
IP Rating
IP42/IP65
H, HL 220-240V AC 50-60Hz
175-275V DC
LED
T5 G5
IP65
175-275V DC
LED
T5 G5
IP65
IP42
HELIOS DS CBS series Luminaire type
Surface-mounted, ceiling
Light source
LED 1, LFL 8W
IP Rating
IP42/IP65
HD, HDL 220-240V AC 50-60Hz
IP42
EXIT CBS series Luminaire type
Surface/Recessed-mounted*, wall, ceiling**
Light source
LED 1W, 2W
IP Rating
IP65
ETS+ETS/PLX, ETE+ETE/PLX, ETL+ETL/PLX 220-240V AC 50-60Hz
175-275V DC
LED
IP65
220-240V AC 50-60Hz
175-275V DC
LED
IP40
220-240V AC 50-60Hz
175-275V DC
LED
IP40
220-240V AC 50-60Hz
175-275V DC
LED
IP40
220-240V AC 50-60Hz
175-275V DC
LED
IP40
*requires an accessory for Recessed mounting **requires an accessory – plexi glass INFINITY II A CBS series Luminaire type
Surface/Recessed-mounted*, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
IF2ACS
*requires an accessory for Recessed mounting INFINITY II A CBS series
IF2AWS
Luminaire type
Surface/Recessed-mounted*, wall
Light source
LED 1W, 2W
IP Rating
IP40
*requires an accessory for Recessed mounting
INFINITY II A CBS series
IF2ALS
Luminaire type
Surface/Recessed-mounted*, ceiling
Light source
LED 1W, 2W
IP Rating
IP40
*requires an accessory for Recessed mounting
INFINITY II B CBS series
IF2BWS
Luminaire type
Surface/Recessed-mounted*, wall
Light source
LED 1W, 2W
IP Rating
IP40
*requires an accessory for Recessed mounting
*current list of CNBOP fire protection approvals is available at www.awex.eu **current list of products with Kitemark and ENEC is available at www.awex.eu
99
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION PICTOGRAMS – STICKERS Pictograms (compliant with PN-EN ISO 7010:2012)
22
23
24
25
26
27
61
29
Additional pictograms
28 CODE
PSxx
PNxx
PMxx
PBxx
PVxx
PWxx
Dimensions [mm]
100x300
100x200
125x250
150x300
200x400
300x600
Compatible with:
TL, TG, TGS, TLS
ETS
ETE, HL, HEL, HDL, HDEL, ARN, ARP, EL
TW, IF2, SK8, ETL
SC40, SCS40
SC60, SCS60
Legend: xx – pictogram ID number (see the photos above) Versatile pictogram sets (compliant with PN-EN ISO 7010:2012)
34 31
32
33 CODE
PU31
PU32
PU33
PU34
Dimensions [mm]
125x250 (125x375)*
150x300 (150x450)*
100x300 (150x600)*
100x200 (100x300)*
Compatible with:
ETE, HEL, HL, HDL, HDEL, ARN, ARP, EL
TW, IF2, SK8, ETL
TL, TG, TGS, TLS
ETS
*overall size
Arrow signs (compliant with PN-EN ISO 7010:2012)
41
42
43
44
47
48
CODE
PU41, PU42
PU43, PU44
PU47, PU48
Dimensions [mm]
125x125
150x150
100x100
Compatible with:
ETE, HL, HEL, HDL, HDEL, ARN, ARP
TW, IF2, SK8, ETL
ETS
PICTOGRAMS – FOIL Compliant with PN-EN ISO 7010:2012 CODE
PSxxF
PDxxF
PLxxF
Dimensions [mm]
125x250
150x300
150x300
Compatible with:
ARN, ARP
IF2
ETL
100
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION SYMBOLS USED The current list of valid CNBOP fire protection approvals is available at www.awex.eu
LED
Product complies with applicable European Directive requirements
T5 G5
Light source type – LED
Light source type – T5 fluorescent lamp
220-240V AC 50-60Hz
Allowable range of AC input voltage
176-275v DC
Allowable range of DC input voltage
Protection class II
Safe voltage (SELV)
Protection class III
Protection class I
Current list of products with Kiteramk and ENEC is available at www.awex.eu
24V DC
IPxx
Ingress protection e.g. IP65
STANDARD LED INDICATIONS IN RU MODULES∗ LED indication COLOUR
State
Description
Off
No power, no battery connected, test or emergency mode
Green on
Conversion kit powered / Battery is fully charged
Red on
Battery fault
Green flashing
Conversion kit powered / Battery in charging mode
Red flashing
Communication or luminaire fault
*Indications may vary depending on the module type. CODE
CAPACITY [mAh]
Ni-Cd
DIMENSIONS [mm] A x B x C x D x E x F
WEIGHT [Kg]
1000
153x179x18x15x14x4
0,076
1500
136x162x25x22x18x4
0,14
2500
VOLTAGE [V]
3.6
152x178x30x26x20x4
0,21
189x210x30x33x25x4
0,352
175x202x25x22x18x4
0,184
202x228x30x26x20x4
0,288
4000
245x270x36x33x25x4
0,452
1500
218x244x25x22x18x4
0,228
248x275x30x26x20x4
0,354
4000
303x329x36x33x25x4
0,574
1500
153x179x18x15x14x4
0,088
136x162x25xx22x18x4
0,172
4000 1500 Ni-Cd
2500
Ni-Cd
2500
Ni-MH
2500
Ni-MH
4.8
6.0
3.6
4000
152x179x30x26x20x4
0,26
1500
202x228x18x15x14x4
0,114
2500
4.8
4000 1500 Ni-MH
175x202x25x22x18x4
0,22
202x228x30x26x20x4
0,338
251x276x18x15x14x4
0,14
220x246x26x23x18x4
0,268
4000
251x276x30x26x20x4
0,398
1000
105x135x31x19x20x4
0,09
6.4
135x165x31x19x20x4
0,112
140x170x31x27x20x4
0,197
9.6
203x233x31x19x20x4
0,152
2500
LiFePO4
1500
LiFePO4
1500
6.0
3000
F
E
D
C
A B Photographs and parameters of the products shown in this catalogue are for reference only and cannot be relied upon as a legal offer. Certain parameters of supplied products may differ from the parameters of the products described in this catalogue. The appearance of actual products may slightly differ from the photographs and drawings contained in this catalogue. P.P.H.U AWEX reserves the right to discontinue products shown in this catalogue or to modify their parameter without notice.
101
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION STANDARDS AND REGULATIONS SCOPE OF APPLICATION Emergency lighting systems should be designed for all civil structures where a power cut or mains supply failure may cause a risk of injury or death to the public, a major environmental hazard or substantial property damage (Regulation of the Minister of Infrastructure of 12 April 2002). Journal of Laws No. 75, Item 690, as amended; Regulation of the Minister of Infrastructure of 12 March 2009, Journal of Laws No. 56, Item 461 and Regulation of the Minister of Infrastructure of 10 December 2010, Journal of Laws No. 239, Item 1597). According to the law, emergency lighting is required: 1. In enclosed spaces of: • cinema, theatre and concerts halls, as well as other venues • conference rooms, lecture theatres, entertainment establishments and sports halls for more than 200 people, • exhibition rooms in museums, • areas exceeding 1000 m2 in car parks provided with artificial source of light only. 2. In escape and exit routes: • in the rooms and areas specified in Section 1 above, • provided with artificial sources of light only, • at hospitals and similar facilities, as well as other buildings intended for people with a limited ability to move, • in multi-storey and high-rise public buildings and residential buildings. 3. In temporary buildings and structures, if intended as entertainment venues or other places of assembly. 4. In air-supported structures, if used as temporary production or storage facilities, where the fire load density of the fire zone does not exceed 1000MJ/m². 5. In temporary structures (tents) intended as entertainment venues. 6. control rooms and technical rooms at gas compressor stations (and elsewhere on the premises of such stations).
ELEMENTARY PROBLEMS OF EMERGENCY LIGHTING DESIGN Emergency lighting is designed for use when mains-supplied primary lighting luminaires fail. For this reason, emergency lighting luminaires have to be supplied from an independent source of electric power.
Emergency lighting
Escape route lighting
Exit Signs
Stand-by lighting
Open area illumination
High-risk task area illumination
Emergency lighting must comply with the requirements and parameters specified in PN-EN 1838 and PN-EN 50172. The main purpose of emergency lighting is to enable safe exit or evacuation of the premises where the mains supply fails. As the efficiency of light sources tends to decrease with operation time, the luminaires get dirty and other factors affect the overall performance, it is recommended to design the luminous intensity at least at 1.25 times the level recommended in applicable standards. For the calculation of the luminous intensity of emergency escape lighting only direct illumination of the surface should be considered, without any light reflected in floors, walls or ceilings. For normal activities to be carried out as usual stand-by lighting is provided.
102
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION If stand-by lighting is used as emergency escape lighting, the system should be compliant with the above-mentioned standards and any other standards applicable to the products and wiring used. If the illuminance provided by stand-by lighting is lower than the minimum illuminance level achieved with primary lighting, such lighting should only be used to ensure proper completion or interruption of activities.
ESCAPE ROUTE ILLUMINATION The purpose of illumination of an escape route is to ensure safe evacuation or exit of people from the area and to enable them to locate fire protection and suppression equipment. In the case of escape routes up to 2m wide, the average illuminance level on the floor along the centre line of the route should be at least 1 lx, and in the central band of the route, covering at least a half of the width, it should be at least 50% of the value. Wider escape routes can be treated as a number of 2m strips or they should meet the requirements for open areas. The ratio of the maximum illuminance to the minimum illuminance along the centre line of the es cape route should not exceed 40:1.
OPEN AREA ILLUMINATION (ANTI-PANIC) The purpose of anti-panic illumination of open areas is to reduce the likelihood of panic and to enable safe movement of people towards escape routes and exits by providing enough visibility to reach a place from where the escape route or exit can be located. It is recommended that escape routes or open areas should be illuminated by light falling directly onto the relevant surface; any obstructions located up to 2m above the surface should be illuminated as well. Open area illumination is used in zones with unspecified escape routes: large rooms, halls or buildings with floor area exceeding 60 m2 or less, if a greater number of people gathered there may cause an extra risk. The minimum illumination provided by emergency escape lighting in an open area should be at least 0.5 lx at the floor level across a free core area, except for an outer rim of 0.5m excluded from the area. The ratio of the maximum illuminance to the minimum illuminance of the open area should not exceed 40:1.
HIGH RISK TASK AREAS The purpose of illumination of high risk task areas is to increase the safety of persons involved in potentially dangerous processes or situations and to allow safe and correct completion or interruption of activities in such areas. In high risk task areas, the operating level of illuminance at the reference plane should not be lower than 10% of the normal illuminance required for given activities, however no less than 15 lx. The stroboscopic effect must be eliminated. The uniformity of illuminance in a high risk task area should not exceed 10:1. The minimum duration of emergency lighting should be as long as the safety hazards exist. High risk task area lighting should ensure full and continuous illuminance required at once or within 0.5 s, depending on the application. The luminance of each colour area of a safety sign should be at least 2 cd/m2 in all viewing directions which are important for safety.
103
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION PLACEMENT OF EMERGENCY ESCAPE LUMINAIRES In order to ensure correct visibility, allowing safe evacuation, it is recommended to place emergency lighting luminaires at least 2m above floor level. For appropriate luminance, emergency luminaires should be situated close to each exit door and where necessary to highlight potential danger or safety equipment. Emergency escape luminaires should be placed as shown below:
104
at each emergency exit door
at stairs, with each step receiving direct light
close to firefighting equipment or fire alarm call points
at each change of direction
close to each change of floor level
at each intersection of corridors
outside and close to each final exit
close to each first aid point
mandatory at all exit doors and safety signs
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION If first aid points or firefighting equipment and fire alarm call points are not situated on the escape route or within the open area, they should be illuminated so that the illuminance level of at least 5 lx is ensured on the floor close to these points. NOTE: According to the applicable standard, ‘close to’ means within at a distance of 2m measured horizontally. Emergency lighting should also be provided in other hazardous areas and the areas that should be accessible if primary lighting fails. Such areas include the following: • Lift cars, • Escalators and moving walkways, • Toilets, lobbies, changing rooms, cloakrooms and locker rooms larger than 8 m2 and rooms intended for use by the disabled, • Technical rooms where escape route lighting should meet the requirements for the open area lighting or high risk task areas, as applicable, • Covered car parks, • Hospitals – the illuminance of escape route lighting at ICUs and operating theatres should be at least as required for primary lighting in those areas (unless stand-by lighting is available).
SAFETY SIGNAGE Signs placed at all emergency exits along escape routes should be so illuminated as to indicate the direction to a place of safety in an unambiguous man ner. [PNEN1838:2005] Exit and direction signs should be clearly visible from anywhere along the escape route. All signs indicating emergency exits and escape routes should be in the same colour and format, whereas their minimum illuminance should be 2 cd/m2. As people in the building may not be familiar with its layout, internally illuminated, permanently powered safety signs are recommended. Note that internally illuminated safety signs are visible from a greater distance than the same size signs illuminated from the outside.
d=s*p p
d
where: d [m] – viewing distance (maximum distance at which a sign is visible and recognizable) p [m] – height of sign s – constant value: 100 for externally illuminated signs and 200 for internally illuminated signs.
105
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION 1. EMERGENCY LIGHTING SYSTEMS Power to an emergency escape lighting system should be supplied immediately, automatically and for enough time to ensure illumination of specific areas if the primary lighting fails. An escape lighting system should fulfil the following functions: • Illuminate escape and exit route signs, • Provide adequate illuminance along escape routes to ensure safe movement towards the final exit, • Ensure easy location and use of fire alarm call devices and firefighting equipment distributed along escape routes, • Enable performing safety measures. Emergency escape lighting should be activated not only in the event of a total blackout or failure of the primary lighting, but also if a local failure occurs, such as a damage to a branch circuit. All applicable scenarios should be considered at the emergency lighting system design phase, in order to make sure that the emergency lighting will operate correctly if the power supply of primary lighting should fail in a given zone. An emergency lighting system is to comprise all equipment and components within a facility which are interconnected to fulfil the purposes of emergency lighting. This applies, in particular, to the duration and adequate illuminance of emergency lighting, the application of primary or night time lighting, reporting events and the safety of operation and activities of rescue teams, also in the event of fire. The following equipment and components make up an emergency lighting system: • Emergency lighting systems with a central power supply or self-contained luminaires (with internal batteries), • Emergency luminaires designed for use with a CPS system or internal batteries, including their equipment (ballasts, switching and address modules in the case of CPS or inverters, address modules and batteries in the case of self-contained luminaires), • Cables and wires for the connection of emergency lighting system with luminaires, • Cable trays, cable glands, suspension brackets and mechanical fixing systems to make connections in emergency lighting systems, • Additionally designed emergency lighting system devices and equipment, such as remote controllers, computer connection modules, monitoring systems for luminaire supply circuits, systems used for operation with fire protection equipment and other components used in emergency lighting systems.
2. EVENT LOG AND TESTING OF EMERGENCY LIGHTING SYSTEMS As-fitted drawings of the completed emergency lighting system should be submitted and stored on the relevant premises. The drawings should include all luminaires and primary components installed. The data should be updated whenever any changes are made to the system. The drawings should be signed by a competent person who verifies the design in terms of compliance with the applicable standard. In addition, an event log should be maintained to record routine reports, tests, modifications and damages. The records should be available in a hand-written form or as printouts from an automatic testing device. The event log should be kept on the premises in the custody of an appropriate person appointed by the owner/leaseholder; the log should be available for inspection by authorized parties. The event log should be used for recording the following information: • System order date, including a certificate of any modifications, • Date of each routine test and inspection, • Date and a concise description of each service and inspection activities, or of performed tests, • Date and a concise description of each defect or damage and performed repairs, • Date and a concise description of each change to the emergency lighting system, • Description of basic characteristics and operating modes of an automatic testing device, if used. Regular maintenance and repairs are essential. The property owner/leaseholder should appoint a competent person to supervise the provision of maintenance services. The supervisor should have sufficient competences to ensure that any necessary maintenance and repair work is correctly performed on the system. If an automatic testing device is used, its reports should be recorded every month. In the case of all other system types, tests should be performed according to PN-EN 50172 and the results should be recorded in the log. Tests and inspections of emergency lighting equipment As there is a risk of primary lighting power supply failure shortly after an emergency lighting system test or during subsequent charging of batteries, emergency duration tests should be performed, if possible, at the time when the risk is low. This should allow safe recharging of the batteries. Alternatively, short tests of the emergency lighting system can be performed until the full capacity of batteries is restored. Daily inspection The purpose of visual inspection is to verify that the central power supply system is in good working condition and to identify the need for any tests. The inspection involves visual checking of system indicators.
106
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION Monthly test If automatic testing devices are used, the results of short tests should be recorded. In the case of all other systems, a monthly test involves checking the functionalities of the emergency lighting system by simulating a mains power supply failure. The test is to verify if all specified emergency luminaires and illuminated safety signs switch into emergency mode and resume their normal operating state when the mains supply is restored. The duration of the test should be sufficient to check the functioning of the luminaires within the tested zone. During the test all respective luminaires and signs should be checked to confirm that they are present, clean and function correctly. Annual test If automatic testing devices are used, the results of full rated emergency duration tests should be recorded. In the case of all other systems, an annual test involves checking the functionalities of the emergency lighting system by simulating a mains power supply failure. The test is to verify if all specified emergency luminaires and illuminated safety signs switch into emergency mode and resume their normal operating state when the mains supply is restored. The duration of the test should be sufficient to check the expected emergency duration of the system as specified by the manufacturer. During the test all respective indicator lamps or devices should be checked to confirm that their indications are correct. It is recommended to check the correct operation of the charging system.
3. EMERGENCY ESCAPE LUMINAIRES AND CENTRAL POWER SUPPLY SYSTEMS Emergency escape luminaires should be designed and manufactured according to PN-EN 60598-2-22:2004/AC Luminaires – Part 2-22: Particular requirements. Emergency lighting luminaires should be specified according to their intended place of installation. Luminaires used in Ex-zones should comply with relevant standards and the ATEX directive (94/9/EC). Starters for emergency lighting luminaires should comply with PN-EN 61347:2005 (multi-part document) Lamp controlgear – Part 2-7: Particular requirements for DC supplied electronic ballasts for emergency lighting. Due to the amount of output power, the starting pulse current load and duration are important parameters of the starters. These parameters should be specified so that they do not cause damage of power supply circuit contacts (e.g. fuse bases, relay contacts etc.). Central power supply systems for emergency lighting should be designed and manufactured according to PN-EN 50171:2007 Central power supply systems. Safety requirements for batteries should comply with PN-EN 50272-2:2007 Safety requirements for secondary batteries and battery installations – Part 2: Stationary batteries. Due to a variety of internal designs and operating modes of safety equipment, a description of different types of central power supply systems for emergency lighting is not required. CPS systems should work in the IT earthing system with insulation monitoring in order to allow safe operation of rescue teams. Automatic emergency lighting test systems should be designed, manufactured and installed according to relevant requirements of national standards and regulations.
4. LUMINAIRE ENCLOSURE CLASSIFICATION AND PROTECTION CLASSES Classification of luminaire enclosures The resistance of electrical equipment and devices to harmful effects of the weather and environment, as well as the protection against accidental contact with live parts depend on the execution of enclosures and guards. This kind of protection is referred to as ingress protection and denominated by the so-called IP ratings. According to this classification, electrical enclosures are marked with a two-digit code preceded by the letters IP (PN-EN 60529:2003).
107
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION Classification of luminaire enclosures First number
Second number
IP LEVEL
Protection of people against contact with live and moving parts
Protection of the device against intrusion of solid objects
Protection against water
0
No protection
No protection
No protection
1
Protection against accidental contact with the back of a hand
Protection against intrusion of solid objects with a diameter of 50mm or larger
Vertically falling drops (condensation)
2
Protection against contact with a finger
As above but 12mm or larger
Vertically falling drops on enclosures tilted up to 15o from their normal position
3
Protection against contact with shoes and tools with a diameter of 2.5mm or larger
As above but 2.5mm or larger
Spraying water at an angle up to 60o from the vertical from every side
4
As above but 1mm or larger
As above but 1mm or larger
Spraying water from any direction
5
As above
Protection against intrusion of dust in a quantity to interfere with the operation of the equipment or reducing its safety
Water jets from any direction
6
As above
Complete protection against the intrusion of dust
Powerful water jets from any direction
7
Short-term immersion under standard conditions; no ingress of water in any harmful quantity
8
Continuous immersion in specified conditions, more severe than for level 7 above
9
Flooding with a stream of water under a pressure of 80 to 100 bar at a temperature of up to +80oC
Protection classes AC electric appliances operating at a rated voltage of up to 440V and the voltage to ground not exceeding 250V, depending on the applicable electric shock protection measure, are divided into the following protection classes: Protection class 0 – Protection against electric shock relies on basic insulation only. If the insulation is damaged, electric shock protection should be ensured by favourable conditions, such as: placing out of reach, isolation of the workplace, no earthed devices, systems or structural elements within arm’s reach. In Poland, the use of Class 0 equipment is permitted as long as there is no simultaneous contact with the appliance and earth potential or if the contact is rare. Protection class I – Protection against electric shock by indirect touch is ensured by connecting a protective conductor terminal with a PE or PEN conductor, or directly with the earthing system. This is to ensure: • Fast enough activation of relevant protective devices and disconnection of the power supply, or • Limitation of touch voltage to values which do not exceed the permissible limits under specific conditions.
108
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION Protection class II – In the appliances of this class electric shock protection is ensured by the application of suitable insulation – double or reinforced – whose damage is very unlikely.
Protection class
CLASS 0
CLASS 1
CLASS 2
CLASS 3
Symbol
None
Characteristic execution features
Basic insulation only No protection terminal
Basic insulation only Protection terminal for a PE or PEN conductor
Double or reinforced insulation No protection terminal
Low voltage power supply system SELV or PELV
Specific requirements for the execution of electric shock protection
Isolation of the workplace to prevent simultaneous contact with two different conductive parts
Connection to a PE or PEN conductor of a protection terminal
None
None
Application scope
Rooms with insulated walls and floors, without neutral earth electrodes and structures (isolated workplaces)
Residential, industrial and similar rooms, unless specific requirements for particular places or rooms restrict the use of this class of appliances
In all rooms and any conditions, unless specific requirements for particular places or rooms restrict the use of this class of appliances
In all rooms and any conditions
Application examples
Luminaires (chandeliers)
Motors, metal switchgear, washing machines, refrigerators, electric cookers, dishwashers
Coffee grinders, hairdryers, electric shavers and other handheld power tools
Toys, portable lamps, certain handheld power tools
5. LEGISLATION AND REGULATIONS Regulations and standards concerning emergency lighting: 1. Regulation of the Minister of Infrastructure of 12 April 2002 on technical specifications for buildings and their location. Regulation of the Minister of Infrastructure of 12 April 2002 Journal of Laws No. 75, Item 690, as amended; Regulation of the Minister of Infrastructure of 12 March 2009, Journal of Laws No. 56, Item 461 and Regulation of the Minister of Infrastructure of 10 December 2010, Journal of Laws No. 239, Item 1597. 2. Regulation of the Minister of Interior and Administration of 7 June 2010 on fire protection of buildings, other civil structures and lands (Journal of Laws No. 109, Item 719). 3. Regulation of the Minister of Interior and Administration of 27 April 2010 on the specification of products used to assure public safety or the protection of health, life and property, and rules for issuance of certificates of admittance for these products (Journal of Laws No. 85, Item 553). 4. PN-EN 50172:2013 – Emergency escape lighting systems. 5. PN-EN 1838:2005 Lighting applications. Emergency lighting. 6. MLAR guidelines (standard guidelines adopted by a conference of ministers of construction regarding requirements for technical aspects of fire protection of electrical wiring systems), taking into consideration the requirements of the European Parliament included in the guidelines of Directive 98/24/EC of 11 June 1998, amended by the guidelines of Directive 98/48/EC of 20 July 1998 (Official Journal of the EC, No. L 217, p. 18).
109
EMERGENCY LIGHTING SYSTEMS
USER INFORMATION Additional standards to be followed when designing emergency lighting systems: • PN-EN 60598-2-22: 2004/AC Luminaires – Part 2-22: Particular requirements - Luminaires for emergency lighting. • HD 384/HD 60364 PN-IEC 60364:1999 (multi-part document) Electrical installations for buildings. • PN-EN 13032-1:2005 Light and lighting. Measurement and presentation of photometric data of lamps and luminaires. Part 1: Measurement and file format. • PN-EN 13032-2:2005 Light and lighting. Measurement and presentation of photometric data of lamps and luminaires. Part 2: Presentation of data for indoor and outdoor workplaces. • PN-EN 12464-1:2004 Light and lighting – Lighting of workplaces.–Part 1: Indoor workplaces • PN-EN 50171:2007 Central power supply systems • PN-EN 50272-2:2007 Safety requirements for secondary batteries and battery installations – Part 2: Stationary batteries. • PN-EN 60529:2003 Degrees of protection provided by enclosures (IP Code) • PN-EN 61347:2005 (multi-part document) Lamp controlgear – Part 2-7: Particular requirements for DC supplied electronic ballasts for emergency lighting. • PN-EN 60617-11:2004 Graphical symbols for diagrams – Part 11: Architectural and topographical installation plans and diagrams. • PN-N-01256-5:1998 Safety signs. Rules for placement of safety signs along escape routes and fire access roads. • PN-N-01255:1992 Safety colours and safety signs.
110
EMERGENCY LIGHTING SYSTEMS
notes
AWEX SP. Z O.O. SPÓŁKA KOMANDYTOWA Masłomiąca, ul. Długa 39 32-091 Michałowice, Poland tel. +48 12 681 55 00 fax. +48 12 681 55 22 e-mail: export@awex.eu www: awex.eu
Distributor